Bell & Gossett S14141B User Manual

Page 1
70X Multiple Pump Pressure Booster Systems
Installation, Operation and
INSTRUCTION MANUAL
S14141B
Service Instructions
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
DESCRIPTION
A Bell & Gossett Packaged Pressure Booster System is factory assembled, tested and shipped as a complete modular unit. Each Pressure Booster System is tested to internal quality standards.
The information contained in this manual is intended to assist operating personnel by providing information on the charac­teristics of the purchased equipment. It does not relieve the user of the responsibility to adhere to local codes and ordi­nances and the use of accepted practices in the installation, operation and maintenance of this equipment. Further infor­mation pertaining to the installation, operation, and mainte­nance can be found in the I.O.M.s for the specific equipment provided.
OPERATIONAL LIMITS
See unit nameplate for pump capacity, boost, full load current draw, and operating voltage. The pump discharge pressure must not exceed 175 PSI unless specifically designed.
SAFETY INSTRUCTIONS
This safety alert symbol will be used in this manual and on the Safety Instruction decal to draw attention to safety related instructions. When used, the safety alert symbol means
ATTENTION! BECOME ALERT! YOUR SAFETY FAILURE TO FOLLOW THE INSTRUC A SAFETY HAZARD!
TION MAY RESULT IN
IS INVOLVED!
Page 2
UNIT IDENTIFICATION
The unit nameplate gives identification and rating information as identified in Figure 1.
UNIT IDENTIFICATION
Records for this unit are kept by the order number (Q______) and it must therefore be used with all correspondence and spare parts orders.
PRESSURE BOOSTER SYSTEM
PREFACE
The 70X modular variable speed pressure booster system is designed to maintain a constant discharge pressure while minimizing power consumption by combining a variable speed lead pump with one or two constant speed lag pumps. This system creates an efficient and practical solution to a building’s low demand water usage profile. A typical building’s water demand varies throughout the course of a day and often a single pump is capable of meeting the demand for more than half of the day. The 70X controller manages pump operation to match the wide range of pressure boosting sys­tem conditions. The pump controller uses a combination of kW, pressure and speed to calculate the most efficient points to stage on and off pumps for operation.
PREFACE
Power consumption is minimized by varying the speed of the lead pump to satisfy a varying system demand. As the system demand exceeds the capacity of the lead pump, a constant speed lag pump is staged on. The constant speed lag pump operates at full capacity while the lead variable speed pump adjusts its speed to supplement the system requirement. When speed demand decreases the lead pump slows down. While monitoring system pressure, pump speed and power consumption, the constant speed lag pump is staged off at an optimal point and the variable speed pump takes over.
FIGURE 1 - Technologic 500X Control Panel Nameplate
2
Page 3
TABLE OF CONTENTS
70X Multiple Pump Pressure Booster Systems
Page
SECTION 1 GENERAL
Purpose of Manual ..............................................................................................................................4
Safety Requirements...........................................................................................................................4
Handling .............................................................................................................................................4
Storage................................................................................................................................................4
Ground Connections ...........................................................................................................................5
Power Wiring .......................................................................................................................................5
Field Connection Diagrams.................................................................................................................5
SECTION 2 INSTALLATION
Location...............................................................................................................................................5
Foundation .........................................................................................................................................5
Leveling ...............................................................................................................................................5
Grouting ..............................................................................................................................................5
Piping Connections .............................................................................................................................5
Misc Connections................................................................................................................................6
Lubrication ..........................................................................................................................................6
Wiring ....................................................................................................................................................
Power Wiring..................................................................................................................................6
Analog Signal Wiring .....................................................................................................................6
Pressure Transmitter Wiring ..........................................................................................................6
Differential Pressure Switch Piping and Wiring .............................................................................7
Low Suction Pressure Switch .......................................................................................................7
..........................................................................................................................................................
SECTION 3 START UP
Putting Unit into Service......................................................................................................................7
Adjustments ........................................................................................................................................7
Thermal Relief Valve .......................................................................................................................7
Pressure Reducing Valve (PRV) .....................................................................................................7
High Pressure PRV ........................................................................................................................7
Differential Pressure Switch ..........................................................................................................7
Low Suction Pressure Switch ........................................................................................................7
SECTION 4 MAINTENANCE
Maintenance (Physical)........................................................................................................................8
..........................................................................................................................................................
APPENDIX A System Piping and Unit Installation – Final Check List .......................................................................9
APPENDIX B Electrical Wiring and Control Settings – Final Check List ...................................................................9
APPENDIX C Procedure for Field Balancing Pressure Reducing Valve ..................................................................10
APPENDIX D Troubleshooting Combination Pressure Reducing and Check Valves ........................................11-12
APPENDIX E Hydropneumatic Tank Field Installation ............................................................................................12
3
Page 4
SECTION 1 - GENERAL
1.1 PURPOSE OF MANUAL
1.1.1 This manual is furnished to acquaint the user with some of the practical ways to install, operate, and maintain this unit. Read it care­fully before doing any work on your unit and keep it handy for future reference. This manual provides general instructions for installa­tion, commissioning and operation to ensure optimal performance and reliability.
1.1.2 Equipment cannot operate well without proper care. To keep this unit at top efficiency, fol­low the recommended installation and servic­ing procedures outlined in this manual.
1.1.3 The control panel installed on the pressure booster system shall have a safety instruc­tion decal (part #S11550 shown below). If the decal is missing or illegible contact your local B&G representative for a replacement.
1.2 SAFETY REQUIREMENTS
1.2.1 Motor must have a properly sized starter with properly sized overload block to provide over load and undervoltage protection. Ground fault protection should be sized properly.
1.2.2 Refer to the motor manufacturers I.O.M. (Installation, Operation & Maintenance manual) for specific installation information.
1.2.3 Even when the motor is stopped, it should be considered "alive" as long as its controller is energized. Keep hands away from the output shaft until the motor has completely stopped and power is disconnected from the pump controller.
1.2.4 Motor control equipment and electronic con­trols are connected to hazardous line volt ages. When servicing electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. Always use accurate test meters when check ing electrical components. Always work with another person in case of an emergency. Disconnect power when performing mainte­nance. Be sure equipment is properly grounded. Wear safety glasses whenever working on elec­tronic control or rotating equipment.
1.3 HANDLING
1.3.1 Care should be taken to prevent damage due to dropping or jolting when moving the unit. Inspect the unit thoroughly for damage upon receipt. Transportation damage should be brought to the carrier’s attention immediately. Ensure that sensing lines are free of crimps and kinks.
1.3.2 The unit should be unloaded and handled by qual­ified personnel. The unit is top heavy due to the position of the motors. Use the motor eyebolts to stabilize the unit while lifting to prevent overturn­ing. Do not use the motor eyebolts to lift.
1.4 STORAGE
1.4.1 For periods of storage, the unit should be covered to prevent corrosion and contamina­tion from dirt. It should be stored in a clean, dry location to prevent condensation as well as protected from freezing. After storage, again check that it is dry before applying power. Specific component storage instruc­tions must be followed in accordance with the respective equipment manufacturers recommendations.
WARNING: Make sure the area surrounding the unit
is safe. Be aware of any hazardous conditions that can exist. Always wear protective glasses and protective shoes when working with the unit. Do not wear loose fitting or torn clothing. Remove all jewelry when working.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING:
Motor can start automatically. Keep
hands away from output shaft until motor is com­pletely stopped and input power is removed from the motor control panel. Lockout main power switch while working near the motor shaft.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: Troubleshooting live control panels exposes
personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Falling Objects Hazard. Eyebolts or lifting
lugs, if provided, are for lifting only the components
to which they are attached.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
CAUTION: Extreme temperatures are to be avoided.
(Below 32ºF and above 110ºF).
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
4
Page 5
1.5 GROUND CONNECTIONS
1.5.1 A grounding terminal is provided for a dedicated ground wire connection. All provisions of the National Electrical Code and local codes must be followed.
1.6 POWER WIRING
1.6.1 Power wire types and sizes must be selected based upon conformance with the National Electrical Code and all local codes and restric­tions. In addition, only copper (Cu) wire rated for 75°C (minimum) may be used for the power con­nections. Refer to the input current as listed on the nameplate on the enclosure door when sizing wire.
1.7 FIELD CONNECTION DIAGRAMS
1.7.1 Actual equipment manufacturers/models installed are system specific. Refer to specific manufacturers Installation, Operation & Maintenance Manuals for details unique to each component. The following instruction manual categories are supplied with the system (if applicable): Pump Technologic 500X Pump Controller
(IOM part #176U7761) Thermal Relief Valve PRV Check Valve
1.7.2 The following field connection diagrams should be reviewed prior to unit installation and operation.
SECTION 2 - INSTALLATION
2.1 LOCATION
2.1.1 Locate the pumping system in a clean, well ventilated and properly drained location. It is rec­ommended that the location selected facilitates ease of inspection, maintenance and service. Outside installations require protection from freezing.
2.2 FOUNDATION
2.2.1 This unit is built to give you years of service; install it properly and provide a suitable foundation. A base of concrete weighing 2-1/2 times the weight of the unit is recommended. (Check the shipping ticket for unit weight.) Tie the concrete pad in with the finished floor. Foundation bolts of proper size and pipe sleeve should be set in con­crete. The pipe sleeve will allow some flexibility in bolt alignment to match the holes in the base plate. Allow sufficient bolt length for grout, shims, base plate, nuts and washers.
2.3 LEVELING
2.3.1 Place the unit on its concrete foundation, support-
ing it with steel wedges or shims totaling 1" in thickness. These wedges or shims should be put on both sides of each anchor bolt to provide a means of leveling the base. After leveling is com­plete, evenly and firmly tighten the foundation nuts. Do not fully tighten the bolts until after grouting.
2.4 GROUTING
2.4.1 After the frame has been leveled and securely
bolted to the pad, a good grade of grout should be installed beneath the base. A suggested mixture for grout is: one part Portland Cement and two or three parts plain, sharp sand mixed with water until it will pour easily. Commercial grout mixtures with suspended iron particles are available. Wet the concrete base before pouring grout. Build a strong form around the foundation to contain grout. Allow the grout to flow around wedges & shims and beneath the entire length of the base flange. Allow the grout to set, usually 48 hours after pouring, before fully tightening the foundation bolts.
2.5 PIPING CONNECTIONS
2.5.1 Important. Do not install and operate a Bell &
Gossett Pressure Booster in a closed system unless the system is equipped with properly sized control devices. Such devices include the use of properly sized and located pressure relief valves, compression tanks, pressure control, temperature controls and flow controls as appropriate. If the system does not include these devices, consult the responsible engineer or architect before mak­ing pumps operational.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the ground lug provided in the enclosure to avoid potential safety hazards.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
Drawing # Job Specific Print(s) Job Specific Print(s)
Description
Wiring Diagram
Dimensional Drawing
DANGER: Heavy load, may drop if not lifted properly. Do not lift the entire unit by component eyebolts.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: The heating of water and other fluids
causes volumetric expansion. The associated forces may cause failure of system components and releases of high temperature fluids. This will be prevented by installing properly sized and located pressure relief valves and com­pression tanks.
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN SERIOUS PROPERTY DAMAGE AND SERI­OUS PERSONAL INJURY OR DEATH.
CAUTION: Extreme temperatures are to be avoided
(below 32°F and above 110°F).
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
5
Page 6
2.5.2 After hydrotesting, drain plugs are removed, to facilitate system drainage, placed in a cloth bag and secured to the unit. Drain plugs shall be rein­stalled prior to filling the system with fluid. Inspect all unit piping connections. Joints may also become loose during transit due to vibration and shock. All joints are to be checked for tightness. Flanged joints should be checked for proper torque of all flange bolts prior to filling the system with fluid.
2.5.3 Make all necessary system piping connections. Be aware that connecting dissimilar metals to the headers can lead to corrosion damage due to gal­vanic corrosion. The rate of corrosion is dependant on various factors some of which are; the potential between the dissimilar metals, electrolyte conduc­tivity, geometry and area of the metals. Dielectric connections are recommended between dissimilar metals at the header connection. Be sure to elimi­nate any pipe strain on the unit. Support all pipes independently by use of pipe hangers near the unit. DO NOT ATTEMPT TO FORCE THE SUCTION OR DISCHARGE LINES INTO POSITION. Refer to assembly drawing for customer piping connections.
2.5.4 The maximum suction pressure shall not exceed 150 psi. Dead head pressure plus suction pressure shall not exceed 175 psi.
2.5.5 As a rule, ordinary wire or band hangers are not adequate to maintain alignment. It is very impor­tant to provide a strong, rigid support for the suc­tion line. A saddle hanger is recommended.
2.5.6 For critical installations, equipment for absorbing expansion and vibration should be installed at the inlet and outlet connections of the unit.
2.5.7 Eccentric increasers can be used in the suction pipe line when increasing the pipe size, with straight sides of increaser on top to eliminate air pockets.
2.5.8 On an open system with a suction lift, a foot valve of equal or greater area than the pump suction is recommended. Prevent clogging by using a strainer at the suction inlet next to the foot valve. The strainer should have an area three times that of the suction pipe. Provisions must be made to prime the pump suction piping on start up. Do not start the pump unless all suction piping is full of water.
2.6 MISCELLANOUS CONNECTIONS
2.6.1 Hydro-Pneumatic Tank (optional): The tank is sup­plied mounted on a separate base for ease of han­dling, unit installation and space considerations. Mount the tank adjacent to the unit. A union con­nection is provided to allow quick connection to the unit. The tank is intended to maintain system pressure due to minor system leaks and periods of low demand.
2.6.2 Pre-charge the Hydro Pneumatic tank prior to fill­ing the system. The tank should be air charged to the pump restart pressure minus 1 psi. If the tank is located above the booster, the precharge pres­sure is calculated by pump restart pressure minus tank elevation above pressure booster (psi) minus 1 psi.
2.6.3 For tanks supplied by others, refer to appendix E
for tank installation.
2.7 LUBRICATION
2.7.1 Before starting, all pumps and motors should be checked for proper lubrication.
2.8 WIRING
2.8.1 Refer to the controller instruction manual for elec­trical connection, set-up and troubleshooting.
2.9 POWER WIRING
2.9.1 The Control Panel is designed to operate at a spe­cific voltage as indicated on the control panel nameplate. Verify proper transformer primary wiring per the job-specific wiring diagram. Check power leads in accordance with wiring diagram enclosed in control cabinet. The voltage tolerance is +10%/-10%.
2.10 ANALOG SIGNAL WIRING
2.10.1 If installing the panel on an existing system, twisted
pair shielded cable (#22 AWG, Belden type 8762, Alpha #2411 or equal) should be installed for the DC control wiring. The shield must be terminated in the control panel. Do not connect the shield at the other end of the cable! Insulate the shield so that no electrical connection is made at the other end of the cable. A twisted pair of #22 AWG con­ductors (Belden 8442 or equal) can be used in place of shielded cable. The cable length must be limited to 3000 feet for #22 AWG wire.
2.11 PRESSURE TRANSMITTER WIRING (4-20 mA Analog Signals)
2.11.1 (Optional) A pressure transmitter, if supplied with the booster unit, is installed at the discharge header. Otherwise, a pressure transmitter is sup­plied loose. It is recommended that the sensor be installed in the zone furthest away or at the most critical zone. Refer to wiring diagram for exact ter­minal locations.
DANGER: Electrical shock hazard. Inspect all
electrical connections prior to powering the unit. Wiring connections must be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
6
CAUTION: Failure to reinstall drain plugs, check all joints for tightness and flange bolts for proper torque
could result in leaks and/or flooding.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
Page 7
2.12 DIFFERENTIAL PRESSURE SWITCH PIPING AND WIRING
2.12.1 (Optional) Differential pressure switches are avail­able to sense the increase in pressure between the pump suction and discharge gauge taps that is used to determine whether a pump is running. The switch is wired normally closed to the control panel. Refer to wiring diagram for exact terminal locations. (Differential pressure switch may require field calibration.) Ref-3.6.1.
2.13 LOW SUCTION PRESSURE
2.13.1 (Optional) Low suction pressure switch is avail­able and intended to stop pump operation when an insufficient pump suction condition exists. The switch is wired normally closed to the control panel. Refer to wiring diagram for exact terminal locations.
SECTION 3 - START UP
3.1 PUTTING THE UNIT INTO SERVICE
3.1.1 After package is installed and foundation bolts
are tightened, check pump alignment. Refer to specific pump Installation, Operation & Maintenance manual for alignment procedures.
3.1.2 Fill system with fluid after reading the cautions in
the piping connection section of this manual.
3.1.3 Vent all high points in the piping system to
removed trapped air.
3.1.4 Before starting all pumps and drivers should be
checked for proper lubrication.
3.1.5 Piping should be clean and flushed prior to operation.
3.1.6 PUMP ROTATION, 3 PHASE MOTORS ONLY
3.1.7 With the disconnect switch engaged to the "ON" position, momentarily start and stop each motor. Observe the pump shaft rotation.
3.1.8 If incorrect, turn the main disconnect off and inter-
change any two wire leads leaving the starter over­load block and going to the motor.
3.1.9 Unit is now ready for operation.
3.2 ADJUSTMENTS
3.2.1 Final adjustments on the following adjustable devices shall be made to match exact system requirements.
3.3 THERMAL RELIEF VALVE
3.3.1 A thermal relief valve is installed on the discharge header to prevent potentially dangerous thermal pressure buildup. The valve automatically opens on temperature increase and closes on tempera­ture decrease. This valve acts as a safety device and should never be removed or plugged. It is fac­tory set to open and discharge when the water temperature in the discharge header reaches 125°F. The 3/8" NPT opening of this valve shall be piped to a floor drain in accordance with local codes.
3.3.2 To raise the valve opening point, turn the adjust­ment screw counter-clockwise; to lower the valve opening point, turn the screw clockwise. The clos­ing point is non adjustable, approximately 3 to 5º F below opening point.
3.3.3 To flush valve manually, insert a screwdriver under each side of the lower spring guide. Pry both guide and spring away from body to open valve.
3.3.4 After long periods of operation, valve seat and disc may become worn or pitted, allowing leakage through valve in closed position. Internal parts can be replace if desired.
3.4 PRESSURE REDUCING VALVE (PRV)
3.4.1 The PRV is used to maintain a desirable pressure at the discharge header. The PRV is preset at the factory to the exact system requirements. If fur­ther adjustments are necessary refer to the PRV instruction manual.
3.5 High PRESSURE PRV (If Required)
3.5.1 On systems where the system pressure reaches
above 135 psi a high pressure PRV is required to protect the thermal relief valve from exceeding its pressure rating. The high pressure PRV has an adjustable range from 30 to 300 psi and is manu­facturer set at 60 psi. No further adjustments are recommended.
3.6 DIFFERENTIAL PRESSURE SWITCH (Optional)
3.6.1 The differential pressure switch has a range from 1/2-36 psid and is manufacturer set at 18 psid. It is recommended that the setting be adjusted to 2 psi less than the minimum pump differential pressure to avoid nuisance alarms. The minimum pump dif­ferential pressure is equal to the pump discharge pressure at minimum speed minus suction pres­sure. To adjust the setting, remove the cover. To decrease the operating point, face the switch, place a flat bladed screwdriver in the slots of the main range adjustment nut and rotate from left to right. For further information refer to switch instruction manual supplied with the unit.
3.7 LOW SUCTION PRESSURE SWITCH (Optional)
3.7.1 Manufacturer set at 40 psi. It is recommended that the setting be adjusted to 10 psi below rated suc­tion pressure. To adjust the setting, remove the cover. Turn the reference dial to the desired set point by aligning setting on dial with the dowel pin.
WARNING: Rotating shafts can catch loose clothing. Do not operate the pump without all guards in place.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: High Voltage 3 phase power can kill.
Disconnect and lockout power prior to servicing unit.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
CAUTION: Seal Damage may occur. Do not run
pumps dry. Fill and vent the pump volute prior to
operation.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
7
Page 8
SECTION 4 - MAINTENANCE
4.1 MAINTENANCE (PHYSICAL)
4.1.1 Refer to specific component IOM for maintenance information.
4.1.2 Mechanical - A Series 1531 pump was lubricated at the factory. Future lubrication should be accord­ing to the motor manufacturer’s instructions.
4.1.3 A Series 1510 pump requires regreasing after every 2500 hours of operation or every six months whichever occurs first. Lubricate motor per motor manufacturer’s instruction.
4.1.4 If there is a danger of freezing, drain the pump. Inspect pump and system piping regularly.
4.1.5 For leaky seals or gaskets and loose or damaged components, replace or repair as required.
For more instruction on the B&G pumps see the following manuals: 1510 (IOM Part #P81673) or 1531 (IOM Part #P81567).
8
Page 9
9
APPENDIX A
____ 1. Is the unit base properly leveled, grouted and
secured? ____ 2. Are all lubrication points properly lubricated? ____ 3. Is the outlet side of the high temperature regulat-
ing valve connected to the drain with tubing or
pipe size 3/8" or greater? ____ 4. Is the shut-off valve to the pressure transmitter(s)
open? ____ 5. Is the shut-off valve to the pump suction open? ____ 6. Is the shut-off valve on the discharge line open? ____ 7. Is the bypass valve, if used, closed? This valve
may be left open if a check valve is installed in
series with it. ____ 8. Are the stop cocks for the check feature on the
PRV open? They must never be completely closed
during normal operation. Throttle cock if check
slamming is noted.
____ 9. Is the piping properly supported so as to prevent
strains on unit?
____ 10. Is the system, including the pumps and PRVs,
purged of debris and air?
____ 11. Is the Hydro Pneumatic tank charged properly?
The tank must be empty of water when checking the air charge.
____ 12. Are the bleed valves at the high temperature valve
header open?
APPENDIX B
APPENDIX B
____ 1. Does the feeder line voltage correspond to the unit
voltage? Check the unit nameplate or motor ter­minal connection.
____ 2. Are the feeder wires correctly sized for the load?
____ 3. Are the fuses correctly sized? They must not
exceed 1.75 times the full load current of the motor. Usual sizing is 1.15 to 1.5 times the full load current.
____ 4. Is the unit properly grounded?
____ 5. Have all the power terminals in the control panel
been checked for tightness? This is imperative since stranded wires tend to "flow" and become loose after initial installation.
____ 6. Are motor overloads set properly? Set the over-
loads to FLA as a minimum and SF x FLA as a maximum.
____ 7. Is the pump rotation correct?
CAUTION: Seal Damage may occur. Do not run pumps dry. Fill and vent the pump volute prior to
operation.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
WARNING: Electrical shock hazard. Inspect all
electrical connections prior to powering the unit. Wiring connections must be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the ground lug provided in the enclosure to avoid potential safety hazards.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: High Voltage 3 phase power can kill.
Disconnect and lockout power prior to servicing unit.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
ELECTRICAL WIRING AND CONTROL SETTINGS - FINAL CHECK LIST
SYSTEM PIPING AND UNIT INSTALLATION - FINAL CHECK LIST
Page 10
10
APPENDIX C
PROCEDURE FOR FIELD BALANCING PRESSURE REDUCING VALVE
COMBINATION PRESSURE REDUCING AND CHECK VALVE
Item Name Primary Function
1 Strainer Prevents orifice from clogging 2 Check Valve Prevents backflow from top of diaphragm when pumping stops. 3 Orifice Provides metered water flow to top-side of diaphragm. 4 Opening Speed Flow Control Dampens pressure fluctuations (slow opening). 5 CRD Pilot PRV. 6 Gauge Optional location for system pressure gauge. 7 Cock Adjustment for rate of closure (non-slam). 8 Check Valve Prevents backflow from top of diapgragm during normal operation. 9 Vent Bleeds air from top of diaphragm.
10 Diaphragm Divides inlet and outlet pressures.
Figure 2
1.0 Pressure Reducing valve (PRV) Adjustment
1.1 The pressure reducing valves are "factory set". If needed, the following items should be checked first before any attempt is made to change the setting: a) Does the desired system pressure correspond
to the pressure indicated on the nameplate?
b) Is the suction pressure equal to or higher than
the pressure indicated on the nameplate?
c) Is the demand (GPM) within the capacity indi-
cated on the nameplate?
d) Has the PRV been properly vented?
1.2 Any deviation from the above conditions will pre­vent the unit from operating at the factory (name­plate) settings.
1.3 To adjust the PRV place the pump in manual oper­ation per Technologic 500X instruction manual. With the pump now running, slowly close the main gate valve downstream of the discharge header allowing a trickle of water to flow through it. Read the system pressure on the display. It should read 3 or 4 psi higher than the desired system pres-
sure. If not, remove the protective cap on the pilot control valve and loosen the jam nut on the adjusting stem of the PRV. Slowly turn the stem clockwise to increase the delivery pressure and counter clockwise to decrease pressure. (Note that a pilot valve furnished for a 20 to 300 psi range will change the main valve setting approxi­mately 28 psi for each full turn of the adjusting screw.) Set the screw so the system display reads 3 to 4 psi higher than the desired system pressure.
1.4 Open the gate valve fully. If feasible, draw be­tween 50 to 80% of the designed pump capacity to recheck valve setting. The display should now read the desired system pressure. Tighten jam nut and replace cap.
1.5 Repeat the above procedure for all pump and valve combinations as required.
1.6 The CV Flow Control Valve (opening speed con­trol) may require field adjustment if pressure hunt­ing occurs. Normal setting of the valve is from 4 to 7 turns open. Never open more than 8 turns.
Page 11
TROUBLESHOOTING COMBINATION PRESSURE REDUCING AND CHECK VALVES
11
DANGER: Troubleshooting live control panels exposes personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
APPENDIX D
1.0 System Pressure Higher than Desired Set Point
1.1 Primary Causes a) Insufficient pressure on top side of diaphragm. b) Leakage through main valve seat. c) Pressure build-up due to thermal expansion,
such as caused by volumetric expansion of the water in a heater connected to the system side of the PRV.
d) Inaccurate system pressure signal.
1.2 Tests and Remedies (see Figure 2 for item numbers) a) Install gauge, install on CRD (Item 6), if
necessary.
b) Vent air from air vent (Item 9) and from other
high points of PRV trim. Valve cover bolts may have to be loosened on some units with PRV
mounted horizontally. c) Check CRD set point adjustment. d) Close stop cock (Item 7) in check line. If PRV
now operates properly, clean or replace adja-
cent check valve (Item 8). e) Inspect CRD (Item 5) disc and seat for proper
seating. f) Inspect strainer (Item 1) that the screen is clean. g) Inspect orifice (Item 3) that it is not clogged. h) Plug outlet side of CRD. If main valve closed
tight, the problem most likely is in the CRD.
Replace same. If the main valve does not close
tight, disassemble it for inspection. Check for
scored seat.
2.0 System Pressure Lower than Desired Set Point
2.1 Primary Causes a) Excessive pressure on top side of diaphragm. b) Suction pressure below design conditions
(check nameplate on panel door for design conditions).
c) Desired system pressure is higher than design
condition (check panel nameplate). d) Flow Rate is greater than design condition. e) Inaccurate system pressure signal.
2.2 Tests and Remedies (see Figure 2 for item numbers) a) Install gauge, install on CRD (Item 6), if
necessary. b) Vent air from air vent and all high points. c) CRD disc guide or yoke binding. d) Check motor amps. If greater than full load
amps (motor nameplates), flow rate may be
greater than design.
e) Leak into upper diaphragm chamber. Close
stop cock (Item 7) and remove a connection between the flow control valve (Item 4) and the PRV valve cover. Plug the flow control side. Open pump suction valve and start pump. If water emits from the valve cover plate, there is a leak passing the diaphragm into the upper chamber.
f) Remove valve cover plate for inspection.
Remove "cancerous" buildups which may pre­vent diaphragm from lifting fully. Check for binding of valve stem assembly.
g) Opening speed control valve (Item 4)
clogged in restricted flow mode (out of PRV valve cover).
h) Orifice (Item 3) missing. The orifice fitting identi-
cal in appearance to a flare to MPT adapter, therefore may have been inadvertently replaced or misplaced during valve service.
i) Check pump discharge pressure. Does it corre-
spond to the TDH curve?
3.0 System Pressure Slow to Recover from Under Pressure to Set Point
3.1 Primary Causes
a) Pressure above the diaphragm is not being
removed quickly enough.
b) Mechanical binding in main PRV or CRD pilot
valve.
c) Excessive suction supply line pressure drop.
3.2 Remedies (see Figure 2 for item numbers)
a) Any of the items of 2.2 may be a contributing
factor.
b) Readjust flow control valve (Item 4) to less
restrictive setting, turn counter clockwise.
NOTE: Forcing the stem too far CCW will shear the stem snap ring and cause the stem to blow out. Recommend that the stem be initially turned CW, noting the number of turns required to seat the stem, then backing it out CCW a few more turns than the original setting. The maximum CCW setting is about 9 turns.
4.0 System Pressure Overshoots Greatly and Slow to Recover to Set Point
4.1 Primary Causes
a) Pressure above the diaphragm is not being
applied soon enough.
b) Mechanical binding in main PRV or CRD pilot
valve. c) Leaky seat in main PRV or CRD valves. d) Excessive suction supply line pressure drop. e) System side surge (water hammer) due to
sudden closure of a quick opening valve. f) Strainer (Item 1) clogged.
4.2 Remedies (see Figure 2 for item numbers) a) Any of the items of 1.2 may be contributing
factors.
b) Install larger orifice (Item 3).
Page 12
5.0 PRV Does Not Close (Check) on Pump Shut Down
5.1 Primary Causes a) Insufficient pressure on top of diaphragm. b) Leak through main valve seat or diaphragm assembly.
5.2 Remedies (see Figure 2 for item numbers) a) Stop cock (Item 7) closed preventing pressure
from reaching valve cover. b) Leaking check valve (Item 2). c) To determine whether leak is in main valve seat
or diaphragm assembly:
1. Disconnect line between flow control valve (Item 4) and valve cover.
2. Plug flow control side.
3. Install pressure gauge in valve cover.
4. Remove vent plug in pump volute to drain inlet side of PRV.
5. Apply pressure to top side of diaphragm by opening shutoff valve on outlet side of PRV.
6. Read gauge pressure.
7. Close stop cock (Item 7).
If gauge pressure fails, there is a leak in the dia­phragm assembly. This test, however, does not indicate whether the seat is also leaking.
6.0 PRV Slams Shut on Pump Shut Down
6.1 Primary Causes a) Too rapid buildup of pressure on top of
diaphragm. b) Main valve assembly binding. c) Check valve (Item 2) sticking open momentarily
6.2 Remedies (see Figure 2 for item numbers) a) Throttle stop cock (Item 7).
NOTE: Closing this stop cock will completely prevent PRV from functioning as a check valve.
b) Vent air from PRV (see 1.2b).
APPENDIX E
HYDRO-PNEUMATIC TANK FIELD INSTALLATION
Figure 3
Xylem Inc.
10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. S14141B August 2012
Loading...