Bell & Gossett S13641B User Manual

VARIABLE SPEED PUMPING SYSTEMS INSTRUCTION MANUAL
Technologic®5500 Series
INSTRUCTION MANUAL
S13641B
Pump Controller
WARNING LABEL PART #S11550 INSTALLED IN THIS LOCATION. IF MISSING IT MUST BE REPLACED.
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
DESCRIPTION
Microprocessor based dedicated pump controller for variable volume pumping systems. The control panel consists of the following components: microprocessor, operator interface with 4 line display and membrane key pad, 24 VDC power supply. Multi-pinned connecting cables for connection to bypass panels are available as options.
OPERATIONAL LIMITS
See the control panel nameplate for operating voltage, current draw, as well as information on the equpiment to be con­nected to the control panel.
This safety alert symbol will be used in this manual and on the Technologic 5500 Safety Instruction decal to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS
INVOLVED! FAILURE TO FOLLOW THE INSTRUCTION MAY RESULT IN A SAFETY HAZARD!
SAFETY INSTRUCTIONS
2
Preface
The following manual describes the new microproces­sor based Technologic 5500 Controller. This unit is in the tradition of the other members of the Technologic Control Panels as it incorporates many original, novel, and proprietary features that may only be found on B&G controllers. Some of these features require spe­cial emphasis here.
The controller is best described as a specific purpose programmable pump controller. This means that the hardware and software have been created for the con­trol and diagnostics of pumps with consideration for their inherent characteristics. This results in an optimum pump controller without the cost of general purpose control hardware. Software is dedicated and estab­lished for the unit only after extensive testing. Changes
to this software are not taken lightly and must pass rigid version control.
The controller has the unique analog input protection of other members of the control family. In the event of a short circuit condition the current limit circuitry pre­vents failure of the analog input components.
This new controller has standard manual bypass switches when a Bell & Gossett automatic bypass is supplied. The manual bypass switches allow the user to de-energize the programmable logic controller and take manual control of the pumping system. This is helpful during system startup to confirm pump rotation and to purge air from the system prior to switching to automatic control.
3
SECTION 1 - GENERAL Page
Purpose of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Safety Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Safety Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Temperature and Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Ground Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Output/Motor Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Analog Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Field Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Sensor & Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SECTION 2 - INSTALLATION & STARTUP
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Putting Unit into Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SECTION 3 - SETUP AND FEATURES
General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sensor Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pump Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Stage/Destage Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PID Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Alternation Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Bypass Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
AFD Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Date/Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Password Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
I/O Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Communication Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Special Functions Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Testing Inputs & Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Index
4
INDEX (continued)
SECTION 4 - TYPES OF PROGRAMS Page
AO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
B3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
C0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
D0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
D4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Special Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Pump Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Hand Manual Speed Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Hand Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Setpoint Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Process Variable Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SECTION 5 - MAINTENANCE
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Technical Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Instruments and Their Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Field Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Program Updating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Program Type and Version Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Maintenance (Physical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
APPENDIX A System Check List - Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
APPENDIX B System Check List - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
APPENDIX C Valid I/O Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Drawing, Exterior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Drawing, Interior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Drawing, Operator Interface and CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
NOTE: The information contained in this manual is intended to assist operating personnel by providing information on the characteristics of the purchased equipment.
It does not relieve the user of the responsibility to adhere to local codes and ordinances and the use of accepted practices in the installation, operation and maintenance of this equipment.
Further information pertaining to the installation, operation, and maintenance of your Technologic 5500 series pump controller can be found in the I.O.M.s for the associated equipment provided see Section 5, Maintenance, for a list of relevant manuals.
1.1 PURPOSE OF MANUAL
1.1.1 This manual is furnished to acquaint you with some of the practical ways to install, operate, and maintain this unit. Read it carefully before doing any work on your unit and keep it handy for future reference.
1.1.2 Equipment cannot operate well without proper care. To keep this unit at top efficiency, follow the recom­mended installation and servicing procedures out­lined in this manual.
1.1.3
SAFETY INSTRUCTION
This safely alert symbol will be used in this manual and on the unit safety instruction to draw attention to safety related instructions. When used the safety alert symbol means
ATTENTION BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOL­LOW THIS INSTRUCTION MAY RESULT IN A SAFETY HAZARD.
1.1.4 Your Technologic 5500 Series Pump Controller should have a safety instruction decal (part #S11550). If the decal is missing or illegible contact your local B&G representative for a replacement.
1.2
ADDITIONAL SAFETY REQUIREMENTS
1.2.1 Each motor must have a properly sized starter with properly sized overload block to provide overload and undervoltage protection. Ground fault protection should be sized properly. Refer to local electrical codes for sizing and selection.
1.2.2 Refer to the motor manufacturers I.O.M. (Installation Operation Manual) for specific installation information.
1.2.3 Even when the motor is stopped, it should be consid­ered alive as long as its controller is energized. Keep hands away from the output shaft until the motor has completely stopped and power is discon­nected from the pump controller.
5
Section 1 - General
WARNING: Motor can start automatically. Keep hands
away from output shaft until motor is completely stopped and input power is removed from the motor con­trol panel. Lockout main power switch while working near the motor shaft.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
Glossary of Terms
AFD – Adjustable Frequency Drive; converts a constant power input into a variable power output for the motor; a device for controlling motor speed.
Alternation – Process of determining which pump will serve as lead pump and which pump will serve as lag pump.
Bypass – Controller bypasses the AFD, pumps stop running in variable speed mode and run at constant speed (50 Hz / 60 Hz).
Destage – To turn off a lag pump. EOC – End Of Curve; point at which a pump is staged or
destaged.
I.O.M. – Installation Operation Manual. Lag pump – Standby pump which activates only when lead
pump alone cannot efficiently provide sufficient pressure or flow rate.
Lead pump – Duty pump which runs continuously until a standby pump is required.
LED – Light emitting diode, located on OIP and controller. OIP – Operator Interface Panel. O.L. – Overload, device to protect a motor from overheating. PID – Proportional Integral Derivative; 3 variables required
for error control. Process variable – Signal generated by a sensor which is
set up to control the system. Proof timer – Minimum time period before controller
acknowledges an input; time period for which a signal must be stable before it is accepted by the controller as a sustained and valid signal.
RTC – Real time clock. Stage – To start a lag pump
6
1.2.4 The use of motor disconnect switches is acceptable. Consult the factory for proper interlocking with adjustable frequency drives, AFDs. See Section 1.9.
1.2.5 Motor control equipment and electronic controls are connected to hazardous line voltages. When servic­ing electronic controls, there will be exposed compo­nents at or above line potential. Extreme care should be taken to protect against shock. Stand on an insu­lating pad and make it a habit to use only one hand when checking components. Always use accurate test meters when checking electrical components. Always work with another person in case of an emer­gency. Disconnect power when performing mainte­nance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic control or rotating equipment.
1.3
STORAGE
For long periods of storage, the unit should be cov­ered to prevent corrosion and contamination from dirt. It should be STORED in a clean, dry location between -20 and +60ºC. The relative humidity should not exceed 85%. The unit should be checked period­ically to ensure that no condensation has formed. After storage, again check that it is dry before apply­ing power.
NOTE: EXTENDED STORAGE OF AFDs MAY REQUIRE SPECIAL ATTENTION PRIOR TO START­UP. SEE MANUFACTURERS I.O.M. FOR DETAILS.
1.4
HANDLING
Care should be taken to prevent damage due to dropping or jolting when moving the Technologic Pump Controller. Transportation damage should be brought to the carriers attention immediately upon receipt.
1.5
TEMPERATURE AND VENTILATION
All electrical equipment is susceptible to failure if operated in ambient temperatures outside of its rat­ing. The OPERATING temperature range for this unit is 0 to 40°C. The relative humidity should not exceed 95% non-condensing. The unit should not be operat­ed outside these extremes.
1.6
INPUT VOLTAGE
The AFD and Technologic Pump Controller can be set up to operate across a broad range of voltages. It was factory set to operate on the voltage shown on the nameplate. Check the AFD nameplate for the proper input and output voltages before wiring the AFD.
The voltage tolerance is +10/-5% and phase to phase voltage must not have an imbalance greater than 5 VAC.
1.7
GROUND CONNECTIONS
A grounding terminal is provided for a dedicated ground wire connection. All provisions of the National Electrical Code and local codes must be followed.
1.8
POWER WIRING
Power wire types and sizes must be selected based upon conformance with the National Electrical Code and all local codes and restrictions. In addition, only copper (Cu) wire rated for 75°C (minimum) may be used for the power connections. Refer to the input current as listed on the nameplate on the enclosure door when sizing wire.
1.9
OUTPUT/MOTOR DISCONNECT
It is necessary that any device which can disconnect the motor from the output of the AFD be interlocked to the emergency shutdown circuits of the AFD. This will provide an orderly shutdown if the disconnecting device is open circuited while the AFD is in operation. Failure to provide this interlock may result in dam­aged components due to improper installation.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the ground lug provided in the enclosure to avoid potential safety haz­ards.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
CAUTION: Metal filings can create electrical short
circuits. Do not drill, saw, file or perform any opera­tion on the AFD conduit entry plate while attached to the AFD.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
DANGER: Troubleshooting live control panels exposes
personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Prevent electrical shocks. Disconnect
the power supply before beginning installation.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Prevent electrical shocks. Disconnect
the power supply before beginning installation.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
7
1.10
ANALOG SIGNALS
Shielded cable (#22 AWG, Belden type 8762, Alpha #2411, or equal) should be installed for all D.C. con­trol wiring. The shield must be terminated in the Technologic Pump Controller panel. Do not connect the shield at the other end of the cable! Insulate the shield so that no electrical connection is made at the other end of the cable. A twisted pair of #22 AWG conductors (Belden 8442, or equal) can be used in place of shielded cable. The cable length must be limited to 5,000 feet for #22 AWG wire.
1.11
FIELD CONNECTION DIAGRAMS
1.11.1 Refer to the pump Installation, Operation, and Maintenance Manual for specific details unique to the pump.
1.11.2 Refer to the flow sensor/transmitter Installation, Operation, and Maintenance manual for specific details unique to the flow sensor/transmitter.
1.11.3 The following field connection diagrams should be reviewed prior to unit installation and operation.
Drawing # Description
Job Specific Wiring Diagram(s)
Print(s) Dimensional Drawings
Job Specific Field Connection
Print Diagram
Job Specific
Print
1.12
SENSOR AND CONTROL WIRING
1.12.1 The following sections are based on the installation of standard Technologic 5500 product. Because customized software and hardware is available the installing contractor should base all wiring connec­tions on the wiring diagrams that accompany each controller. These sections are meant to complement, not replace, those wiring diagrams.
1.12.2 Differential pressure switches installed to sense the increase in pressure between the pump suction and discharge gauge taps are used to determine whether a pump is running. Each switch should be wired from the normally closed contact.
1.12.3 To monitor if an adjustable frequency drive is running it is necessary to wire from each AFDs normally open run or on contact.
1.12.4 For the Technologic 5500 Controller to start and stop each AFD it is necessary to wire to the remote start terminals in each AFD.
1.12.5 Additional wiring to each of the adjustable frequency drives may be required with certain types of con­troller programs. Refer to the wiring diagram for all connection points.
1.12.6 With certain bypass and control methods it is neces­sary to disable an adjustable frequency drive from running. This is accomplished by wiring from the Technologic 5500 terminals to each AFDs interlock terminals. Should this wiring be required, any jumpers which may be found on the AFDs interlock terminals should be removed.
1.12.7 The Technologic 5500 control family may be pro­vided with the capability to accept many analog inputs. Typically all analog inputs must be 4-20mA and powered by the 24VDC power supply in the Technologic 5500. All shields must be grounded in the Technologic 5500 only to prevent ground loops and improper signals.
It is not necessary for all analog inputs to be used to monitor system zones. It is necessary, however, that all zone transmitters be connected consecutively starting with zone 1. Optional transmitters (i.e., other than zones) may be supplied.
1.12.8 Analog Input Sensors Powered By Others
The following steps describe the general procedure for rewiring an analog input sensor when the sensor’s power source is not the Technologic 5500 controller.
1) Turn off all power to the Technologic 5500 controller
2) Refer to the appropriate controller wiring diagram
that was shipped with unit. Locate the analog input sensors on the wiring diagram that will be rewired. They are labeled AI X.
3) Remove the 24 VDC positive (+) wire from TB 40
for the respective analog input sensor connection. This wire needs to be removed completely or terminated if used as a jumper, to avoid any accidental contact with a negative (-) voltage source (i.e. control panel); as this could become a short circuit. Care should be taken to ensure that 24 VDC positive (+) voltage is still provided to any remaining sensors that will still be powered by the Technologic 5500 controller.
4) Remove the 24 VDC negative (-) wire from TB 41
for the respective analog input sensor connection. This wire needs to be removed completely or terminated if used as a jumper, to avoid any accidental contact with a positive (+) voltage source; as this could become a short circuit. Care should be taken to ensure that 24 VDC (-) negative voltage is still provided to any remaining sensors that will still be powered by the Technologic 5500 controller
WARNING: Prevent electrical shocks. Disconnect the power supply before beginning installation.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Prevent electrical shocks. Disconnect
the power supply before beginning installation.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
8
5) Terminate the negative (-) wire of the sensor to TB 41 of the respective analog input sensor con­nection. Terminate the positive (+) wire of the sensor to the terminal block which is connected to the positive (+) terminal shown on the Analog input card.
NOTE: Be certain that the power supplied to other terminal blocks has not been interrupted since the wires that have been removed in the proceeding steps may have been used as jumpers.
1.12.9 Drive speed (follower) signals must be wired from the Technologic 5500 Controller to each of the adjustable frequency drives. The AFDs must be configured to accept a 0-10 VDC speed signal with the minimum speed set for 30% (0 VDC) and maximum speed set for 100% (10 VDC). All shields must be grounded in the Technologic 5500 only to prevent ground loops and improper signals.
1.12.10 Hardwire communications refers to the capability of the Technologic 5500 Controller to communicate with
an energy management system. Standard communi­cation features are listed below:
1.12.11 Remote Start/Stop
Install a switch as indicated on the wiring diagram. With the LOCAL-REMOTE-OFF switch in the REMOTE position this contact closure will provide the start signal.
1.12.12 Remote Alarm Indication
A digital output rated 8 AMPs at 115V is supplied. This output closes to indicate an alarm condition exists.
1.12.13 User Configurable I/O
The Technologic 5500 Controller comes equipped with the capability to define the operation of any unused input or output signal. Refer to Section 3.15 for detailed information on the I/O setup menus
2.0
LOCATION
2.1 Install the pumping unit appropriately for ease of inspection, maintenance and service. Observe local electrical codes concerning control panel spacing.
2.2
INSTALLATION OF SKID MOUNTED SYSTEMS WITH FACTORY SUPPLIED PUMPS
This unit is built to give you years of service; install it properly and provide a suitable foundation. A base of concrete weighing 2-1/2 times the weight of the unit is recommended. (Check the shipping ticket for unit weight.) Tie the concrete pad in with the finished floor. Use foundation bolts and larger pipe sleeves to give room for final bolt location.
2.2.1 Place the unit on its concrete foundation, supporting it with steel wedges or shims totaling 1 in thickness. These wedges or shims should be put on both sides of each anchor-bolt to provide a means of leveling the base.
2.2.2 After the frame has been leveled and securely bolted to the pad, a good grade of grout should be installed beneath the base. A suggested mixture for grout is: one part Portland Cement and two or three parts plain, sharp sand mixed with water until it will pour easily. Commercial grout mixtures with suspended iron particles are available. Wet the concrete base before pouring grout. To hold wedges or shims in place, allow the grout to flow around them and beneath the entire length of the base flange.
2.2.3 Important. Do not install and operate the Bell & Gossett Technologic 5500 pump controller in a closed system unless the system is constructed with properly sized safety and control devices. Such devices include the use of properly sized and located pressure relief valves, compression tanks, pressure controls, temperature controls and flow controls as appropriate. If the system does not include these devices, consult the responsible engineer or architect before making pumps operational.
2.2.4 Eccentric increasers can be used in the suction lines when increasing the pipe size, with straight sides of increaser on top to eliminate air pockets. Be sure to eliminate any pipe strain on the unit. Support the suc­tion and discharge pipes independently by use of pipe hangers near the unit. Line up the vertical and horizontal piping so that the bolt holes of the flanges match. DO NOT ATTEMPT TO SPRING THE SUC­TION OR DISCHARGE LINES INTO POSITION.
2.2.5 As a rule, ordinary wire or band hangers are not ade­quate to maintain alignment. It is very important to provide a strong, rigid support for the suction line. A saddle hanger is recommended.
2.2.6 For critical installations, equipment for absorbing expansion and vibration should be installed in the inlet and outlet connections of the unit.
2.2.7 Before starting, all pumps and motors should be checked for proper lubrication.
Section 2 - Installation
DANGER: The heating of water and other fluids
causes volumetric expansion. The associated forces may cause failure of system components and releases of high temperature fluids. This will be prevented by installing properly sized and located pressure relief valves and com­pression tanks.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN SERIOUS PROPERTY DAM­AGE AND SERIOUS PERSONAL INJURY OR DEATH.
DANGER: Heavy load, may drop if not lifted properly.
Do not lift the entire unit by the motor eyebolts. Lift
the unit with slings placed under the unit base rails.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
9
2.3
PUTTING THE UNIT INTO SERVICE
2.3.1 PUMP ROTATION, 3 PHASE MOTORS ONLY
With the disconnect switch engaged to the ON position, momentarily start and stop each motor . Observe the pump shaft rotation.
2.3.2 If a Bell and Gossett bypass panel is supplied, place the AUTO-OFF-HAND switch in HAND. In the HAND position the controller is off and the user has local control of the pumps through the DRIVE-BYPASS switches. Momentarily start the pump in the DRIVE and BYPASS mode.
2.3.3 If incorrect, turn the main disconnect off and refer to Section 4.9.
2.3.4 While the unit may be hydro tested at the factory to internal quality standards, there may be some joints that are not pressure tested. Some joints may have also been loosened to allow for draining of the sys­tem, and not retightened. Thus, some joints may be loose for due to system grainage or shocks during the shipping process.
All flanged joints are to be checked for tightness and proper torque of the flange bolts prior to filling the system with fluid. See the next section for proper setup.
3.1
GENERAL NOTES
3.1.1 The HELP key can be pressed at any time without disrupting system operation. The HELP key will give details on alarm conditions
or if used in conjunction with any function key will give a detailed explanation of the function key application.
3.1.2 The key names are shown as CAPITAL LETTERS and the operator interface responses are shown as bold CAPITAL LETTERS.
3.1.3 On data input screens the ENTER key can be used to advance to the next item, the CLEAR key can be used to return to the previous item.
3.1.4 When the green LEDs on the PREV. SCREEN or NEXT SCREEN keys are flashing the keys can be pressed to navigate to neighboring screens.
3.2
POWER-UP
3.2.1 Put LOCAL-REMOTE-OFF (LRO) switch in the LOCAL position. Put the optional AUTO-OFF-HAND switch in the AUTO position.
3.2.2 Turn main disconnect on.
3.2.3 The operator interface will display the Technologic Pump Controller default screen.
3.2.4 The START-STOP LED will be flashing.
3.2.5 If the START-STOP LED is not illuminated as described above, press the START-STOP button once to light the LED.
3.2.6 The Auto-Manual LED should be green for auto oper­ation. The display should also indicate
MANUAL in
the lower right hand corner. If not, press the AUTO­HAND key to enter the operation mode menu, press the SET POINT/2 key, then the ENTER key to select manual operation.
Section 3 - Setup and Features
CAUTION: Seal damage may occur. Do not run pump dry. Fill and vent the pump volute prior to oper-
ation.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
WARNING: Electrical shock hazard. Inspect all elec
trical connections prior to powering the unit. Wiring
connections must be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Electrical shock hazard. Multiple power
sources. The off position of the LOCAL-REMOTE­OFF switch does not disconnect all of the power sources in the technologic panel, All power sources must be discon­nected prior to entering the control panel.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROP­ERTY DAMAGE.
WARNING: Rotating shafts can catch loose clothing.
Do not operate the pump without all guards in place.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Failure to check all joints for tightness,
and flange bolts for proper torque, could result in
leaks and/or flooding.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PER­SONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
10
3.3
SETUP
3.3.1 Upon powering up the controller the display will light and show the following:
TECHNOLOGIC PUMP
CONTROLLER MM/DD/YY HH:MM:SS A/P Normal Manual
The current date and time will be displayed on the third line.
3.3.2 Press the SETUP/3 key once and the following will be displayed:
SETUP SELECTION: 0 1 = SENSORS 4 = TEST 2 = PUMPS 5 = DEFAULT 3 = SYSTEM 0 = EXIT
3.3.3 A detailed description of each setup menu item follows.
3.4
SENSOR SETUP
3.4.1 Press the PROCESS VARIABLE/1 key at the Setup Selection menu. Then press the ENTER key.
3.4.2 The display will show:
SENSOR NO: #
Press the numeric key(s) for the sensor you wish to set up. The sensor number is limited to the maximum number of sensors allowed, typically 16. Press the ENTER key to proceed with the set up.
3.4.3 The display will now show:
SENSOR NO # 1 - Edit 2 - Copy : #
0 – Exit
Press the PROCESS VAIABLE/1 and ENTER keys to edit the sensor setup. Continue to section 3.4.4
Press the SET POINT/2 and ENTER keys to from an existing sensor 3.4.6.
3.4.4 When sensor is set up the display will show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, DELTA T, or NONE) SPAN= # ZERO= # PV: (Y or N) SET POINT NO: ## OVERRIDE: (Y or N) OK? (Y/N)
Press the YES/7 and ENTER keys to accept the values and continue to section 3.4.6.
Press the NO/0 and ENTER keys to set up each field and skip to section 3.4.7.
3.4.5 If the sensor is not set up, the display will show:
SENSOR NO ## NONE SPAN= 0 ZERO= 0
OK? (Y/N)
Press the YES/7 and ENTER keys to accept the values and continue to section 3.4.16.
3.4.6 The displays will show:
Copy to Sensor No: # From Sensor No: #
OK (Y/N)
The copy to sensor number will refer to the sensor number for which the setup is being performed.
The from sensor will be the sensor from which the information will be copied from.
To change this valve, enter the approprite number using the key pad. Then press Enter to accept the valve.
Press the YES/7 and Enter keys to accept the values and proceed to section 3.4.4
Press the NO/0 and ENTER keys to set up each field and continue to section 3.4.7.
3.4.7 If YES is selected at the sections 3.4.4 or 3.4.5; or NO is selected from 3.4.6 the following is displayed:
DO ANOTHER ? (Y/N)
Press the YES/7 and ENTER keys to set up another sensor. Return to section 3.4.2 and repeat for all remaining sensors.
Press the NO/0 and ENTER keys to return to the setup selection screen.
3.4.8 If NO is selected at section 3.4.3, the following is dis­played:
NO: ## SENSOR TYPE: # 1 = DP, 2 = PR, 3 = Flow 4=KW, 5 = Temp, 6 = DT 7 = SysDP, 8 = SysKW, 0 = None
The following selections are valid.
1 = DP: Differential Pressure, the display will show units in PSID. 2 = PR Sns: Pressure, the display will show units in PSI. 3 = Flow: Capacity, the display will show units in GPM. 4 = KW Sns: Power, the display will show units in KW. 5 = Temp: Temperature, the display will show units in °F. 6 = Delta T: Differential Temperature, the display will show units in °F 7 = SysDP: System Differential Pressure, the display will show units in PSID. 0 = Non-standard transmitter, units will not be displayed.
3.4.9 Enter the numeric key for the type of sensor you are setting up. Press the ENTER key. The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = #####
11
3.4.10 Obtain the span of the sensor from the nameplate on the sensor. Enter the span by pressing the appropri­ate numeric keys followed by the ENTER key.
3.4.11 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ####
Typically the variable value is zero at 4mA for many sensors. An exception would be for a temperature sensor. Enter the desired zero value by pressing the appropriate numeric keys followed by the ENTER key.
3.4.12 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ##### PV: (Y or N) (Y/N)
Press the YES/7 key for all sensors that will control the system by supplying a process variable feedback signal. Typical process variable signals are supplied by one
of the following: Pressure, Differential Pressure, Temperature, or Differential Temperature Sensors.
Press the NO/0 key for all sensors that supply op­tional signals. Typical optional signals are supplied by any
of the following: System Differential Pressure, Temperature Differential Temperature, Flow, and KW Sensors.
Press the ENTER key to continue.
3.4.13 If NO is selected at the above section, skip to section
3.4.13. If YES is selected at the above section, the display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ##### PV: Y SET POINT NO ##
Enter a set point number by using the numeric key pad. Enter the number zero for all sensors that do not supply the process variable. Press the ENTER key.
Make sure the setpoint number agrees with the sen­sor number, example sensor 5 should be configured for setpoint 5. Defining the value associated with the setpoint number is defined in Section 4.14.
3.4.14 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ##### PV: Y SET POINT NO ## OVERRIDE: (Y or N) (Y/N)
The controller is capable of accepting sensor input either through a 4-20mA analog input or through the RS-485 communication port. The communication port must be set up properly and connected to an
external building automation system. The LOCAL­REMOTE-OFF switch must be in the REMOTE posi­tion to allow the controller to receive sensor informa­tion via the RS-485 port.
Press the YES/7 key to receive sensor signals via the RS-485 port. Press the ENTER key.
Press the NO/0 key to receive the sensor signals via the analog input card. Press the ENTER key.
3.4.15 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ##### PV: Y SET POINT NO ## OVERRIDE: (Y or N) OK? (Y/N)
Press the NO/0 and ENTER keys to correct any errors. By pressing the PREV SCREEN or NEXT SCREEN keys, correct the item in error.
Press the YES/7 and ENTER keys after confirming all variables are correct.
Skip to section 3.4.14
3.4.16 If NO was selected at section 3.4.9, the display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS, TEMP, PR SNS, or DELTA T, SYS KW) SPAN = ##### ZERO = ##### PV: N
OK? (Y/N)
Press the NO/0 key then ENTER to correct any errors. After pressing the ENTER key, press the PREV SCREEN or NEXT SCREEN keys to correct the item in error.
Press the YES/7 key after confirming all variables are correct.
3.4.17 The screen will now display:
DO ANOTHER ? (Y/N)
Press the YES/7 key if additional sensors must be set up. Return to section 3.4.2 and repeat for all remain­ing sensors.
Press the NO/0 key to return to the setup selection screen.
Press ENTER to continue.
3.5
PUMP SETUP
3.5.1 Press the SET POINT/2 key at the Setup Selection menu. Then press the ENTER key.
12
3.5.2 The display will show:
# PUMPS = # P1: * P2: * P3: * P4: * P5: * P6: *
OK ? (Y/N)
* The pump status will be displayed for each defined pump. The valid options are as follows:
N/A = pump not available as defined by setup Rdy = pump available, not running On = pump is running Off = pump disabled, will not be allowed to start
Press the YES/7 and ENTER keys to accept pump configuration and return to setup selection screen.
Press the NO/0 and ENTER key to set up any pumps.
3.5.3 The screen will now display:
TOTAL # PUMPS = #
Press the numeric key for the total number of pumps (1 to 6 pumps). Press ENTER to continue.
3.5.4 The screen will now display:
EDIT PUMP ? (Y/N)
Press the YES/7 and ENTER keys if any of the pumps must be set up.
Press the NO/0 and ENTER keys to return to the pump status screen and return to section 3.5.2.
3.5.5 The display will show:
EDIT PUMP # #
Press the numeric key(s) for the pump you wish to set up. The pump number is limited to the maximum number of pumps. Press the ENTER key to proceed with the set up.
3.5.6 The screen will now display:
PUMP # # ENABLE/DISABLE: #
1=ENABLE 0=DISABLE
Press the PROCESS VARIABLE/1 and ENTER keys if the pump will be enabled.
Press the NO/0 and ENTER keys if the pump will be disabled.
3.5.7 The screen will now display:
DO ANOTHER ? (Y/N)
Press the YES/7 and ENTER keys to set up another pump. Return to section 3.5.5 and repeat for all remaining pumps.
Press the NO/0 and ENTER keys to return to the pump status screen and return to section 3.5.2.
3.6
SYSTEM SETUP
3.6.1 Press the SETUP/3 key at the setup selection menu. Press the ENTER key.
3.6.2 The display will now show:
SELECTION: # 0 = EXIT 1 = STAGE/DESTAGE 2 = PID 3 - ALARMS
Press the NEXT SCREEN key.
The display now shows:
SELECTION: # 0 = EXIT 4 = ALTERNATION 5 = BYPASS 6 = AFD
Press the NEXT SCREEN key.
The display now shows:
SELECTION: # 0 = EXIT 7 = DATE/TIME 8 = PASSWORD 9 = I/O SETUP
Press the NEXT SCREEN key. The display now shows:
SELECTION: # 0 = EXIT 10 = COMMUNICATION 11 = SPECIAL FUNCTIONS 12 = CHANGE LANGUAGE
Press the NEXT SCREEN key. The display now shows:
SELECTION: # 0 = EXIT 13 = SAVE TO FLASH 14 = LOAD FROM FLASH 15 = SET BRITE/CNTRST
Use the appropriate numeric key to select the setup menu desired, press the ENTER key. A detailed description of each menu follows.
DANGER: High voltage 3 phase power can kill. Pumps can start automatically. Disconnect and lock-
out power prior to servicing pumps.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
STAGE/DESTAGE SETUP MENU ITEMS
Field
Menu Item Variable Default Range Value
Pv Stg Stg Spd: ##% 95 0-100
The maximum speed at which the lead pump will operate prior to starting a lag pump, %.
Pv Stg
Stg Proof Timer: ### s 30 0-999 Proof timer prior to starting lag pump, seconds.
Pv Stg
Stab Timer: ###s 60 0-999 Staging stabilization time, delay prior to calculating destage value, seconds.
13
PV Destg Destage: ###% 85 0-100
Enter the percentage of the stabilized speed at which the lag pump will stop, %.
PV Destg
Destg Pr Timer: ### s 30 0-999 Proof timer prior to stopping lag pump, seconds.
PV Destg
HD Spd: ### % 50 0-100 The lowest speed at which parallel pumps will operate prior to destaging the lag pump, %.
PV Destg
HD Pr Tm: ### s 30 0-999 The proof timer prior to destaging the lag pump when operating below the HD speed, seconds.
EOC Stg Pump Max Flow: ##### 0 0-65,535
The maximum flow allowable prior to starting a lag pump, GPM.
EOC Stg
Stg Proof Tm: ###s 30 0-999 Proof timer prior to end of curve staging, seconds.
EOC Stg
Flow offset: ### gpm 0 0-999 Flow rate of constant speed pump supplying variable speed pump, input only required on series pumping applications. The flow rate of the constant speed pump is deducted from the total system flow rate in order to provide end of curve protection for the variable speed pump.
EOC Dest Destage Flow: ### % 45 0-100
Enter the percent of stabilized flow at which the lag pump is destaged, %.
EOC Dest
Destage Pr TM: ###s 30 0-999 Proof timer prior to destaging lag pump, seconds.
3.7 STAGE/DESTAGE SETUP
3.7.1 The first screen is displayed below:
SELECTION: # 1 = PV STG 2 = PV DESTG 3 = EOC STG 4 = EOC DEST 0 = EXIT
By pressing the appropriate numeric key and ENTER, the setup can be completed. See the following table for all Stage/Destage menu items.
When setting up the system, recording configuration values in the Field Value column allows this manual to serve as a future reference.
14
3.8
PID SETUP
3.8.1 See the following table for all PID menu items.
3.9
ALARM SETUP
3.9.1 See the following table for all alarm menu items.
PID MENU ITEMS
Field
Menu Item Variable Default Range Value
PID PID-P ### 200 0-999
Enter the desired proportional value.
PID
PID-I ### 5 0-999 Enter the desired integral value.
PID
PID-D ### 1 0-999 Enter the desired derivative value.
PID
Reversed ? N Y or N Enter NO for direct acting control which increases output as process variable falls below setpoint. Enter YES for reverse acting control which increases output as process variable rises above setpoint.
PID
SP Deviation ### 0 0-999 Enter the value for the number of PV units at which a dead band will be created around the setpoint. The PID will be modified within the dead band per the index setting below.
PID
Index ### 0 0-999 Enter a value to buffer the response of the PID while operating in the dead band defined above. Index = 1 no impact Index = 999 maximum buffer.
ALARM MENU ITEMS
Field
Menu Item Variable Default Range Value
Alarms AFD Fail Pr Tm: ###s 20 0-999
The proof timer prior to setting the AFD fail alarm, seconds.
Alarms
Pump Fail Pr Tm: ###s 30 0-999 The proof timer prior to setting the pump fail alarm, seconds.
Alarms
O.L. Fail Pr Tm: ###s 10 0-999 The proof timer prior to setting the O.L. fail alarm, seconds.
Alarms
Reset Tm: ###s 10 0-999 The time delay between pressing the RESET key and restarting the pumps in variable speed mode. Allows for pump deceleration, seconds.
15
3.10
ALTERNATION SETUP
3.10.1 See the following table for all alternation menu items.
ALTERNATION MENU ITEMS
Field
Menu Item Variable Default Range Value
Alternation Time Between: ###hr 0 0-999
Enter the time between automatic alternation cycles, hours.
Alternation
Duration: ###s 20 0-999 The amount of time allowed to decelerate the running pump(s) and start the new lead pumps, seconds.
3.11 BYPASS SETUP
3.11.1 See the following table for all bypass menu items.
BYPASS MENU ITEMS
Field
Menu Item Variable Default Range Value
Bypass No of AFDs Fail to go to bypass: # 0 0-6
Enter the number of AFDs that are required to fail prior to running the pump(s) across the line. Generally the number of drives controlled by the system.
Bypass
No of Pumps go to bypass: # 0 0-6 After the number of AFDs fail as per above, this item determines the maximum number of pumps allowed to start in bypass. Before setting for all available pumps confirm that the system can handle the flow.
16
3.12
AFD SETUP
3.12.1 See the following table for all AFD menu items.
AFD MENU ITEMS
Field
Menu Item Variable Default Range Value
AFD AFD Min Spd: ###% 30 0-99
Enter the percent speed at which the AFD will operate with the speed follower signal minimized.
AFD
AFD Max Spd: ###% 100 0-999 Enter the percent speed at which the AFD will operate with the speed follower signal maximized.
AFD
Reset Tm: ###s 0 0-999 Enter the time it takes the AFD to reset after detecting a self protecting fault, seconds. Refer to the AFD manufacturer’s setup manual for proper set up.
AFD
Reset NO.: ## 0 0-10 Enter the number of resets the AFD will attempt after detecting a self protecting fault prior to determining that the AFD is in the fault condition. Refer to the AFD manufacturers setup manual for proper set up.
AFD
All PV Fail Spd = ### 100 0-100 Enter the % speed for the drive(s) to operate at in the event that all zones fail.
AFD
# of Pumps = # 1 0-6 Enter the number of pumps that should operate at the above speed in the event that all zones fail.
17
3.13
DATE/TIME SETUP
3.13.1 See the following table for all date/time menu items.
DATE/TIME MENU ITEMS
Field
Menu Item Variable Default Range Value
Date/Time MM
Enter the current month using both digits, example Jan. should be entered as 01.
Date/Time
DD
Enter the current date using both digits, example the 6th should be entered as 06.
Date/Time
YYYY
Enter the current year using all 4 digits.
Date/Time
HH
Enter the hours using the 24 hour format, example 9:00 p.m. should be entered as 21.
Date/Time
MM
Enter the minutes using both digits.
Date/Time
Display 24 Hour Format: ? (Y/N) N Y or N Enter yes to display the time in the 24 hour format. Enter no to display the time in AM/PM format.
Date/Time
Daylite Savings Tm: ?(Y/N) N Y or N Enter yes for automatic set back during daylight savings time. Enter no to disable the automatic setback during daylight savings time.
3.14 PASSWORD SETUP
3.14.1 See the following table for all PASSWORD menu items table missing.
PASSWORD MENU ITEMS
Field
Menu Item Variable Default Range Value
Password ENABLE PASSWORD TO SETUP MENU: ? N Y or N
Enter yes for password protection of the entire setup menu.
Password
ENABLE PASSWORD TO SET POINT MENU: ? N Y or N Enter yes for password protection of the entire set point menu.
New Password
ENTER NEW PASSWORD
> _ _ _ _ _ _< None 0-999999 If either of the above are set to yes this screen prompts the user to define the password.
Verify
VERIFY THE PASSWORD
PASSWD >_ _ _ _ _ _< After entering data in password definition screen this screen requires the user to confirm the requsted password. If the confirmed number does not agree with the first number the Enter New Password screen is repeated to allow the user to get both input screens to agree.
I/O MENU ITEMS
Field
Menu Item Variable Default Range Value
DI Opt. DI #### N/A 0-9999
Enter the input to be configured as it appears on the digital input module. The first digit is the rack number. The second digit is the slot number. The third and fourth digits are the input numbers. For example, a digital input configured on rack 0, slot 0, input 1 would be encoded as 0001
DI
Avail: ## N/A 0-99 This screen can not be modified. It is here to advise the user of how many digital inputs can be customized
DI
* Code: ### 0 0-255 Enter the code to define the desired functionality of the input. Valid codes are defined in the Appendix C of this manual.
DI
Delay: ###s 0 0-999 Enter the proof timer in seconds.
18
Field
Menu Item Variable Default Range Value
DO Total Avail. DO = O N/A 0-99
This screen can not be modified. It is here to advise the user of how many digital outputs can be customized
DO
* DO No: #### N/A 0-9999 Enter the output to be configured as it appears on the digital output module. The first digit is the rack number. The second digit is the slot number. The third and fourth digits are the input numbers. For example, a digital output configured on rack 2, slot 1, input 1 would be encoded as 2101
DO
* Code: ### 0 0-255 Enter the code to define the desired functionality of the output. Valid codes are defined in the Appendix C of this manual.
3.15 I/O SETUP
3.15.1 See the following table for all I/O menu items.
NOTE: The total available number of I/O to be config­ured is dependent on the system setup. Complete all previous setup screens, specifically pumps and sen­sors prior to completing the following.
19
Field
Menu Item Variable Default Range Value
AO Total Avail. AO = O N/A 0-99
This screen can not be modified. It is here to advise the user of how many analog outputs can be customized
AO
* AO No: ## N/A 0-99 Enter the output to be configured as it appears on the wiring diagram. The analog output card can be configured for 0-10VDC or 4-20mA signals. Remove the card from the rack, there are two switches below the pin connector on the back of the card. The bottom switch #1 configures the first analog output. The top switch #2 configures the second analog output. Select position “U” for 0-10VDC and position “I” for 4-20mA output signals.
AO
* Code: ### 0 0-255 Enter the code to define the desired functionality of the output. Valid codes are defined in the Appendix C of this manual.
* NOTE: If a programming error is made, ERROR is shown on the display. An error is due to reprogramming an input that is currently used by the system or inputting an undefined code number.
20
COMMUNICATION MENU ITEMS
Field
Menu Item Variable Default Range Value
COM COMM. Setting, Select: # 0 1-3
Select the software protocol to drive the communications on the optional RS-485 port.
1 = Bacnet, 2 = JC N2, 3 = MODBUS, 0 = EXIT
BACNET
BACnet MS/TP N/A N/A 9600, 8, 1, 1, N Slave MAC Address: 0 SP Ovrd: (Y/N)
The first line confirms setup for the BACnet protocol. The second line defines the 9600 bps baud rate, 8 bit data packets, 1 stop bit, 1 start bit and no parity. The third line requires user input. Obtain the node number from the manufacturer that supplied the device that will communicate with the Technologic Controller. Select “Y” for SP Ovrd to allow the external device to override the local setpoint data.
JCN2
Metasys N2 N/A N/A 9600, 8, 1, 1, N VND Node: # SP Ovrd: (Y/N)
The first line confirms setup for the Johnson Controls N2 protocol. The second line defines the 9600 bps baud rate, 8 bit data packets, 1 stop bit, 1 start bit and no parity. The third line requires user input. Obtain the node number from the manufacturer that supplied the device that will communicate with the Technologic Controller. Select “Y” for SP Ovrd to allow the external device to override the local setpoint data.
MODBUS
Modbus N/A N/A 9600, 8, 1, 1, N RTU Node: # SP Ovrd: (Y/N)
The first line confirms setup for Modbus protocol. The second line defines the 9600 bps baud rate, 1 stop bit, 0 start bits, and no parity. The third line requires user input. Obtain the node number from the manufacturer that supplied the device that will communicate with the Technologic Controller. Select “Y” for SP Ovrd to allow the external device to override the local setpoint data.
3.16 COMMUNICATION SETUP
3.16.1 See the following table for all communication menu items.
3.16.2 There may have been additional protocols added to the communication setup menu, contact your Bell & Gossett representative concerning additional pro­tocols and setups.
21
SPECIAL FUNCTIONS MENU ITEMS
Field
Menu Item Variable Default Range Value
Special Selection: # 1 1-2
Functions Select the special function.
1 = Pump Duty/Standby 2 = PB. Application 0 = EXIT
Pump Duty/ # of Duty Pump # # of pumps
Standby
# of Standby Pump # 0 The number of duty pumps equals the number of pumps configured in the pump setup menu. Standby pumps are those pumps that will not run unless one of the duty pumps fail.
PB. Application
PB. Setup # 0 0-2 Select the pressure booster staging scheme
1 = System Press. Alm. 2 = NFSD 0 = Exit
System High Sys. Press
Press. Alm. High Sys. Press. # 0
HSP Proof Tmr #s 0 The high system pressure is the pressure at which the high system pressure alarm will activate and the system will shut down. A manual reset is necessary to clear the alarm and restart the system
The HSP Proof timer is the amount of time, in seconds, that the system will still run while operating above high system pressure point before shutting down.
NFSD
NFSD Tst Pr. Tmr #s 0 Min Spd Pr. Tmr #s 30 Restart PV Drop 50 0 Min Run #m 10
The No Flow Shut Down test proof timer is the amount of time, in seconds, the controller will run the system while the PV is greater then SP.
The Minimum Speed Proof Timer is the amount of time, in seconds, the system will run at minimum speed before shutting off. The Restart PV Drop is the value the PV variable needs to be less then the SP in order to restart the system.
Minimum Run is the minimum amount of time, in minutes, that the system will run once it shuts down from a no flow condition and restarts.
3.17 SPECIAL FUNCTIONS
3.17.1 See the following table for special functions.
3.17.2 Your controller may have additional setup menus that were requested prior to delivery. Refer to the setup addendum that was shipped with the product for a definition of the unique setup items.
SET BRITE/CNTRST MENU ITEMS
Field
Menu Item Variable Default Range Value
Set Brite/Cntrst **WARNING** N/A Y or N
PRIOR SETTTINGS WILL BE LOADED FROM FPROM PROCEED (Y/N)
Select.
22
CHANGE LANGUAGE MENU ITEMS
Field
Menu Item Variable Default Range Value
Change Select Language: # 0 0-3
Language Select the language.
0 = English 1 = Deutsch 2 = Espanol 3 = Francais
English is the only available language at this time
SAVE TO FLASH MENU ITEMS
Field
Menu Item Variable Default Range Value
Save to Flash **WARNING** N/A Y or N
CPU YOU BE HALTED DATA WILL BE SAVED PROCEED (Y/N)
Select.
Saving to flash memory will save all setup information to the FPROM chip within the controller
3.18 CHANGE LANGUAGE
3.18.1 See the following table for language options.
3.19
SAVE TO FLASH
3.19.1 See the following table for saving setup.
LOAD FROM FLASH MENU ITEMS
Field
Menu Item Variable Default Range Value
Load to Flash **WARNING** N/A Y or N
PRIOR SETTTINGS WILL BE LOADED FROM FPROM PROCEED (Y/N)
Select.
Loading from flash memory will load all setup information that was saved to the FPROM chip within the controller
3.20 LOAD FROM FLASH
3.20.1 See the following table for loading setup.
3.21
SET BRITE/CNTRST
3.21.1 See the following table for changing screen bright­ness and contrast
23
3.22
TESTING INPUTS AND OUTPUTS
3.22.1 At the Setup Selection menu, press the ALTER­NATION/4 and ENTER keys.
3.22.2 The display will show:
TEST SELECTION: # 1=DI 4=AO 7=DISP 2=DO 5=LED 8=COMM 3=AI 6=KEY 0=EXIT
3.22.3 Press the PROCESS VARIABLE/1 and ENTER keys to test digital inputs.
The display will now show:
DIGITAL INPUTS
SLOT 0 1 SLOT 1-4 1 1234567890 1234567890 0000000000 0000000000
The zero below each corresponding input will change to a one upon receiving a digital input.
A signifies the inputs at the first digital input module and “B” signifies the inputs at the second digital input module.
Press clear to exit the test.
3.22.4 At the Test Selection screen, press the SET POINT/2 and ENTER keys to test digital outputs.
The display will now show:
DO SLOT 2-x 1 2 3 4 5 6 7 8 x x x x x x x x Enter DO# 0 (0 = EXIT)
The “x” will be replaced by the current state of the specific digital output channel. An “0” indicates that the relay is de-energized and a “1” indicates that the relay is energized which will change the state of the contacts.
Press any numeric key numbered 1-8. To change the state of the digital output press the ENTER key. To exit press “0” followed by the ENTER key.
3.22.5 At the Test Selection screen, press the SETUP/3 and ENTER keys to test analog inputs.
The display will now show: Analog Inputs:
1: ###% 4: ###% 7: ###% 2: ###% 5: ###% 8: ###% 3: ###% 6: ###% 9: ###%
The current % of span signal will be indicated next to each input 0% = 4mA and 100% = 20mA.
Press clear to exit the test.
3.22.6 At the Test Selection screen, press the ALTER­NATION/4 and ENTER keys to test analog outputs.
The display will now show:
A01 ###% A04 ###% A02 ###% A05 ###% A03 ###% A06 ###%
EXIT ? (Y/N)
The ### will be replaced by the actual digital output signal in %. The cursor will be flashing at the A01 value. Enter an alternate value by using the numeric keys and press ENTER to output the new value or press ENTER to move to the next channel.
This menu will only allow you to modify the output signals that are connected to the system, therfore A03 - A06 may not be modified unless the cor­responding output cards are attached to the system.
3.22.7 At the Test Selection screen, press the F1/5 key to test the LEDs. All of the LEDs on the left key set turn on, then turn off, then flash. The entire test takes 15 seconds to complete prior to returning to the Test Selection menu. Press the CLEAR key at any time to terminate the test and return to the Test Selection menu.
3.22.8 At the Test Selection screen, press the F2/6 key to test the keypad. The display will show:
KEY TEST PRESS A KEY FOR TESTING
Press any key except for the CLEAR key and the dis­play will confirm that the key is working by displaying the key name. After all of the keys have been tested press the CLEAR key to return to the Test Selection menu.
3.22.9 At the Test Selection screen, press the YES/7 key to test the display. The display will scroll ASCII charac­ters from right to left. All four lines will be tested at the same time. To exit the test press the CLEAR key and return to the Test Selection menu.
3.22.10 When the controller is setup to communicate with the building automation, press the INFO/8 key while at the test selection screen, to test the RS communica­tion. The display will show:
Test Communication B&G Read # B&G Write #
If the controller is communicating properly, the num­bers will continue increasing in value. For Modbus protocol the read and write numbers will be equal, BACnet and Johnson N2 protocol the numbers will not be equal. If the numbers are not increasing in value then the controller is not communicating prop­erly. If it is not communicating, check the wiring at the terminal blocks and the RS communication card mounted on the controller.
3.23
DEFAULT SETUP
3.23.1 In the event the user would like to change all of the setup variables back to the default values the default setup menu will complete the task. The default values are defined in the tables included in Sections 3.7 to
3.18. In addition all sensor and pump setup informa­tion will be erased.
Prior to completing the default setup it is strongly recommended that all factory/field variables be recorded for future reference. Use the Field Value location in the tables shown in Sections 3.7 - 3.18 to record your current data. Also record your sensor and pump setup information on the wiring diagram that was included with the unit.
24
3.23.2 Press the F1/5 key at the Setup Selection menu. Then press the ENTER key.
3.23.3 The display will show:
*WARNING* ALL SETUP DATA WILL BE OVER WRITTEN. PROCEED: ? (Y/N)
Press the NO/0 key to exit the default setup menu and save all current factory/field variables. Press the YES/7 key to load all of the pre-defined default vari­ables. Once the variables are loaded the controller will return to the display screen that was present prior to entering the setup menu.
3.23.4 After setting the default values proceed with complet­ing the system setup per Sections 3.4 to 3.18.
Section 4 - Operation
4.0 TYPE OF PROGRAM
There are nine operational programs with the Technologic 5500 family of controls. Refer to the nameplate on the front of the controller to determine which program has been furnished.
B&G
No. of Bypass
Program Pumps Provided Description
A0 1 No One Pump/One AFD A1 1 Yes One Pump/One AFD
Constant speed or variable speed operation
B3 2 Yes Two Pumps/One AFD
Either pump operating constant speed or variable speed.
C0 2 No Two Pumps/Two AFDs
Two 100% duty pumps and AFDs without staging.
D0 2 No Two Pumps and AFDs
Both pumps may stage and run variable speed.
D4 2 Yes Two Pumps and AFDs
Both pumps may stage and run variable speed or constant speed.
NOTE: Constant Speed refers to across-the-line operation.
4.0.1 Normal Scrolling Operation
Other screens may be viewed by scrolling from the Technologic Pump Controller screen shown below:
TECHNOLOGIC PUMP CONTROLLER MM/DD/YY HH:MM:SS STATUS MODE
The status portion of the display indicates the current alarm status. If
NORMAL is displayed there are no
alarms. If
*ALARM* is displayed there are alarms that
may prevent normal operation, refer to Section 4.15 for additional information.
The mode portion of the display indicates the current auto/manual mode of operation. The following table indicates all possible options:
Sections for
Additional
Mode Description Infomation
AUTO Pump Controlled by 4.1 - 4.7
Controller
MANUAL Variable Speed Pumps 4.11
Controlled by User
MAN. BPS Constant Speed Pumps 4.10
Controlled by User
4.0.2 Press the NEXT SCREEN key.
The display now shows:
PUMP STATUS P1:(RDY or N/A)P2: (RDY or N/A) P3:(RDY or N/A) P4:(RDY or N/A)P5: (RDY or N/A) P6:(RDY or N/A) STATUS MODE
Press the NEXT SCREEN key.
The display now shows:
ACTIVE VALUES Zone: ## Speed: ###% Seq: # STATUS MODE
Press the NEXT SCREEN key.
The display now shows the following if any of the transmitters are set up:
FLOW RATE: #### GPM TOTAL KW: ### SYS DP: ## EFF: ## % STATUS MODE
Press the NEXT SCREEN key.
The display now returns to the Technologic Pump Controller screen.
4.1
A0 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 1
3.7.1 PV stage speed % 0
3.7.1 EOC pump max. flow 0
3.11.1 Number of pumps in bypass 0
25
4.1.1 Local Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Press the START/STOP key. The flashing green LED will turn solid green. After a brief delay the Pump 1 LED will turn solid green indicating that it is running variable speed. It will then try to maintain setpoint by varying pump speed.
4.1.2 Remote Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
If a pump is not running this means the remote start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.2
A1 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 1
3.7.1 PV stage speed % 0
3.7.1 EOC pump max. flow 0
3.11.1 Number of pumps in bypass 1
4.2.1 Local Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Press the START/STOP key. The flashing green LED will turn solid green and the message
STARTUP-
STANDBY
will be displayed. After a brief delay the
Pump 1 LED will turn solid green indicating that it is running variable speed. It will then try to maintain set­point by varying pump speed.
4.2.2 Remote Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition
Meaning
Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
If a pump is not running this means the remote start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.4
B3 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 2
3.7.1 PV stage speed % 0
3.7.1 EOC pump max. flow 0
3.11.1 Number of pumps in bypass 1
4.4.1 Local Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
Take note of the pump sequence. Only the first pump in the sequence will run in normal operation. The sec­ond pump is a standby and will run only if the duty fails. To change which pump is the duty pump press the ALTERNATION/4 key.
Press the START/STOP key. The flashing green LED will turn solid green and the message
STARTUP-
STANDBY
will be displayed. After a brief delay the duty pump LED will turn solid green indicating that it is running variable speed. It will then try to maintain setpoint by varying pump speed.
26
4.4.2 Remote Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
If a pump is not running this means the start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.5
C0 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 2
3.7.1 PV stage speed % 0
3.7.1 EOC pump max. flow 0
3.11.1 Number of pumps in bypass 0
4.5.1 Local Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED
Condition Meaning
Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
Take note of the pump sequence. Only the first pump in the sequence will run in normal operation. The sec­ond pump is a standby and will run only if the duty fails. To change which pump is the duty pump press the ALTERNATION/4 key.
Press the START/STOP key. The flashing green LED will turn solid green. After a brief delay the duty pump LED will turn solid green indicating that it is running variable speed. It will then try to maintain setpoint by varying pump speed.
4.5.2 Remote Automatic Operation
With the Local-Off-Remote (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
If a pump is not running this means the start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.6
D0 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 2
3.7.1 PV stage speed % 95%
3.7.1 EOC pump max. flow max. pump
flow
3.11.1 Number of pumps in bypass 0
4.6.1 Local Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
Take note of the pump sequence. The first pump in the sequence will be the lead pump. The other pump will stage on if it is needed to maintain setpoint. To change which pump is the lead pump press the ALTERNATION/4 key.
Press the START/STOP key. The flashing green LED will turn solid green and the message
STARTUP-
STANDBY
will be displayed. After a brief delay the lead pump LED will turn solid green indicating that it is running variable speed. It will then try to maintain setpoint by varying pump speed. The lag pump will stage on if required.
27
4.6.2 Remote Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
If a pump is not running this means the start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.7
D4 OPERATION
Confirm the setup of the following items:
Section Item Value
3.5.3 Total # of pumps 2
3.7.1 PV stage speed % 95%
3.7.1 EOC pump max. flow max. pump
flow
3.11.1 Number of pumps in bypass 1 - 2
4.7.1 Local Automatic Operation
With the Local-Off-Remote (L-R-O) switch in the LOCAL position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
Take note of the pump sequence. The first pump in the sequence will be the lead pump. The other pump will stage on if it is needed to maintain setpoint. To change which pump is the lead pump press the ALTERNATION/4 key.
Press the START/STOP key. The flashing green LED will turn solid green and the message
STARTUP-
STANDBY
will be displayed. After a brief delay the lead pump LED will turn solid green indicating that it is running variable speed. It will then try to maintain setpoint by varying pump speed. The remaining pump will stage on if required.
4.7.2 Remote Automatic Operation
With the LOCAL-REMOTE-OFF (L-R-O) switch in the REMOTE position check that the LED indicators on the Operator Interface Panel (OIP) are as follows:
LED Condition Meaning Start/Stop Flashing Green System is stopped.
No pumps running.
Pump 1 On/Off Flashing Green Pump1 is enabled
but not on.
Pump 2 On/Off Flashing Green Pump2 is enabled
but not on.
If a pump is not running this means the start contact (from the energy management system or other source) is not closed and the controller has not been given a start signal.
Once operating in remote it is possible to stop opera­tion (i.e., override the remote start command) by either turning the L-R-O switch to off or by pressing the START/STOP key on the OIP. It is recommended to TURN THE L-R-O SWITCH TO OFF to stop the system if it is running in remote.
4.8
SPECIAL PROGRAMS
4.8.1. If your nameplate does not indicate one of the model numbers defined above the program was created per specific customer needs. The local and remote operation logic will be similar to that defined in the above sections. Job specific setup menus and draw­ings will be included with the unit. If additional infor­mation is required contact your local Bell & Gossett representative.
4.9
PUMP ROTATION
4.9.1 It will be necessary to operate all pumps in both vari­able speed and bypass to check for proper rotation.
4.9.2 Place the Technologic 5500 into operation as described in previous sections.
4.9.3 Run each pump in auto and then in bypass (if so equipped, see the next section) noting rotation in each.
4.9.4 If both rotations (AFD and bypass) are wrong, exchange the wiring on two
motor phases.
4.9.5 If the rotation is incorrect in the AFD mode but it is correct in the bypass mode, exchange the wiring on two of the AFD
output phases.
4.9.6 If the rotation is correct in the AFD mode but is in­correct in the bypass mode, exchange the wiring on two of the bypass input phases.
4.9.7
NOTE: Changing phase at AFD input does not change output phasing.
DANGER: High voltage 3 phase power can kill. Pumps can start automatically. Disconnect and lock-
out power prior to servicing pumps.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
28
4.10
MANUAL BYPASS OPERATION
4.10.1 The following programs support constant speed operation of pumps: A1, B0, B2, B3, & D4. Refer to the following steps to override the automatic opera­tion of the unit to allow manual control of the con­stant speed pumps.
4.10.2 Press the START/STOP key to stop the system. The solid green LED will flash and any running pumps will stop.
4.10.3 Press the AUTO/MANUAL key and the screen will display the following:
Enter Operation Mode
# 1 = AUTO, 2 = MANUAL 3 = MANUAL BYPASS
Where the # symbol will be replaced by 1, 2, 3 de­pending on the current mode of operation.
Press the SETUP/3 key followed by ENTER to pro­ceed to manual bypass operation.
The display will now show the following:
TECHNOLOGIC PUMP CONTROLLER
DATE TIME NORMAL MAN. BPS
4.10.4 If the PUMP LED is not flashing green, enable a pump to run in bypass by pressing the PUMP 1 or PUMP 2 key. The D4 program will allow operation of all pumps.
4.10.5 Press the START/STOP key to run the enabled pump(s) in bypass. The flashing green LED(s) will turn solid green after the pump(s) starts.
4.10.6 Press the START/STOP key to stop the system. The running pump(s) will stop.
4.10.7 Press the AUTO/MANUAL key and proceed with selecting the desired method of operation as described in Section 4.10.3.
4.11
HAND MANUAL OPERATION
4.11.1 Press the START/STOP key to stop the system. The solid green LED will flash and any running pumps will stop.
4.11.2 Press the AUTO/MANUAL key and the screen will display the following:
Enter Operation Mode
# 1 = AUTO, 2 = MANUAL 3 = MANUAL BYPASS
Where the # symbol will be replaced by 1, 2, 3 de­pending on the current mode of operation.
Press the Set Point/2 key followed by enter to pro­ceed to hand manual speed control.
This display will now show the following:
MANUAL SPEED: 0%
NORMAL MANUAL
4.11.3 If the PUMP LED is not flashing green, enable a pump to run in manual by pressing the PUMP 1 or PUMP 2 key. The D4 program will allow operation of all pumps.
4.11.4 Press the START/STOP key to run the enabled pump(s) in manual. After a brief time delay the pump(s) starts, and the flashing green LED(s) will turn solid green.
4.11.5 Press the F2/6 key to increase pump speed to a maximum of 100% of rated speed. Press the F4/9 key to decrease the speed to 0% where the pump will run at the minimum speed configured in the AFD, typically 18 HZ.
4.11.6 Press the START/STOP key to stop the system. The running pump(s) will stop.
4.11.7 Press the AUTO/MANUAL key and proceed with selecting the desired method of operation as described in Section 4.11.2.
4.12
HAND BYPASS OPERATION
4.12.1 The following programs include a Bell & Gossett bypass panel: A1, B2, B3, & D4. The bypass panel allows for switch control of the starters during system startup or failure.
4.12.2 Place the AUTO-OFF-HAND switch in HAND. The control power to the controller will be switched off, while the control power in the bypass panel will remain on.
4.12.3 Place the PUMP X (replace X by desired pump num­ber), DRIVE - BYPASS switch in the desired position.
4.12.4 To return to Automatic control place the AUTO-OFF-HAND switch in the AUTO position.
4.12.4 To return to Automatic control place the AUTO-OFF­HAND switch in the AUTO position.
4.13
SETPOINT MODIFICATION
4.13.1 To modify any of the setpoints for the transmitter configured in the setup press the SETPOINT/2 key and press ENTER.
4.13.2 The following will be displayed:
SP1 = # SP4 = # SP2 = # SP5 = # SP3 = # SP6 = #
OK ? (Y/N)
The # symbol will be replaced by the current setpoint for the specific zone. To view zones 7 - 12, press the NEXT SCREEN key once. To view zones 13 - 16, press the NEXT SCREEN key twice. To return to zones 1 - 6 press the PREV. SCREEN key the required number of times depending on the current screen on the display.
HELP SCREEN ALARM HELP/HELP SCREEN DISPLAY DETAILED DESCRIPTION
AFD Failure Check H-O-A switch, wiring , and The controller is not receiving a closed run signal
AFDs LED from AFD number X after it has been given a start
command
Battery Empty Check batterys voltage and Check for less then a 3V charge on the battery,
its continuity check battery connection
High Level Check setting of level switch Check for open or closed contacts, refer to
wire diagram for proper connection.
High Suction Check setting of the Check for open or closed contacts, refer to
HIGH SUCTION switch wire diagram for proper connection
High System Check system pressure – Check the pressure setting in the setup menu.
manual RESET required
Low Suction Check setting of the Check for open or closed contacts, refer to
low suction switch wire diagram for proper connection.
Low Level Check setting of level switch Check for open or closed contacts, refer to
wire diagram for proper connection.
NFSD System will restart automatically For variable speed, check the Reset PV Drop
when flow occurs value and the pressure sensor connections,
refer to the wire diagram. For constant speed, check the RTD connections, refer to the wire diagram.
Overload Fail Check amp draw, Use manual reset On Systems with Bell & Gossett bypasses the
if its OK controller is not receiving a digital input from the
pump number X starter confirming that it has closed
Pump Fail Check DP switch, impeller, The controller is receiving a closed signal from
coupler, motor the differential pressure switch for pump number
X after it has been given a start command
Sensor Fail Check wiring, piping, The controller is not receiving the proper 4-20mA
polarity, continuity signal from zone number X transmitter
Can IO Fail Check remote IO wire connection The controller has lost communication to the
remote IO rack
29
4.13.3 If you agree with the current setpoint settings press the YES/7 key followed by ENTER. If you would like to modify any of the setpoints press the NO/0 key fol­lowed by ENTER at which point the setpoint in the upper left portion of the screen will begin flashing.
4.13.4 Press the numeric key to modify the setpoint and press ENTER to proceed to the next setpoint. Press ENTER to advance to next zone without modification or press CLEAR to return to the previous zone.
4.13.5 After modifying all of the zones press the ENTER key until the “?” flashes, press the YES/7 key to accept the values and return to the Technologic Pump Controller screen.
4.14
PROCESS VARIABLE MONITORING
4.14.1 To view the actual process variable signals that are being sent to the controller press the PROCESS VARIABLE/1 key.
4.14.2 The following will be displayed:
PV1 = # SP1 = # PV2 = # SP2 = # PV3 = # SP3 = # PV4 = # SP4 = #
For process variables the # symbol will be replaced by the actual value. The display is updated con­tinuously as the signal fluctuates. The units for the numbers are defined in the sensor setup menu. The source of the PV signal is also defined in the sensor setup menu.
For setpoints the # symbol will be replaced by the actual setpoint value. If the setpoint is defined by the Technologic the number remains static. If the set­point is supplied by an external device the number will fluctuate as the SP signal fluctuates from the controlling device. The source of the SP value is defined in the communications setup menu.
4.15
ALARMS
4.15.1 When the controller detects an alarm condition, the display will flash
*ALARM* in the lower left corner of
the main screen.
4.15.2 The green LED on the HELP key will also flash during an alarm condition. Press the HELP key for additional information on the alarm(s). If there are more than one alarm the alarms will be listed in order of occurrence.
To view possible causes for alarms press the HELP key again after the alarm is displayed.
Refer to table below for an overview of the possible alarms and their respective causes.
4.15.3 Press the CLEAR key to return to the main screen. After addressing the source of the alarm press RESET to re-start the system and/or clear the alarms.
4.15.4 The controller logs alarms as they occur to aid in troubleshooting unobserved alarms. Refer to Section
5.13 for alarm logging information.
30
Section 5 - Maintenance
5.0 Preface: The following is a description of the hard-
ware, diagnostics, and corrective action to maintain a process being controlled by the Technologic 5500 Pump Controller.
NOTE: THE FOLLOWING SHOULD NOT BE INTER­PRETED AS THE MAXIMUM CONFIGURATION OF THIS CONTROLLER, RATHER THIS DESCRIBES ITS APPLICATION AS A TECHNOLOGIC 5500 PUMP CONTROLLER ONLY.
5.1
TECHNICAL OVERVIEW
The Technologic 5500 Pump Controller is a micro­processor based dedicated pump controller unique
Gossett. All aspects of this unit are strictly proprietary to Bell & Gossett.
The operator interface is connected (with a serial cable) to the CPU assembly.
The CPU is mounted to a rack which allows connec­tion to the analog and digital input/output modules.
5.2
DIGITAL INPUTS
The controller has provision for digital inputs with an operating voltage of 24 VDC. This signal voltage must be obtained from the 24 VDC power supply mounted to the subpanel.
It is not recommended that other power sources be used without factory approval.
Customer connections are made directly to the termi­nals mounted on the digital input module.
5.3
DIGITAL OUTPUTS
The controller has provision for relay outputs to con­trol 120 V 50/60 HZ devices.
The relays are not removable. If defective the digital output module must be returned to the factory for repair.
All relays operate as single pole single throw. Components are provided to reduce contact arc and extend electrical life.
Customer connections are made directly to the termi­nals mounted on the digital output module.
5.4
ANALOG INPUTS
Analog inputs are provided for process variables and optional transmitters. All analog inputs operate at 4-20mA. They must be powered from 24 VDC power supply included with the controller
5.5
MEMORY
The logic is stored in a non-removable EEPROM chip which can only be updated from the RS-232 program port on the CPU. The user setup data is stored in non-volatile memory or fixed RAM. The fixed RAM requires power to hold the information. While the controller is powered up the CPU controller provides the power to save the user values. When the con­troller is powered down a 3V Lithium battery provides the power to store the user values. When the battery voltage drops below 2.5 VDC the controller will dis­play
*ALARM*. After pressing the HELP key the dis-
play will indicate
# of # Low Battery. You will have
approximately 25 weeks to replace the battery before losing memory due to an under voltage condition during a power loss.
5.6
CPU
The CPU does not require any maintenance, and cannot be replaced as a field repair.
5.7
POWER SUPPLY
The power supply provides 24 VDC for all digital and analog signals as well as the CPU. It is specifically rated only for the controller and other loads should not be applied without factory approval.
The power supply is protected with 500 mA fuses on the primary and secondary circuits
The 24 VDC power supply includes overvoltage pro­tection circuitry. After detecting high output voltage the power supply will trip. 0.7 to 0.8 volts DC is pre­sent at the output of the device indicating an over­voltage trip. To reset remove power from the power supply by cycling the 115 VAC control power. If the power supply does not reset it may require re­calibration. To recalibrate you will need a DC voltmeter and a screw driver. The following steps detail calibration of the power supply:
1. Turn the silver overvoltage protection (OVP) pot.
(labeled R1, located just to the left side
of the
transformer) fully clockwise.
2. Turn the voltage adjustment pot. (labeled R9,
located below the left-hand corner of the trans­former) fully counter-clockwise.
3. Cycle power.
4. Turn R9 fully clockwise (you should read approxi-
mately 27 VDC at the output).
5. Slowly
turn R1 counter-clockwise until the unit trip and displays approximately 0.77 VDC at the output.
to and exclusively manufactured by Bell &
31
6. Turn R9 fully counter-clockwise.
7. Cycle power.
8. Slowly
turn R9 clockwise until 24 VDC is obtained
at the output.
9. Cycle power and verify that 24 VDC is present at the output.
5.8
PROTECTION
5.8.1 Analog inputs - the analog inputs provided on the Technologic 5500 Pump Controller must be wired according to the wiring diagram that shipped with the unit.
5.8.2 Protection - all analog inputs are protected from high voltage, crossed wiring, etc. A sustained fault will be limited to 20mA by the current limiting circuit.
5.8.3 Digital Inputs - as long as input power is derived from the integral 24VDC power supply they are protected.
5.8.4 Digital Outputs - each output shall not exceed the ratings on the digital output module.
5.8.5 The digital outputs are fuse protected, replace with a 5x20mm SPT 5A time lag fuse only.
5.9
INSTRUMENTS AND THEIR USE
With the diagnostics described herein extensive instruments are not required. However, the instru­ments used should be quality units to meet the fol­lowing at a minimum.
Under no circumstances shall any instrument be used to test any on board components. Especially risky is an ohmmeter with battery voltage higher than TTL logic or applied with incorrect polarity.
5.9.1 AC/DC Voltmeter -
- Input impedance shall not be less than 10 MEGOHM.
- Accuracy - AC ± 2% of Full Scale
- DC ± 3% of Full Scale
- Rated circuit to ground voltage = 1000V.
5.9.2 OHMMETER
- Accuracy ± 2_%
- Max open circuit voltage = _ volt
5.9.3 Millimeter
- Accuracy ± 2% of Full Scale
5.9.4 Signal Generator (analyzer) - recommended
A. Beta calibrator Model 434 20mA signal analyzer.
B. Altek calibrator Model 334 4-20mA loop analyzer.
Either instrument may be purchased from a Local Process Control Distributor.
NOTE: If some other instrument is used it must float above ground, preferably battery powered.
5.10
FIELD REPAIR
5.10.1 General - typical field repair should include: replacing fuses, replacing input/output modules and assuring connections are correct and secure.
5.11
PROGRAM UPDATING
To update to a new version of the program the pro­gram must be down loaded through the RS 232 port on the CPU. This can be accomplished by one of the following means:
1) Down loaded by factory authorized service techni-
cian at the job site.
2) Replacing the CPU module with one that was pre-
programmed at the factory.
3) Down loading the program from the factory to the
CPU via factory supplied modem.
Contact your Bell & Gossett representative for the preferred method of upgrading your software.
5.12
PROGRAM TYPE AND VERSION NUMBER
To check the program type and version number press the F3/8 key while at the Technologic Pump Controller screen.
5.12.1 The screen will now display:
Sys Info CPU V xxx AS V xxx OS V xxx Prog Type: xxxxx #xx Scheme Set xx
Press the CLEAR key to exit this screen.
5.12.2 The # symbol will be replaced by the actual version numbers and program type. If the factory is called for information or service on this unit this information may be requested.
5.13
DATA LOGGING
5.13.1 To view data recorded to the memory, press the F1/5 key while at the Technologic Pump – See the follow­ing table for data logging.
5.13.2 Pump – See the following table for data logging.
DANGER: Troubleshooting live control panels exposes personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: Troubleshooting live control panels exposes
personnel to hazardous voltages. Electrical trouble-
shooting must only be done by a qualified electrician.
FAIL­URE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
32
DATA LOGGING MENU ITEMS
Field
Menu Item Variable Default Range Value
Data Logging SELECTION: # 0 0-3
Select the log to view.
1 = ALARM LOG 2 = PUMP LOG 3 = DATA LOG 0 = EXIT
Pressing the Next Screen button displays
Alarm Log
DATE TIME ALARM N/A MMDD HHMM
" " " "
The four digit date is displayed in the MMDD format. The four digit time is displayed in the 24 hour HHMM format.
Pump Log
View Selection # 0 0-2 Select the pump log to view
1 = Pump Run Time. 2 = Pump On/Off Time 0 = Exit
Pump Run Time Pump Run Time N/A
P1: # P2: # P3: # P4: # P5: # P6: #
The pump run time is displayed in total accumulated elapsed time in hours.
Pump On/ Pump On/Off N/A
Off Times
P1: # P2: # P3: # P4: # P5: # P6: #
The pump on/off times are displayed in total accumulated times the pumps are switched on and off.
Signal Log
View Selection # 0 0-3 Select the signal log to view
1 = PV 2 = KWH 3 = Flow 0 = Exit
33
PV
PV: # MAX: # N/A MM/DD/YY 00:00:00 NOW: # MIN: # MM/DD/YY 00:00:00
The process variable number is displayed along with its current, maximum, minimum values. The times and dates that the max and min values occurred are also displayed. To view other process variables press the Next Screen button
KWH
KiloWatt Hours P1: # P2: # P3: # P4: # P5: # P6: #
The pump kilowatt consumption is displayed in total accumulated hours.
Flow
MAX: # NOW: # MM/DD/YY 00:00:00 MIN: # MM/DD/YY 00:00:00
The process variable number is displayed along with its current, maximum, minimum values. The times and dates that the max and min values occurred are also displayed. To view other process variables press the Next Screen button
5.14 MAINTENANCE (PHYSICAL)
5.14.1 Electrical – no maintenance is required for the electri­cal panel except to keep the modules free of dirt and dust that might hold moisture. Cabinet door should be kept closed, and the components kept dry.
5.14.2 Mechanical – If a B&G pump was supplied it was lubricated at the factory. Future lubrication should be according to the instructions that came with the pump.
If there is a danger of freezing, drain the pump. Inspect pump and system piping regularly.
For leaky seals or gaskets and loose or damaged components, replace or repair as required.
For more instruction on the B&G pumps see the fol­lowing manuals:
Manual # Description
A91310I Suction Diffuser Instruction Sheet PO6451A Series 60 Pump Installation & Operation P95200B Series 1550 Pump Instruction Sheet V50960B Triple Duty Valve with Soft Seat None Flow Transmitter None Temp/Pressure Transmitter None Misc. Transmitter PO6452 Series 60 Pump Service P70620A Series 3510 Centrifugal Pumps P70621B Series 3531 Centrifugal Pump P81547A Series 90 In-Line Mounted Pumps P81555B Series 1510 Pump Kit Instructions P81567D Series 1531 Pump Instruction Manual P81568B Series 1535 Pump Instruction Sheet P81569A Series 1522 Pump Instruction Sheet P81629C Series 80 Pump Instruction Manual P81630C VSC & VSCS Instruction Manual P81673E Series 1510/Universal Pump
Instruction Sheet
P81875A Series HSC Centrifugal Pump
34
SYSTEM PIPING AND UNIT
INSTALLATION – FINAL CHECK LIST
____ 1. Is the unit base properly leveled, grouted and
secured?
____ 2. Are all lubrication points properly lubricated?
____ 3. Are the shut-off valves to the transmitters open?
____ 4. Is the shut-off valve to the pump suction open?
____ 5. Is the shut-off valve on the discharge line open?
____ 6. Is the piping properly supported so as to prevent
strains on unit?
____ 7. Is the system, including the pumps and valving,
purged of debris and air?
____ 8. Are the pump and motor shafts properly aligned?
____ 9. Is the pump rotation correct?
ELECTRICAL WIRING AND CONTROL
SETTINGS – FINAL CHECK LIST
____ 1. Does the feeder line voltage correspond to the unit
voltage? Check the unit nameplate or motor terminal connection.
____ 2. Are the feeder wires correctly sized for the load?
____ 3. Are the fuses correctly sized? They must not exceed
1.75 times the full load current of the motor. Usual sizing is 1.15 to 1.5 times the full load current.
____ 4. Is the unit properly grounded?
____ 5. Have all the power terminals in the control panel
been checked for tightness? This is imperative since stranded wires tend to flow and become loose after initial installation.
WARNING: Electrical shock hazard. Inspect all elec-
trical connections prior to powering the unit. Wiring connections must be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
WARNING: Conduit grounds are not adequate. A
separate ground wire must be attached to the ground lug provided in the enclosure to avoid potential safety hazards.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
DANGER: High voltage 3 phase power can kill.
Disconnect and lockout power prior to servicing
unit.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
CAUTION: Seal damage may occur. Do not run
pumps dry. Fill and vent the pump volute prior to
operation.
FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN PROPERTY DAMAGE AND/OR MODERATE PERSONAL INJURY.
Appendix A
Appendix B
35
Appendix C - Valid I/O Codes
Code Function Description I/O Type Range Equate to the Signal
101 Pump 1 Status (On/Off) DO 1/0 On/Off 102 Pump 2 Status (On/Off) DO 1/0 On/Off 103 Pump 3 Status (On/Off) DO 1/0 On/Off 104 Pump 4 Status (On/Off) DO 1/0 On/Off 105 Pump 5 Status (On/Off) DO 1/0 On/Off 106 Pump 6 Status (On/Off) DO 1/0 On/Off
111 Pump 1 Failure DO 1/0 On/Off 112 Pump 2 Failure DO 1/0 On/Off 113 Pump 3 Failure DO 1/0 On/Off 114 Pump 4 Failure DO 1/0 On/Off 115 Pump 5 Failure DO 1/0 On/Off 116 Pump 6 Failure DO 1/0 On/Off
121 AFD 1 Failure DO 1/0 On/Off 122 AFD 2 Failure DO 1/0 On/Off 123 AFD 3 Failure DO 1/0 On/Off 124 AFD 4 Failure DO 1/0 On/Off 125 AFD 5 Failure DO 1/0 On/Off 126 AFD 6 Failure DO 1/0 On/Off
131 Pump 1 Overload Failure DO 1/0 On/Off 132 Pump 2 Overload Failure DO 1/0 On/Off 133 Pump 3 Overload Failure DO 1/0 On/Off 134 Pump 4 Overload Failure DO 1/0 On/Off 135 Pump 5 Overload Failure DO 1/0 On/Off 136 Pump 6 Overload Failure DO 1/0 On/Off
140 A-V Alarm Output DO 1/0 On/Off
171 Low Suction Detected, W/ Proof Time DI 1/0 On/Off 172 High Suction Detected, W/ Proof Time DI 1/0 On/Off 173 High Level Alarm Detected, W/ Proof Time DI 1/0 On/Off 174 Low Level Alarm Detected, W/ Proof Time DI 1/0 On/Off 175 Push to Silence Switch Input DI 1/0 On/Off
201 Speed Signal AO 0-100 4 - 20 ma 202 Active PV AO 0-Span 4 - 20 ma 203 System Flow Rate AO 0-Span 4 - 20 ma 204 System KW AO 0-Span 4 - 20 ma 205 System DP AO 0-Span 4 - 20 ma 206 System Efficiency AO 0-100 4 - 20 ma
211 Analog Input 1 AO 0-Span 4 - 20 ma 213 Analog Input 2 AO 0-Span 4 - 20 ma 213 Analog Input 3 AO 0-Span 4 - 20 ma 214 Analog Input 4 AO 0-Span 4 - 20 ma 215 Analog Input 5 AO 0-Span 4 - 20 ma 216 Analog Input 6 AO 0-Span 4 - 20 ma 217 Analog Input 7 AO 0-Span 4 - 20 ma 218 Analog Input 8 AO 0-Span 4 - 20 ma 219 Analog Input 9 AO 0-Span 4 - 20 ma 220 Analog Input 10 AO 0-Span 4 - 20 ma 221 Analog Input 11 AO 0-Span 4 - 20 ma 222 Analog Input 12 AO 0-Span 4 - 20 ma 223 Analog Input 13 AO 0-Span 4 - 20 ma 224 Analog Input 14 AO 0-Span 4 - 20 ma 225 Analog Input 15 AO 0-Span 4 - 20 ma 226 Analog Input 16 AO 0-Span 4 - 20 ma
36
Appendix – Drawings
Drawing # Description
1.0 Technologic 5500 Pump Controller - Door
2.0 Technologic 5500 Pump Controller - Subpanel
3.0 Operator Interface and CPU
OPERATOR INTERFACE
LOCAL-REMOTE-OFF
SWITCH
NAMEPLATE MOUNTED INSIDE DOOR
WARNING LABEL PART # S11550
NAMEPLATE MOUNTED INSIDE DOOR
WARNING LABEL PART # S11550
OPERATOR INTERFACE
LOCAL-REMOTE-OFF
SWITCH
PIN CONNECTOR
WITHOUT BYPASS
WITH BYPASS
TECHNOLOGIC 5500 PUMP CONTROLLER
(FRONT VIEW DOOR CLOSED)
DRAWING 1.0
CPU & OPERATOR
INTERFACE
SLOT 1, RS COM PORT SLOT 2, OPTIONAL I/O SLOT 3, OPTIONAL I/O
RACK 1
SLOT 6, DIGITAL INPUT
SLOT 5, ANALOG INPUT
SLOT 4, ANALOG OUTPUT
24 VDC POWER SUPPLY
SLOT 2, DIGITAL OUTPUT SLOT 1, DIGITAL OUTPUT
SLOT 0, CAN CONNECTION
RACK 2
CUSTOMER CONNECTIONS
(FRONT VIEW DOOR OPEN, BYPASS & NON BYPASS)
FUNCTION KEYS WITH LEDS
DRAWING 2.0
4 LINE DISPLAY
NUMERIC KEY PAD
TECHNOLOGIC 5500 OPERATOR INTERFACE AND CPU
DRAWING 3.0
37
Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,500 people unified in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com
Xylem Inc.
10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. S13641B August 2012
Loading...