11
3.4.10 Obtain the span of the sensor from the nameplate on
the sensor. Enter the span by pressing the appropriate numeric keys followed by the ENTER key.
3.4.11 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = ####
Typically the variable value is zero at 4mA for many
sensors. An exception would be for a temperature
sensor. Enter the desired zero value by pressing the
appropriate numeric keys followed by the ENTER
key.
3.4.12 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = #####
PV: (Y or N) (Y/N)
Press the YES/7 key for all sensors that will control
the system by supplying a process variable feedback
signal. Typical process variable signals are supplied
by one
of the following: Pressure, Differential
Pressure, Temperature, or Differential Temperature
Sensors.
Press the NO/0 key for all sensors that supply optional signals. Typical optional signals are supplied by
any
of the following: System Differential Pressure,
Temperature Differential Temperature, Flow, and KW
Sensors.
Press the ENTER key to continue.
3.4.13 If NO is selected at the above section, skip to section
3.4.13. If YES is selected at the above section, the
display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = #####
PV: Y SET POINT NO ##
Enter a set point number by using the numeric key
pad. Enter the number zero for all sensors that do not
supply the process variable. Press the ENTER key.
Make sure the setpoint number agrees with the sensor number, example sensor 5 should be configured
for setpoint 5. Defining the value associated with the
setpoint number is defined in Section 4.14.
3.4.14 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = #####
PV: Y SET POINT NO ##
OVERRIDE: (Y or N) (Y/N)
The controller is capable of accepting sensor input
either through a 4-20mA analog input or through the
RS-485 communication port. The communication
port must be set up properly and connected to an
external building automation system. The LOCALREMOTE-OFF switch must be in the REMOTE position to allow the controller to receive sensor information via the RS-485 port.
Press the YES/7 key to receive sensor signals via the
RS-485 port. Press the ENTER key.
Press the NO/0 key to receive the sensor signals via
the analog input card. Press the ENTER key.
3.4.15 The display will now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = #####
PV: Y SET POINT NO ##
OVERRIDE: (Y or N) OK? (Y/N)
Press the NO/0 and ENTER keys to correct any
errors. By pressing the PREV SCREEN or NEXT
SCREEN keys, correct the item in error.
Press the YES/7 and ENTER keys after confirming all
variables are correct.
Skip to section 3.4.14
3.4.16 If NO was selected at section 3.4.9, the display will
now show:
SENSOR NO ## (FLOW, DP, SYSDP, KW SNS,
TEMP, PR SNS, or DELTA T, SYS KW)
SPAN = ##### ZERO = #####
PV: N
OK? (Y/N)
Press the NO/0 key then ENTER to correct any
errors. After pressing the ENTER key, press the PREV
SCREEN or NEXT SCREEN keys to correct the item
in error.
Press the YES/7 key after confirming all variables are
correct.
3.4.17 The screen will now display:
DO ANOTHER ? (Y/N)
Press the YES/7 key if additional sensors must be set
up. Return to section 3.4.2 and repeat for all remaining sensors.
Press the NO/0 key to return to the setup selection
screen.
Press ENTER to continue.
3.5
PUMP SETUP
3.5.1 Press the SET POINT/2 key at the Setup Selection
menu. Then press the ENTER key.