Bell & Gossett S11865A User Manual

Page 1
INSTRUCTION MANUAL
Bell & Gossett
TECHNOLOGIC™1100 SERIES PUMP CONTROLLER
The attached pages are a revision of sections 2.3.3, 2.3.4, and 2.3.5 of the Technologic 1100 Series Pump Controller Instruction Manual (B&G Part #S11865). Replace these sections (of the manual) in entirety with the attached.
S11865
Addendum
Revision A
2.3.3 Confirm the system setup values per the following table. Use the UP or DOWN ARROW keys to move through the menu. To change values press ENTER,
Menu Default Allowable
Item # System Setup Display Value Range Field Value
01) User Password 0 0-65529
Password for entering User Setup and password protected Service Test menu.
02) Factory Setup Counter 1 1-10
# of times factory setup menu was performed. The factory menu can not be accessed without authorization from the factory.
03) Horizontal Scroll Rate 3 1-10
Horizontal scroll rate in 100 milli-second units.
04) Stage Stable 60 6-600
Staging stabilization time in seconds.
05) Destage Proof 30 3-180
Destage proof time in seconds.
06) AFD Minimum % 30 0-30
AFD minimum % speed.
07) AFD Maximum % 100 0-100
AFD maximum % speed.
08) AFD 1 Fail Time 20 5-999
Proof time for AFD 1 failure time in seconds.
09) AFD 2 Fail Time 20 5-999
Proof time for AFD 2 failure in seconds.
10) Destage % 85 0-99 Enter the percent of the stabilize pump speed to be used as a destage point.
11) Min. Destage % 0 0-100 Enter minimum % speed for staged pumps to operate.
12) Forced Dstg Tmr 0 0-999 Proof time prior to forced destaging of the lag pump when min. speed (Min. Destage %) of staged pumps is satisfied.
modify the value using the numeric key pad or UP and DOWN ARROW keys , press ENTER to accept the modification.
Packaged Systems Group
Bell & Gossett
Page 2
Menu Default Allowable
Item # System Setup Display Value Range Field Value
13) GPM Destg. Val = 0 0 0-9999 Enter GPM at which destage will be forced; “0” disables this function.
14) GPM Destg. Pr. Tmr. = 0 0 0-999 Enter in seconds (0-999) value of GPM forced destage proof timer.
15) Time Forced DeStg = 0 0 0-99 Enter in hours (0-99) time after which the lag pump will be destaged regardless of staging method (EOC or speed.) “0” disables this function.
16) DP1 Proof Time 3 0-30 Pump #1 failure proof time in seconds.
17) DP2 Proof Time 3 0-30 Pump #2 failure proof time in seconds.
18) Software DP Failure 0 0-999 Process variable value used to determine software pump failure. Enter 0 (zero) for units with differential pressure switches.
19) DP1 Start Time 30 15-60 Time period in seconds to allow Pump 1 to start prior to detecting a pump failure.
20) DP2 Start Time 30 15-60 Time period in seconds to allow Pump 2 to start prior to detecting a pump failure.
21) Speed Default 50 0-100 Operating speed (%) when all zones fail.
22) D4 Fail Mode Pumps 2 0-2 Number of pumps to run when all drives fail 0 = No pumps 1 = Lead pump 2 = Both pumps
23) Max Pump GPM 0 0-9999 End of curve pump protection.
24) Eoc Stg Pr. Tmr 30 0-999 Proof timer (in seconds) prior to starting lag pump, seconds.
25) Eoc De-Stg % 50 0-100 Percentage of maximum pump GPM at a given speed below which destaging can occur.
26) Eoc De-Stg Pr. Tmr 30 0-999 Proof timer (in seconds) prior to stopping lag pump.
27) PID Index 1 1-5 Multiplier of P, I, & D variable for slower PID response within PID index limit.
28) PID Index Limit 0 0-150 Deviation from setpoint within which PID Index is active.
2
Page 3
Menu Default
Item #
29) Invert P
System Setup Display Value Range Field Value
.I.D. No Y/N
Used to change from dir
ect to reverse
Allowable
acting. P.I.D.
30) Low Suct. Pr
. Tmr 0 0-999 Low suction alarm proof time delay in seconds. A value of 0 will disable the option.
31) High Suct. Pr. Tmr 0 0-999 High suction alarm proof time delay in seconds. A value of 0 will disable the option.
32)
High Sys. Press. 0 0-30,000 V
alue when high system pressure
alarm will be activated.
33) HSP Proof Tmr 0 0-60 Proof time prior to High System pressure shutdown.
34) NFSD Test Pr
. Tmr 0 0-999 No flow shutdown proof time delay, seconds. A value of 0 will disable the option.
35) Min Speed Pr. Tmr 30
0-999 Length of time (seconds) drive(s) will operate at min. speed during no flow shutdown sequence. If = 0 drive(s) will not stop.
36) Restart PV Drop 0 0-150 Max. difference between setpoint and process variable prior to restart after no flow shutdown. If = 0 no flow shutdown is disabled.
37) Min. Run Timer 10 0-999 Time period (minutes) to ignore no flow shutdown sequence after restart from no flow shutdown.
38) Active A-V Alarm 0 0-3 If = 0 Disabled If = 1 Low Suction Alarm only If = 2 High System Alarm only If = 3 Low Suct. & High System Alarm
2.3.4 Press the CLEAR key to return to the User Setup Menu.
2.3.5 Confirm the user setup values per the table on page 4. Use the UP or DOWN ARROW keys to move through the menu. To change values press
ENTER, modify the value using the numeric key pad or UP and DOWN ARROW keys, press ENTER to accept the modification.
3
Page 4
Loading...