Bell & Gossett P86272B User Manual

INSTRUCTION MANUAL
P86272B
Model VS Variable Speed Pump Control
DESCRIPTION
The VS is a hydronic heating control. The temperature of the
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR
SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
heating water is controlled by regulating the speed of a pump which injects water from a hot boiler loop (Primary loop) into a cooler heating loop (Secondary loop). As the speed of the pump increases, more hot water is sent into the Secondary loop, and the temperature of the heating water increases.
The VS can be used as an outdoor reset control. When the outdoor temperature falls below an adjustable start point, the heating system is activated. The temperature of the Secon­dary loop water is then automatically regulated based on outdoor temperature. The outdoor reset function maintains constant and comfortable ambient building temperature in all weather conditions.
The VS can also be used as a set point control. In this mode of operation, the VS will control the pump speed to hold a con­stant temperature (determined by the user) in the Secondary loop. The outdoor start temperature can be set to ON so the set point will be held regardless of outside temperature.
The VS is equipped with a Primary loop sensor. This sensor monitors the temperature of the boiler return water. If the boiler return water falls below an adjustable temperature, the VS can be configured to slow down the speed of the injection pump to help the boiler return water temperatures recover.
The VS can be enabled or disabled from a standard thermostat or switch, or the VS can reduce the temperature of the heating loop water when the building is not occupied or when occupants are sleeping.
REQUIREMENTS
ELECTRICAL SAFETY
WARNING: ELECTRICAL SHOCK HAZARD
Electrical connections are to be made by a qualified electrician in accordance with all applicable codes, ordi­nances and good practices. Failure to follow these instruc­tions could result in serious personal injury, death and/or property damage.
VS
Outdoor
Sensor
Secondary Loop
Sensor
Boiler Return
Sensor
VS Pump
PRIMARY
LOOP
SECONDARY
LOOP
Boiler
Primary-Secondary Variable Speed Injection Mixing
Lower Temperature System
VS
Outdoor
Sensor
Secondary Loop
Sensor
Boiler Return
Sensor
VS Pump
PRIMARY
LOOP
SECONDARY
LOOP
Boiler
Primary-Secondary Variable Speed Injection Mixing
Multiple Temperature System
VS
Outdoor
Sensor
Secondary Loop
Sensor
Boiler Return
Sensor
PRIMARY
LOOP
SECONDARY
LOOP
Boiler
Primary-Secondary
Variable Load System
VS Pump
2
OPERATIONAL LIMITS
These controls are to be used with wet rotor pumps designed to pump liquids compatible with their cast iron, bronze or stainless steel body constructions.
Electrical Rating
VS Control: 115v, 60hz, 1Ø Injection Pump: 115v, 60hz, 1Ø
Max. Rating 1/8 HP Permanent Split Capacitor
Secondary Loop Pump: 115v, 60hz, 1Ø or 230v, 60hz, 1Ø
Max. Rating of 8 amps
TYPICAL APPLICATIONS (Fig. 1)
DESIGN SELECTION
To select the correct pump, pipe size and balance valve:
1.Determine the Primary Loop Temperature. This is the temperature the primary loop will maintain.
2. Determine the Secondary Loop Temperature. This is the design temperature of the secondary loop. If an outdoor reset function is being employed, this is the required temperature of the secondary loop under maximum load.
3. Determine the design temperature drop (
T or delta T) of the secondary loop. This is the design drop in tem­perature through the secondary loop. In most radiant heat applications,
T is 10. Other types of radiation such
as baseboard have a higher design
T.
4. Determine the Maximum Injection Heat Load. This is the maximum heat requirement of the secondary loop. The maximum injection heat load is based on the injection pump running at the highest speed. As the pump speed is reduced, less heat will be delivered to the secondary loop.
5. Use the equation below to determine the design injection flow rate.
Design Injection Flow Rate (GPM) =
Maximum Injection Heat Load (BTU/hr)
500 (T
primary - Tsecondary + Tsecondary) (ºF)
6. Use the table below to select the appropriate pump, pipe size and balance valve.
Design Injection Injection B&G Circuit Setter
®
B&G Circuit Setter
®
B&G
Flow Rate (GPM) Pipe Size Balance Valve Valve Setting Pump
1.5
1
/2" CB-1/2 / CB-1/2S 18 / 25 NRF-22
3.5
1
/2" CB-1/2 / CB-1/2S full open / 6 NRF-22
6
3
/4" CB-3/4 / CB-3/4S full open / 12 NRF-22 10 1" CB-1 / CB-1S full open / full open NRF-22 15 11/4" CB-11/4 / CB-11/4S 5 / 5 NRF-22 24 1
1
/2" CB-11/2 full open NRF-33
Example:
1. Primary Loop Temp: 140ºF
2. Secondary Loop Temp: 100ºF
3. Design temperature drop: 10ºF
4. Maximum injection heat load: 150,000 BTU/hr
5. Calculate Injection flow rate Design Injection Flow Rate (GPM) =
150,000 (BTU/hr)
=
150,000
= 6 GPM
500 (140 - 100 + 10) (ºF) 25,000
6. Injection Pipe size is
3
/4", full open CB-3/4 balancing valve and NRF-22
Minimum of 1' of pipe drop required to create a thermal trap
Rule of Thumb 3 pipe diameters between tees
Minimum of 8 pipe diameters upstream and 4 pipe diameter downstream of straight pipe on either side of tees to prevent any possibility of jet flow through the common piping.
Secondary
Loop
Secondary
Loop Pump
Primary
Loop Pump
Secondary
Loop Sensor
Boiler Return
Sensor
Primary
Loop
Injection Pump
Balance
Valve
3
FIG. 2
Based on (5) feet of pipe, (4) 90° elbows, (4) tees. Correct pipe and pump size calculation for any application should be performed by a qualified engineer or contractor.
PIPING
PIPING OVERVIEW
The Primary loop may have multiple injection loops or other takeoffs. However, the piping for each injection system must meet the requirements described below.
The Injection piping can be installed in either a horizontal or a vertical configuration.
The pipe diameters of the Primary and Secondary loops may differ.
The Injection Piping diameter must be at least one pipe size smaller than the smaller of the Primary and Secondary loop piping. For example, if the Primary loop diameter is 1
1
/4" and the Secondary loop diameter is 1", then the diameter of the Injection piping must be
3
/4" or smaller.
The Injection pump motor must be a fractional B&G NRF, NBF or SSF permanent split capacitor type pump. (Refer to operational limits on Page 2 for pump information.) The Injection pump will control the amount of water pumped from the Primary loop into the Secondary loop.
A balancing valve should be installed on the injection return piping. This helps to balance the system.
The distance between the injection tees should be as short as possible. The rule of thumb distance between the tees is 3 times the pipe diameter. For instance, if the pipe diameter is 1" then the length of straight pipe between the two injection tees should be 3".
HORIZONTAL PIPING CONFIGURATION
The Injection piping can be installed horizontally as shown in Fig. 2.
The Injection supply piping should run horizontally from the Primary to the Secondary loop.
On the Injection piping it is necessary to install a heat trap to prevent heat from the Primary loop entering the Secon­dary loop when the Injection pump is not running.
The injection piping must drop down vertically at least 18" and then rise back up vertically at least 18".
VERTICAL PIPING CONFIGURATION
The Injection piping can be installed vertically.
The Primary loop must be at least 18" vertically above the
Secondary loop.
4
CAUTION: The Injection pump and pipe sizing should be performed by a qualified engineer or
contractor.
Secondary Loop Sensor
Secondary Loop Pump
Outdoor Sensor
BLUE
RED
BLACK
120 VAC
LINE NEU
Setback or Remote Enable
L O A D
Pump Starter / Motor
••
Pump
Motor
Injection
Pump
Boiler Return
Sensor
Boiler
Injection pump must be connected directly to 120VAC motor N.O. pump starter.
••
Secondary pump starter/motor can be 115V or 230V.
VS WIRING DIAGRAM (Fig. 3)
NOTE: Injection Pump and the VS Control MUST be wired to the same power circuit. The secondary loop pump can be wired to a different circuit if required.
Loading...
+ 8 hidden pages