1 Introduction and Safety............................................................................................................................................................. 3
1.2 Safety terminology and symbols................................................................................................................................................3
2 Transportation and Storage.......................................................................................................................................................4
2.1 Inspect the delivery..................................................................................................................................................................... 4
3.4 Scope of delivery......................................................................................................................................................................... 5
4.3.2 Minimum inlet pressure at the suction port..................................................................................................................... 6
4.6 Change the position of the motor housing.............................................................................................................................. 7
4.7.1 Power supply connection................................................................................................................................................... 7
5 System Description................................................................................................................................................................... 8
5.1 User interface............................................................................................................................................................................... 8
5.1.1 User interface locking/unlocking.......................................................................................................................................8
5.2.1 Control mode.......................................................................................................................................................................8
5.2.2 Night set back mode...........................................................................................................................................................9
5.2.3 ∆p-T control .........................................................................................................................................................................9
5.2.4 T-Constant temperature control........................................................................................................................................ 9
5.2.5 ∆p-∆T control ...................................................................................................................................................................... 9
5.2.8 Analog Input.........................................................................................................................................................................9
5.2.9 Signal relay........................................................................................................................................................................... 9
5.2.11 Communication bus .......................................................................................................................................................10
6 System Setup and Operation.................................................................................................................................................. 10
Configure the pump settings...................................................................................................................................................10
6.1
6.1.1 Change the communication parameters........................................................................................................................10
6.1.2 Change the control mode................................................................................................................................................ 10
6.1.3 Change the set point.........................................................................................................................................................10
6.1.4 Change the displayed unit of measurement..................................................................................................................10
6.2 Start or stop the pump..............................................................................................................................................................11
6.2.1 Automatic air venting procedure.................................................................................................................................... 11
8.3 Fault and error codes................................................................................................................................................................12
Table of Contents
ecocirc XL Installation, Operation, and Maintenance manual1
8.5 Faults, causes, and remedies................................................................................................................................................... 12
9 Other Relevant Documentation or Manuals............................................................................................................................ 13
9.1 Embedded Software and Driver Software License Agreement.......................................................................................... 13
2ecocirc XL Installation, Operation, and Maintenance manual
1 Introduction and Safety
1.1 Introduction
Purpose of this manual
The purpose of this manual is to provide necessary information for:
• Installation
• Operation
• Maintenance
CAUTION:
Read this manual carefully before installing and using the
product. Improper use of the product can cause personal injury and damage to property, and may void the warranty.
NOTICE:
Save this manual for future reference, and keep it readily available at
the location of the unit.
1.2 Safety terminology and symbols
Hazard levels
Hazard levelIndication
DANGER:
WARNING:
CAUTION:
NOTICE:
A hazardous situation which, if not
avoided, will result in death or serious injury
A hazardous situation which, if not
avoided, could result in death or
serious injury
A hazardous situation which, if not
avoided, could result in minor or
moderate injury
• A potential situation which, if
not avoided, could result in
undesirable conditions
• A practice not related to personal injury
1 Introduction and Safety
• Appropriately dispose of all waste.
• Handle and dispose of the processed liquid in compliance with
applicable environmental regulations.
• Clean up all spills in accordance with safety and environmental
procedures.
• Report all environmental emissions to the appropriate authorities.
CAUTION: Radiation Hazard
Do NOT send the product to Xylem if it has been exposed to
nuclear radiation, unless Xylem has been informed and appropriate actions have been agreed upon.
Electrical installation
For electrical installation recycling requirements, consult your local
electric utility.
Recycling guidelines
Always follow local laws and regulations regarding recycling.
FCC Statement — USA only (Federal Communications Commission)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1.this device may not cause harmful interference and
2.this device must accept any interference received, including interference that may cause undesirable operation.
This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Consult the dealer or an experienced radio/TV technician for help.
Changes or
responsible for compliance could void the user’s authority to operate
the equipment.
modifications not expressly approved by the manufacturer
Hazard categories
Hazard categories can either fall under hazard levels or let specific symbols replace the ordinary hazard level symbols.
Electrical hazards are indicated by the following specific symbol:
Electrical Hazard:
Hot surface hazard
Hot surface hazards are indicated by a specific symbol that replaces the
typical hazard level symbols:
CAUTION:
Qualified personnel
WARNING:
This product is intended to be operated by qualified personnel only.
1.3 Environmental safety
The work area
Always keep the station clean.
Waste and emissions regulations
Observe these safety regulations regarding waste and emissions:
1.4 Product warranty
Coverage
Xylem undertakes to remedy defects in products from Xylem under
these conditions:
• The faults are due to defects in design, materials, or workmanship.
• The faults are reported to a local sales and service representative
within the warranty period.
• The product is used only under the conditions that are described
in this manual.
• The monitoring equipment that is incorporated in the product is
correctly connected and in use.
• All service and repair work that is done by Xylem authorized personnel.
• Genuine Xylem parts are used.
• Only Ex-approved spare parts and accessories that are authorized
by an Ex-approved Xylem representative are used in Ex-approved
products.
Limitations
The warranty does not cover defects that are caused by these situations:
Deficient maintenance
•
• Improper installation
• Modifications or changes to the product and installation that are
made without consulting a Xylem authorized representative
• Incorrectly executed repair work
• Normal wear and tear
Xylem assumes no liability for these situations:
ecocirc XL Installation, Operation, and Maintenance manual3
2 Transportation and Storage
• Bodily injuries
• Material damages
• Economic losses
Warranty claim
Xylem products are high-quality products with expected reliable operation and long life. However, should the need for a warranty claim
arise, contact your local sales and service representative.
1.5 Spare parts
WARNING:
Only use original spare parts to replace any worn or faulty
components. The use of imitation spare parts may cause malfunctions, damage, and injuries as well as void the warranty
and the UL listing.
2 Transportation and Storage
2.1 Inspect the delivery
1.Inspect the package for damage or missing items upon delivery.
2.If applicable, unfasten the product by removing any screws, bolts,
or straps. For your personal safety, be careful when you handle
nails and straps.
3.Remove packing material from the product.
4.Dispose of all packing material in accordance with local regulations.
5.Inspect the product to determine if any parts have been damaged
or are missing.
Contact your local sales representative if there are any issues.
2.2 Transportation guidelines
Precautions
WARNING:
• Observe accident prevention regulations in force.
• Crush hazard. The unit and the components can be
heavy. Use proper lifting methods and wear steel-toed
shoes at all times.
Check the gross weight that is indicated on the package in order to select proper lifting equipment.
Position and fastening
The unit should be transported in an upright position as indicated on
the package. Make sure that the unit is securely fastened during transportation and cannot roll or fall over. The product can be safely transported at ambient temperature from -40°F to +158°F (-40°C to +70°C)
with humidity <95% (non-condensing) and protected against dirt, heat
source, and mechanical damage.
2.3 Storage guidelines
2.3.1 Storage location
NOTICE:
• Protect the product against humidity, dirt, heat sources, and mechanical damage.
• The product must be stored at an ambient temperature from
-13°F to +131°F (-25°C to +55°C) and humidity < 95% (non-condensing).
3 Product Description
3.1 Pump design
• The ecocirc XL is a large wet rotor pump with energy efficient,
electronically commutated permanent magnet motor.
• The pump is designed for systems with variable flow rates to optimize pump operation thus reducing energy consumption. The
pump can be set to any one of the multiple operating modes
available, with each designed for a
high performance and maximum energy savings.
• A single pump can handle heating, cooling, and plumbing applications with a choice for cast iron or bronze lead-free body pumps
to handle HVAC and potable water applications. The pumps are
also suitable for a 50/50 percent water/glycol circulating
built-in electrical overload and dry run protection provide safety
and protection to pump from damage.
Intended use
WARNING:
California Proposition 65 warning! This product contains
chemicals known to the state of California to cause cancer
and birth defects or other reproductive harm.
The pump is suitable for:
• Potable hot water (only with bronze pump body models)
• Hot water heating systems
• Cooling and cold water systems
The pump can also be used for:
• Solar systems
• Geothermal applications
Improper use
DANGER:
Do not use this pump to handle flammable and/or explosive
liquids.
WARNING:
Unintended use of the pump may create dangerous conditions and cause personal injury and damage to property.
WARNING:
Do NOT install this pump in swimming pools or marine areas.
Failure to follow these instructions could result in serious personal injury, death and/or property damage.
THIS IS A NON-SUBMERSIBLE PUMP
WARNING:
Do NOT exceed the maximum working pressure of the
pump. This information is listed on the nameplate of the
pump.
NOTICE:
Do not use this pump to handle liquids containing abrasive, solid, or
fibrous substances, toxic or corrosive liquids, potable liquids other than
water, or liquids not compatible with the pump construction material.
Water pH must be maintained between 7-9 and water hardness must
not exceed 14 grains/ gallon.
An improper use of the product leads to the loss of the warranty.
specific application to achieve
fluid. The
3.2 Product nomenclature
Example: ecocirc XL B 15–75
ecocirc XLhigh efficiency pump series
BPump type:
Blank = Cast iron
B = bronze pump body for pota-
ble hot water pumping
4ecocirc XL Installation, Operation, and Maintenance manual
4 Installation
Example: ecocirc XL B 15–75
-15Maximum pump head (FT)
-75Maximum pump flow rate (GPM)
3.3 Technical data
FeatureDescription
Motor modelElectronically commutated motor with perma-
Seriesecocirc XL
Rated voltage1 x 115 V ±10%
Frequency50/60 Hz
Power consumption100–1700 W
IP protectionIP 44
Insulation classClass 155 (F)
Maximum working
pressure
Liquid temperature
range
Ambient temperature
range
Ambient humidity95% non-condensing
Pumping mediaWater and water/glycol mixtures1 up to 50%.
Sound pressure≤ 43 dB (A)
EMC (electromagnetic
compatibility)
Leakage current< 3.5 mA
I/O auxiliary +15 VDC
power supply
Fault signal relayVmax < 250 VAC
CSA certificationNSF/ANSI-372 compliant (bronze body parts)
nent magnet rotor
1 x 208–230 V ±10%
The maximum pressure is indicated on pump
nameplate
175 PSI (12 bars)
14°F (-10°C) to 230°F (110°C)
32°F (0°C) to 104°F (40°C)
EN 55014-1:2006 + A1:2009 + A2:2011, EN
55014-2:1997 + A1:2001 + A2:2008, EN
61000-3-2:2006 + A1:2009 + A2:2009, EN
61000-3-3:2008, 61800-3:2004+A1:2012.
Imax < 40 mA
Imax < 2 A
3.4 Scope of delivery
Inside the package you will find:
• Pump unit
• Insulating shells for pump body — for heating applications
• O-ring to be used as replacement between motor housing and
pump body
• Two (2) gaskets for flanged connection
• 20 mm x ½” NPT electrical fitting
• IOM and Quick Start guide
4 Installation
Precautions
WARNING:
• Observe accident prevention regulations in force.
• Use suitable equipment and protection.
• Always refer to the local and/or national regulations,
legislation, and codes in force regarding the selection of
the installation site, plumbing, and power connections.
4.1 Pump handling
WARNING:
Observe local codes and regulations setting the limits for
manual lifting or handling.
Always lift the pump by the motor housing or pump body. If the pump
weight exceeds the manual handling limits, use lifting equipment with
lifting straps.
• Fastener Packs consisting of 4 bolts and 4 nuts (for 2–bolt models)
• Fastener Packs consisting of 8 bolts and 8 nuts (for 4–bolt models)
• Pressure sensor (for details see section 5.2.10 of this manual)
• Temperature sensor (for details see section 5.2.10 of this manual)
• Wireless module
• RS–485 module
1
The pump can be used with water/propylene glycol mixtures up to 50% with a maximum viscosity of 50cST at 14°F (-10°C). The pump has built-in overload and
thermal protection to protect the pump from overload due to increased fluid viscosity. Pump performance is based on 77°F (25°C). Therefore pumping of glycol
mixtures will affect max performance, depending on mixture concentration and temperature.
4.3.1 Pump location
DANGER:
Do not use this unit in environments that may contain flam-
mable/explosive or chemically aggressive gases or powders.
Guidelines
Observe the following guidelines regarding the location of the product:
ecocirc XL Installation, Operation, and Maintenance manual5
4 Installation
• Make sure that the installation area is protected from any fluid
leaks, or flooding.
• If possible, place the pump slightly higher than the floor level.
• Provide shut-off valves on the suction and discharge sides of the
pump.
• The relative humidity of the ambient air must be less than 95%
non-condensing.
• This pump is suitable for indoor use only.
CAUTION:
CAUTION: PROPERTY DAMAGE HAZARD. It is not advisable
to install circulators in an attic or upper floor over finished living space. If the circulator must be installed over head, or
over expensive equipment, provide adequate drainage in
the event of leakage. Failure to follow these instructions
could result in property damage.
4.3.2 Minimum inlet pressure at the suction port
The values in the table below are the inlet pressures above the atmospheric pressure.
• Line up the vertical and horizontal piping so that the boltholes in the pump flanges match the bolt-holes in the pipe
flanges.
• Do not attempt to spring the suction or discharge lines in position. This may result in unwanted stress in the pump body,
flange connections and piping.
• The code for pressure piping (ANSI B31.1) lists many types of
supports available for various applications.
4.4 Electrical requirements
• The NEC and local codes must be followed at all times. If a branch
circuit is
cuit breaker is suitable for use with inverter-driven appliances.
Electrical connection checklist
Check that the following requirements are met:
• The electrical wires are protected from high temperature and vibrations.
• The current type and power supply voltage connection must correspond to the
• Use wires at least 14 AWG to supply power to the pump. Follow
all local and NEC wiring codes and practices.
The electrical control panel checklist
NOTICE:
The electrical supply must match the electrical rating of the pump. Improper combination could fail to guarantee protection of the unit.
Check that the following requirements are met:
• The control panel circuit breaker be sized properly to protect the
pump against short-circuit.
• The pump has built in overload and thermal protection, no additional overload protection is required.
The motor checklist
Electrical supply and grounding wires must be suitable for at least
194°F (90°C).
fitted with ground fault circuit breaker, ensure that the cir-
specifications on the name plate on the pump.
4.5 Pump installation
1.Install the pump according to the liquid flow direction.
• The arrow on the pump housing shows the flow direction
through the pump body.
• The pump must be installed with the motor in a horizontal
position. For more information about allowed positions, refer
to the following image:
4.3.4 Piping requirements
Precautions
CAUTION:
• Use pipes suited to the maximum working pressure of
the pump. Failure to do so can cause the system to rupture, with the risk of injury.
• Make sure that all connections are performed by qualified installation technicians and in compliance with the
regulations in force.
• Do not use a shut-off valve on the discharge side in the
closed position for more than a few seconds. If the
pump must operate with the discharge side closed for
more than a few seconds, a bypass circuit must be installed to prevent overheating of the water inside the
pump.
Piping checklist
• Pipes and valves must be correctly sized.
• Pipe work must not transmit any load or torque to pump flanges.
• Be sure to minimize any pipe-strain on the pump:
• Support suction and discharge piping by the use of pipe
hangers near the pump.
2.If necessary, rotate the position of the motor for better visibility of
3.If applicable, install the thermal insulation shells.
6ecocirc XL Installation, Operation, and Maintenance manual
Figure 1: Allowed pump installation
the user interface.
Section 4.6 below describes the procedure of changing of motor
orientation.
3
2
4
6
5
1
1
2
3
L
N
115V
L
1
L
2
208-230V
CB
4 Installation
• Only use the pump thermal shells that are included in the delivery. Do not insulate the motor housing, the electronics can
overheat and cause the pump to thermally overload.
• The thermal shells that are included with the pump must only
be used in hot water circulation applications with fluid temperature above 68°F (20°C). The thermal shells are permeable to water vapor.
• If the customer installs the vapor barrier insulation shells for
cold water application, then the pump housing must not be
insulated above the motor
flange. The drain opening must
be kept unobstructed in order that the accumulated condensation can run out.
4.6 Change the position of the motor
housing
WARNING:
• Drain the system if possible or close the service valves
on both sides of the pump before disassembling the
pump. The pumped fluid can be pressurized and may
be scalding hot.
• There is the risk of escaping vapor when the motor is
separated from the pump housing.
Electrical Hazard:
Before starting work on the unit, make sure that the unit and
the control panel are isolated from the power supply and
cannot be energized.
CAUTION:
Burn hazard. During operation various surfaces on the unit
will become hot. To avoid burn injury, use heat protective
gloves.
WARNING:
• A strong magnetic field is created when the rotor is removed from or inserted into the motor housing. This
magnetic field can be harmful to pacemaker wearers
and others with medical implants. In addition, the magnetic field may attract metal parts to the rotor which can
cause injuries and/or damage the bearing of the pump.
4.Properly align and tighten the four hex-head screws (2) that
affix
the motor to the pump body (4) according to the torque table given below in a criss cross pattern.
M690 in-lb
M8170 in-lb
M10340 in-lb
CAUTION:
Check for the presence of leaks after reassembling the
pump.
4.7 Electrical installation
Precautions
WARNING:
• Make sure that all connections are performed by a qualified electrician in accordance with all applicable codes,
ordinances and good practices. Failure to follow these
instructions could result in serious injury, death and/or
property damage.
• Before starting work on the unit, make sure that the unit
and the control panel are isolated from the power supply and cannot be energized.
Grounding (earthing)
WARNING:
Reduced risk of electric shock during operation of this pump
requires the provision of acceptable grounding.
Be sure the following are adhered to. Failure to follow these instructions could result in serious personal injury, death, and/or property
damage.
• If means of connection to the supply connection box (wiring compartment) is other than grounded metal conduit, ground the
pump back to service using a copper conductor at least the size of
the circuit conductors supplying the pump.
• Connect the ground wire to the green grounding terminal in the
wiring compartment.
Figure 2: Change the position of the pump head
1.Loosen the four hex-head screws (2) that fix the motor to the
pump housing (4) using the T-handle allen wrench described.
2.Rotate the motor (1) in 90° steps to the desired position.
3.In case of separation of the motor housing from the pump body
(4):
a)avoid removing the rotating assembly from motor housing;
b)pay attention to the magnetic hazard listed before.
A defective O-ring must be replaced. An O-ring is already available inside the package as spare part.
4.7.1 Power supply connection
WARNING:
Do not make any connection in the pump control box unless
the power supply has been switched off for at least 2 minutes.
For models with standard terminal block connection:
1.Open the terminal box cover removing the screws (5).
2.Thread the ½” NPT electrical
the pump.
3.Connect the cable according to the wiring diagram.
a.Connect the ground wire, if used.
b.Connect the wires.
4.Close the terminal box cover.
Figure 3: Wiring diagram
fitting into the conduit connection of
ecocirc XL Installation, Operation, and Maintenance manual7
Start / Stop
20
1918
17
1615
14
1312
11
10987654321
CNLNO 15V
S+S- P+ P-T+ T-
AB GND AB
GND
9
8
7
6
5
4
2
1
3
Hset
5 System Description
Figure 4: Connection diagram
For cable terminations, see above connection diagram.
4.7.2 I/O connections
1.Open the terminal box cover removing the screws (5). Refer to figure 2 on page 7. Use control screwdriver described under section
4.2 to access terminal blocks.
2.Connect the appropriate wires according to the terminal block diagram and the requirements of section Connection assignment
(page 8) given below in section 4.7.3.
3.Close the terminal box cover.
• For a two-pump connection, wire them through a communication
cable connecting the 2 RS-485 ports at the pumps to terminals 15,
16 & 17.
5 System Description
5.1 User interface
Figure 5: User interface diagram
1.Control mode button
2.Control mode indicators
3.Parameter button
4.Parameter indicators
5.Setting buttons
6.Numeric display
7.Power indicator
8.Status / Fault indicator
9.Remote control indicator
Hot Surface:
Burn hazard. During the normal operation, the pump surfaces may be so hot that only the buttons should be touched to
avoid burns.
5.1.1 User interface locking/unlocking
The user interface will automatically lock if no button is pressed for ten
minutes, or if the upper setting button (5) and the parameter button (3)
are pressed for two seconds. See User interface (page 8).
If a button is pressed when the user interface is locked, the display (6)
shows:
4.7.3 Connection assignment
• For all electrical connections use heat resistant wires or cable rated for at least 194°F (90°C). The cables should not touch the mo-
To unlock the user interface, press the upper setting button (5) and the
parameter button (3) for two seconds. The display (6) will show:
tor housing, the pump or the piping.
• Power and control wires must be run in separate channels.
• Metal conduit for power wiring must only be attached to 1/2” NPT
fitting.
conduit
Now it is possible to change the pump setting as preferred.
NOTICE:
Cable glands are only available for low voltage wiring to protect
against cable slippage and vapor ingress into the terminal box.
5.2 Functions
The main functions of the pump and control modes are selectable
through the pump user interface and the embedded I/O. Advanced
functions or communication features, can only be set via bus protocol
or the optional Wireless module. See the advanced functions manual at
www.bellgossett.com.
5.2.1 Control mode
ModeDescription
Constant pressure
8ecocirc XL Installation, Operation, and Maintenance manual
The pump maintains a constant
pressure at any flow demand. The
desired head of the pump can be
set via user interface. See section
6.1.2 Change set point.
2
Hset
Hset
Max
min
Speed
setpoint
Vin[V]
Speed
[rpm]
Vset
101.51.2
min
Max
Setpoint
5 System Description
ModeDescription
Proportional pressure
The pump pressure is continuously increased/decreased depending on the increased/decreased
flow demand. The maximum head
NOTICE:
• The pump provides 5 VDC through the start / stop terminals.
• No external voltage must be provided to start / stop terminals.
• The cables connected to terminals 11 and 12 shall not exceed 65
feet in length.
of the pump can be set via user in-
Fixed speed control
terface. See section 6.1.2 Change
set point.
The pump maintains a fixed speed
at any flow demand. The speed of
the pump can be set via user interface. See section 6.1.2 Change set
point.
5.2.8 Analog Input
The pump integrates a 0-10 V analog input at terminals 7 and 8. See
terminal diagram figures for changing the setpoint. See Figure 4 on
page 8.
When a voltage input is detected, the pump switches to
control mode automatically and starts to run according to the following
diagram:
fixed speed
All the above control modes can be combined with the night mode
function.
5.2.2 Night set back mode
The night set back mode cannot be used in cooling systems.
Prerequisite
• The pump is installed between boiler outlet and system supply.
• The night set back feature is initiated when the pump recognizes a
water temperature change brought about by the boiler or high
level control system.
The night set back mode is active only in combination with:
• Proportional pressure
• Constant pressure
• Constant speed
This function reduces power consumption of the pump to the minimum
when heating system is not running. An algorithm detects the water
temperature change and automatically adjusts the speed of the pump.
The pump returns to the original set point as soon as the system restarts.
5.2.3 ∆p-T control
This function adjusts the nominal differential pressure set point according to the temperature of the pumped media.
For details refer to advanced functions manual on www.bellgossett.com
5.2.4 T-Constant temperature control
This functional mode changes the speed of the pump in order to maintain a constant temperature of the pumped media. It is suitable for
heating systems with
tic Hot Water Systems.
For details, refer to the advanced functions manual on www.bellgossett.com
fixed system characteristics, for example Domes-
Figure 6: Voltage input detected
Pump stops at 1.2 V
Pump restarts at 1.5 V
5.2.9 Signal relay
A dry contact relay is provided at terminals 4 and 5. See connection diagram, figure 4 on page 8, for location. If there is a fault, the relay contact closes to display a red status light and the error code on the user
interface display. See User interface (page 8). The relay contact closure
can also be used to energize a remote fault display.
Ratings
• Voltage: 115/208 – 230/1
• Imax < 2 A
5.2.10 External sensors (optional)
The pump can be equipped with a differential pressure sensor and a
temperature sensor according to the following table:
This function requires the external temperature probe type KTY83 (see
section 5.2.10 of this manual).
This function adjusts the nominal differential pressure set point depending on the differential temperature of the pumped media. An external temperature sensor Type: KTY83 is required for this functionality
(see section 5.2.10 of this manual for details).
For details, refer to the advanced functions manual on www.bellgossett.com
5.2.6 ∆T constant
This function alters the speed of the pump in order to maintain a constant differential temperature of the pumped media.
For details, refer to the advanced functions manual on www.bellgossett.com
5.2.7 External start/stop
The pump can be started or stopped via an external dry contact or a
relay that is connected to terminals 11 and 12. The pump unit is provided by default, with the terminals 11 and 12 jumpered. See Figure 4 on
page 8.
ecocirc XL Installation, Operation, and Maintenance manual9
Pressure sensor setup
1.Install pressure sensor on the pipe
2.Connect wires at terminals 9 and 10. See Figure 4 on page 8.
3.Power the pump on.
4.Upon startup, the pump detects the sensor and displays the setup
menu.
5.Select the right sensor model and confirm the selection using the
parameter button (3). See User interface (page 8).
6.The pump will run through the startup sequence and automatically start working in constant pressure mode.
7.The setpoint can be changed using the settings button (5). See
User interface (page 8).
External temperature sensor setup
The external temperature sensor setup and related control modes are
available only through RS-485 or wireless module connection.
For details refer to advanced functions manual on www.bellgossett.com
mode
mode
mode
mode
mode
mode
6 System Setup and Operation
Wireless module
The wireless module is an optional module, to be coupled with the
ecocircXL circulators. When correctly configured, it generates a wireless network accessible by a mobile device, tablet or a personal computer. See wireless module instructions manual for details.
5.2.11 Communication bus
The pump has a built-in RS-485 communication channel (terminals
15-16-17). See Figure 4 on page 8.
The pump can communicate with external BMS systems via Modbus or
BACnet protocol. For a complete description of the protocols, refer to
the advanced functions manual at www.bellgossett.com.
NOTICE:
When remote control is active, the set points and control modes are
managed only through communication channels and cannot be
changed via the user interface. The displayed quantity and unit of
measurement remain active on the user interface.
5.2.12 Automatic two-pump operation
Backup operation
Only the lead pump runs. The second pump starts in case of failure of
the lead pump.
Alternate operation
Only one pump runs at the time. The working time is switched every 24
hours so that workload is balanced between both pumps. The second
pump is started immediately in case of failure of the lead pump.
Parallel operation
Both pumps run simultaneously at the same set point. The lead pump
determines the behavior of the full system and is able to optimize the
performance. To guarantee the required performance with the minimum power consumption, the lead pump starts or stops the lag (second) pump to satisfy system requirement of
flow and head.
Wait until the power indicator light turns off.
2.Switch on the pump.
3.When the display shows COMM (COM), press the parameter button (3) to access the communication menu.
4.Select one of the below parameters using the settings button (5).
• ADDR (ADD) = address setup (available address 1-255 for
Modbus 0÷127 for BACnet)
• MODU (MDL) = optional module setup (0 = no module; 1 =
Wireless module; 2 = RS-485 module)
5.Press the parameter button to enter the submenu
6.Edit the values using setting buttons.
7.Press the parameter button to
8.Press mode button to exit the submenu.
9.Repeat above procedure for each of the three parameters.
If no buttons are pressed for 10 seconds, then the pump exits the cur-
rent menu and continues start-up procedure. All the parameters that
are changed but not
confirmed restore back to previous state.
confirm and store the new values.
6.1.2 Change the control mode
The pump can be controlled by a BMS (Building management system)
or other devices through the RS-485 communication port via Modbus
or BACnet protocol.
The following instructions are used when making the change on the
user interface. See User interface (page 8).
• Press the operating mode button (1).
• The operating modes are cyclically changed by the pressed button.
6 System Setup and Operation
Precaution
CAUTION:
Always wear protective gloves when handling the pumps and
motor. When pumping hot liquids, the pump and its parts
may exceed 40°C (104°F).
NOTICE:
The pump must not run dry as this can result in the destruction of the
bearings. Fill the system correctly with liquid and vent the air before
first start-up.
NOTICE:
• Never operate the pump with discharge valve closed for longer
than a few seconds.
• Do not expose an idle pump to freezing conditions. Drain all liquid that is inside the pump. Failure to do so can cause liquid to
freeze and damage the pump.
• The suction plus shut-off discharge pressure must not exceed the
pump pressure rating.
• Do not use the pump if cavitation occurs. Cavitation can damage
the internal components.
6.1 Configure the pump settings
Change the pump settings using one of the following methods:
• User interface
• Bus communication
• Wireless communication
6.1.3 Change the set point
See User interface (page 8).
1.Press one of the arrow setting buttons (5).
The display starts to blink.
2.Change the value using the buttons (5).
3.Wait 3 seconds to store and activate the new set point.
The display will stop blinking to confirm the change.
NOTICE:
If a check valve is installed on the system, ensure that the pump head is
sufficient to allow flow through the system.
6.1.4 Change the displayed unit of measurement
Power, Flow, Head and Speed parameters cyclically change by pressing the parameter button (3). In order to change the unit of measurement, follow these steps:
1.Press the button (3) to change the unit of measurement. See User
interface (page 8).
6.1.1 Change the communication parameters
Change pump communication parameters. See User interface (page 8).
1.Switch off the pump.
10ecocirc XL Installation, Operation, and Maintenance manual
Power
Speed
Head
Flow
Parameter
button
Parameter
button
Parameter
button
Parameter
button
2.When flow and head are displayed, by pressing the button (3) for
more than one second at each of these parameters, the unit of
measurement automatically changes as below:
• Flow: m3/h ↔ gpm (US)
• Head: m ↔ ft
7 Maintenance
6.2.2 Activate automatic two-pump operation
Once the communication cable is connected, configure only the “lead”
pump. The twin pump submenu for this configuration is available at
each power-on, when the drive is displaying SING (which stands for
“Single Pump).
The following procedure must be executed during the start-up phase
of the pump.
1.Enter the two-pump sub menu when the display is showing
TWMA (two-pump master) or TWSL (two-pump slave).
2.Select the applicable two-pump operation.
• bcup = backup operation
• alte = alternative operation
• para = parallel operation
3.Push the parameter button to activate the new setting.
The second pump is
configured by the lead pump.
6.2 Start or stop the pump
CAUTION:
• The pump must not run dry as this can result in premature failure of the bearings in a very short time. Fill and
vent the system correctly before first start-up. The pump
rotor chamber will be vented after the pump is powered
on with an automatic air venting procedure. "deg" will
be displayed indicating degassing process.
NOTICE:
The system cannot be vented through the pump.
• Start the pump in one of the following ways:
• Switch on power to supply the pump.
• Close the start/stop contact by jumpering terminals 11 and
12 or through a remote dry contact..
• Send start command through the communication bus.
The pump starts pumping in constant pressure mode with the following default set points:
7.5 ft15–XX (Max head 15 ft)
10 ft20–XX (Max head 20 ft)
18 ft36–XX (Max head 36 ft)
20 ft40–XX (Max head 40 ft)
27.5 ft55–XX (Max head 55 ft)
32.5 ft65–XX (Max head 65 ft)
For more information about how to change setting, see Configure
the pump settings (page 10).
• Stop the pump in one of the following ways:
• Switch off power supply to the pump.
• Open the start/stop contact.
• Send stop command through the communication bus.
6.2.1 Automatic air venting procedure
At each power-on of the pump unit, an automatic air venting procedure is executed. During this phase, the user interface displays "deg"
(degassing) and a count-down begins until the completion of the procedure.
The procedure can be recalled or skipped:
• Manually by pressing simultaneously the two buttons (5). See User
interface (page 8). The feature will remain disabled until power to
pump is disconnected.
The procedure can be permanently enabled or disabled by:
• Manually by pressing simultaneously the two buttons (5) for at
least 10 seconds. See User interface (page 8). Or
www.bellgossett.com.
• Via communication bus. See the advanced functions manual on
7 Maintenance
Precaution
Electrical Hazard:
Disconnect and lock out electrical power before installing or
servicing the unit.
Wait 2 minutes before opening the conduit box.
WARNING:
• Always wear protective gloves when handling the
pumps and motor. When pumping hot liquids, the
pump and its parts may exceed 40°C (104°F).
• Maintenance and service must be performed by skilled
and qualified personnel only.
• Observe accident prevention regulations in force.
• Use suitable equipment and apply personal protection.
• Risk of property damage, serious personal injury or
death. You must repair or replace the pump if corrosion
or leakage is found.
8 Troubleshooting
Introduction
See User interface (page 8).
• In case of any alarm that allows the pump to continue running, the
display shows a blinking alarm code and the last quantity selected, while the status indicator (8) becomes orange.
• In case of a failure that stops the pump, the display shows the error code permanently and the status indicator (8) becomes red
8.1 Periodic inspection
Bell & Gossett ecocircXL circulators are designed to provide years of
trouble-free service. It is recommended that periodic inspections be
made to check for potential problems with the pump. If any leakage or
evidence of leakage is present, repair or replace the unit.
8.2 Display messages
Table 1: Default
Operating LEDs / DisplayCause
Power OnPump powered
All LEDs and display OnStart-up of the pump
Status Green lightPump is working properly
Remote OnRemote communication is activated
ecocirc XL Installation, Operation, and Maintenance manual11
8 Troubleshooting
Table 2: Fault messages
Operating LEDs / Display
Power OffPump is not connected
Status light OrangeAlarm for system prob-
Status light RedPump failureCheck the displayed
Remote OffRemote communica-
CauseSolution
or is incorrectly connected
Power failureCheck power supply
lem
tion is deactivated
Check connection
and circuit breaker
Check the displayed
alarm code and find
cause from table 8.3.
error code and find the
cause from table 8.2.
If the communication
does not work, check
the connection and the
configuration parameters for communication
on the external controller.
8.3 Fault and error codes
Error codeCauseSolution
E01Internal communication lostRestart the pump
E02High motor currentRestart the pump
E03DC Bus overvoltageIndicates excessive
E04Motor stallRestart the pump
E05Data memory corruptedRestart the pump
E06Voltage supply out of operating
range
E07Motor thermal protection tripCheck the presence of
E09Hardware errorRestart the pump.
E10Dry runCheck for system leak-
power through the
pump. Confirm system
setup, verify correct
position and operation of check valves.
Check the electrical
system voltage and
wiring connection.
foreign material
around impeller and
rotor that cause overload. Check installation conditions and
temperature of the
water and ambient air.
Wait until the motor is
cooled. If the error
persists try to restart
the pump2.
ditions and ambient
air temperature.
age or fill the system.
2
2
2
2
8.4 Alarm codes
Alarm code CauseSolution
A01Fluid sensor malfunctionSwitch off the pump for 5
A02High temperature of the
fluid
A03Automatic speed reduction
to prevent inverter overheating
A05Data memory corruptedSwitch off the pump for 5
A06External temperature
probe malfunction
A07External pressure sensor
malfunction
A122–pump communication
lost
A20Internal alarmSwitch off the pump for 5
minutes and then power
on.
If the problem persists,
contact local B&G representative.
Check water temperature
value
Check installation conditions and rectify status of
the system
minutes and then power
on. If the problem persists,
contact local B&G representative.
Check the probe and the
connection to the pump
Check the sensor and the
connection to the pump
If both pumps show the
A12 alarm, check the connection between the
pumps. If one of the pump
is switched off or shows another error code, check the
section 8.1 and 8.2 to
the problem
minutes and then power
on. If the problem persists,
contact local B&G representative.
find
8.5 Faults, causes, and remedies
The pump does not start
CauseRemedy
No power.Check the power supply and ensure that
Tripped circuit breaker or
ground-fault protection device or the circuit breaker.
The pump starts but the thermal protection is triggered after a short
time
CauseRemedy
Incorrect wiring size or circuit break-
er rating not suitable for motor current.
Thermal overload protection due to
excessive input.
Missing a phase in the power supply. Verify continuity and ensure
it is properly terminated to the pump
power.
Reset power supply circuit breaker and
determine cause for overload.
Check and replace the components as necessary.
Check the pump working conditions.
proper wiring connections.
2
Switch off the pump for 5 minutes and then power on. If the problem persists, contact service.
12ecocirc XL Installation, Operation, and Maintenance manual
The pump is noisy
CauseRemedy
Not thoroughly vented.Switch off the pump and after 30 seconds
Cavitation due to insuffi-cient suction pressure.
Foreign objects in pump.Clean the system.
Worn out bearingContact local B&G representative.
switch on again to restart the automatic
air-venting procedure.
Increase the system suction pressure
within the admissible range.
9 Other Relevant Documentation or
Manuals
9.1 Embedded Software and Driver Software
License Agreement
With the purchase of the product, the terms and conditions of the license for the software embedded on the product are considered accepted. For more information see license condition on www.bellgossett.com
9 Other Relevant Documentation or Manuals
ecocirc XL Installation, Operation, and Maintenance manual13
Xylem |’zīləm|
1) The tissue in plants that brings water upward from the roots
2) A leading global water technology company
We're 12,500 people
unified in a common purpose: creating innovative solutions to meet our world's
water needs. Developing new technologies that will improve the way water is used, conserved, and
re-used in the future is central to our work. We move, treat, analyze, and return water to the
environment, and we help people use water
efficiently, in their homes, buildings, factories and farms.
In more than 150 countries, we have strong, long-standing relationships with customers who know us
for our powerful combination of leading product brands and applications expertise, backed by a
legacy of innovation.
For more information on how Xylem can help you, go to xyleminc.com
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
USA
Tel: (847) 966-3700
Fax: (847) 965-8379
www.bellgossett.com
Visit our Web site for the latest version of this document
and more information
The original instruction is in English. All non-English
instructions are translations of the original instruction.