Bell & Gossett IMOSSSR00 User Manual

INSTRUCTION MANUAL
IMOSSSR00
Oil Smart® Simplex Panel
Model #A1SEE1
INSTALLATION MANUAL
OIL SMART SIMPLEX SYSTEM
The Oil Smart Simplex System, when combined with a manual sump pump, will automatically pump water without the risk of pumping oil into the environment. Additionally, the system alerts maintenance or building personnel in the event of a high oil or high water condition. Installation of the Simplex Panel allows you to comply with Elevator Code ASME A17.1 and State/Federal regulations while reducing the risk of adverse publicity, fines and expensive cleanup costs.
FEATURES
Patented Oil Smart® and Liquid Smart® Controls with 20' cords and mounting brackets.
Indoor/Outdoor NEMA 4X Heavy Duty Polycarbonate Enclosure: 10"x8"x4", color gray material 94V-2,
polycarbonate, IP-56 rating.
Voltage: 120/208/240 VAC single phase 50/60 hz
CSA International Certified No. 229294
External Mounting Feet: Quick installation
5. Run pump cable, Liquid Smart® cable, and Oil Smart® cable through conduit. Make field connections as shown on wiring diagram (see page
3).
6. Run power line conductor through conduit. Wire to terminals per enclosed schematic. Branch circuit protection to be provided by end-user.
COMPONENTS INSTALLATION
1. The Oil Smart Pump Switch and Liquid Smart Alarm Sensor shall be mounted in a clean environment, clear of mud and all metallic debris.
2. The switches shall be installed where the water intrusion will not directly contact or splash the white plastic case.
3. Mud or other conductive materials left on the body of the switches will hamper its operation; take effort to clean the switch prior to initial installation.
4. Mount with enclosed mounting brackets. Note: Keep sensors at least 2" clear of any metallic material.
High liquid alarm with test and silence features, red beacon alarm light, white light for water present, yellow light for oil present, high 85 decibel audible alarm. Complete dry contacts for each alarm condition.
HOA switch and green light for pump run
ALL INSTALLATIONS MUST BE IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND ANY OTHER APPLICABLE STATE AND LOCAL ELECTRICAL REQUIREMENTS.
PANEL INSTALLATION
1. CAUTION: To maintain the NEMA 4X rating, make
all wiring connections with seal tight cable grips or conduit connections to be supplied by end user.
2. Determine mounting location for control panel.
Mount panel using mounting feet supplied.
3. Determine hole location on panel for liquid-tight
or conduit connections. Attach connectors and conduits.
TESTING
Liquid Smart® Alarm Sensor: Fill small cup supplied with oil. Submerge only the plastic lens (optic sensor) into oil, the alarm will activate showing oil present (yellow light). Now touch finger to the exposed stainless steel sensor, the alarm will show water present (white light) will turn on.
4. If pump is present, it is important that the alarm
circuit is independent of the pump to assure that the alarm will activate if pump circuit fails.
2