Hoffman Specialty Model 62 Vacuum Breaker
®
CAUTION
• Before using this product read and understand instructions.
• Turn off steam or water before servicing.
• To prevent serious burns, wear heat resistant gloves when handling hot equipment.
Failure to follow this caution could result in property damage or personal injury.
OPERATION
As system pressure falls sufficiently below atmospheric pressure to
compress the spring, the vacuum breaker will open, allowing air to enter the system. The vacuum breaker is factory set to open at approximately 2 inches Hg vacuum. It is adjustable from 1/4” to 20” (8 - 508 mm) Hg vacuum.
Temperature 
R
egulator
Hot Water Converter
Y
Strainer
F & T
Trap
F & T
Trap
Y Strainer
Y Strainer
S
team
Supply
Cold
W
ater Supply
Drain
Vacuum Breaker
Thermo
Bulb
Storage Tank Water Heater
F & T
Trap
Temperature
Regulator
Y
Strainer
Vacuum Breaker
Temperature
Regulator
Vacuum 
Breaker
Tankless
Water Heater
Y
Strainer
F & T
Trap
INSTALLATION –
STEP 1 - Determine Where to Install the Vacuum Breaker
TYPICAL PIPING DIAGRAMS
The Model 62 vacuum breaker can be installed vertically or horizontally. However, installing the vacuum breaker horizontally results in fouling of the seating surface, which prevents tight sealing. The life of the o-ring may be increased by installing the vacuum breaker in a standpipe where temperatures are lower.
Adjusting the Set Point
To increase the vacuum breaker set point, increase the spring tension. To decrease the vacuum breaker set point, decrease the spring tension.