Bell & Gossett HS 793 User Manual

INSTRUCTION MANUAL
I-793
REVISION B
Hoffman Specialty® No. 793 Drain Valve Capacity: Discharge Orifice
for operating pressures up to 150 psig, 3/32" seat for operating pressures over 150 psig, 5/64" seat
CAPACITY
Pressure
(PSIG)
15
30
50
80
100
125
150
200
250
Capacity (Lbs. of Water per Hour)
3/32 Orice
375
530
690
870
975
1100
1200
5/64 Orice
220
315
400
510
570
630
690
800
900
FIG. 1
FIG. 1. INSTALLATION FOR SMALL AMOUNT OF WATER. 3/4 MIN.
PIPE SIZE & SHORT AS POSSIBLE WITH GATE VALVE. FIG. 2. INSTALLATION WITH VENT LINE TO DOWN STREAM SIDE
OF AIR SEPARATOR & SIDE INLET TO DRAIN VALVE FOR FAST FLOW OF WATER TO DRAIN VALVE.
FIG. 3. INSTALLATION NEAR COMPRESSED AIR TANK WITH VENT LINE & SIDE INLET. LOCATION OF DRAIN VALVE MAY BE VARIED VERTICALLY IN RELATION TO TANK FOR LONG DISCHARGE, INFREQUENT OPERATION OR IF WATER IN TANK IS OBJECTIONABLE LOWER DRAIN VALVE BELOW TANK AS SHOWN.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett