Bell & Gossett HS 601G User Manual

INSTRUCTION MANUAL
!
HS-601
REVISION G
Hoffman Specialty
®
Pilot Operated Pressure and/or Temperature Steam Regulators Series 2000
WARNING
CAUTION
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of steam systems in accordance with all applicable codes and ordinances.
• To prevent serious burns, wear heat resistant gloves when opening and closing steam valves, or handling hot e
• To prevent serious personal injury from steam pipe blow down, connect a temporary pipe between the steam pipe opening and a drain, or stand at least 100 ft. (30m) from the front of the pipe opening.
• To prevent property damage, personal injury, or death, cap off the gate valves if they are not connected to a drain and when they are not in use for test or pressure relief.
Failure to follow this warning could cause property damage, personal injury or death.
quipment.
WARNING
PLANNING THE INSTALLATION
Planning for the Main Valve Installation
1. The regulator main valve must be located in an accessible straight run of horizontal piping.
OTE: Main valve must be installed with diaphragm
N located on bottom, as shown in Main Valve Installation illustration, page 3.
2. Allow clearance on top of the main valve to remove the cover plate to inspect and service the valve.
3. Allow clearance under the main valve diaphragm cover to replace diaphragms and drop out the stem for service.
4. Piping should be sized per good engineering practice. HVAC applications generally use 6,000 FPM velocity. Industrial applications generally use 8,000 to 10,000 FPM.
5. Blow out all piping with steam or compressed air before installing the main valve to remove mill scale and dirt.
6. Use long radius elbows in the low pressure piping. Avoid the use of bull-headed tees.
7. Provide a bypass line with a globe valve to allow inspection without interrupting service.
8. Install pressure gauges on inlet and outlet sides of regulator to indicate system performance.
9. Install drip traps to prevent:
• Accumulation of condensate that can cause water
hammer and destroy the main valve and pilot diaphragms.
• Slow response times that cause temperature or
pressure fluctuations.
10. Install "Y" Strainers in steam lines with the dirt pocket turned to the side to prevent collection of condensate that can be carried into the regulator and cause water hammer.
11. Install pressure relief valves in accordance with local nd national codes. The relief valve must be capable
a of passing the full capacity of the regulator with its largest seat trim.
Select the relief valve opening set point pressure
ased on the downstream pressure from the regulator.
b The actual relief valve set point pressure depends on the relationship of the flow (load) to the main valve rated capacity.
For systems with spring or air pilots:
Determine the relief pressure set point pressure for systems as follows:
Downstream Flow Relief valve
System (Load) opening set
Pressure (DSP) Condition point pressure
< 35 psig < 50% of capacity DSP + 5 psig
< 35 psig 51% of capacity (1.1 x DSP) + 5 psig
36 psig < 50% of capacity DSP + 10 psig
36 psig 51% of capacity (1.1 x DSP) + 10 psig
For systems with temperature pilots only:
The steam system relief valve opening set point pressure is based on the supply steam inlet pressure to the regulator and must be set as follows:
Supply Steam Relief valve Inlet Pressure opening set
(SSIP) point pressure
< 35 psig SSIP + 5 psig
36 psig SSIP + 10 psig
12. Locate temperature regulators close to the temperature sensing location. The temperature pilot capillary tube must allow the sensing bulb to be fully inserted into the system fluid.
Planning for the Pilot Installation
1. The pilot valves can be installed on either side of the main valve. The main valve is shipped with the U-tubing and the bleed orifice installed for left-hand side mounting of the pilot valves. (U-tubing is mounted on the right-hand side and the bleed orifice is installed on the left-hand side.)
If right-hand side mounting of the pilot(s) is desired, the U-tubing and the bleed orifice must be relocated to the opposite sides of the main valve.
Note: Right-hand side and left-hand side positioning is determined when the main valve inlet directly faces the observer.
2. Determine which pilot(s) are to be used for the instal­lation. Multiple pilots can be used in combination on one main valve. Mount the pilot(s) as follows:
• SLD Solenoid Pilot
Always mount closest to the main valve.
2
• SPS Spring or AP Air Pressure Pilots
When used in combination with other pilots,
always mount spring or air pilots furthest from the main valve.
• STPA Temperature Pilot When used with pressure pilot mount closest to
main valve.
When used with pressure and solenoid pilots –
mount between pressure and solenoid pilots.
• 315 PNT or 240PNT Pneumatic Temperature Pilots
Mounted remotely from main valve.
• GT610-IP Electronic Pilot (used with customer supplied temperature sensor and controller)
Mounted remotely from main valve.
3. Hardware kits containing steel pipe nipples and copper tube lines are required to mount the pilots. Refer to "Mounting Hardware for Pilot Installation" Page 4.
N
10 Pipe
Diameters
O
M
H
F
G
E
J
L
P
R
S
Z
Y
X
W
U
V
T
B
A
C
K
D
INSTALLATION DETAIL
Main Valve Installation
1. Connect a steam line (A) from the steam supply to the area where regulator valve is to be located. Install tee fittings (B) for a bypass line, and (C) for the regulator line.
Note: Drip traps prevent condensate from collecting in the piping during light loads or when the regulator is closed. Collected condensate in the piping ahead of the regulator can cause water hammer when the regulator opens.
2. Install a shut off valve (E) to allow servicing the trap.
3. Provide a dirt pocket ahead of the strainer to allow large solids to drop out.
4. Install a drip trap (H), Y-strainer (F) equipped with a screen and blow down valve (G).
5. Cap the blow down valve outlet to prevent steam discharge due to accidental opening of valve.
6. Connect a horizontal pipe from tee (C).
7. Connect a reducer (D), if required, to reduce the steam line to the pipe size of the main valve.
Use additional reducers when the pipe needs to be reduced more than two pipe sizes. When noise is a concern, reducers should not have more than a 15 degree taper.
8. Install shut off valve (J) and Y- strainer (K). Turn the strainer so that the screen is horizontal to prevent condensate from collecting in the screen pocket.
Condensate pockets can carry with the steam flow, causing water hammer that can destroy the main valve diaphragms.
9. Install a strainer blow down valve (L).
10. Cap the blow down valve outlet to prevent steam discharge due to accidental opening of valve.
11. Install tee, siphon loop tube, petcock, and pressure gauge.
On NPT sized regulator valves, install a pipe union (M)
12. to allow regulator removal for service or replacement.
13. Use compressed air or steam to clean piping before installing the regulator.
• Cap off the end of the steam line.
• Remove caps from the strainer blow down
valves (G) and (L).
• Turn on the steam or air to full pressure and allow
it to blow down for five minutes.
• Close off compressed air or steam.
• Allow piping to cool below 100˚F.
• Reinstall end of line caps on blow down valves.
• Remove cap from end of the steam line.
14. Install main valve (N) with the direction arrow pointing to the low-pressure side outlet piping.
NPT sized regulator valves:
• Use pipe sealant on male threads only, keeping the
sealant out of the system.
• Use a wrench on the flats of the body to tighten
the joint.
• Use the wrench on the side of the body that is being
tightened to prevent stress and distortion on the body.
Flanged regulator valves:
• Inspect flange surfaces and gaskets.
• Tighten flange bolts using a star pattern. Uneven
bolting may cause steam leakage.
15. Install silencer orifice plate (when used) immediately after the main valve:
NPT sized regulator valves: Install orifice plate between two ASME flanges.
Flanged regulator valves: Install the orifice plate between the valve flange and the outlet pipe flange.
16.
On NPT sized regulator valves, install a pipe union (O) to allow regulator removal for service or replacement.
17. Install gate valve (P).
18. Install pipe tee (R) for bypass connection.
3
19. Install the bypass piping and globe valve (T).
1
2
4
3
5
1076
1
9
4
8
5
10
76
• Use the same size pipe for the bypass piping and globe valve in the bypass line as the main valve (N) to allow manual regulation during service of regulator.
Support piping to remove any stress from the
• regulator valve body before connecting to the system.
• Make sure pipes and flanges are properly aligned to
revent stress on the regulator valve body.
p
20. Install pipe reducer (S) to increase the pipe size, if necessary, to meet the velocity requirements.
Use additional reducers when the pipe needs to be increased more than two pipe sizes.
21. Install a 1/4 NPT pipe tapping (U) at least 10 pipe diameters downstream in a straight run of the enlarged pipe for the pressure gauge and feedback line (for spring and/or air pilots) connection.
PILOT INSTALLATION
Mounting Hardware for Pilot Installation
Note: For heat exchanger shell applications, it is recommended that the feedback line and pressure gauge be installed directly into the heat exchanger shell.
22. Install pressure relief valve (V) in the downstream iping as required by codes.
p
23. Install a tee fitting (W) for pressure feedback line.
4. Install a siphon loop tube (X), petcock (Y) and
2
pressure gauge (Z) in vertical port of tee fitting (W).
25. Connect system piping to complete the installation.
26. Refer to "Pilot Installation" for pilot mounting and
piping instructions.
Kit A – For spring or air pilots only or in combination with temperature or solenoid pilots.
Kit B – For temperature pilot or solenoid pilot only.
Hardware Kit Components
No Part Description Kit A Kit B
1 L-Tubing; from main valve bottom XX
Elbow connection to tee fitting Branch connection.
2 S-Tubing; from bleed orifice fitting X
to tee fitting on pilot.
3 Nipple, 1/4 NPT x 4" (101mm) X
4 Nipple, 1/4 NPT x 1-1/2" (38mm) (2) XX
5 Union Connection, 1/4 NPT Female XX
6 Tee fitting XX
7 L-fitting XX
8 Bushing X
9 J-Tubing; From bleed orifice fitting X
to tee fitting on pilot.
10 1/8" Tubing connector XX
4
1. L-Tube
C
D
A
B
Cut L- tube to appropriate A & B dimensions listed on Tubing Length chart. No cutting is required if dimension is marked with an *.
9. J-Tube
No cutting of J-tubes
s required
i
2. S-Tube
Cut S- tube to appro­priate C & D dimen­sions listed on Tubing Length chart. No cutting is required if dimension is marked with an *.
Tubing Length
DIMENSIONS
ABCD
PILOT MAIN VALVE SIZE In mm In mm In mm In mm
1/2 NPT, 3/4 NPT, 1 NPT 6.0 152 7.6 178 6.4 163 3.5 89
1-1/4 NPT, 1-1/2 NPT 6.8 173 8.1 206 6.4 163 4.8 122
2 NPT, 2 (50) * 8.6 218 8.2 208 6.4 163 * 5.7 145
Spring or Air 2-1/2 (65) 10.6 269 9.1 231 6.4 163 5.9 150
3 (80) 11.2 284 9.4 239 6.4 163 6.4 162 4 (100) 13.0 330 10.3 262 6.4 163 7.9 200 6 (150) *16.6 422 12.3 312 6.4 163 * 9.5 241
1/2 NPT, 3/4 NPT, 1 NPT 6.0 152 11.3 287 *10.0 254 3.5 89
1-1/4 NPT, 1-1/2 NPT 6.8 173 11.7 297 *10.0 254 4.8 122
2 NPT, 2 (50) * 8.6 218 * 11.9 302 *10.0 254 * 5.7 145
Combination 2-1/2 (65) 10.6 269 12.8 325 *10.0 254 5.9 150
Pilots 3 (80) 11.2 284 13.1 333 *10.0 254 6.4 162
4 (100) 13.0 330 13.9 353 *10.0 254 7.9 200 6 (150) *16.6 422 * 14.9 378 *10.0 254 * 9.5 241
1/2 NPT, 3/4 NPT, 1 NPT 5.2 132 7.9 200
1-1/4 NPT, 1-1/2 NPT 6.0 152 8.6 218
2 NPT, 2 (50) 7.8 198 8.8 223
Temperature 2-1/2 (65) 9.8 249 9.7 246
3 (80) 10.4 264 10.0 254 4 (100) 12.2 310 10.9 277 6 (150) 15.8 401 12.0 305
* No cutting of tube length is required.
5
A
D
10 Pipe
Diameters
C
B
Bleed Orifice
The function of the bleed orifice is to bleed steam off the
ain valve diaphragm when the pilot(s) close(s). A 1/16"
m (1.6mm) diameter orifice is standard, and is installed in
he outlet side of the main valve when shipped. This
t diameter orifice is used in most applications.
In special situations, the bleed orifice may be drilled out to 3/32" (2.4mm) diameter to produce faster closing time of the main valve and thus improve response time.
• A 3/32 in. (2.4mm) diameter orifice should NOT be
used in conjunction with a temperature pilot, as accuracy of temperature control will be reduced.
Pilot Installation Detail
• Typical applications for 3/32 in (2.4mm) diameter leed orifice may include:
b – Pressure differential across the reducing valve is
0 psig (3.5 bar) or greater.
5
– High pressure PRV on a 2-stage pressure
reducing station.
– Pressure reducing valve with a fast acting
pneumatic temperature regulator downstream of the main valve.
Applies to All Pilots
1. The pilot valve(s) can be installed on either side of the main valve. The main valve is shipped with the U-
tubing and the bleed orifice installed for left-hand side mounting of the pilot valve(s). If right-hand side mounting of the pilot(s) is desired, the U-tubing and the bleed orifice must be relocated to the opposite sides of the main valve.
Note: Right-hand side and left-hand side positioning is determined when the main valve inlet directly faces the observer.
2. Make sure the bleed orifice is installed in the 1/8 NPT
tapping on the outlet end of the main valve on the opposite side from the U-tubing. Remove the 1/8 NPT pipe plug from the bleed orifice and replace it with a 1/8 NPT x 1/4" (6mm) OD tubing, straight compression fitting (from the hardware kit).
3. Install the 1/4 NPT x 1-1/2" (38mm) nipple and half of
the union connection (from the hardware kit) on the inlet end of the main valve.
6
Use the 1/4 NPT x 4" (101mm) nipple and the remaining
4. half of the union connection (from the hardware kit) to mount the first pilot. Mount additional pilots as required using 1/4" steel pipe nipples.
5. Install the copper tee fitting (from the hardware kit) in the 1/8 NPT signal tapping on the side of the last pilot with the tee pointing down.
6.
Install the L-fitting (from the hardware kit) in the tapping at the center of the main valve diaphragm cover.
Note: For steps 7 and 8, trim the length of the copper tubing as required (see "Tubing Length Chart", page
5) to make a neat installation. Be sure to ream the
tube to the full tube diameter after cutting.
7. Install the S- or J-copper tubing (from the hardware kit) from the tee fitting to the bleed orifice.
8. Install the L- copper tubing (from the hardware kit) from the bottom of the tee fitting to the L-fitting in the main valve diaphragm cover.
Outlet
Balance Tube
Bleed O
rifice
Signal
Feedback Line
Main Valve Inlet
Pilot Inlet
S
pring
Pilot
Air Supply
Feedback Line Balance Tube
Outlet
Bleed Orifice
Main Valve Inlet
Pilot Inlet
Signal
AP Air Pilot
Air PRV Regulator
High Pressure Supply Air
T
emperature
S
ensor
Balance Tube
S
ignal
Temperature Pilot
Outlet
Bleed Orifice
Main Valve I
nlet
Pilot Inlet
Spring/Air Pilots
!
!
Flow from System
Pipe Tee
Pipe Bushing
Sensing Bulb
1. The 1/4" feedback tapping must be connected to the downstream piping for either a spring or air pressure pilot:
• Use 1/4 black steel pipe for the feedback line (B).
• Install a 1/4 NPT shut off valve (D) and union (C)
in this line to allow service of the pilot while operating the system on the by-pass line.
• The feedback line must pitch away from the pilot
to avoid erratic operation, excessive fouling and eliminate water pockets.
2. When the regulator is used with a heat exchanger, connect the feedback line (B) to the heat exchanger shell. A tee fitting can be installed in the heat exchanger for a vacuum breaker connection.
Temperature Pilots
CAUTION
Temperature pilot bulb will be immersed in the heated fluid. Before immersing, check compatibility of copper bulb with heated fluid. Failure to insure compatibility may cause property damage.
CAUTION
System should be supplied with overheat protection (such as temperature relief valve or aquastat solenoid combination) at 10˚F over set temperature. Failure to fol­low this warning may result in property damage, personal injury, or death.
1. When only a temperature pilot is used, the outlet tapping port must be reduced. Use the 1/8 x 1/4 NPT bushing (from the hardware kit) in the 1/4 NPT outlet.
2. Insert the sensing bulb so the full length of the bulb is exposed to the fluid whose temperature is being controlled.
a) Use a 1/2 NPT compression fitting to install the
bulb at the outlet of instantaneous heaters and in the middle of storage tanks.
b) The preferred bulb mounting when installed in
the system piping is illustrated below:
3. For air pilot installations, connect the regulated air pressure supply to the top of the pilot bonnet.
c) Optional dry well (separable socket) allows the
sensing bulb to be removed from the tank or piping without draining the system.
• When using a dry well, coat the bulb with high temperature grease or heat transfer compound, to aid heat transfer.
• Make sure that bulb and dry well are fully inserted into the fluid being controlled.
7
Temperature and Spring Pilot Combination
Spring Pilot
O
utlet
B
alance Tube
S
elf-Contained Temperature Pilot
Bleed O
rifice
Main Valve I
nlet
P
ilot Inlet
Air Supply
Feedback Line Balance Tube
Outlet
Bleed Orifice
Main Valve Inlet
Pilot Inlet
S
ignal
A
P Air 
Pilot
Temperature Sensor
315 PNT
T
emperature
Pilot
Air PRV Regulator
High Pressure Supply Air
Main
Branch
Supply Air Port
Branch Air Port
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y
y


yy
yy

yyy
y
Signal Port
Reverse Acting Signal Port
1/2" NPT
Direct Acting
Signal Port
Pneumatic Temperature and Air Pilot Combination
1. Install the temperature pilot next to the main valve.
2. Install a 1/4" NPT nipple between the outlet tapping port of the temperature pilot and the inlet port of the spring pilot.
3. The 1/4" feedback tapping port of the spring pilot must be connected to the downstream piping:
• Use 1/4 black steel pipe for the feedback line.
• Install a 1/4 NPT shut off valve and union in the
feedback line to allow service of the pilot while operating the system on the by-pass line.
• The feedback line must pitch away from the pilot to
avoid erratic operation and excessive fouling and to eliminate water pockets.
4. When the regulator is used with a heat exchanger, connect the feedback line (B) (see illustration on page 6 to the heat exchanger shell. A tee fitting can be installed in the heat exchanger for a vacuum breaker connection.
5. Insert the sensing bulb of the temperature pilot so the full length of the bulb is exposed to the fluid whose temperature is being controlled.
a) Use a 1/2 NPT compression fitting to install the
bulb at the outlet of instantaneous heaters and in the middle of storage tanks.
b) The preferred bulb mounting when installed in the
8
system piping is illustrated on page 7.
c) Optional dry well (separable socket) allows the
sensing bulb to be removed from the tank or piping without draining the system.
• When using a dry well, coat the bulb with high
• Make sure that bulb and dry well are fully inserted
temperature grease or heat transfer compound, to aid heat transfer.
into the fluid being controlled.
Series 315 PNT Pilot
1. Connect a regulated air supply to the "Reverse Acting" inlet port of the 315 PNT pneumatic temperature pilot.
2. Do not plug the "Direct Acting" inlet port of the pneumatic temperature pilot. This port serves as an air bleed.
3. Connect the output "Signal" port of the pneumatic temperature pilot to the top of the AP-1A or AP-4A pneumatic air pilot.
Series 240 PNT Pilot
1. Connect a regulated air supply to the "Supply Air" port of the 240 PNT pneumatic temperature pilot.
2. Connect the output "Branch Air" port of the pneumatic temperature pilot to the top of the AP-1A or AP-4A pneumatic air pilot.
Loading...
+ 16 hidden pages