INSTRUCTION MANUAL
HS219C
Dura-Stat
™
Thermostatic Module
For Dunham-Bush
Thermostatic Traps,
Model 1E, 1/”
CAUTION: TURN OFF STEAM SUPPLY
VALVE AND ALLOW RADIATOR TO COOL
BEFORE REPLACING MODULE.
1 Remove the cover from the trap. Then,
unscrew the old thermostatic element from the
cover using a
old element.
IMPORTANT: After removing the old element,
be sure to remove any scale or debris from the
trap body interior. NOTE: Some traps may
include a threaded seat insert. If so, do not
remove this seat when installing Dura-Stat.
2 Install the replacement Dura-Stat Module in
the Model 1E trap body by inserting the module
into the machined seat. Then, place the
retainer spring included with the Dura-Stat
Module on top of the module as shown to the
right.
1
"
open-end wrench. Discard the
⁄2
1
COVER (SAVE)
OLD ELEMENT
(DISCARD)
2
RETAINER
SPRING
3
NEW DURA-STAT
MODULE
3 Securely (leak tight) re-install the cover on
the trap body, taking care to ensure that the
retainer spring and module remain squarely in
the trap body. Open the radiator supply valve.
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. HS-219C October 2012 Part No. 510665