Bell & Gossett HS 219C User Manual

INSTRUCTION MANUAL
HS219C
Dura-Stat
Thermostatic Module
For Dunham-Bush Thermostatic Traps, Model 1E, 1/”
CAUTION: TURN OFF STEAM SUPPLY VALVE AND ALLOW RADIATOR TO COOL
BEFORE REPLACING MODULE.
1 Remove the cover from the trap. Then, unscrew the old thermostatic element from the cover using a old element.
IMPORTANT: After removing the old element, be sure to remove any scale or debris from the trap body interior. NOTE: Some traps may include a threaded seat insert. If so, do not remove this seat when installing Dura-Stat.
2 Install the replacement Dura-Stat Module in the Model 1E trap body by inserting the module into the machined seat. Then, place the retainer spring included with the Dura-Stat Module on top of the module as shown to the right.
1
"
open-end wrench. Discard the
2
1
COVER (SAVE)
OLD ELEMENT
(DISCARD)
2
RETAINER
SPRING
3
NEW DURA-STAT
MODULE
3 Securely (leak tight) re-install the cover on the trap body, taking care to ensure that the retainer spring and module remain squarely in the trap body. Open the radiator supply valve.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. HS-219C October 2012 Part No. 510665