Bell & Gossett HS 218B User Manual

INSTRUCTION MANUAL
HS218B
Dura-Stat
Thermostatic Module
For Barnes & Jones Thermostatic Traps, Model 122, 1/”
CAUTION: TURN OFF STEAM SUPPLY
1 Remove the cover from the trap. Then, remove the old thermostatic element from the trap body. Discard the old element.
IMPORTANT: After removing the old element, be sure to remove any scale or debris from the trap body interior, especially in the area around the machined seat.
2 Install the replacement Dura-Stat Module in the Model 122 trap body by inserting the module into the machined seat. Then, place the retainer spring included with the Dura-Stat Module on top of the module as shown to the right.
VALVE AND ALLOW RADIATOR
!
TO COOL BEFORE REPLACING MODULE.
1
COVER (SAVE)
OLD ELEMENT
(DISCARD)
2
RETAINER
SPRING
3
NEW DURA-STAT
MODULE
3 Securely (leak tight) re-install the cover on the trap body, taking care to ensure that the retainer spring and module remain squarely in the trap body. Open the radiator supply valve.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. HS-218B October 2012 Part No. 510666
Loading...