Bell & Gossett HS-203C Engineering Data Manual

Page 1
• Application
• Selection
• Piping Diagrams
Hoffman Specialty® Steam Traps
ENGINEERING DATA MANUAL
HS-203C
Page 2
Contents
3
Introduction
Steam Trap Functional Requirements 4 Operation, Advantages, Disadvantages
and Primary Applications 5
Chapter 1
Selection Guide Chart 10 4-Step Method for Sizing 11 Helpful Hints, Formulas and Conversion Factors 12 Properties of Saturated Steam 13 Steam Flow in Pipes 15 Condensation in Pipes 15
Chapter 2
Flash Steam Explanation and Calculation 16 Operating Pressure Limits 17 Installation and Calculating Differential Pressure 18 Drip Traps for Distribution Pipes 20
Chapter 3
Selecting Traps for Heat Exchangers 24 Lock-out Traps for Start-up Loads 27 Draining Condensate to Overhead Returns 28 Draining Submerged Coils 29 Jacketed Kettles 30 Cylinder Dryers 31 Unit Heaters 31 Steam Radiators 32 Typical Piping for Steam Heating 33 Trapping Steam Tracer Lines 39
Chapter 4
4-Step Method for Sizing Steam Lines 40 4-Step Method for Sizing Return Lines 42
Chapter 5
Testing Steam Traps 43
Chapter 6
Definition of Heating Terms 46
Page 3
Steam Trap Functional Requirements
Selecting the proper type of steam trap is an important element in steam systems.
There are many types of steam traps each having its unique characteristics and system benefits. Hoffman Specialty offers thermostat­ic, thermodisc, float and thermostatic, and bucket traps which are the most commonly used types. Deciding which type of trap to use is sometimes confusing and, in many cases, more than one type can be used. The follow­ing is intended to point out system conditions that may be encountered and the characteris­tics of each type of trap.
Within steam systems, important considera­tions must be taken into account. These con­siderations include venting of air during start-up; variations of system pressures and condensing loads; operating pressure and system load; continuous or intermittent opera­tion of system; usage of dry or wet return lines; and overall probability of water hammer.
Air Venting
At start-up all steam piping, coils, drums, tracer lines, or steam spaces contain air. This air must be vented before steam can enter. Usually the steam trap must be capable of venting the air during this start-up period. A steam heating system will cycle many times during a day. Fast venting of air is necessary to obtain fast distribution of steam for good heat balance. A steam line used in process may only be shut down once a year for repair and venting of air may not be a major con­cern.
Modulating Loads
When a modulating steam regulator is used, such as on a heat exchanger, to maintain a constant temperature over a wide range of flow rates and varying inlet temperatures, the condensate load and differential pressure across the trap will change. When the conden­sate load varies, the steam trap must be capable of handling a wide range of condi­tions at constantly changing differential pres­sures across the trap.
Differential Pressure Across Trap
When a trap drains into a dry gravity return line, the pressure at the trap discharge is nor­mally at O psig. When a trap drains into a wet return line or if the trap must lift condensate to an overhead return line, there will normally be a positive pressure at the trap discharge. To assure condensate drainage, there must be a positive differential pressure across the trap under all load conditions.
Water Hammer
When a trap drains high temperature conden­sate into a wet return, flashing may occur. When the high temperature condensate at saturation temperature discharges into a lower pressure area, this flashing causes steam pockets to occur in the piping, and when the latent heat in the steam pocket is released, the pocket implodes causing water hammer. Floats and bellows can be damaged by water hammer conditions.
When traps drain into wet return lines, a check valve should be installed after the trap to prevent backflow. The check valve also reduces shock forces transmitted to the trap due to water hammer. Where possible, wet returns should be avoided.
Application
The design of the equipment being drained is an important element in the selection of the trap. Some equipment will permit the conden­sate to back up. When this occurs the steam and condensate will mix and create water hammer ahead of the trap. A shell and tube heat exchanger has tube supports in the shell. If condensate backs up in the heat exchanger shell, steam flowing around the tube supports mixes into the condensate and causes steam pockets to occur in the conden­sate. When these steam pockets give up their latent heat, they implode and water hammer occurs, the water hammer often damages the heat exchanger tube bundle. The trap selec­tion for these types of conditions must com­pletely drain condensate at saturation temperature under all load conditions.
Steam mains should be trapped to remove all condensate at saturation temperature. When condensate backs up in a steam main, steam flow through the condensate can cause water hammer. This is most likely to occur at expan­sion loops and near elbows in the steam main.
Applications such as tracer lines or vertical unit heaters do not mix steam and conden­sate. In a tracer line, as the steam condens­es, it flows to the end of the tracer line. Back up of condensate ahead of the trap does not cause water hammer. Steam does not pass through condensate.
Vertical unit heaters normally have a steam manifold across the top. As the steam con­denses in the vertical tubes, it drains into a bottom condensate manifold. Because steam does not pass through the condensate, water hammer should not occur.
4
Introduction
Page 4
FLOAT & THERMOSTATIC TRAP
The condensate port is normally closed during no load. As condensate enters the float cham­ber, the seat opens to provide drainage equal to the condensing rate.
Primary Applications
Heating main drip traps. Shell & tube heat exchangers. Tank heaters with modulating temperature
regulators. Unit heaters requiring fast venting. Steam humidifiers. Air blast heating coils. Air pre-heat coils. Modulating loads. Fast heating start-up applications.
TRAP OPERATION
A review of the trap operating principle will show how various types of traps meet the dif­ferent system characteristics.
Float & Thermostatic Traps
Advantages
Completely drains condensate at satura­tion temperature.
Modulates to handle light or heavy loads, continuous discharge equal to condensing load.
Large ports handle high capacities. Separate thermostatic vent allows fast
venting of air during start-up. Modulating ports provide long life. Cast iron bodies.
Disadvantages
Float or bellows may be damaged by water hammer.
Primary failure mode is closed. Does not withstand freezing temperatures. Pressure limit of 175 psig.
FLOAT & THERMOSTATIC TRAP
During start-up the thermostatic vent is open to allow free passage of air.
The thermostatic vent will close at near satu­ration temperature. The balanced design will allow venting of noncondensables that collect in the float chamber, when operating at design pressure.
Operation, Advantages, Disadvantages, and Primary Applications
5
Page 5
Bucket Traps
Advantages
Completely drains condensate at saturation temperature.
Open bucket will tolerate moderate water hammer.
Available in pressures up to 250 psig. Normal failure mode is open. Cast iron bodies.
Disadvantages
Marginal air handling during start-up. Cycles fully open or closed. May lose prime during light loads and blow
live steam. Requires manual priming to provide
water seal. Does not withstand freezing temperatures.
Primary Applications
Process main drip traps. Where condensate is lifted or drains into wet
return line. Drum type roller dryers. Steam separators. Siphon type or tilting kettles.
6
BUCKET TRAP
The trap body must be manually primed at ini­tial start-up. Under operation the body will remain full of condensate.
During start-up, air is vented through the bleed hole in the top of the bucket into the return line.
Condensate entering the trap will flow around the bucket and drain through the open seat.
BUCKET TRAP
As steam flows into the trap it collects in the top of the bucket. The buoyancy of the steam raises the bucket and closes the seat.
BUCKET TRAP WITH OPTIONAL THERMAL VENT.
An optional thermal vent installed in the buck­et allows faster air venting during start-up.
COVER
A
V
INLET
BUCKET
STEAM BUBBLES
THROUGH WATER
OUTLET
BODY
COVER
A
V
INLET
BUCKET
OUTLET
BODY
COVER
A
V
INLET
BUCKET
STEAM BUBBLES
THROUGH WATER
OUTLET
BODY
Page 6
Applications
Radiators, convectors, unit heaters. Cooking kettles. Sterilizers. Heating coils. Tracer lines. Evaporators.
NOTE: A solid fill expansion element (see Hoffman Specialty 17K) thermostatic trap should be used where water hammer (cavita­tion) may occur.
Thermostatic Bellows Type Trap
Advantages
Sub-cools condensate usually 10° to 30°F. Normally open at start-up to provide fast
air venting. Follows steam saturation curve to operate
over wide range of conditions. Brass bodies. Self draining. Energy efficient. Compact size and inexpensive. Fast response to changing conditions. Fail open models.
Disadvantages
Water hammer can damage bellows. Superheat can damage bellows if it
exceeds trap temperature rating. Pressure limit of 125 psig. Cooling leg required in some applications.
THERMOSTATIC TRAP
Thermostatic traps are normally open. This allows fast venting of air during start-up.
THERMOSTATIC TRAP
Cold condensate during start-up drains through the trap. As temperatures reach 10° to 30° F of saturation, the trap closes.
During operation, thermostatic traps find an equilibrium point to drain condensate approxi­mately 10° to 30°F below saturation at a con­tinuous flow.
7
INLET
OUTLET
INTERNAL FLEXIBLE DIAPHRAGM
INLET
OUTLET
INTERNAL FLEXIBLE DIAPHRAGM
Page 7
Disc Traps
Advantages
Completely drains condensate at satura­tion temperature.
May be installed vertically, to drain trap body when steam is off, to prevent freezing.
Compact size. Easily serviced in line, replaceable seat
and disc (some models). All stainless steel. Will tolerate water hammer and superheat.
Disadvantages
Noise. Sensitive to dirt, prevents tight closing
of disc. Available in sizes up to 1” only.
Applications
Steam tracer lines where maximum tem­perature is required.
Outdoor applications including drips on steam mains.
Drying tables. Tire mold press and vulcanizing equipment Dry kilns. Pressing machines. Rugged applications (superheat & water
hammer).
Description
Thermodisc steam traps provide dependable performance for applications with light to moderate condensate loads. Thermodisc traps are excellent for high pressure drip and steam tracing applications.
Because the disc is the only moving part, the traps are rugged and resistant to dam­age. However, if the seat and disc require servicing they may be easily replaced with­out removing the trap body from the piping.
8
Page 8
Orifice Traps
Advantages
No moving parts to wear.
Disadvantages
Does not close against steam. Small hole easily plugs due to dirt. Backs up condensate on heavy loads and
during start-up. Does not respond to modulating loads. Does not vent air when handling conden-
sate—causes slow system start-up and may cause water hammer.
Not easily recognized as trap during energy survey.
Built-in small screen plugs easily. Discharges condensate at saturation
temperature with some live steam, often causes excessive condensate tempera­tures and cavitation at condensate pumps.
Waste energy. Sizing critical.
Applications
Should be limited to constant load continuous operation.
Start-Up
The disc is pushed off the seat by the inlet pressure and is held open by the impact force of the condensate hitting the disc.
Operating
As the condensate nears saturation tempera­ture, greater amounts of flash steam will appear. Some of the flash steam escapes to the area above the disc, causing the pressure above the disc to increase, pushing the disc closer to the seat.
Closing
When all the condensate is discharged, flash steam enters the seat-disc chamber at high velocity. This high velocity causes a sudden pressure drop at the lower side of the disc and it snaps closed against the seat.
Closed
At the instant the disc snaps closed on the seat, the pressure above the disc is approxi­mately equal to the upstream line pressure. The disc is held closed because the pressur­ized area above the disc is much larger than the inlet area. The pressure above the disc decreases either by steam condensation or by non-condensables being removed via the micro-bleed on the disc. When the pressure is low enough, the disc is pushed off the seat and the process is repeated.
9
Disc Trap Operation
Page 9
Selection Guide Chart
The proper type of steam trap selected is an important consideration in steam systems. There are many types of steam traps. Each has unique characteristics and system bene­fits. Hoffman Specialty offers thermostatic, float and thermostatic, bucket
and disc traps. This line chart points out sys­tem conditions that may be encountered and suggests a trap that may best handle the requirement. Several types of traps may be used for a specific application. The line chart should be used only as a guide.
10
Chapter 1
Condensate must be completely
removed at saturation condition
to prevent water hammer
Type of Steam Trap Required Based on System Conditions
Modulating load,
wide range of
condensate load
Water hammer
due to
wet returns or lifts
Float and
thermostatic
Bucket trap
with thermal
vent
Bucket
trap
Disc
trap
Constant
load
Outdoor location
Super heat or
water hammer
Fast air venting
required
Air vent
rate not
important
Fast air venting
required
Condensate may be sub-cooled
ahead of trap to improve
operating efficiency of system
Varying pressure and load where fast
response is required
Pressure
up to 125 psig
Thermostatic bellows type trap
Pressure
over 175 psig
Page 10
Step 1: Collect All Required Information.
A. Determine maximum condensate load in
Lbs./Hr. (Pounds per Hour). See “Helpful Hints—Approximating Condensate Loads” on page 12.
B. Inlet pressure at steam trap. It could be
different than supply pressure at boiler. Heat exchanger applications with modulat­ing control valves are good examples.
C. Back-pressure at steam trap. Pressure
against outlet can be due to static pres­sure in return line or due to lifting to overhead return.
D. Determine Pressure Differential.
Inlet pressure (B) - Back-pressure (C) = Differential Pressure.
Step 2: Select Proper Type ot Trap.
A. Other Things to Consider.
1. Condensate Flow—Fluctuate?
1. Continuous?
2. Large Amount of Air?
3. Pressure—Constant? Fluctuate?
B. Application.
1. Main.
2. Drip Leg.
3. Process Heat Exchanger.
4. Other.
C. Critical Process.
1. Fail Cold.
2. Fail Hot.
Step 3: Apply Safety Factor.
A. SFA Recommended.
1. Float & Thermostatic Trap 1.5 to 2.5.
2. Bucket Trap 2 to 4.
3. Thermostatic 2 to 4.
4. Disc Traps 1 to 1.2. See specific applications.
B. The SFA Will Depend On Degree of
Accuracy at Step 1.
1. Estimated Flow.
2. Estimated Pressure—Inlet.
3. Estimated Pressure—Back.
Step 4: Select Correct Trap Size.
A. Use manufacturer’s capacity table to size
trap. Capacity tables should be based on hot condensate (some specified tempera­ture below saturation) rather than cold water rating. Hoffman Specialty published actual test data, unless stated, is 10°F. below saturation.
B. The trap seat rating must always be
higher than the maximum inlet pressure specified.
C. When inlet to equipment is controlled by a
modulating control valve, the trap size should be selected with a pressure rating greater than the maximum inlet pressure at the trap. The capacity should be checked at the minimum differential pres­sure to assure complete condensate removal under all possible conditions.
4 Step Method for Sizing
11
Page 11
3. Steam heats a solid or slurry indirectly through a metallic wall.
—Clothing press, cylinder driers, platen
press.
Lbs./hr. condensate = 970 x (W
1-W2) + W1 x (T2-T1)
L x T
When:
W
1
= Initial weight of product
W
2
= Final weight of product
T
1
= Initial temp.
T
2
= Final temp. L = Latent heat in Btu/lb. T = Time required for drying (hours).
Note: 970 is the latent heat of vaporization at atmospheric pressure. It is included because the drying process requires that all moisture in the product be evaporated.
4. Steam heats a solid through direct contact.
—Sterilizer, autoclave Lbs./hr. condensate =
W = Weight of material being
heated in Ibs.
S
h
= Specific heat of material
being heated.
T
1
= Initial temp.
T
2
= Final temp. L = Latent heat Btu/lb. T = Time to reach final temp. (hours)
Conversion Factors
One Boiler Horsepower = 140 sq. ft. EDR or 33,475 Btu/hr. or 34.5 Ibs./hr. steam at 212° F.
1,000 sq. ft. EDR yields .5 gpm condensate. To convert sq. ft. EDR to Ibs. of condensate—
divide sq. ft. by 4. .25 Ibs./hr. condensate = 1 sq. ft. EDR. One sq. ft. EDR (Steam) = 240 Btu/hr. with
215°F. steam filling radiator and 70°F. air surrounding radiator.
To convert Btu/hr. to Ibs./hr.— divide Btu/hr. by 960.
One psi = 2.307 feet water column (cold). One psi = 2.41 feet water column (hot). One psi = 2.036 inches mercury. One inch mercury = 13.6 inches water column. Size condensate receivers for 1 min. net
storage capacity based on return rate. Size condensate pumps at 2 to 3 times
condensate return rate.
W x S
h x (T2-T1)
L x T
Helpful Hints, Formulas and Conversion Factors
Helpful Hints
Approximating Condensate Loads
Heating Water with Steam
lbs./hr. Condensate =
GPM
x Temperature Rise °F.
Heating Fuel Oil with Steam
lbs./hr. Condensate =
GPM
x Temperature Rise °F.
Heating Air with Steam Coils
lbs./hr. Condensate =
CFM
x Temperature Rise °F.
SHEMA Ratings
Thermostatic traps and F & T traps for low pressures may be rated in accordance with the Steam Heating Equipment Manufacturers Association (SHEMA). SHEMA ratings have a built-in safety factor.
Formulas
1. Steam heats a liquid indirectly through a metallic wall.
—Cooking coils, storage tanks, jacketed
kettles, stills.
Lbs./hr. condensate = Q
l x 500 x Sg x Sh x (T2-T1)
L
When:
Q
l
= Quantity of liquid being
heated in gal/min
S
g
= Specific gravity
S
h
= Specific heat
L = Latent heat in Btu/lb
500 = Constant for converting
gallons per minute to pounds per hour.
T
2
= Final temperature
T
1
= Initial temperature
2. Steam heats air or a gas indirectly through a metallic wall.
—Plain or finned heating coils,
unit space heaters.
Lbs./hr. condensate = Q
g x D x Sh x (T2-T1) x 60
L
When:
Q
g
= Quantity of air or gas in ft3/min.
D = Density in Ib/ft
3
Sh= Specific heat of gas being heated.
T
1
= Initial temp.
T
2
= Final temp.
L = Latent heat in Btu/lb
60 = Minutes in hour
12
2
4
900
Page 12
The Properties of Saturated Steam table provides the relationship of temperature and pressure. The table also provides Btu heat values of steam and condensate at various pressures and shows the specific volume of steam at various pressures.
Saturated Steam:
Pure steam at the temperature corresponding to the boiling point of water.
Pressure psig:
Gauge pressure expressed as Ibs./sq. in. The pressure above that of atmosphere. It is pres­sure indicated on an ordinary pressure gauge.
Sensible Heat:
Heat which only increases the temperature of objects as opposed to latent heat. In the sat­uration tables it is the Btu remaining in the condensate at saturation temperature.
Latent Heat:
The amount of heat expressed in Btu required to change 1 Ib. of water at saturation temper­ature into 1 Ib. of steam. This same amount of heat must be given off to condense 1 Ib. of steam back into 1 Ib. of water. The heat value is different for every pressure temperature combination shown.
Total Heat:
The sum of the sensible heat in the conden­sate and the latent heat. It is the total heat above water at 32° F.
Specific Volume Cu. Ft. Per Lb.:
The volume of 1 Ib. of steam at the corre­sponding pressure.
See Properties of Saturated Steam table on the following page.
Properties of Saturated Steam
13
Page 13
14
Properties of Saturated Steam
Specfic
Heat Content
Latent
Vacuum Saturated Volume
Btu per Ib.
Heat of
Inches of Temp Cu. ft. Saturated Saturated Vaporization
Mercury °F. per Ib. Liquid Vapor Btu per Ib.
29 79 657.0 47 1094 1047 27 115 231.9 83 1110 1027 25 134 143.0 102 1118 1017 20 161 74.8 129 1130 1001
15 179 51.2 147 1137 990 10 192 39.1 160 1142 982
5 203 31.8 171 1147 976 1 210 27.7 178 1150 971
BELOW ATMOSPHERIC PRESSURE
ABOVE ATMOSPHERIC PRESSURE (Cont.)
ABOVE ATMOSPHERIC PRESSURE
Specfic
Heat Content
Latent
Pressure Saturated Volume
Btu per Ib.
Heat of
PSI Temp Cu. ft. Saturated Saturated Vaporization
(Gauge) °F. per Ib. Liquid Vapor Btu per Ib.
0 212 26.8 180 1150 970 1 215 24.3 183 1151 967 2 218 23.0 186 1153 965 3 222 21.8 190 1154 963 4 224 20.7 193 1155 961 5 227 19.8 195 1156 959
6 230 18.9 198 1157 958 7 232 18.1 200 1158 956 8 235 17.4 203 1158 955
9 237 16.7 205 1159 953 10 239 16.1 208 1160 952 11 242 15.6 210 1161 950
12 244 15.0 212 1161 949 13 246 14.5 214 1162 947 14 248 14.0 216 1163 946 15 250 13.6 218 1164 945 16 252 13.2 220 1164 943 17 254 12.8 222 1165 942
18 255 12.5 224 1165 941 19 257 12.1 226 1166 940 20 259 11.1 227 1166 939 25 267 10.4 236 1169 933 30 274 9.4 243 1171 926 35 281 8.5 250 1173 923
40 287 7.74 256 1175 919 45 292 7.14 262 1177 914 50 298 6.62 267 1178 911 55 302 6.17 272 1179 907 60 307 5.79 277 1181 903 65 312 5.45 282 1182 900
70 316 5.14 286 1183 897 75 320 4.87 290 1184 893 80 324 4.64 294 1185 890 85 327 4.42 298 1186 888 90 331 4.24 301 1189 887 95 334 4.03 305 1190 884
100 338 3.88 308 1190 882 105 341 3.72 312 1189 877 110 343 3.62 314 1191 877 115 347 3.44 318 1191 872 120 350 3.34 321 1193 872 125 353 3.21 324 1193 867
130 355 3.12 327 1194 867 135 358 3.02 329 1194 864 140 361 2.92 332 1195 862 145 363 2.84 335 1196 860
Specfic
Heat Content
Latent
Pressure Saturated Volume
Btu per Ib.
Heat of
PSI Temp Cu. ft. Saturated Saturated Vaporization
(Gauge) °F. per Ib. Liquid Vapor Btu per Ib.
150 366 2.75 337 1196 858 155 368 2.67 340 1196 854 160 370 2.60 342 1196 854 165 373 2.53 345 1197 852 170 375 2.47 347 1197 850 175 378 2.40 350 1198 848
180 380 2.34 352 1198 846 185 382 2.29 355 1199 844 190 384 2.23 357 1199 842 195 386 2.18 359 1199 840 200 388 2.14 361 1199 838 210 392 2.05 365 1200 835
220 396 1.96 369 1200 831 230 399 1.88 373 1201 828 240 403 1.81 377 1201 824 250 406 1.75 380 1201 821 260 410 1.68 384 1201 817 270 413 1.63 387 1202 814
280 416 1.57 391 1202 811 290 419 1.52 394 1202 807 300 421 1.47 397 1202 805 325 429 1.37 405 1202 797 350 436 1.27 412 1202 790 375 442 1.19 419 1202 782
400 448 1.09 426 1202 774 425 454 1.06 432 1202 770 450 459 .972 438 1202 761 475 465 .948 444 1202 757 500 469 .873 449 1201 748 525 475 .850 455 1201 746
550 480 .820 461 1200 740 575 485 .784 466 1200 734 600 490 .733 472 1199 727 625 493 .721 476 1198 723 650 498 .692 481 1197 718 675 502 .645 485 1197 712
700 505 .642 490 1195 703 750 513 .598 498 1195 697 800 520 .555 514 1194 680 850 527 .521 523 1193 670 900 534 .489 532 1192 661 950 540 .462 540 1191 651
1000 548 .435 547 1189 642 1050 553 .413 550 1187 637 1100 558 .390 564 1185 621 1150 563 .372 572 1183 612 1200 567 .353 579 1182 603 1300 579 .322 593 1176 583
1400 588 .295 606 1172 565 1500 597 .271 619 1167 548 1570 604 .2548 624 1162 538 1670 613 .2354 636 1155 519 1770 621 .2179 648 1149 501 1870 628 .2021 660 1142 482
1970 636 .1878 672 1135 463 2170 649 .1625 695 1119 424 2370 662 .1407 718 1101 383 2570 674 .1213 743 1080 337 2770 685 .1035 770 1055 285 2970 695 .0858 801 1020 219 3170 705 .0580 872 934 62
Page 14
Steam Flow in Pipes
15
REASONABLE VELOCITIES for fluid flow through pipes
Pipe Size, Inches
1
2
3
4 111⁄4 11⁄2 221⁄2 331⁄2 441⁄2 5678910
Capacity Factor 2.0 3.5 5.5 10.0 13.5 22.5 31.5 48.5 65.0 84.0 105. 131.5 190. 255. 329. 430. 539.
COMPARATIVE CAPACITIES of different sizes of pipe
STEAM PRESSURE PSI (Gauge)
Pounds Condensed Per Hour, Per Lineal Foot of Pipe
12468102030405075100125150200
.11 .13 .14 .14 .15 .15 .16 .18 .20 .22 .26 .29 .32 .35 .40 .15 .15 .16 .16 .17 .18 .20 .23 .25 .27 .31 .35 .39 .42 .49 .21 .21 .22 .23 .23 .24 .28 .33 .36 .39 .45 .50 .55 .60 .69 .24 .25 .26 .27 .27 .29 .33 .38 .42 .46 .54 .61 .68 .74 .81 .30 .31 .32 .33 .34 .36 .41 .46 .51 .55 .65 .73 .81 .88 .97 .38 .39 .40 .41 .43 .44 .50 .56 .61 .66 .77 .86 .94 1.03 1.19 .46 .47 .48 .49 .51 .53 .61 .68 .76 .83 1.04 1.11 1.23 1.33 1.50 .55 .56 .59 .60 .62 .64 .74 .83 .91 1.00 1.24 1.32 1.46 1.59 1.81
.34 .35 .36 .37 .39 .41 .47 .53 .59 .65 .73 .81 .90 1.00 1.15
CONDENSATION RATES at 70°F. (for bare steel pipe with natural movement of air)
Pipe Size
(Inches)
3
4
1 1
1
2
2 2
1
2
3 4 5
Per Sq. Ft.
Heat. Surface
Sq. Ft. of
Surface = to 1 Lineal Ft. of Pipe
.275 .345 .497
.622
.752 .917
1.179
1.459
EXAMPLE: To get size of pipe to serve a
1
2" and 3⁄4" pipe, add factors: 1⁄2" factor (2) + 3⁄4" factor (3.5) = 5.5 (1" factor).
Condensation in Pipes
Fluid Pressure PSI (Gauge) Service Velocities—FPM
SATURATED STEAM 0-15 Heating Mains 4000-6000 SATURATED STEAM 50-up Miscellaneous 6000-8000 SUPERHEATED STEAM 200-up Turbine and Boiler Leads 10000-15000
WATER 25-40 City Service 120-300 WATER 50-150 General Service 300-600 WATER 150 Boiler Feed 600
Pipe Size
PRESSURE PSI (GAUGE)
(Inches) 5 10 15 30 50 75 100 125 200 250
1
2 30 40 45 60 90 120 150 180 270 330
3
4 55 70 80 110 160 220 280 340 510 620 1 90 110 125 180 270 390 460 560 840 1020 11⁄4 160 200 225 325 480 650 820 990 1490 1830 11⁄2 220 270 300 450 650 900 1100 1300 2060 2550
2 370 455 520 750 1100 1500 1900 2300 3450 4200 2
1
2 525 650 750 1050 1600 2175 2750 3300 4950 6050 3 800 950 1350 1600 2500 3350 4250 5150 7700 9450 31⁄2 1100 1350 1550 2200 3300 4550 5700 6900 10200 12700 4 1450 1800 2000 2900 4300 5850 7400 8900 13450 16400
5 2300 2800 3200 4600 6900 9300 11700 14100 21200 26000 6 3200 3900 4500 6400 9800 13200 16800 20300 30800 36900 8 5700 7000 8000 11400 17200 23300 29300 35400 53100 65200
10 9300 11400 13000 18900 28200 38000 48100 58100 87100 106500 12 13500 16600 18900 27000 40800 55300 69700 84200 126500 154700
SATURATED STEAM (lbs/hr) at 6000 ft/min (velocity) in iron or steel pipe
DIAMETER OF PIPE IN INCHES
3
4 111⁄2 221⁄2 345681012
233445678111315 233445679111415 3344556710121417 3344557911131518 33455581012151821 34556791113162024
CONDENSATION (lbs/hr) per 100 ft. pipe with 2-in. thick 85% magnesia insulation
Pressure
PSI
(Gauge)
1 3
5 10 20 30
DIAMETER OF PIPE IN INCHES
3
4 111⁄2 221⁄2 345681012
445679111316192428 4567810131518222732 5578912151820253137 5678913161922283541 66891014172124313845 67891115192428354451
Pressure
PSI
(Gauge)
50
70 100 125 150 200
Condensation in 3" and larger pipe are corrected for heat loss due to friction. Velocity taken at 8000 ft./min. Based on standard formulas.
Page 15
Flash Steam Explanation and Calculation
Flash Steam
When hot condensate above the saturation temperature under pressure, is released to atmospheric pressure, the excess heat is given off by reevaporation or what is common­ly referred to as flash steam.
Flash steam is important because it contains heat which can often be utilized for economy. It is necessary to know how it is formed and how much will be formed under given condi­tions.
The Btu values given in the Properties of Saturated Steam tables provide the neces­sary data for calculating energy loss due to flash steam.
Float and thermostatic traps, bucket traps, and disc traps discharge condensate at approximately saturation temperature. Thermostatic traps discharge condensate 10° to 30°F. below the saturation temperature.
Flash Steam Heat Loss Calculation
The form provided to the right will allow you to easily calculate the flash steam loss and associated energy cost.
Lines A, B, C, D, and E are based on the actu­al operating conditions. It may be necessary to estimate the average conditions when loads fluctuate.
Lines F, G, H and I can be filled in using the values from the Properties of Saturated Steam table.
The calculation for flash loss may now be made with the annual loss determined.
The calculation of energy cost may now be made to determine the flash loss and required heating of make-up water to replace the flash loss.
The amount of make-up water and water cost can also be determined using this form.
How to Calculate Your Own Flash Steam and Energy Loss
List Operating Conditions:
A. ____Initial Saturation Pressure. B. ____Reduced Pressure. C. ____System Load in Lbs. Per Hr.. D. ____Cost of Steam Per 1,000 Lbs. E. ____Make-up Water Temperature ° F.
From Properties of Saturated Steam Table:
F. ____Btu/Lb. in Condensate at Initial
F. ____Pressure.
G. ____Btu/Lb. in Condensate at Reduced
G. ____Pressure.
H. ____Btu/Lb. Latent Heat in Steam at
H. ____Reduced Pressure.
I._____Btu/Lb. in Make-up Water.
Calculation of Flash Steam Loss
F – G
x 100 = % flash loss
______ x 100 = ______% of flash loss
C x % flash loss = lbs. per hr. loss
To obtain annual loss multiply Ibs. per hr. Ioss x hr. per day x days per year process operates = Ib. of flash steam annually.
Calculation of Energy Loss:
This calculation must take into consideration that, not only are we reducing the tempera­ture of the returns, but that the condensate removed in the form of flash steam must be replaced with cooler make-up water.
% of returns x system load Ibs./hr. x (F - G) = Btu/hr. condensate cooling.
% of flash loss x system load Ibs./hr. x (F - I) = Btu/hr. make-up water loss.
Btu condensate cooling + make-up loss = Btu/hr. Ioss.
Btu/hr. Ioss x hr. per day x days per year = annual Btu loss.
Btu annual loss ÷ H = equivalent Ib./yr. Ioss.
Lb./hr. Ioss ÷ 1,000 x D
= annual cost of flash steam loss.
Lb./Year Flash Loss ÷ 8.33
= Gallons per year make-up water.
16
H
Page 16
Steam Trap Operating Pressure Selection
A given size float and thermostatic trap or bucket trap is offered with various orifice sizes which determine the maximum pressure rating. A Hoffman Specialty F & T trap for example is offered with seats rated 15 psi, 30 psi, 75 psi, 125 psi and 175 psi. A low pressure seat and pin has a larger orifice size which provides a higher condensate rating than a high pressure seat.
When actual operating pressure is higher than the seat rating, the differential pressure across the seat will prevent the trap from opening. Thus, the trap must be selected for the maximum differential pressure that will be encountered. The trap capacity tables show capacities at lower pressures to allow selec­tion at various operating points.
A high pressure seat may be used at lower differential pressures, however, the capacity rating will be less than the same size trap with a low pressure rated seat.
Operating Pressure Limits
17
Excessive Steam Pressure Forces Trap Closed
ATMOSPHERIC PRESSURE
WEIGHT OF
BUCKET
STEAM
PRESSURE
Page 17
Installation and Calculating Differential Pressure
Trap Installation
Steam traps should be installed in an acces­sible location at least 15 inches below the condensate outlet of equipment or steam mains being drained. A 15 inch static head at the trap will provide approximately
1
2 psi differ-
ential across the trap when it drains into a vented gravity return system. During start-up, before a positive steam pressure is achieved, the static head is the only differential pres­sure across the trap. When the steam equip­ment is controlled by a temperature regulator, the steam pressure will be reduced as the valve modulates toward the closed position. When the pressure drops to O psi, the static head is the only differential pressure across the trap. The differential pressure across the trap can be increased by lowering the trap be­low the steam equipment.
A 2.4 ft. static head will provide 1 psig. A greater differential pres­sure will reduce the size of the trap required.
Piping Details
A dirt pocket should be provided ahead of the steam trap to collect scale and dirt. A shut-off valve should be provided ahead of the trap to permit service.
Strainers should be provided ahead of the steam trap to prevent dirt from entering the trap. Dirt entering the trap can deposit on the seat and prevent tight closing. A blow-off valve on the strainer will permit strainer screen cleaning. Unions or flanges should be provid­ed to allow removal of the trap for testing, repair or replacement.
A test and relief valve installed after the trap permits visual indication of the trap operation, and assures that internal pressures are relieved prior to servicing.
A shut-off valve in the trap outlet to the return line isolates the trap from the return line for service.
18
Trap Installation Trap draining to open drain
Trap Installation Trap draining to gravity return line
EQUIPMENT DRAIN POINT
STATIC
HEAD
SHUT-OFF VALVE
“Y”
STRAINER
DIRT
POCKET
TO DRAIN
TRAP
PRESSURE
TO RETURN LINE
TEST & RELIEF
GRAVITY RETURN TO
VENTED RECEIVER
EQUIPMENT DRAIN POINT
STATIC
HEAD
SHUT-OFF VALVE
STRAINER
DIRT
POCKET
“Y”
TO DRAIN
TRAP
Page 18
The use of bypass piping around steam traps is not recommended. Bypass valves, if opened, may cause pressurization of conden­sate receivers and cause a safety hazard. Where stand-by protection is desired the use of a stand-by trap in parallel to the normal trap is recommended.
Where the trap drains into a pressurized return line or to an overhead return, a check valve should be installed after the trap to pre­vent backflow through the trap when the steam is off. The check valve also helps pro­tect the trap from cavitation (water hammer) that may occur when traps discharge high temperature condensate into wet return lines. Water hammer occurs when high temperature condensate under pressure ahead of the trap discharges into a lower pressure return line. The high temperature condensate flashes, causing steam pockets to form. When these steam pockets give up their heat they implode and cause water hammer.
Differential Pressure
The differential pressure across the trap will be the sum of the minimum operating pres­sure, plus the positive static head at the trap inlet minus any back-pressure in the return line minus static head in the discharge piping. Trap capacities should be calculated at the minimum differential pressure to assure com­plete condensate drainage.
Lifts in the return piping should be avoided wherever possible. High temperature conden­sate discharging from the trap may flash at the lower return line pressure. The flashing into a wet return line will cause steam pock­ets. As these steam pockets lose their latent heat they implode, causing water hammer. Water hammer can damage traps, pipe and fittings.
Lifts in the discharge piping after a trap will cause back-pressure. A 2.4 ft. Iift is equal to a 1 psig pressure. This is especially important on low pressure operation or where a modu­lating control valve is used to control the flow of steam. Reduced flow will cause pressure drops. A positive differential must be assured under all possible conditions to assure com­plete condensate drainage.
19
Trap Installation Trap draining to overhead return line or pressurized return line
Differential Pressure = P
1
minus P
2
P1(Inlet) P2(Outlet)
TRAP
EQUIPMENT DRAIN POINT
RETURN
STATIC
HEAD
SHUT-OFF
DIRT
POCKET
VALVE
“Y”
STRAINER
TO DRAIN
TRAP
CHECK
VALVE
TEST &
PRESSURE
RELIEF
SHUT-OFF
VALVE
LINE
STATIC
HEAD
AGAINST
DISCHARGE
1
/2 PSI/FT.
PRESSURIZED
RETURN LINE
Page 19
Drip Traps for Distribution Pipes
Drip Traps for Steam Distribution Piping
The steam distribution piping, often referred to as steam mains, provides the link between the boiler and the steam utilizing equipment. The steam piping must be kept free of air and condensate. This requirement is met with the use of steam traps installed in the piping. The traps used for draining the steam mains are commonly referred to as drip traps. If the steam mains are not adequately trapped the results are often water hammer in the piping. Water hammer is caused by slugs of conden­sate traveling at high speed in the steam pipes, which can damage valves and piping.
Drip traps are installed in the steam mains at all risers, ahead of all reducing valves, ahead of all regulators, at the end of mains, through­out the piping at intervals at least every 500 feet, at expansion joints and at all steam separators.
The size and type of drip traps used will depend on the method used in heating the steam mains to final pressure and tempera­ture. The two methods commonly used are automatic start-up and supervised start-up.
In systems using automatic start-up the steam boiler is used to bring the mains up to final pressure and temperature without supervision. The drip traps must handle the full condensing load during start-up of the system.
In systems using supervised start-up the oper­ator opens manual valves in the steam piping before steam is admitted to the system. When the system reaches normal pressure and temperature, the manual valves are closed. The drip traps for supervised start-up are sized only for the running load.
The sizing of drip traps will depend on the type of start-up used. During the initial start­up of automatic startup systems, a large amount of condensing occurs, bringing the steam piping from ambient temperature up to the final steam temperature.
When supervised start-up is used the drip trap is sized only to handle the heat loss through the steam piping.
20
Page 20
Calculation of the running load is figured using the following formula:
Ibs./hr. running load heat loss = L x U x T x E
S x H
L = Length of steam line.
U = Heat transfer from curve in Figure 1.
T = Temperature difference between steam
temperature and minimum ambient in degrees F.
E = 1- Efficiency of insulation (for 80% effi-
cient insulation use 1.80 = .2).
S = Linear feet of pipe to provide 1 sq. ft.
surface area.
H = Latent heat of steam in Btu/lb. (see
Properties of Saturated Steam Table).
Calculation for warm-up load at start-up: Warm-up load Ib./hr. = W x(T
1- T2)x.114 L
W = Weight of pipe (see table below for
weight per ft.).
T
1 = Steam temperature at saturation.
T
2 = Initial pipe temperature at ambient.
L = Latent heat of steam at final
operating pressure.
.114= Specific heat of steel or wrought
iron pipe.
21
S VALUE FT. OF PIPE PER
SQ. FT. OF SURFACE AREA
Pipe Size S Value
1" 2.904
1
1
4" 2.301
1
1
2" 2.010
2" 1.608 3" 1.091 4" 0.848 5" 0.686 6" 0.576
8" 0.442 10" 0.355 12" 0.299 14" 0.272 16" 0.238 18" 0.212 20" 0.191 24" 0.159
W VALUES
WEIGHT OF WELDED SEAMLESS STEEL PIPE
Schedule 40 Schedule 80
Nominal Wt. Lbs. Wt. Lbs.
Pipe Size Per Linear Ft. Per Linear Ft.
1
2" .85 1.09
3
4" 1.13 1.47
1" 1.68 2.17
1
1
4" 2.27 3.0
1
1
2" 2.72 3.63
2" 3.65 5.02
2
1
2" 5.79 7.66
3" 7.58 10.25
4" 10.79 14.98
6" 18.97 28.57
8" 28.55 43.39
Page 21
Example: Assume a steam supply header to feed tracer lines is 11/4” pipe size operating at 30 psig and is 800 ft. Iong, insulated 75% effect, minimum ambient at start-up is 10°F. Calculate running load and warm-up load.
Step 1
Running load Ib./hr. =
L x U x T x E
S x H
= 800 x 2.7 x (274 -10) x .25
2.301 x 926
= 66.9 Ib./hr.
Step 2
Calculate warm-up load: C =
W x(T
1- T2) x.114
L
= (2.27 x 800) x (274 -10) x .114
926 = 59 Ibs. of steam A warm-up time must be selected to compute
Ibs./hr. Assuming a warm-up of 15 minutes, we must multiply 59 Ibs. x 4 = 236 Ibs./hr. Thus, the trap must be sized for 236 Ibs./hr. for a 15 minute start-up period, plus a safety factor.
Step 3
We will size the trap for the large value (run­ning load vs. warm-up load), which in almost all instances will be the warm-up load.
Traps should be sized with a safety factor to handle start-up and abnormal loads. Normal
practice is to size the trap at three times the running load or two times the warm-up load.
The final sizing for our example would be to size the trap for 236 x 2 = 472 Ibs./hr. con­densate based on the differential pressure between the header supply pressure and return line pressure. Assuming a gravity return line, this would be 30 psi.
Step 4
Select the trap. Based on the previous description of traps, if
the trap from a steam header is not subject to freezing conditions, the normal selection would be an F & T or Bucket Trap.
If the trap is located in an area subject to freezing, to assure complete condensate drainage during shut-down, we should use either a Thermostatic or Thermodisc Trap. Based on the calculated condensate rate plus the applied safety factor, we would go directly to the trap manufacturer’s catalog and select the trap.
The drip trap should be installed in a drip con­nection that is at least equal to the size of the steam main for pipe size up to 4 inches. Above 4 inch size the drip connection should be at least 4 inches minimum or 1/2 the size of the steam main, whichever is larger. The height of the drip connections should be the larger of 5 inches or 1
1
2 times the diameter of
the pipe. The static head will provide the differential
pressure across the trap during automatic start-up until the steam pressure is above 0 psig. A 15 inch static head will provide 1/2 psi differential assuming the trap drains into a gravity return line. A 2.4 ft. static head will provide 1 psi differential pressure.
22
Installation at end of steam main drip trap
STATIC
HEAD
SHUT-OFF
VALVE
“Y” STRAINER
TRAP
SHUT-OFF
VALVE
Page 22
Trapping Ahead of Steam Regulators
When steam pressure or temperature regula­tor valves are installed in a steam line, con­densate may back up ahead of the valve when it is off. When the valve opens with con­densate backed up on the inlet side, the con­densate will cause water hammer.
Where the branch connection to a control valve is less than 10 ft., the branch line may pitch toward the steam main to allow conden­sate to flow back into main.
When the branch line is over 10 ft., pitch the branch line toward the control valve and install a steam trap. The steam trap should be as close to the control valve as possible.
23
Installation of drip trap ahead of riser or expansion joint
Installation of drip trap in long run of steam piping or ahead of control valves
STATIC
HEAD
SHUT-OFF
VALVE
“Y” STRAINER
TRAP
SHUT-OFF
VALVE
STATIC
HEAD
SHUT-OFF
VALVE
“Y” STRAINER
TRAP
SHUT-OFF
VALVE
10' OR LESS
PITCH TOWARD STEAM
MAIN 1/2" PER FOOT
STEAM
MAIN
OVER 10'
PITCH TOWARD
STEAM MAIN
1/2" PER FOOT
STEAM
MAIN
TRAP
Page 23
Selecting Steam Traps for Heat Exchangers
Steam heating devices using a modulating temperature regulator must operate over a wide range of conditions. As the temperature regulator controls the flow of steam, condesa­tion causes a change in pressure. Thus, the steam trap must be capable of handling a wide range of capacities at varying pressures. Selection of the trap for these conditions is more involved than it would be for drip traps or steam equipment operating at constant pressure.
A heat exchanger is sized to heat a maximum expected flow rate through the tubes, over the maximum expected temperature rise with a predetermined maximum steam operating pressure.
When the tube side flow rate is reduced, or the incoming fluid being heated requires less of a temperature rise, the steam control valve partially closes, reducing the flow of steam to maintain a constant set temperature of the fluid being heated. The condensing of the steam under reduced load conditions results in a lower steam pressure in the shell of the heat exchanger.
During very low load conditions the condens­ing of the steam can create an induced vacu­um in the shell of the heat exchanger. This condition requires that a vacuum breaker be installed to allow air to enter and relieve the induced vacuum. Without a vacuum breaker, the induced vacuum would cause a negative pressure differential across the trap and the condensate would not be drained from the heat exchanger shell.
Complete condensate drainage under all vary­ing pressure and condensing loads is essen­tial to prevent tube damage due to water hammer. The steam flow in the heat exchang­er shell must pass around the tube support sheets. If condensate builds up in the heat exchanger shell, it will condense rapidly as steam is mixed with it, causing water ham­mer. The water hammer is often evident by indentations in the tubes and collapsed tubes.
Thus, it becomes evident that the design con­densing rate at design pressure is not the only load the trap must handle. The condens­ing load of a heat exchanger designed for 15 psi may in fact be in excess of 90% at 0 psig. When the heat exchanger is selected, a foul­ing factor is added to assure adequate tube area as scale builds up on the tube walls. Before this scale develops, the heat exchang­er is in fact oversized which results in a lower steam operating pressure.
A steam trap must then be selected to handle the full condensing load with the heat exchanger operating at 0 psig. The heat exchanger may operate at a slight vacuum due to the condensing of steam. A vacuum breaker is required on a heat exchanger to prevent induced vacuum. The differential required to open the vacuum breaker is usual­ly less than 0.25 psi.
Recommended practice is to install the trap as far below the heat exchanger as possible. The minimum distance should be 15 inches. A 15 inch static head will develop approxi­mately 0.5 psig at the trap inlet, less the dif­ferential required to open the vacuum breaker. Assuming 0.25 psi to open the vacu­um breaker, a properly sized trap must be capable of draining the full rated condensing load with 0.25 psi differential across the trap, draining into an atmospheric gravity return line. A static head of 2.4 feet will provide 1 psig. The differential required to open the vac­uum breaker must be subtracted from the static pressure to determine the differential across the trap.
Selecting the type of trap becomes the next step. Traps that operate in response to tem­perature should be avoided for heat exchang­er operation. This eliminates thermostatic traps from our selection. As described above, the trap must be capable of responding to varying condensing rates at various differen­tial pressures. The two types of traps that can meet these requirements are Float and Thermostatic Traps and Bucket Traps. The Float and Thermostatic Trap has the ability to
24
Chapter 3
Steam to Fluid Heat Exchanger
HEATED FLUID
OUT
FLUID TO BE
HEATED IN
VACUUM BREAKER
HEAT EXCHANGER
SHELL
TEMPERATURE
REGULATOR
STEAM LINE
TUBE SUPPORTS
HEAT EXCHANGER
TUBE BUNDLE
F&T TRAP
Page 24
modulate over a wide range of conditions, pro­viding a drainage rate equal to the system load. The Float and Thermostatic Trap also has a separate thermostatic vent to provide quick passage of air during start-up or during a change of condition. The bucket trap will completely drain the condensate but operates in cycles between full open and close. The bucket trap has a slower air venting rate unless fitted with a separate thermostatic ele­ment. Return line sizing can be minimized using the Float and Thermostatic Trap due to its modulating feature which provides a con­tinual flow equal to the condensing rate.
General practice in sizing traps is to allow a safety factor in the selection. During start-up when the heat exchanger shell is cold, the steam piping is cold and the fluid to be heat­ed may be at less than design temperature. All these conditions will cause a higher steam condensing rate. Float and Thermostatic Trap safety factors are normally 1.5 to 2.5 times rated load. Bucket Trap safety factors are nor­mally 2 to 4 times rated load .
Guidelines for selecting traps for heat exchangers using modulating steam tempera­ture regulators are as follows:
—Select capacity based on maximum con­densing load at minimum differential pressure that can occur. The heat exchanger manufac­turer can provide this information.
—No lifts should be installed in the return line piping. The trap must drain into an atmo­spheric gravity return line.
—Install a vacuum breaker to prevent induced vacuum in the heat exchanger from causing a reverse in differential pressure across the trap.
—Install the trap as far below the heat exchanger as possible to develop a static pressure to the trap inlet. The minimum should be 15 inches.
—Select a trap that provides complete drainage of condensate. Avoid use of temper­ature controlled traps.
—Allow an adequate safety factor for start-up conditions.
25
Typical Heat Exchanger Installation
Float & Thermostatic Traps assure complete condensate drainage at saturation temperature. They also modulate to handle varying condensate loads associated with temperature regulators. The thermostatic element provides rapid air venting during start-up.
PRESSURE
GAUGE
Y STRAINER
FLOAT AND
THERMOSTATIC
GATE
VALVE
CONDENSATE
RETURN
TRAP
THERMOSTATIC
FLOAT AND
TRAP
Y STRAINER
Y STRAINER
GATE
VALVE
BREAKER
VACUUM
GATE
VALVE
GLOBE
VALVE
TEMPERATURE
REGULATING VALVE
HEAT EXCHANGER
15" MINUMUM
RECOMMENDED
GATE
VALVE
PRESSURE
GAUGE
CONNECTION TO
HEAT EXCHANGER
HOT
WATER
THERMOMETER
COLD
WATER
CONDENSATE
RETURN
Page 25
Condensate Coolers
When heat exchangers are selected for opera­tion above 2 psig, consideration should be given to the addition of a condensate cooler. The justification will vary depending on the size of the heat exchanger and the actual time the unit is in operation.
With a condensate cooler, the discharge from the trap on the primary heat exchanger is piped through a water-to-water heat exchanger. This lowers the condensate temperature and recovers wasted heat. A second trap is then installed on the discharge of the condensate cooler to maintain saturation pressure and prevent flashing and water hammer in the condensate cooler.
The water-to-water heat exchanger design dif­fers from steam heat exchangers. The water­to-water heat exchanger has internal baffles to direct the water flow across the tubes to improve heat transfer. The water-to-water heat exchangers are externally distinguishable because the top and bottom shell openings are both the same size. The steam-to-water heat exchangers have a large opening in the top for the steam inlet and a smaller bottom outlet for the condensate drainage.
When a modulating steam regulator is used on the steam-to-water heat exchanger, the vacuum breaker will allow air to enter to pre­vent an induced vacuum from holding up con­densate. The F & T Trap must be installed 15 inches below the heat exchanger to provide condensate drainage when the internal pres­sure drops to O psig. A separate Thermostatic Trap should be provided to allow the air to be vented when the pressure increases above O psig. This trap bypasses the condensate cool­er to allow free passage of the air into the gravity return line.
The fluid in the condensate cooler on the tube side, may be the same fluid that is to be heat­ed in the steam heat exchanger when the ini­tial temperature is sufficiently low. When the initial temperature of the fluid is too high to cool the condensate below 212°F, other fluids may be heated. Heating domestic hot water or pre-heating boiler make-up water are two possibilities.
26
Piping Detail of Condensate Cooler
When fluid being heated is too hot to cool condensate below 212°F., other heating requirements may be circulated through the condensate cooler.
TEMPERATURE
REGULATOR
STEAM LINE
HEAT EXCHANGER
THERMOSTATIC
TRAP
F&T TRAP
HEAT EXCHANGER
CONDENSATE COOLER
TO RETURN
LINE
Page 26
Lock-out Traps For Draining Condensate Under Low Pressure.
In the discussion of trap operation, we point­ed out that if the differential pressure across the trap seat exceeds the trap pressure rat­ing, the trap will fail closed. This occurs when the differential force across the seat and pin exceeds the drop-away force created by the weight of the float or bucket and linkage. Under certain conditions we can use a trap with a low differential pressure in a high pres­sure application to drain condensate during start-up or operation at reduced pressure. Low pressure F & T or Bucket Traps may be used for lock-out applications.
Lock-out Trap Used to Drain Underground Steam Main.
One application of a lock-out trap is to drain condensate from underground steam lines during start-up. The low pressure trap con­nected to an open drain or sump drains con­densate during start-up. When the steam line pressure exceeds the trap rating it will close and remain closed. The differential pressure will then allow the condensate to flow through the high pressure drip trap and be recovered through the return line.
This method may also be used where a modu­lating temperature regulator may reduce pres­sure ahead of the trap. When the regulator reduces the flow of steam, the pressure in the steam space drops due to the condensing rate in relation to steam flow. The low pres­sure trap connected to a sump or drain will then operate when the pressure drops approx­imately to the rated pressure of the trap.
Lock-Out Traps for Start-Up Loads
27
Lock-out trap used to drain underground steam main
POWER
PLANT
UNDERGROUND WET
RETURN LINE
UNDERGROUND
STEAM LINE
LOCKOUT
TRAP TO DRAIN
HIGH PRESSURE
DRIP TRAP
Page 27
Draining Condensate to Overhead Returns
Draining Condensate to Overhead Returns or into Pressurized Return Lines
When a positive pressure is assured across the steam trap, 1 psi will raise condensate 2 feet. When a positive pressure is not assured, such as the case when using a steam control valve, provision must be made to drain condensate at reduced pressure loads and during initial start-up. The use of a second trap installed at a higher elevation and connected to a drain may be used as shown below. The normal trap is connected to the overhead return line with a check valve to prevent backflow. The second trap may be a low pressure trap. When condensate backs up 4 inches it will drain into the second trap which will drain condensate into a floor drain or sump.
When a trap drains into an overhead return line or pressurized return line, water hammer may occur due to high temperature conden­sate flashing as it drains through the trap into a lower pressure. The check valve after the trap protects it from the forces created by water hammer. It also prevents backflow through the trap when the steam is off.
28
Draining condensate to overhead return lines
TEMPERATURE
REGULATOR
OVERHEAD RETURN
STEAM LINE
TRAP
MAX. LIFT
2 FOOT
PER PSI
DRIP
TRAP
4" MIN.
TRAP
Page 28
Submerged Pipe Coils
Submerged pipe coils are sometimes gravity drained, with the trap installed below the coil. Figure 2 shows such an installation. Use a safety factor of 2 for trap sizing.
When it is not practical to install the trap below the tank level, a lift fitting or water seal must be provided to bring the condensate to the trap level over the heated tank. Figure 3 shows a water seal arrangement. Note that the trap is installed below the siphon looped over the top of the tank. Condensate collects in the water seal and is elevated to the siphon loop by the differential pressure. A safety factor of 3 should be used.
Large diameter coils may require yet another type of installation. Where the coil diameter is larger than the trap inlet size, the installation shown in Figure 4 should be used. A smaller
tube is placed inside the large tube and insures that steam will not enter the trap until all of the condensate has been drained from the coil. The lift fitting tube is usually sized one pipe size smaller than the trap inlet, but never less than 1/2” pipe size.
The coils in Figures 2,3 and 4 are of the con­tinuous type. Coils are often multi-circuited. A safety factor of 4 is needed where this is the case because of the higher warm-up load.
Embossed plate coils are piped in the same fashion as ordinary pipe coils. Where the coil is of the continuous type and gravity drained, the safety factor is 2 to 1. Siphon drained coils require a 3 to 1 safety factor. Multiple header plate coils should have a safety factor of 3 to 1 if they are gravity drained and 4 to 1 if siphon drained. Figure 5 illustrates these coil types.
Draining Submerged Coils
29
Continuous coils–gravity drained
Figure 2
Continuous coils–siphon drained
Figure 3
Large diameter continuous coil
siphon drained
Figure 4
Typical embossed plate coil installations
Figure 5
Continuous coil–gravity drained Continuous coil–siphon drained
Multiple header coil
siphon drained
Multiple header coil
gravity drained
STEAM
TANK
STRAINER
STEAM
TANK
PLATE COIL
STEAM
TRAP
TANK
STRAINER
PLATE COIL
TANKTANK
TRAP
TRAP
PLATE COIL
SWING CHECK VALVE
PLATE COIL
TRAP
STRAINER
TRAP
SWING CHECK VALVE
TRAP
TANK TANK
TRAP
Page 29
Jacketed Kettles
Jacketed Kettles
Kettles are often of the tilting type. These require the use of a siphon drain. Siphon drains may either be internal or external. The Fig. 6 shows both types.
As shown in the illustration, external siphons are surrounded by ambient air, while the inter­nal siphon is surrounded by steam.
Flash steam tends to form in siphons and the trap must be able to operate properly with a certain amount of it present in the conden­sate. Figure 7 illustrates how this takes place, and how a steam main is drained. First, condensate drains into the water seal. Steam in the siphon above the water seal condenses, dropping the pressure. Condensate rises in the siphon as this takes place. The siphon may form and break several times before it is established and condensate enters the trap.
A check valve must be used to hold the siphon while it is forming. This should be installed after the strainer as shown. Once the siphon is established, the drop in static pressure as the elevation decreases causes some of the hot condensate to “flash off.” The presence of steam in the condensate decreases its density and actually assists the flow. An external type siphon loses some heat by radiation to the ambient air and the con­densate within it tends to cool. As a result, the amount of flash steam is less than in an internal siphon, which absorbs heat from the steam surrounding it.
Air Handling Capability
The excellent air handling capability of Thermostatic Traps makes them suitable for trapping applications where quick air removal is required. For example, batch processes resulting in on-off operation of steam heating equipment are prone to air problems. The steam space becomes filled with air in between heating cycles. Unless this air is quickly removed with the condensate, slow heating of the batch results. Thermostatic Traps must be fitted with a cooling leg, when used for this purpose, to minimize back up of condensate into the equipment.
Figure 8 shows a steam kettle serviced by a Thermostatic Trap. A cooling leg with a mini­mum length of 5 ft. is provided to insure enough cooling of the condensate to open the trap.
Notice the check valve provided at the trap outlet. This prevents back drainage of the condensate in the vertical line. A check valve should always be provided at the trap outlet where vertical lifts exists.
The safety factor for steam kettles is usually 3 times rated capacity. Siphon type kettles may use either F & T or Bucket Traps. Stationary kettles may use Thermostatic Traps.
30
External and internal jacketed kettles
Figure 6
Principle of condensate line siphon
Figure 7
Steam kettle showing cooling leg
Figure 8
Stationary type
jacketed kettle with
internal siphon
Tilting type
jacketed kettle with
external siphon
STRAINER
CHECK VALVE
STRAINER
CHECK VALVE
TRAP
TRAP
STRAINER
STATIC PRESSURE DROPS AND FLASH
STEAM FORMS
MAXIMUM STATIC
PRESSURE
SIPHON
WATER SEAL
CHECK VALVE
STEAM MAIN
TRAP
OVERHEAD
RETURN MAIN
THERMOSTATIC
TRAP
COOLING LEG 5 FT. MINIMUM
STRAINER
CHECK VALVE
Page 30
Cylinder Dryers
Cylinder dryers are widely used in the process­ing industry. Since they are usually rotating in nature, siphon drainage of the condensate is involved. Figure 9 shows a typical arrange­ment. Condensate is drained from the bottom of the rotating cylinder by a typical siphon arrangement.
Because of their large volume and surface area, traps for this type of application should be sized with a substantial safety factor. This is required to eliminate the air and handle the large warm-up load. It is not uncommon to use safety factors of between 5 and 8 for cylinder dryers.
Unit Heaters
Unit heaters may be selected to operate over a wide range of pressures. Operation may have maintained steam pressure in coils with a thermostat to control the fan or steam con­trol may be on-off as heat load is required.
Small low pressure unit heaters up to 15 psi often use Thermostatic Traps. Large unit heaters or those operating at higher pressure may use F & T as first choice and Bucket Traps as second choice.
When the ambient air may be below freezing or when outside make-up air is used, a vacu­um breaker is required to prevent an induced vacuum from occurring when the steam is turned off. Induced vacuum causes a reverse differential pressure across the trap and holds up condensate in the coils. This is the major cause of coil freezeup. The trap must also be able to drain by gravity to assure com­plete condensate removal.
The recommended safety factor for sizing traps for unit heaters is 3 times rated capacity. Low pressure traps may be sized using SHEMA rating without any additional safety factor.
Cylinder Dryers, Unit Heaters
31
Siphon drained cylinder dryer Figure 9
Unit heater
STRAINER
SWING CHECK VALVE
TRAP
VACUUM
BREAKER
UNIT HEATER
UNIT HEATER
TRAP
GRAVITY
RETURN
LINE
Page 31
Steam Radiators
Radiators
Radiators normally use Thermostatic Traps to drain condensate. The Thermostatic Trap is a pressure balanced device that will open usual­ly 10° to 30° F. below saturation temperature. A Thermostatic Trap on a low pressure 3 psi system will open at approximately 190° to 200°F. A 10° to 30° F. drop in condensate temperature normally occurs in the return pip­ing in a low pressure heating system. This controls the return condensate at about 160°F. and simplifies the selection of conden­sate return units.
Low pressure Thermostatic Traps are normally rated in sq. ft. E.D.R. heating load and have a SHEMA rating which allows the proper safety factor.
Thermostatic Traps are inexpensive in relation to other types of traps. This makes them attractive for heating systems where many large numbers of traps are required.
Trap Damage from Water Hammer
When automatic temperature controlled sup­ply valves are used, water hammer may occur when the valve closes. This occurs due to the condensing of steam in the radiator causing an induced vacuum. The induced vacuum may pull in flash steam from the return line. As this steam enters the condensate in the bot­tom of the radiator, steam pockets form and implode as they lose their heat. The forces of water hammer (cavitation), can quickly destroy bellows or diaphragm type radiator traps. A solid fill Hoffman Specialty 17K is designed to withstand this service.
Water hammer may also occur during start-up when lifts are present in the discharge piping after the trap.
32
SUPPLY MAIN
RETURN MAIN
SUPPLY VALVE
TRAP
SUPPLY VALVE
TRAP
RETURN MAIN
SUPPLY MAIN
Page 32
33
Typical Piping for Steam Heating
The piping and radiator connections shown in this section are diagrammatic and illustrate the proper method of making piping connections. They are not dimensional and cannot be scaled for pipe size or product size.
DRY RETURN
SUPPLY MAIN
SUPPLY
VALVE
TRAP
DRY RETURN
TRAP
REDUCING TEE
SUPPLY MAIN
FULL SIZE OF TAPPING
SUPPLY VALVE WITH CHAINPULL
SUPPLY MAIN
NO-PRESSURE WET RETURN
REDUCING ELL
NOT LESS THAN 24
"
WATERLINE OF BOILER
SUPPLY VALVE WITH CHAINPULL
TRAP
FULL SIZE
OF TAPPING
DRY RETURN MAIN
MINIMUM COOLING LEG 5'-0" LONG
SUPPLY VALVE
DOWN FEED RISERS
TRAP
Two pipe steam systems radiator connections
Dripping heel of downfeed riser into dry return
Connections to ceiling radiators with return bled into wet return
Connections to ceiling radiator located above supply & return
Connections to radiator wall panel
SUPPLY MAIN
RETURN MAIN
SUPPLY VALVE
TRAP
Radiator connections taken from up or downfeed risers
Page 33
34
Low pressure closed gravity system
High pressure system
Unit heater connections for two pipe gravity
or vacuum system
Unit heater connections for two pipe gravity or
vacuum system with supply branch dripped
through trap
Vacuum or low pressure open
gravity system
Piping connections for unit heaters (steam)
GRAVITY OR VACUUM DRY RETURN MAIN
GRAVITY OR VACUUM DRY RETURN MAIN
SUPPLY LINE
UNIT HEATER
SEDIMENT POCKET
UNIT HEATER
VENT VALVE
AT LEAST 12" RETURN
CHECK VALVE
SUPPLY LINE
UNIT HEATER
SEDIMENT POCKET
UNIT HEATER
VENT VALVE
STRAINER
BUCKET TRAP
SUPPLY LINE
UNIT HEATER
SEDIMENT
POCKET
STRAINER
GATE VALVE
SUPPLY MAIN
UNIT HEATER
SAME SIZE AS TRAP
FULL SIZE
OF
TAPPING
GRAVITY VACUUM DRY RETURN MAIN
MINIMUM COOLING LEG 5'-0" LONG
TRAP
SUPPLY MAIN
GATE VALVE
UNIT HEATER
TRAP
MINIMUM COOLING LEG 5'-0" LONG
FULL SIZE
OF
TAPPING
GRAVITY VACUUM DRY RETURN MAIN
SAME SIZE AS TRAP
TRAP
Page 34
35
Connections to header coils
having more than 8 pipes
Connections to header coils
of not over 8 pipes
Connections for upfeed risers
Method of reducing size of main
Dripping end of supply main into dry return
Dripping drop riser or end of main
into dry return
Two pipe steam systems convector connections
Two pipe– steam trap installations
Exposed pipe coils– two pipe steam
TRAP
DRY RETURN
SUPPLY MAIN
RETURN RISER
HORIZONTAL BRANCH
45° ELBOWS
SUPPLY RISER
PIPES
BRANCH
ECCENTRIC REDUCER
DRY RETURN MAIN
SUPPLY MAIN
MINIMUM COOLING LEG 5'0" LONG
SAME SIZE AS TRAP
DROP RISER OR
END OF MAIN
MINIMUM COOLING LEG 5'0" LONG
SAME SIZE AS TRAP
TRAP
DRY RETURN
TRAP
SUPPLY
VALVE
OR UNION
SUPPLY
VALVE
OR UNION
SUPPLY
VALVE
OR UNION
SUPPLY
VALVE
OR UNION
PITCH DOWN
PITCH DOWN
PITCH DOWN
PITCH DOWN
VERTICAL
ANGLE
TRAP
ANGLE
TRAP
SWIVEL
TRAP
Distance from center of radiator tapping to face of sill must be given
Straight extended stem on supply valve
TRAP
DIRT POCKET
GATE VALVE
DIRT POCKET
TRAP
TRAP
TRAP
DIRT
POCKET
Page 35
36
WET RETURN
SUPPLY MAIN
PACKLESS RADIATOR VALVE
REDUCER
CAN BE
REDUCED
(Never Less
than 3/4 ")
NOT LESS
THAN 18"
WATER LINE OF BOILER
VENT
VALVE
DRY RETURN
SUPPLY MAIN
PACKLESS RADIATOR VALVE
VENT
VALVE
TRAP
MINIMUM COOLING LEG 5'-0" LONG
RISER
PITCH DOWN FROM HERE
PACKLESS RADIATOR
VALVE
AIR VALVE
SUPPLY MAIN
PITCH DOWN FROM HERE
PACKLESS
RADIATOR
VALVE
AIR VALVE
Upfeed connection to radiator
Radiator connection taken
from up or downfeed riser
One pipe steam systems radiator connections
Downfeed connections with wet return
Downfeed connections dripping riser into condensation pump return
Page 36
37
AT LEAST 12"
One pipe steam systems convector connections
Venting concealed radiator
of header type–air vent
tapping in top
Dripping end of one pipe steam main where
same extends beyond wet return
Expansion joint made up of pipe
for horizontal pipes–dripped into
wet return
Expansion joint made up of pipe
for horizontal pipes–not dripped
WET RETURN
STEAM MAIN
MAIN VENT
AT LEAST 18" ABOVE W.L.
AT LEAST
24"
DRY BLEEDER
DIRT POCKET
AIR VALVE
PITCH DOWN
PACKLESS
RADIATOR
VALVE
PITCH DOWN
PITCH DOWN
AIR VALVE
AIR CHAMBER
AIR VALVE
AIR CHAMBER
SUPPLY
VALVE
OR UNION
SUPPLY
VALVE
OR UNION
Page 37
38
B Constant
11
1
4° 5.126
22
1
2° 2.613
30° 2.000 45° 1.414 60° 1.155
Upfeed branch connection
taken from main at 45°
Expansion joint made up of
pipe for risers
Drop riser branch taken
from top of main at 45°
Drop riser taken from
bottom of main
Riser branch taken from bottom of
main and dripped into wet return
Method of taking double radiator
branch connections from riser
Method of taking branches from mains
Looping main around beam
Looping dry return main around door
To find C—multiply A by
constant for angle B
NOTE: Indicates direction of pitch
in piping connections
Method of reducing size of mains
RADIATOR
BRANCH
RISER
RISER
45°
ECCENTRIC REDUCER
FULL SIZE
AT LEAST 1"
RISER
MAIN
AT
LEAST
1"
PLUG FOR
CLEANOUT
PREFERREDACCEPTABLE
RISER
ANCHOR
45° ELL
DRIP PIPE
DIRT POCKET
WET RETURN
B.
C.
A.
Page 38
Each individual steam tracer line requires a separate trap to assure condensate drainage. When more than one tracer line is manifolded into a common trap, condensate can back up in the line with the greatest pressure drop.
Individual tracer line trap selection guide:
1. Bucket Traps may be used for tracer lines in areas not subject to freezing. The tracer lines should be installed for gravity drainage when Bucket Traps are used. Condensate will drain at saturation temper­ature for maximum heat transfer. Bucket Traps are normally too expensive for larger tracer applications.
2. Thermodisc Traps were designed for tracer line applications. The pulsation of the ther­modisc opening will cause condensate col­lected at low points to move through the tracer line. When installed according to manufacturer’s instructions, Thermodisc Traps completely drain all condensate from the body when the steam is off, to prevent freezing. Thermodisc Traps drain conden­sate at saturation temperature for maxi­mum heat transfer. They are inexpensive and the Hoffman 650 Series allow com­plete replacement of the seat and disc without removing the trap body from the line.
3. Thermostatic Traps open in response to temperature, not condensate level. Use where maximum heat transfer is not impor­tant. Thermostatic Traps normally open 10° to 30°F. below saturation temperature to extract the maximum Btu’s from the steam before draining condensate. Applications using Thermostatic Traps should be pitched to allow gravity conden­sate drainage. Thermostatic Traps select­ed for tracer lines should fail open. When the steam is off, the thermostatic element will open draining condensate to prevent freezing.
4. F & T Traps should never be used for trac­er line applications. They are subject to freezing when located in low ambient con­ditions when the steam is off. They are more expensive and normally fail in a closed position.
Trapping Steam Tracer Lines
39
1. Each tracer line must have its own trap.
2.A common trap with manifold tracer lines may cause short cir­cuiting through lines with lower pressure drop.
3. Longer lines will back-up condensate and will not provide ade­quate heat transfer.
CORRECT
WRONG
Page 39
Chapter 4
4-Step Method for Sizing Steam Lines
40
Based on Moody Friction Factor where flow of condensate does not inhibit the flow of steam.
Basic Chart for Weight-Flow Rate and Velocity of Steam in Schedule 40 Pipe
Based on Saturation Pressure of 0 PSIG
Figure 10
Reprinted by permission from ASHRAE 1972 Handbook of Fundamentals
Page 40
Velocity of Steam
General Heating Applications—
4,000 to 6,000 fpm.
Process Pipe—
6,000 to 12,000 fpm.
Sample Problem Using Steam Velocity Charts (Fig. 10).
General Heating Application—2,000 Ibs./hr. Required at 30 psi supply pressure.
Size Pipe and Determine Velocity and Pressure Drop
Step 1
Correct 30 psi flow rate to O psi on basic chart. This is done by entering bottom at 2,000 Ibs./hr. Follow this point vertically to the 30 Ib. Iine, then follow slope to the 0 psi line.
Step 2
Draw vertical line from 0 point into upper curve. Stop at some point above 6,000 fpm. Velocity shown is O psi steam and requires correction.
Step 3
Try 3 inch pipe showing 10,000 fpm velocity and pressure drop of approximately .9 psi per 100 feet.
Step 4
Use velocity multiplier chart. Enter left column at 10,000 fpm, follow sloping line to 30 psi. Read corrected velocity of 6,000 fpm in right column.
NOTE:
1. Use velocity chart to correct 6,000 fpm, required velocity, to 10,000 fpm before using basic chart.
2. Heat exchanger steam entrance nozzles are normally sized at reduced velocities to avoid impingement damage to the tube bun­dle. Check with heat exchange manufacturer for nozzle size.
Example of Use of Basic and Velocity Multiplier Charts. Given:
a. Weight-Flow Rate = 6700 Ib. per hr. b. Initial Steam Pressure = 100 psig. c. Pressure Drop = 11 psi per 100 ft.
Velocity Multiplier Chart
Figure 10 (continued)
Reprinted by permission from ASHRAE 1972
Handbook of Fundamentals
Find:
a. Size of Schedule 40 pipe required. b. Velocity of steam in pipe.
Solution: The following steps are illustrated by the broken line on Fig. 10:
Step 1. Enter Fig. 10 at a weight-flow rate of 6700 Ib. per hr. and move
vertically to the horizontal line at 100 psig.
Step 2. Follow along inclined multiplier line (upward and to the left) to horizontal 0 psig line. The equivalent weight flow at 0 psig is about 2500 Ib. per hr.
Step 3. Follow the 2500 Ib. per hr. Iine vertically until it intersects the hori­zontal line at 11 psi per 100 ft. pressure drop. The nominal pipe size is
1
2 in. The equivalent steam velocity at 0 psig is about 32,700 fpm.
2
Step 4. To find the steam velocity at 100 psig, locate the value of 32,700 fpm on the ordinate of the velocity multiplier chart at 0 psig.
Step 5. Move along the inclined multiplier line (downward and to the right) until it intersects the vertical 100 psig pressure line. The velocity as read from the right (or left) scale is about 13,000 fpm.
NOTE: The preceding Steps 1 to 5 would be rearranged or reversed if different data were given.
41
Page 41
42
Flow Rate Supply Pressure= 100 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 28 62 133
3
4 62 134 290
1 120 260 544 11⁄4 250 540 1130 11⁄2 380 810 1700
2 750 1590 a 21⁄2 1200 2550 a
3 2160 4550 a
4 4460 9340 a
6 13,200 a a
8 27,400 a a
Flow Rate Supply Pressure= 150 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 23 51 109
3
4 50 110 230
1 100 210 450 11⁄4 200 440 930 11⁄2 310 660 1400
2 610 1300 a 21⁄2 980 2100 a
3 1760 3710 a
4 3640 7630 a
6 10,800 a a
8 22,400 a a
Flow Rate Supply Pressure= 100 psig (lbs./hr.) Return Pressure=15 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 56 120 1100
3
4 120 260 2400
1 240 500 4540 11⁄4 500 1060 9500 11⁄2 750 1600 14,200
2 1470 3100 a 21⁄2 2370 5000 a
3 4230 8860 a
4 8730 18,200 a
6 25,900 53,600 a
8 53,400 110,300 a
Flow Rate Supply Pressure= 150 psig (lbs./hr.) Return Pressure=15 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 43 93 200
3
4 93 200 420
1 180 390 800 11⁄4 380 800 1680 11⁄2 570 1210 2500
2 1120 2350 4900 21⁄2 1800 3780 7800
3 3200 6710 a
4 6620 13,800 a
6 19,600 40,600 a
8 40,500 83,600 a
Flow Rate Supply Pressure= 30 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 60 130 274
3
4 130 280 590
1 250 530 1120 11⁄4 520 1110 2340 11⁄2 780 1670 3510
2 1540 3270 a 21⁄2 2480 5250 a
3 4440 9360 a
4 9180 19,200 a
6 27,300 a a
8 56,400 a a
Flow Rate Supply Pressure= 15 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 95 210 450
3
4 210 450 950
1 400 860 1820 11⁄4 840 1800 3800 11⁄2 1270 2720 5700
2 2500 5320 a 21⁄2 4030 8520 a
3 7200 15,200 a
4 14,900 31,300 a
6 44,300 a a
8 91,700 a a
Flow Rate Supply Pressure= 5 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 240 520 1100
3
4 510 1120 2400
1 1000 2150 4540 11⁄4 2100 4500 9500 11⁄2 3170 6780 14,200
2 6240 13,300 a 21⁄2 10,000 21,300 a
3 18,000 38,000 a
4 37,200 78,000 a
6 110,500 a a
8 228,600 a a
Condensate that collects ahead of a steam trap is approximately at saturation temperature and corresponds to the operating pressure. As the condensate (normally above 212°F.) drains into the return line, it must flash to reach saturation temperature at atmospheric pressure. The excess Btu’s are released in the form of flash steam in the return lines. The return lines must be sized to handle the volume of steam and condensate at reasonable velocities to minimize any backpressure. The volume of steam is normally several times the volume of condensate and is generally maintained at less than 7,000 feet per minute. The following tables are for horizontal return lines draining to a return system. Return lines should pitch 1
1
2 in. per 10 ft. of
horizontal run. Select the return line size
ASHRAE Method for Sizing Return Lines
based on the steam operating pressure and the allowable p/L, psi/100 ft. Selections for 100 and 150 psig steam for either a vented return system or a 15 psig pressurized return system such as a flash tank, deaerator or closed return system.
Example: A condensate return system has a steam supply at 100 psig and the return line is at 0 psig and not vented. The return line is horizontal and must have a capacity of 2500 lbs./hr. What size pipe is required?
Solution: Since the system will be throttling non-subcooled condensate from 100 psig to 0 psig there will be flash steam and the system will be a dry-closed return with horizontal pipe. Select a pressure drop of
1
4 psi/100 ft. and
use a 2
1
2 in. pipe for this system.
For these sizes and pressure losses, the velocity is above 7000 fpm. Select another combination of sizes and pressure loss.
Reprinted by permission of the American Society of Heating, Refrigeration and Air-Conditioning Engineers, Atlanta, Georgia, from the 1989 ASHRAE Handbook-Fundamentals
a
FLOW RATE (lbs./hr.) FOR DRY RETURN LINES
Flow Rate Supply Pressure= 50 psig (lbs./hr.) Return Pressure=0 psig
p/L, psi/100 ft.
Pipe Size (in.)
1
16
1
4
1
1
2 42 92 200
3
4 91 200 420
1 180 380 800 11⁄4 370 800 1680 11⁄2 560 1200 2520
2 1110 2350 a 21⁄2 1780 3780 a
3 3190 6730 a
4 6660 13,800 a
6 19,600 a a
8 40,500 a a
Page 42
Where a test valve is installed in the trap dis­charge piping, visual inspection is the most positive method of testing.
Thermostatic Traps, and F & T Traps modulate in operation. The discharge should be steady. Bucket Traps and Disc Traps cycle and the discharge should be intermittent. The trap is often discharging condensate above 212°F. When this high temperature condensate dis­charges to atmosphere flash steam may be present. Flash steam is normal and is not an indication of trap failure. Flash steam is a low velocity white colored discharge with a large stream of condensate. If the trap is blowing live steam it will be at high velocity—a clear area will be present ahead of where the steam begins to condense. Then, a bluish steam will begin and there will be less condensate along with the steam.
When no test valve is installed other methods may be used.
When the piping ahead of the steam trap is cold, this is an indication that the trap has failed in a closed position.
Temperature measuring devices may be used to test thermostatic traps. The temperature immediately ahead of the trap should be lower than the steam coil, radiator, etc.
Listening devices may be used to test traps that cycle, these include Bucket Traps and Disc Traps. As the linkage or disc opens, a low pitch sound occurs as condensate dis­charges. The linkage or disc closing can then be heard. No other sound should follow. A trap blowing live steam will have a higher pitch whistle as steam blows across the orifice.
F & T Traps modulate and discharge at satura­tion temperature. A fast response tempera­ture scanner may be used to test operation. You will be looking for two-phase flow in the discharge line. Two-phase flow has steam in the discharge line and will be over 212° F. along the piping. Flash steam normally con­denses in a short length of piping and will drop in temperature along the pipe. Live steam carried through the pipe will maintain a near constant temperature.
Where several traps are used in similar appli­cations make a comparison between different trap discharge temperatures. You will soon be able to pick out a defective trap. Both a listen­ing device and a temperature scanner should be available to spot trap problems.
Sight checkers provide a positive way to check steam traps. A sight checker would be installed in the outlet piping from the trap. When the trap opens the ball check lifts off the seat. It can be seen moving inside the glass enclosure. When the trap closes the
ball should seat. If the trap is blowing live steam the ball will move inside the housing.
Many independent trap survey companies will do field testing of traps. Due to the high cost of waste energy from defective steam traps, a trap survey normally has a good payback.
Testing Steam Traps
43
Chapter 5
START
HAS STEAM
SYSTEM
STABILIZED?
WAIT FOR
STABILIZATION
NO
IS TRAP
HOT?
IS STEAM
TURNED ON?
YES
TURN
STEAM
ON
PRESSURE
TO
TRAP?
A SYSTEM PROBLEM
YES
FIND AND
CORRECT
WHAT
KIND OF
TRAP?
TRAP HAS
PROBABLY
FAILED CLOSED
OR IS AIRBOUND
NO NO
YES
YES
NO
Testing Steam Traps
Objective:
Determine if trap is performing properly & efficiently.
Types of Tests:
Temperature, pressure, flow.
How to Check:
Listening device, temperature device, visual.
Listening Devices:
Screwdriver, stethoscope, ultrasonic tester.
Temperature Devices:
Gloves, water gun, crayons, pyrometer, infrared.
Real Reason:
Hot-cold, Go/no go, Repair or replace.
Check list–step by step
Page 43
Trap Type is a Factor
Thermostatic
• Modulates
• Discharges continuously.
• Sound test—rush of condensate, hiss of live steam.
• Visual—must distinguish between flash & live steam.
Float & Thermostatic
• Modulating device.
• Element passes air.
• More intense—for failed element passing
steam.
• Orifice failure—erosion.
• Must distinguish between live steam &
flash steam.
• Crushed ball—failure mode is closed.
44
THERMOSTATIC
TRAP
IS TRAP
CYCLING?
NO
IS RUSHING
STEAM
HEARD?
NO
YES
YES
TIGHT
CLOSURE
BETWEEN
CYCLES?
NO
TRAP IS
PROBABLY
LEAKING
REPLACE
OR
REPAIR
YES
GOOD
TRAP
FLOAT AND
THERMOSTATIC
TRAPS
IS RUSHING
STEAM
HEARD?
YES
DOES TRAP
APPEAR TO LEAK
STEAM?
NO
NO
PROBABLY A
GOOD TRAP
PROBABLY A
GOOD TRAP
DOES TRAP
APPEAR TO LEAK STEAM?
YES
REPAIR
OR
REPLACE
NO
PROBABLY
A GOOD TRAP
YES
REPAIR
OR
REPLACE
Page 44
Bucket Trap
• Discharges full capacity then shuts off.
• Muffled rattle of bucket on outer chamber.
• Violent bucket rattle & sound of rushing steam—
lost prime.
• Clogged air vent—fails closed.
• Discharge under loads
—Modulates under light load
—Continuous discharge at full capacity.
Disc
• Best test is sound.
• Trap cycling is audible.
• Disc slams against seat.
• Leaking seat—would be heard.
• Rapid cycle—excessive wear.
• Machine gunning—live steam.
45
INVERTED
BUCKET
TRAP
CHECK
SIZING
PROBABLY
LEAKING
DISC
TRAP
YES
HIGH
CYCLE
RATE
CAN TRAP
DISCHARGE
BE HEARD?
NO–
CONTINUOUS
DISCHARGE
CYCLE
YES LOW
CYCLE
RATE
LEAK STEAM?
GOOD
TRAP
NO
DOES TRAP APPEAR TO
YES
REPAIR
OR
REPLACE
CAN CYCLES
BE HEARD?
NO–
CONTINUOUS
DISCHARGE
APPROACHING
CAPACITY?
NO
IS RUSHING
STEAM SEEN
OR HEARD?
YES
REPLACE
LOAD TRAP
REPAIR
OR
YES
YES
NO
SHUT
TIGHT
BETWEEN
DISCHARGES?
NO
IS RUSHING
STEAM HEARD
OR SEEN?
YES
PROBABLY
A GOOD
TRAP
GOOD TRAP—
BUCKET TRAPS CAN MODULATE
ON A SMALL % OF RATED CAPACITY
YES
NO
GOOD
TRAP
GOOD
TRAP
REPAIR
OR
REPLACE
DOES TRAP APPEAR TO
LEAK STEAM?
YES
REPAIR
OR
REPLACE
NO
COULD BE
RESPONDING
TO HEAVY
CONDENSATE
LOAD
Page 45
Definition of Heating Terms
The definitions given in this section are only those applying to heating and particularly as used in this book. Some do not define the terms for all usages.
Absolute Humidity: The weight of water vapor in grains actually contained in one cubic foot of the mixture of air and moisture.
Absolute Pressure: The actual pressure above zero. It is the atmospheric pressure added to the gauge pressure. It is expressed as a unit pres­sure such as Ibs.per sq. in. absolute.
Absolute Temperature: The temperature of a substance measured above absolute zero. To express a temperature as absolute temperature add 460° to the reading of a Fahrenheit ther­mometer or 273° to the reading of a Centigrade.
Absolute Zero: The temperature (-460°F. approx.) at which all molecular motion of a sub­stance ceases, and at which the substance con­tains no heat.
Air: An elastic gas. It is a mechanical mixture of oxygen and nitrogen and slight traces of other gases. It may also contain moisture known as humidity. Dry air weighs 0.075 Ibs. per cu. ft.
One Btu will raise the temperature of 55 cu. ft. of air one degree F.
Air expands or contracts approximately 1/490 of its volume for each degree of rise or fall in tem­perature from 32° F.
Air Change: The number of times in an hour the air in a room is changed either by mechanical means or by the infiltration of outside air leaking into the room through cracks around doors and windows, etc.
Air Cleaner: A device designed for the purpose of removing air-borne impurities such as dust, fumes, and smokes. (Air cleaners include air washers and air filters.)
Air Conditioning: The simultaneous control of the temperature, humidity, air motion, and air distribution within an enclosure. When human comfort and health are involved, a reasonable air purity with regard to dust, bacteria,and odors is also included. The primary requirement of a good air conditioning system is a good heating system.
Air Infiltration: The leakage of air into a house through cracks and crevices, doors, windows, and other openings, caused by wind pressure and/or temperature difference.
Air Valve: See Vent Valve.
Atmospheric Pressure: The weight of a column
of air, one square inch in cross section and extending from the earth to the upper level of the blanket of air surrounding the earth. This air exerts a pressure of 14.7 pounds per square inch at sea level, where water will boil at 212°F. High altitudes have lower atmospheric pressure with correspondingly lower boiling point tempera­tures.
Boiler: A closed vessel in which steam is gener­ated or in which water is heated by fire.
Boiler Heating Surface: The area of the heat transmitting surfaces in contact with the water (or steam) in the boiler on one side and the fire or hot gases on the other.
Boiler Horsepower: The equivalent evaporation of 34.5 Ibs. of water per hour at 212° F. to steam at 212° F. This is equal to a heat output of 33,475 Btu per hour, which is equal to approximately 140 sq. ft. of steam radiation (EDR) .
British Thermal Unit (Btu): The quantity of heat required to raise the temperature of 1 Ib. of water 1°F. This is somewhat approximate but sufficiently accurate for any work discussed in this book.
Bucket Trap (Inverted): A float trap with an open float. The float or bucket is open at the bottom. When the air or steam in the bucket has been replaced by condensate the bucket loses its buoyancy and when it sinks it opens a valve to permit condensate to be pushed into the return.
Bucket Trap (Open): The bucket (float) is open at the top. Water surrounding the bucket keeps it floating and the pin is pressed against its seat. Condensate from the system drains into the bucket. When enough has drained into it so that the bucket loses its buoyancy it sinks and pulls the pin off its seat and steam pressure forces the condensate out of the trap.
Calorie (Small): The quantity of heat required to raise 1 gram of water 1°C (approx.).
Calorie (Large): The quantity of heat required to raise 1 kilogram of water 1°C (approx.).
Centigrade: A thermometer scale at which the freezing point of water is 0° and its boiling is 100°.
Central Fan System: A mechanical indirect sys­tem of heating, ventilating, or air conditioning consisting of a central plant where the air is heated and/or conditioned and then circulated by fans or blowers through a system of distribut­ing ducts.
Chimney Effect: The tendency in a duct or other vertical air passage for air to rise when heated due to its decrease in density.
46
Chapter 6
Page 46
Coefficient of Heat Transmission (Over-all)-U-:
The amount of heat (Btu) transmitted
from air to
air
in one hour per square foot of the wall, floor, roof, or ceiling for a difference in temperature of one degree Fahrenheit
between the air on the inside and outside of the wall, floor, roof, or ceiling.
Column Radiator: A type of direct radiator. This radiator has not been sold by manufacturers since 1926.
Comfort Line: The effective temperature at which the largest percentage of adults feel com­fortable.
Comfort Zone (Average): The range of effective temperatures over which the majority of adults feel comfortable.
Concealed Radiator: See Convector. Condensate: Water formed by cooling steam.
The capacity of traps, pumps, etc., is some­times expressed in Ibs. of condensate they will handle per hour. One pound of condensate per hour is equal to approximately 4 sq. ft. of steam heating surface (240 Btu per hour per sq. ft.).
Conductance (Thermal)-C-: The amount of heat (Btu) transmitted from surface to surface, in one hour through one square foot of a material or construction for the thickness or type under con­sideration for a difference in temperature of one degree Fahrenheit between the two surfaces.
Conduction (Thermal): The transmission of heat through and by means of matter.
Conductivity (Thermal)-k-: The amount of heat (Btu) transmitted in one hour through one square foot of a homogenous material one inch thick for a difference in temperature of one degree Fahrenheit between the two surfaces of the material.
Conductor (Thermal): A material capable of read­ily transmitting heat by means of conduction.
Convection: The transmission of heat by the cir­culation (either natural or forced) of a liquid or a gas such as air. If natural, it is caused by the difference in weight of hotter and colder fluid.
Convector: A concealed radiator. An enclosed heating unit located either within, adjacent to, or exterior to the room or space to be heated, but transferring heat to the room or space mainly by the process of convection. A shielded heating unit is also termed a convector. If the heating unit is located exterior to the room or space to be heated, the heat is transferred through one or more ducts or pipes.
Convertor: A piece of equipment for heating water with steam without mixing the two. It may be used for supplying hot water for domestic purposes or for a hot water heating system.
Cooling Leg: A length of uninsulated pipe through which the condensate flows to a trap and which has sufficient cooling surface to per­mit the condensate to dissipate enough heat to prevent flashing when the trap opens. A thermo­static trap may require a cooling leg to permit the condensate to drop enough in temperature to permit the trap to open.
Degree-Day: (Standard) A unit which is the differ­ence between 65° F. and the daily average tem­perature when it is below 65°F. The “degree day” on any given day is equal to the number of degrees F. that the average temperature for that day is below 65° F.
Dew-Point Temperature: The air temperature corresponding to saturation (100 percent rela­tive humidity) for a given moisture content. It is the lowest temperature at which air can retain water vapor.
Direct-lndirect Heating Unit: A heating unit located in the room or space to be heated which is fully or partially closed. The enclosed portion is used to heat air which enters from outside the room.
Direct Radiator: Same as radiator. Domestic Hot Water: Hot water used for purpos-
es other than house heating such as laundering, dishwashing, bathing, etc.
Down-Feed One-Pipe Riser (Steam): A pipe which carries steam downward to the heating units and into which heating units drain condensation.
Down-Feed System (Steam): A steam heating system in which the supply mains are above the level of the heating units which they serve.
Dry-Bulb Temperature: The temperature of the air as determined by an ordinary thermometer.
Dry Return (Steam): A return pipe in a steam heating system which carries both condensation and air.
Dry Saturated Steam: Saturated steam contain­ing no water in suspension.
Equivalent Direct Radiation (E.D.R.): See Square Foot of Heating Surface.
Extended Heating Surface: Heating surface consisting of ribs, fins, or extended surfaces which receive heat by conduction from the prime surface.
Extended Surface Heating Unit: A heating unit having a relatively large amount of extended sur­face which may be integral with the core contain­ing the heating medium or assembled over a core, making good thermal contact by pressure, or by being soldered to the core or by both pres­sure and soldering. An extended surface heating unit is usually placed within an enclosure and functions as a convector.
47
Page 47
Fahrenheit: A thermometer scale at which the freezing point of water is 32° and its boiling point is 212° above zero.
Flash (Steam): The rapid passing into steam of water at a high temperature when the pressure it is under is reduced so that its temperature is above that of its boiling point for the reduced pressure. For example: If hot condensate is dis­charged by a trap into a low pressure return or into the atmosphere, a certain percentage of the water will be immediately transformed into steam. It is also called re-evaporation .
Float & Thermostatic Trap: A float trap with a thermostatic element for permitting the escape of air into the return line.
Float Trap: A steam trap which is operated by a float. When enough condensate has drained (by gravity) into the trap body the float is lifted. In turn, the pin lifts off its seat. This permits the condensate to flow into the return until the float has been sufficiently lowered, to close the port. Temperature does not affect the operation of a float trap.
Furnace: That part of a boiler or warm air heat­ing plant in which combustion takes place. Complete heating unit of a warm air heating system.
Gauge Pressure: The pressure above that of the atmosphere. It is the pressure indicated on an ordinary pressure gauge. It is expressed as a unit pressure such as Ibs. per sq. in. gauge.
Head: Unit pressure usually expressed in ft. of water or mil-inches of water.
Heat: That form of energy into which all other forms may be changed. Heat always flows from a body of higher temperature to a body of lower tem­perature. See also: Latent Heat, Sensible Heat, Specific Heat, Total Heat, Heat of the Liquid.
Heat of the Liquid: The heat (Btu) contained in a liquid due to its temperature. The heat of the liq­uid for water is zero at 32° F. and increases 1 Btu approximately for every degree rise in tem­perature.
Heat Unit: In the foot-pound-second system, the British Thermal Unit (Btu) in the centimeter-gram­second system, the calorie (cal.).
Heating Medium: A substance such as water, steam, or air used to convey heat from the boil­er, furnace, or other source of heat to the heat­ing units from which the heat is dissipated.
Heating Surface: The exterior surface of a heat­ing unit. See also Extended Heating Surface.
Heating Unit: Radiators, convectors, base boards, finned tubing, coils embedded in floor, wall, or ceiling, or any device which transmits the heat from the heating system to the room and its occupants.
Horsepower: A unit to indicate the time rate of doing work equal to 550 ft.-lb. per second, or 33,000 ft.-lb. per minute. One horsepower equals 2545 Btu per hour or 746 watts.
Hot Water Heating System: A heating system in which water is used as the medium by which heat is carried through pipes from the boiler to the heating units.
Humidistat: An instrument which controls the relative humidity of the air in a room.
Humidity: The water vapor mixed with air. Insulation (Thermal): A material having a high
resistance to heat flow. Latent Heat of Evaporation: The heat (Btu per
pound) necessary to change 1 pound of liquid into vapor without raising its temperature. In round numbers this is equal to 960 Btu per pound of water.
Latent Heat of Fusion: The heat necessary to melt one pound of a solid without raising the temperature of the resulting liquid. The latent heat of fusion of water (melting 1 pound of ice) is 144 Btu.
Mechanical Equivalent of Heat: The mechanical energy equivalent to 1 Btu which is equal to 778 ft.-lb.
Mil-lnch: One one-thousandth of an inch (0.001”). One-Pipe Supply Riser (Steam): A pipe which
carries steam to a heating unit and which also carries the condensation from the heating unit. In an up feed riser steam travels upwards and the condensate downward while in a down feed both steam and condensate travel down.
One-Pipe System (Hot Water): A hot water heat­ing system in which one pipe serves both as a supply main and as a return main. The heating units have separate supply and return pipes but both are connected to the same maln.
One-Pipe System (Steam): A steam heating sys­tem consisting of a main circuit in which the steam and condensate flow in the same pipe. There is one connection to each heating unit which serves as both the supply and the return.
Overhead System: Any steam or hot water sys­tem in which the supply main is above the heat­ing units. With a steam system the return must be below the heating units; with a water system, the return may be above the heating units.
Panel Heating: A method of heating involving the installation of the heating units (pipe coils) in the walls, floor or ceiling of the room.
Panel Radiator: A heating unit placed on, or flush with, a flat wall surface and intended to function as a radiator. Do not confuse with panel heating system.
48
Page 48
Pressure: Force per unit area such as Ib. per sq. inch. Unless otherwise qualified, it refers to unit static gauge pressure. See Static, Velocity, Total Gauge and Absolute Pressures.
Pressure Reducing Valve: A device used to decrease the pressure of a gas or liquid.
Prime Surface: A heating surface with the heat­ing medium on one side and air (or extended surface) on the other.
Radiant Heating: A heating system in which the heating is by radiation only. Sometimes used in a Panel Heating System.
Radiation: The transmission of heat in a straight line through space.
Radiator: A heating unit located in the room to be heated and exposed to view. A radiator trans­fers heat by radiation to objects “it can see” and by conduction to the surrounding air which in turn is circulated by natural convection.
Recessed Radiator: A heating unit recessed in a wall but not enclosed.
Reducing Valve: See Pressure Reducing Valve. Re-Evaporation: See Flash. Refrigeration, Ton of: See Ton of Refrigeration. Relative Humidity: The amount of moisture in a
given quantity of air compared with the maxi­mum amount of moisture the same quantity of air could hold at the same temperature. It is expressed as a percentage.
Return Mains: The pipes which return the heat­ing medium from the heating units to the source of heat supply.
Reverse-Return System (Hot Water): A two-pipe hot water heating system in which the water from several heating units is returned along paths so that all radiator circuits of the system are of equal length .
Sensible Heat: Heat which increases the tem­perature of objects as opposed to latent heat.
Specific Heat: In the foot-pound-second system, the amount of heat (Btu) required to raise one pound of a substance one degree Fahrenheit. In the centimeter-gram-second system, the amount of heat (cal.) required to raise one gram of a substance one degree C. The specific heat of water is 1.
Split System: A system in which the heating is accomplished by radiators or convectors and ventilation by separate apparatus.
Square Foot of Heating Surface: Equivalent direct radiation (EDR). By definition, that amount of heating surface which will give off 240 Btu per hour when filled with a heating medium at 215°F. and surrounded by air at 70° F. The equivalent square foot of heating surface may have no direct relation to the actual surface area.
Static Pressure: The pressure at which a pipe will burst. It is used to overcome the frictional resistance to flow through the pipe. It is expressed as a unit pressure and may be in absolute or gauge pressure. It is frequently expressed in feet of water column or in the case of pipe friction in mil-inches of water column per ft. of pipe.
Steam: Water in the vapor phase. The vapor formed when water has been heated to its boil­ing point, corresponding to the pressure it is under. See also Dry Saturated Steam, Wet Saturated Steam, Superheated Steam.
Steam Heating System: A heating system in which the heating units give up their heat to the room by condensing the steam furnished to them by a boiler or other source.
Steam Trap: A device for allowing the passage of condensate and air but preventing the pas­sage of steam. See Thermostatic, Float, Bucket Trap.
Superheated Steam: Steam heated above the temperature corresponding to its pressure.
Supply Mains: The pipes through which the heat­ing medium flows from the boiler or source of supply to the run-outs and risers leading to the heating units.
Tank Regulator: See Temperature Regulator. Temperature Regulator: A device for controlling
the admission of steam to a hot water or liquid heating device in correct quantities so that the temperature of the liquid will remain constant.
Thermostat: An instrument which responds to changes in temperature and which directly or indirectly controls the room temperature.
Thermostatic Trap: A steam trap which closes when the steam reaches it and opens when the temperature surrounding it drops. This occurs when cold condensate or air reaches it. The tem­perature sensitive element is usually a sealed bellows or series of diaphragm chambers con­taining a small quantity of volatile liquid.
Ton of Refrigeration: The heat which must be extracted from one ton (2,000 Ibs.) of water at 32° F. to change it into ice at 32°F. in 24 hours. It is equal to 288,000 Btu/24 hours, 12,000 Btu/hour, or 200 Btu/minute.
49
Page 49
Total Heat: The latent heat of vaporization added to the heat of the liquid with which it is in contact.
Total Pressure: The sum of the static and veloci­ty pressures. It is also used as the total static pressure over an entire area, that is, the unit pressure multiplied by the area on which it acts.
Trap: See Steam Trap, Thermostatic Trap, Float Trap, and Bucket Trap.
Two-Pipe System (Steam or Water): A heating system in which one pipe is used for the supply main and another for the return main. In a two­pipe hot water system each heating unit receives a direct supply of the heating medium.
Unit Heater: A heating unit consisting of a heat transfer element, housing, fan with motor, and outlet deflectors or diffusers. It is usually sus­pended from the ceiling and its heat output is controlled by starting and stopping the fan by a room thermostat. The circulation of the heating medium (steam or hot water) is usually continu­ous. It is used primarily for industrial heating.
Unit Pressure: Pressure per unit area as Ibs. per sq. in.
Up-Feed System (Hot Water or Steam): A heat­ing system in which the supply mains are below the level of the heating units which they serve.
Vacuum Heating System (Steam): A one- or two-pipe heating system equipped with the nec­essary accessory apparatus to permit the pres­sure in the system to go below atmospheric.
Vapor: Any substance in the gaseous state. Vapor Heating System (Steam): A two-pipe
heating system which operates at or near atmo­spheric pressure and returns the condensation to the boiler or receiver by gravity.
Velocity Pressure: The pressure used to create the velocity of flow in a pipe. It is expressed as a unit pressure.
Ventilation: Air circulated through a room for ventilating purposes. It may be mechanically circulated with a blower system or through circulation with an open window, etc.
Vent Valve (Steam): A device that permits air to be forced out of a heating unit or pipe and closes against water and steam.
Vent Valve (Water): A device that permits air to be forced out of a heating unit or pipe and closes against water.
Warm Air Heating System: A warm air heating plant consists of a heating unit (fuel-burning fur­nace) enclosed in a casing, from which the heat­ed air is distributed to the various rooms of the building through ducts. If the motive head pro­ducing flow depends on the difference in weight between the heated air leaving the casing and the cooler air entering the bottom of the casing, it is termed a gravity system. A booster fan may, however, be used in conjunction with a gravityde­signed system. If a fan is used to produce circu­lation and the system is designed especially for fan circulation, it is termed a fan furnace system or a central fan furnace system. A fan furnace system may include air washer, filters, etc.
Wet Bulb Temperature: The lowest temperature which a water-wetted body will attain when exposed to an air current.
Wet Return (Steam): That part of the return main of a steam heating system which is com­pletely filled with water of condensation.
Wet Saturated Steam: Saturated steam contain­ing some water particles in suspension.
50
Page 50
Xylem |’zĪl m|
e
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,500 people unied in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efciently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com/brands/bellgossett
Xylem, Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053
Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem, Inc. or one of its subsidiaries. © 2012 Xylem, Inc. HS-203CA April 2000
Loading...