Bell & Gossett HS 100D User Manual

INSTRUCTION MANUAL
HS-100
REVISION D
Hoffman Specialty
®
Steam Vents for Radiators Model 1A and 1B Air Valve (non vacuum)
1A 1/8" NPT Connection
Maximum operating pressure 11⁄2 psig. Maximum pressure 10 psig.
1B 1/4" NPT Connection
Adjustable ports for
SLOW FAST
No1
2 1 6 54
A
B
proportional venting.
Venting Speed Port No. For
Fast 5 or 6 Radiation
located farthest from the boiler or areas that are hard to heat.
Medium 3 or 4 Normal venting
of radiation under normal conditions.
Slow 1 or 2 Radiation
located nearest the boiler or areas that overheat.
Note: The air valve is factory set on port 6 for fast venting. To change the venting speed follow “Port Adjustment” instructions.
Port Adjustment
• Port 1 provides the slowest venting.
• Port 6 provides the fastest venting.
To decrease venting speed:
1. Loosen nut “A” on the
top of the air valve.
A
No1
SLOW FAST
2 1 6 54
2. Turn cap “B” to the left.
B
3. Hold cap “B” at the desired setting and tighten nut.
To increase venting speed:
1. Loosen nut “A” on the
top of the air valve.
2. Turn cap “B” to the right.
3. Hold cap “B” at the desired setting and tighten nut “A”.
escape from the radiator as the steam pushes in. A cold upper part of the radiator may indicate the vent is plugged with scale or is malfunctioning. Vapor or slight moisture from the vent is normal. Steam continuously passing through the vent indicates a malfunction. Replace the vent as needed or every 10 years.