Bell & Gossett DN0156F User Manual

INSTRUCTION MANUAL
DN0156 REVISION F
Hoffman Specialty
®
Vented Condensate Units Watchman Series WC,™ WCS
and Series SCC
WC SIMPLEX
®
Watchman
WC8-20B
SCC4
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
WCS Duplex
Watchman
WCSD-12-20BMA
®
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on
the unit safety instruction decals to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARLY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
P70644 ALL UNITS
HOFFMAN SPECIALTY WATCHMAN
CONDENSATE UNIT
SERIES MODEL
SERIAL
GPM PSI
VOLT 115 PH 1 HZ60
P70644
TM
EXPLOSIBLE
(2) All Units
DN0483 (Small) - DN0484 (Large)
®
WARNING
DO NOT PRESSURIZE TANK. ISOLATE TANK DURING LEAK TEST. DO NOT RESTRICT VENT. DO NOT PLUG OVERFLOW. OPEN INLET VALVES SLOWLY. DO NOT USE AS A FLASH TANK.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
If the decals as noted below are missing or are illegible contact your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in accordance with all National, State and Local codes.
2. Motor must have properly sized starter with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at extremely high or low temperatures, guarding or insulation is required.
4. Operating personnel should be trained in the operation of condensate return units.
WARNING
EXPLOSIBLE
ISOLATE TANK
DURING LEAK TEST
(2) All Units DN0485 (Small) DN0486 (Large)
TM
SERIES
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ60
CONTROL V. PH. 1 HZ60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
TM
Morton Grove, Illinois 60053
DN0016
SCC UNITS WITH PANEL
SERIES
MODEL
SERIAL
GPM PSI PUMP
POWER V. PH. HZ60
CONTROL V. PH. 1 HZ60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0019
DN0019
SCC UNITS LESS PANEL
TM
TM
Morton Grove, Illinois 60053
Morton Grove, Illinois 60053
DN0039
DN0039 ALL WC AND WCS UNITS
3
MOTOR
1
MOTOR
115/1 60*
LINE
L1
L2
FLOAT SWITCH POWER SUPPLY, PRIMARY PROTECTION BY OTHERS
1DW129A 1DW130A
LINE
L2
L1
POWER SUPPLY, PRIMARY PROTECTION BY OTHERS
FLOAT SWITCH
REPRESENTATIVE WIRING DIAGRAMS
WATCHMAN®SIMPLEX UNITS, SINGLE PHASE
WATCHMAN®AND SCC1 DUPLEX UNITS, SINGLE PHASE
FIELD WIRING SHOULD BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.
DASHED LINE WIRING & COMPONENTS BY OTHERS
*230/1/60 VOLTAGE PERMISSIBLE IF MOTOR IS
RECONNECTED PER 'HIGH VOLTAGE' DIAGRAM ON MOTOR AND APPLICABLE PRIMARY PROTECTION IS SUPPLIED.
MOTOR
2
MOTOR
1
MOTOR
2
MOTOR
1
115/1/60*
LINE
115/1/60*
LINE
L1
L2
L1
L2
1DW129B 1DW130B
LINELINE
L2
L1
L2
L1
POWER SUPPLY, PRIMARY PROTECTION BY OTHERS
POWER SUPPLY, PRIMARY PROTECTION BY OTHERS
MECHANICAL ALTERNATOR
MECHANICAL ALTERNATOR
FIELD WIRING SHOULD BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE.
DASHED LINE WIRING & COMPONENTS BY OTHERS
MODEL SCC2, SCC3 & SCC4 (DUPLEX, 3 PHASE UNITS WITH CONTROL PANEL)
CONNECTION DIAGRAM ELEMENTARY DIAGRAM
LINE
1 H3 H 4
LINE
TRANSFORMER FUSE TYPE FNQ-R OR EQUIV. 600V / AMP
1
2
MAIN DISCONNECT SWITCH AND SHORT CIRCUIT PROTECTION BY OTHERS
FIELD WIRING SHOULD BE IN ACCORDANCE WITH THE N.E.C.
TRANSF. PRIMARY JUMPER PER TRANSF. LABEL
1 H3 H 4
L2 L1
L2 L1
GRN
GRN
COIL COIL
COIL
COIL COIL COIL
X1X1X2
X2
H1
H4
H1
H4
11
54 109
5
7
13
3
S2
S1
T1 T2 T3
T1 T2 T3
3
8
4 7 9 12
MOTOR
1
MOTOR
2
MECHANICAL ALTERNATOR (AUTOMATIC)
7
4
9
12
ALT.1
ALT.2
ENCLOSURE
FUSE
TRANSF #1 (115 V.A.C. SEC. 1)
MECH. ALT. (ALT. 1)
TRANSF. #2 (115 V.A.C. SEC. 1)
FUSE
MECH. ALT. (ALT. 2)
MOTOR
2
MOTOR
1
L1
L2
L3
T1
T2
T3
S1
S1
S1
GRN
GRN
X1 X2
X1 X2
L1
L2
L3
T1
T2
T3
S2
S2
S2
S1
S2
10
9
12
13
10
O.L.
O.L.
4
785
5
2DW128
SCC2, SCC3 AND SCC4 UNITS ARE FACTORY WIRED FOR 230 VOLT, 3 PHASE 60 HERTZ. KITS ARE AVAILABLE TO CONVERT TO 280V OR 460 VOLTS.
4
PUTTING THE UNIT INTO SERVICE
1. Assure that the unit is piped in accordance with instructions
in this manual.
2. Isolate tank before performing any system leak test. Do not pressurize the tank as part of the leak test. Failure to do this can result in serious injury or death.
3. Check floats and alternators for free operation.
4. Wire unit per National Electrical Code. See representative wiring diagrams.
5. Install drain plugs.
6. Fill receiver half full of water to prime pump(s) and prevent possible damage to pump seals. Avoid freezing conditions after unit receiver has been filled.
7. Check for proper rotation of all three phase motors. Rotation must be clockwise looking down on the motor as indicated by directional arrow on pump casting. If pump runs backwards, interchange two wires (3 phase only).
8. Throttle plug cock in discharge line until pressure at pump (while pump is discharging) approaches pump rated pres­sure. Tighten plug nut to secure adjustment.
9. Remove start-up label (below) from panel (if applicable) after complying with instructions.
10. If possible, observe operation thru several cycles.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.
Inspect pump seal regularly for leaks. Replace as required.
Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT REVERSE
Reverse operation can cause extensive damage to
pumps. Jog the motor to test for direction of rotation. Failure to follow these instructions could result in injury or property damage.
OPERATION AND MAINTENANCE
Operators must be familiar with all sections of this manual to
understand the operation of the unit. Hot water, steam and electricity can be hazardous.
Check motor nameplate for any lubrication requirements. Pumps require no lubrication.
NOTICE / AUTO RESTART
Single phase motors will restart automatically after thermal
overload protector trips. Overload thermal relays in starters must be reset manually. A properly installed unit should function unattended for long
periods of time. Periodic checks to assure proper operations are highly recommended. Refer to trouble shooting section when necessary.
A variety of control options are available and are furnished in accordance with user specifications. Refer to wiring diagrams (when furnished) to determine control switch settings.
The inlet strainer (when furnished) is intended to protect the pump and system. Periodic cleaning should be included in the maintenance schedule. Check frequently in new systems.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: SUBSEQUENT DAMAGE
A unit showing symptoms of possible problems
(overflow, noise, leaks, vibrations, continual operation, etc.) must be corrected immediately. Failure to follow these instructions may result in full liability for subsequent injury or property damage.
SAFETY INSTRUCTIONS
SEE COVER OF THIS MANUAL
ELECTRICIAN/INSTALLER/OPERATOR
REMOVE AND DESTROY THIS TAG AFTER
1. ASSURING THAT ALL PUMPS ROTATE CLOCKWISE PER ARROWS CAST ON VOLUTES. (JOG PUMP MOMENTARILY TO TEST – INTERCHANGE ANY TWO MOTOR POWER WIRES TO REVERSE 3PH MOTORS.)
2. ASSURING THAT SHIPPING LOCKS HAVE BEEN REMOVED FROM ALL FLOAT SWITCHES.