Bell & Gossett DN0154D User Manual

Page 1
INSTRUCTION MANUAL
DN0154
REVISION D
Hoffman Specialty
®
Vented Condensate Units Series HC™ and HS
SERIES HS™with
Optional Panel & Equipment
SERIES HC
Optional Panel & Equipment
with
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on
the unit safety instruction decals to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
WARNING
EXPLOSIBLE
ISOLATE TANK
DURING LEAK TEST
(2) All Units
DN0485 (Small)
DN0486 (Large)
EXPLOSIBLE
(2) All Units
DN0483 (Small) - DN0484 (Large)
WARNING
DO NOT PRESSURIZE TANK. ISOLATE TANK DURING LEAK TEST. DO NOT RESTRICT VENT. DO NOT PLUG OVERFLOW. OPEN INLET VALVES SLOWLY. DO NOT USE AS A FLASH TANK.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
If the decals as noted below are missing or are illegible contact your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in accordance with all National, State and Local codes.
2. Motor must have properly sized starter with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at extremely high or low temperatures, guarding or insulation is required.
4. Operating personnel should be trained in the operation of condensate return units.
TM
SERIES
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ 60
CONTROL V. PH. 1 HZ 60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
TM
Morton Grove, Illinois 60053
DN0116
Units with Panel
SERIES
MODEL
SERIAL
GPM PSI PUMP
POWER V. PH. HZ60
CONTROL V. PH. 1 HZ60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
TM
TM
Morton Grove, Illinois 60053
DN0019
Units Less/Panel
CAUTION
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARLY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
P70644
All Units
P70644
Page 2
Page 3
3
PUTTING THE UNIT INTO SERVICE
1. Assure that the unit is piped in accordance with instructions
on page 2.
2. Isolate tank before performing any system leak test. Do not pressurize the tank as part of the leak test. Failure to do this can result in serious injury or death.
3. Check floats and alternators for free operation.
4. Check power leads in accordance with wiring diagram enclosed in control cabinet (when furnished).
5. Install drain plugs.
6. Fill receiver half full of water to prime pump(s) and prevent possible damage to pump seals. Avoid freezing conditions after unit receiver has been filled.
7. Check for proper rotation of all three phase motors. Rotation must be clockwise looking down on the motor as indicated by directional arrow on pump casting. If pump runs backwards, interchange two wires (3 phase only).
8. Throttle plug cock in discharge line until pressure at pump (while pump is discharging) approaches pump rated pres­sure. Tighten plug nut to secure adjustment.
9. Remove start-up label (below) from panel (if applicable) after complying with instructions.
10. If possible, observe operation thru several cycles.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.
Inspect pump seal regularly for leaks. Replace as required.
Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT REVERSE
Reverse operation can cause extensive damage to
pumps. Jog the motor to test for direction of rotation. Failure to follow these instructions could result in injury or property damage.
OPERATION AND MAINTENANCE
Operators must be familiar with all sections of this manual to
understand the operation of the unit. Hot water, steam and electricity can be hazardous.
Check motor nameplate for any lubrication requirements. Pumps require no lubrication.
NOTICE / AUTO RESTART
Single phase motors will restart automatically after thermal
overload protector trips. Overload thermal relays in starters must be reset manually. A properly installed unit should function unattended for long
periods of time. Periodic checks to assure proper operations are highly recommended. Refer to trouble shooting section when necessary.
A variety of control options are available and are furnished in accordance with user specifications. Refer to wiring diagrams (when furnished) to determine control switch settings.
The inlet strainer (when furnished) is intended to protect the pump and system. Periodic cleaning should be included in the maintenance schedule. Check frequently in new systems.
GAGE GLASS MAINTENANCE (Vented Systems)
Clean gage glass as required using commercial glass cleaner.
Dilute muratic acid may be used if required (observe handling precautions). Never clean gage glass with wire brushes, scrapers or harsh abrasives. Check exterior only.
Do not reuse gage glass or packing or seals. Immediately replace glass which is broken, cracked, chipped, scratched or otherwise damaged. Inspect periodically with a bright concen­trated light. Anything which glistens and catches the fingernail or any star-shaped or crescent-shaped mark which glistens is cause for replacement. Any gage glass which appears cloudy or roughened and will not respond to cleaning procedures should be replaced.
When replacing gage glass, use new packings specified for this use. Install glass with sufficient end clearance for expansion (keep glass to metal clearance at each end) and tighten nuts just enough to avoid leakage (do not over tighten).
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: SUBSEQUENT DAMAGE
A unit showing symptoms of possible problems
(overflow, noise, leaks, vibrations, continual operation, etc.) must be corrected immediately. Failure to follow these instructions may result in full liability for subsequent injury or property damage.
SAFETY INSTRUCTIONS
SEE COVER OF THIS MANUAL
ELECTRICIAN/INSTALLER/OPERATOR
REMOVE AND DESTROY THIS TAG AFTER
1. ASSURING THAT ALL PUMPS ROTATE CLOCKWISE PER ARROWS CAST ON VOLUTES. (JOG PUMP MOMENTARILY TO TEST – INTERCHANGE ANY TWO MOTOR POWER WIRES TO REVERSE 3PH MOTORS.)
2. ASSURING THAT SHIPPING LOCKS HAVE BEEN REMOVED FROM ALL FLOAT SWITCHES.
Page 4
4
TROUBLE SHOOTING PROCEDURES
All units are thoroughly tested at the factory before shipment.
They should operate satisfactorily without further adjustment if properly installed and providing they have not been damaged by rough handling in transit. If system or unit performance is not satisfactory, refer to the following check list.
Pump Will Not Start
1. The power supply has been interrupted, disconnect switch
is open, or selector switch is improperly positioned.
2. Incorrect voltage for motor. Check voltage and wiring with motor characteristics.
3. Incorrect starter coil for power supply.
4. The overload relays and the starter have tripped out and must be reset. Ambient temperature may be too high.
5. Check pump controls or other controls for proper operation.
6. Wiring to control cabinet is incorrect or connections are loose.
7. The strainer is dirty thus retarding flow. Clean periodically.
Pump Runs Continuously
1. Pump is running backward. Rotation of three phase motors
may be corrected by interchanging any two of the three wires. Rotation should be clockwise looking down on motor.
2. Steam traps are blowing through causing condensate to return at excessive temperatures. This may reduce the capacity of pump below its rating, depending on the unit and type of pump furnished. Traps should be repaired or replaced.
3. The total required pressure at the pump discharge is greater than the pressure for which the pump was designed. Check the total pressure which includes atmospheric pressure, the friction head and the static head.
4. A valve in the discharge line is closed or throttled too tightly. Check valve is installed backwards.
5. The impeller eye is clogged.
6. Pump is too small for system.
Condensate Pump is Noisy
1. The pump is working against a lower pressure than
designed for. While pump is discharging, adjust plug cock in discharge line until pressure at pump approaches pump rated pressure.
2. Excessive condensate temperature. Correct system conditions.
3. Magnetic hum or bearing noise in motor. Consult motor manufacturer’s authorized service station nearest unit location.
4. Starter chatters. Trouble is caused by low line voltage, poor connections, defective starter coil, or burned contacts.
5. Pump is running backward. Rotation of three phase motors may be corrected by interchanging any two of the three wires. Rotation should be clockwise looking down on motor.
The System is Noisy
1. Banging in the steam mains is usually caused by steam
imploding in condensate lying in low points in lines. These problems can be eliminated by dripping low points, prop­erly supporting the pipe, or by increasing the pitch of the lines.
2. Improper dripping of the steam mains and risers; where there is a rise in the steam main, or where it branches off into a riser, a drip trap must be installed in the drain line.
3. The piping is too small to drain properly.
4. A defective trap is holding condensate in steam supply line.
Morton Grove, Illinois 60053
TM
TM
SERIES
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ 60
CONTROL V. PH. 1 HZ 60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
DEALER SERVICING
If trouble occurs that cannot be rectified, contact your local
B&G representative. He will need the following information in order to give you assistance.
1. Complete nameplate data of pump and motor. SEE RATING NAMEPLATE.
2. Suction and discharge pipe pressure gauge readings.
3. Ampere draw of the motor.
4. A sketch of the pump hook-up and piping.
Page 5
5
These close coupled vertical centrifugal pumps are equipped with mechanical seals. If system has not been properly cleaned prior to installation of pump, foreign matter such as dirt, pipe scale, core sand, etc. may clog the impeller and damage the seal. A strainer is recommended in return line to pump.
Pump
must not be operated dry.
Seals may be damaged if operated
without water present.
1. Close inlet line gate valve and operate pump momentarily
to remove as much liquid as possible from pump. Close discharge line gate valve.
2. Shut-off and lock-out power.
3. Disconnect wiring to motor.
4. Make sure unit is cool enough that pump can be handled
safely. Open receiver drain to remove remaining liquid.
5. Loosen the motor to pump volute fasteners. Assure that
pressure is relieved per caution note.
6. Remove four capscrews (7) holding pump case to motor
and lift motor and impeller out of pump case.
7. Remove pump/motor assembly and place on work bench.
8. Hold top end of motor shaft with large screwdriver via
screwdriver slot in shaft and back of impeller (counter­clockwise) with a rectangular bar or other flat tool inserted between the vanes of the impeller.
9. Remove the rotating part of the mechanical seal from the
end of the shaft.
10. Remove seal holder (2) with stationary ceramic part of mechanical seal and cup rubber from the end of the shaft.
11. Remove stationary ceramic part of mechanical seal and cup rubber from recess in seal holder.
12. To install new seal, proceed as follows: Clean recess in seal holder thoroughly. Orient motor so that conduit opening on motor is to the left when looking at motor shaft. Replace seal holder on the face of the motor maintaining concen­tricity with motor face. Place new ceramic part of seal in the cup rubber over motor shaft and press firmly into recess of seal holder by hand, making certain both parts bottom evenly. If assembly cannot be bottomed with fingers place a wooden or cardboard tube over shaft onto ceramic and push into place. Using a clean, lint-free cloth, wipe the mat­ing surfaces of the seal clean of any foreign matter. Moisten the carbon section of the rotating part of the seal and place onto shaft to seat against the ceramic. Place seal spring onto shaft.
13. Hold motor shaft as described in #8 and replace the impeller on the shaft (clockwise rotation) making sure it is tight.
14. Orient motor for pump reassembly with conduit opening to the left. When mounting the pump case, discharge should be 90˚ to the right of the conduit opening on motor. Use care to insure tight gasket fit to prevent water leakage.
15. Replace four capscrews (7). Tighten down capscrews evenly to avoid damage.
16. Reconnect pump bleed line (where applicable) and motor wiring.
17. Close drain and slowly open inlet valves. See warning.
18. Jog to check motor rotation. See caution.
19. Observe operation thru several cycles.
1. Motor
2. Seal Holder
3. Seal
4. Impeller
5. Gasket
6. Case
7. Capscrew (motor to volute)
8. Wear Ring
9. Pipe Plug
10. Slinger
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: PRESSURIZED SYSTEM
Operating system may contain very hot water under
pressure. Close inlet and open drains before servicing. When servicing,
loosen screws and move components to
assure pressure is relieved before
removing screws. Keep
drains open during servicing. Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.
Inspect pump seal regularly for leaks. Replace as
required. Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT REVERSE
Reverse operation can cause extensive damage to
pumps. Jog the motor to test for direction of rotation. Failure to follow these instructions could result in injury or property damage.
PUMP SERVICE INSTRUCTIONS FOR 609PF (WATCHMAN®) CENTRIFUGAL PUMPS
CAUTION: HOT SURFACES
Surfaces are hot when system is in operation. Do not
touch hot receiver, let unit cool before servicing. Failure to follow these instructions could result in injury or property damage.
1
10
7
3
4
8
6
9
5
2
FIG. 2
2DPF01
Page 6
PUMP SERVICE INSTRUCTIONS FOR CENTRIFUGAL PUMPS (EXCEPT WATCHMAN®/609)
Vertical mounting puts motor above floor dirt and water
Close coupled centrifugal pumps are designed for years of
trouble free service. Units have mechanical shaft seals.
1. Close inlet gate valve and operate pump momentarily to remove as much liquid as possible from pump. Close dis­charge line gate valve.
2. Shut-off and lock out power.
3. Make sure unit is cool enough that pump can be handled safely. Open drain to remove remaining liquid.
4. Carefully remove pump drain plug and bleed line. Wait for complete drainage.
5. Loosen the motor bracket to pump volute capscrews. Assure that the pressure is relieved per caution note.
6. Complete the removal of the hardware. Remove pump/ motor assembly and place on work bench.
7. Remove self locking stainless steel capscrews and stain­less steel washer (or self locking brass cap nut and washer) that secure the impeller in place.
8. To remove impeller from motor shaft proceed as follows: (1) Keyed Shafts. Remove impeller with gear puller or other
means which will not damage impeller or bend motor shaft.
(2) Threaded Shafts. Hold end of motor shaft opposite
pump with large screwdriver or other suitable tool and back impeller off with a rectangular bar or other flat tool inserted between the vanes of the impeller.
9. Remove rotating part of seal from shaft, being careful not break carbon face.
10. Remove capscrews holding motor bracket to motor and remove bracket.
11. Remove stationary part of seal assembly, being careful not to chip or break ceramic seal.
12. To install seal proceed as follows: (1) Clean recess in bracket thoroughly. Coat recess and
rubber portion of seat with soap solution. Press seat into recess firmly by hand making certain both parts bot­tom evenly. If seal cannot be bottomed with fingers place cardboard shipping disc on ceramic and force into place with flat tool.
(2) Carefully place bracket in position on motor shaft with-
out displacing ceramic seat and secure bracket to motor with capscrews.
(3) Place motor vertically with pump end up. Do not attempt
assembly of seal and impeller with shaft horizontal.
(4) The carbon of rotating part of seal should not be loose.
If it is, hold in place with grease. Using clean, lint free cloth, wipe mating surfaces perfectly clean. Soap shaft and push seal onto shaft so that carbon will contact ceramic seal. If spacer is required, use grease to cause spacer to adhere to bottom of seal after seal has been put on shaft. Be sure spacer is on larger diameter of shaft so that will not catch between shoulder and impeller.
13. Replace impeller on shaft. Replace stainless steel washer and secure impeller with capscrew or cap nut.
14. Place new gasket on pump volute and reassemble motor and pump subassembly on pump volute.
15. Reconnect pump bleed line and motor wiring.
16. Close drain and slowly open inlet valves. See warning.
17. Jog to check motor rotation. See caution.
18. Observe operation thru several cycles.
CAUTION: PRESSURIZED SYSTEM
Operating system may contain very hot water under
pressure. Close inlet and open drains before servicing. When servicing,
loosen screws and move components to
assure pressure is relieved before
removing screws. Keep
drains open during servicing. Failure to follow these instructions could result in injury or property damage.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: HOT SURFACES
Surfaces are hot when system is in operation. Do not
touch hot receiver, let unit cool before servicing. Failure to follow these instructions could result in serious injury or death.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
CAUTION: DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.
Inspect pump seal regularly for leaks. Replace as
required. Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT REVERSE
Reverse operation can cause extensive damage to
pumps. Jog the motor to test for direction of rotation. Failure to follow these instructions could result in injury or property damage.
6
CUT-AWAY VIEW OF MECHANICAL SEAL TYPE PUMP
VIEW OF THREADED IMPELLER
SLINGER
SEAL
MOTOR
WEAR RING
IMPELLER
VOLUTE
BRACKET
2DPF03
Page 7
7
NOTES:
Page 8
Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,700 people unied in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efciently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.bellgossett.com
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2013 Xylem Inc. DN0154D April 2013
Loading...