Bell & Gossett DN0137D User Manual

Domestic® Pump Vacuum and Boiler Feed Units
INSTRUCTION MANUAL
DN0137
REVISION D
Series VCMD
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on
the unit safety instruction decals to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
WARNING
DO NOT PRESSURIZE TANK. ISOLATE TANK DURING LEAK TEST. DO NOT RESTRICT VENT. DO NOT PLUG OVERFLOW. OPEN INLET VALVES SLOWLY.
EXPLOSIBLE
(2) All Units
DN0483 (Small) - DN0484 (Large)
DO NOT USE AS A FLASH TANK.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
EXPLOSIBLE
DURING LEAK TEST
If the decals as noted below are missing or are illegible contact
your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in accordance with all National, State and Local codes.
2. Motor must have properly sized starter with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at extremely high or low temperatures, guarding or insulation is required.
4. Operating personnel should be trained in the operation of boiler feed units.
WARNING
ISOLATE TANK
(2) All Units DN0485 (Small) DN0486 (Large)
TM
SERIES HV
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ 60
CONTROL V. PH. 1 HZ 60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
DN0116 Units with Panel
TM
Morton Grove, Illinois 60053
CAUTION
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARLY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
P70644 All Units
P70644
2
Domestic®Series VCMD™Combination Boiler Feed and Vacuum Units
Style CMHD-A vacuum unit mounted on horizontal steel boiler feed receiver. Style CMHD-B vacuum unit with separate horizontal steel boiler feed receiver. Style CMVD-A vacuum unit mounted on vertical steel boiler feed receiver. Style CVM vacuum unit with separate cast iron boiler feed receiver.
FIG. 1 REPRESENTATIVE PIPING DIAGRAM - VCMD
Style CMHD-A with vacuum unit mounted on
horizontal steel boiler feed receiver, and returns above receiver inlet. Refer to separate diagram for piping between boiler feed pump(s) and boiler(s).
FIG. 2 REPRESENTATIVE PIPING DIAGRAM - VCMD
Style CMHD-B with separate vacuum unit and
horizontal steel boiler feed receiver, returns above receiver inlet. Refer to separate diagram for piping between boiler feed pump(s) and boiler(s).
FIG. 3 REPRESENTATIVE PIPING DIAGRAM - VCMD
Style CVM with separate vacuum unit and cast iron
boiler feed receiver, returns above receiver inlet. Refer to separate diagram for piping between boiler feed pump(s) and boiler(s).
DESCRIPTION
The Series VCMD family of units consists of various combinations of
boiler feed units combined with Domestic Series MJ vacuum pro­ducers. The vacuum producer may be mounted directly on the boiler feed unit (STyle A) or the units may be independently mounted with field piping between the units (Style B). The boiler feed units can be con­structed with cast iron or steel receivers in many of the standard con­figurations offered as Domestic boiler feed units.
The vacuum producer acts in response to selector switch settings and system vacuum also functions to remove excess water from the boiler feed tank. Various controls are supplied in accordance with system specifications and system requirements. Electrical panels are normally supplied and specific wiring diagrams are supplied with each vacuum producer electrical panel.
The boiler feed system functions like a standard vented boiler feed sys­tem. Again, various control options are available to match system specifications. Electrical panels and electrical diagrams are normally furnished.
The boiler feed units are designed to pump water into an operating boiler. The pumps are controlled by level controls on the boiler. Low water cut-off switches and alarms are often supplied (optional).
Receivers are non-code cast iron or steel.
PRELIMINARY INSPECTION
Assure that there is no shipping damage.
Assure that nameplate ratings agree with job specifications and actual conditions.
HANDLING
Use caring in installing unit.
LOCATION
Place unit for easy access to all parts. Allow adequate space for
servicing. Check ambient conditions.
NOTICE/TEMPERATURE LIMITS
Motors are designed to operate in 104°F max. ambient. Insulate or
ventilate as required.
BOILER FEED SYSTEM
PIPING (General)
Pipe the unit per the Piping Diagram. Locate and support piping so as
to not load the pump discharge.
PIPING (Return)
Gravity return lines from the system must be properly pitched down to
unit inlet. Returns must also be trapped to prevent steam entry into the unit. An inlet basket strainer is recommended.
FLOAT SWITCHES
Floats are locked in place to prevent damage during shipment. Remove
shipping locks. Check factory settings. Floats are adjustable for various levels of operation. The water make-up float switch should make at a higher level than low water cut-off switch “breaks”.
VACUUM SYSTEM
PIPING (General)
Pipe the unit per the Piping Diagram shipped with the unit or as shown
herein. Locate and support piping so as to not load the pump discharge.
PIPING (Suction) (Style B)
Use a suction line at least as large as the unit inlet fitting. Vacuum
storage tanks will reduce system surges or short cycling and a vertical tank can trap liquids and solids.
PIPING (Vent)
Install a vent pipe to atmosphere. Pipe to be size of vent port on unit.
Do not restrict or reduce vent opening or exceed 20 feet vertical height unless an overflow connection is provided.
PIPING (Overflow)
Pipe overflow port to drain.
VACUUM SWITCH ADJUSTMENTS
Vacuum switches, when furnished, are factory adjusted and tested for
the specified operating range. If settings must be readjusted, refer to manufacturer’s instructions.
HURLING WATER MAKE-UP AND CONTROL
The hurling water level is automatically controlled by a solenoid valve
actuated by a float switch. Connect the water make-up assemblies to city water. Use piping at
least as large as the valve piping provided. Install a manual fill valve if not included on the unit. The vacuum producer and the boiler feed unit have separate make-ups.
To operate at a high vacuum, the hurling water must be at a low tem­perature resulting in a low vapor pressure. Cooling water can be auto­matically admitted by using an optional temperature limit switch. This switch actuates the solenoid valve if the temperature rises above a preset point.
The optional condensate Temperature Limit Switch will stop normal operation of the vacuum unit when condensate exceeds the set point temperature (usually 160ºF). Vacuum is not normally required when the system is up to temperature and operation of the vacuum pumps with hot condensate results in condensate loss due to evaporation.
INTERCONNECTING PIPING
On style B units, the interconnecting piping between the boiler feed
unit and the vacuum producer must be the size of the vacuum pro­ducer inlet. The two vacuum inlets on duplex vacuum producers must be connected to the boiler feed tank.
ELECTRICAL WIRING & CONTROLS
Connect power wiring per NEC. Recheck nameplate vs. Specifications
and conditions. All single phase motors have internal thermal protection.
Three phase motors must be use starters with properly sized overload relays. Overload relays furnished are designed for manual reset.
EQUALIZING LINE
A vacuum may be formed on radiation side of system when steam
stops flowing in mains. This vacuum may be higher than return line vacuum, which would prevent condensate from flowing back to pump. To correct this in an unzoned system, install equalizer line as shown in Figures 1 thru 3. To correct this in a zoned system, also install equali­zer line for each zoned section or install a vacuum breaker on supply line on radiation side of each zone valve.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak test.
Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
3
CAUTION: UNIT LIFTING EYE
Use unit lifting eyes only to lift unit as shipped from factory.
Unit must be empty and disconnected from pipes, anchors and other restraints. Use proper rigging procedures. Failure to follow these instructions could result in injury or property damage.
CAUTION: NOT A CHEMICAL PUMP
Inject boiler feed compounds from chemical feed tank into
boiler feed piping – never into condensate tank. Failure to follow these instructions could result in injury or property damage.
WARNING: HIGH VOLTAGE ELECTRICITY
Disconnect and lock out power before connecting or servic-
ing unit. Failure to follow these instructions could result in injury or property damage.
FIG. 4 EQUALIZING CONNECTIONS FOR ZONED SYSTEMS
ZONE CONTROL
VALVE
STEAM MAIN
M
TO ZONE
RETURN MAIN
Loading...
+ 7 hidden pages