Bell & Gossett DN0136C User Manual

Domestic® Pump
WARNING
Vacuum Heating Units
INSTRUCTION MANUAL
DN0136
REVISION C
Series VCD™ and VCL
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on
the unit safety instruction decals to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
DO NOT PRESSURIZE TANK. ISOLATE TANK DURING LEAK TEST. DO NOT RESTRICT VENT. DO NOT PLUG OVERFLOW. OPEN INLET VALVES SLOWLY.
EXPLOSIBLE
(2) All Units
DN0483 (Small) - DN0484 (Large)
DO NOT USE AS A FLASH TANK.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
EXPLOSIBLE
ISOLATE TANK
DURING LEAK TEST
(2) All Units
DN0485 (Small)
DN0486 (Large)
If the decals as noted below are missing or are illegible contact
your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in accordance with all National, State and Local codes.
2. Motor must have properly sized starter with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at extremely high or low temperatures, guarding or insulation is required.
4. Operating personnel should be trained in the operation of vacuum/condensate return units.
TM
WARNING
SERIES HV
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ 60
CONTROL V. PH. 1 HZ 60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
DN0116 Units with Panel
TM
Morton Grove, Illinois 60053
CAUTION
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARLY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
P70644 All Units
P70644
2
DESCRIPTION
The Series VCD and Series VCL vacuum heating units are
designed to serve the dual purpose of pumping accumulated condensate back to the boiler feed tank and maintaining vacuum in the condensate system.
These units have separate compartments for the vacuum pro­ducer (the hurling water chamber) and for the condensate (the condensate receiver).
The 25VCD and 50VCD models have both compartments inte­grally cast in one casting while the 100 and 150 VCD models have separate compartments bolted together with external lift pipes connecting them.
Series VCL units are customized to user specifications and constructed using a choice of rectangular cast iron condensate receivers, underground receivers, or cylindrical steel receivers. In the case of steel condensate receivers, the vacuum unit can be mounted on this receiver or mounted separately and field piped. All models will have one or two condensate pumps and one or two vacuum pumps as specified.
A variety of control options are available and furnished as spec­ified. When control panels are factory supplied, electrical dia­grams are shipped in the cabinets.
Receivers and hurling chambers are non-code cast iron or steel.
PRELIMINARY INSPECTION
Assure that there is no shipping damage.
Assure that nameplate ratings agree with job specifications and actual conditions.
HANDLING
Use care in installing unit. Utilize Lifting Eyes equally when
slinging.
LOCATION
Place unit for easy access to all parts. Allow adequate space
for servicing. Check ambient conditions.
NOTICE/TEMPERATURE LIMITS
Motors are designed to operate in 104°F (40°C) max. ambient.
Insulate or ventilate as required.
PIPING (General)
Pipe the unit per the Representative Piping Diagram. Locate
and support piping so as to not load the pump discharge.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
CAUTION: UNIT LIFTING EYE
Use unit lifting eyes only to lift unit as shipped from
factory. Unit must be empty and disconnected from pipes, anchors and other restraints. Use proper rigging pro­cedures. Failure to follow these instructions could result in injury or property damage.
CAUTION: NOT A CHEMICAL PUMP
Inject boiler feed compounds from chemical feed tank
into boiler feed piping – never into condensate tank. Failure to follow these instructions could result in injury or property damage.
FIG. 1
100 & 150 VCD CONFIGURATION
SERIES VCL (NOT SHOWN) USES SIMILAR PIPING
25 & 50 VCD CONFIGURATION
REPRESENTATIVE PIPING DIAGRAM
PIPING (Returns)
Gravity return lines from system must be properly pitched down
to unit inlet. Returns must also be trapped to prevent steam entry into the unit. An inlet basket strainer is recommended.
SUCTION PIPING
Suction piping between the condensate receiver and the
vacuum producer should be at least as large as the inlet to the vacuum producer.
PIPING (Vent)
Install a vent pipe to atmosphere. Pipe to be size of vent port
on unit. Do not restrict or reduce vent opening or exceed 20 feet vertical height unless an overflow connection is provided.
PIPING (Overflow)
Pipe overflow port to drain using an overflow loop when con-
densate temp will exceed 200ºF. (93°C). The overflow port on the hurling chamber acts as the overflow
for both the vacuum producer and condensate return units. Pipe to a suitable drain.
Series VCL units have a high level (overflow control) float switch to start the vacuum pumps when the lower receiver is at the full level. The vacuum pumps will siphon condensate from the receiver into the hurling chamber.
Excess condensate will then overflow out of the hurling cham­ber to drain.
FLOAT SWITCHES & MECHANICAL ALTERNATORS
Floats are locked in place to prevent damage during shipment.
Remove shipping locks. Check factory settings. Floats and mechanical alternators are adjustable for various levels of oper­ation. The lead pump should start with tank
3
/4 full and shut off at 2" or more above pump inlet. Lag pump should start before the tank overflows. Settings should avoid short cycling of the pump.
Vacuum switch adjustment is explained on the following page. An electric alternator (when furnished) must operate off the lead vacuum switch.
ELECTRICAL WIRING & CONTROLS
Connect power wiring per the National Electrical Code.
Recheck nameplate vs specifications and conditions. All single phase motors have internal thermal protection.
Three phase motors must use starters with properly sized over­load relays. Overload relays furnished are designed for manual reset.
EQUALIZING LINE
A vacuum may be formed on radiation side of system when
steam stops flowing in mains. This vacuum may be higher than return line vacuum, which would prevent condensate from flowing back to pump. To correct this in an unzoned system, install equalizer line as shown. To correct this in a zoned sys­tem, install equalizer line for each zoned section or install a vacuum breaker on supply line on radiation side of each zone valve.
ACCUMULATOR TANK
An accumulator tank may be used to facilitate lifting conden-
sate. The accumulator tank will be fitted with a float switch to start the vacuum pump as accumulator fills. The vacuum pump will then siphon condensate into the condensate receiver.
The vacuum sensor line in an accumulator tank system must sense the vacuum in the accumulator tank as shown on the low return piping diagrams. (Figure 9, page 5.)
3
ZONE CONTROL
VALVE
STEAM MAIN
M
TO ZONE
RETURN MAIN
WARNING: HIGH VOLTAGE ELECTRICITY
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
FIG. 2 EQUALIZING CONNECTIONS FOR ZONED SYSTEMS
SEQUENCE OF OPERATION
There are two separate and independent cycles of operation
in the VCD design – one of air evacuation and the other for condensate return. This is accomplished by completely sep­arating the air pumps from the condensate storage receiver and water pumps. Fig 3 below illustrates a single, two com­partment receiver, divided horizontally, where the air pumps operate from the upper compartment or separation chamber while the water pumps operate from the lower compartment or condensate receiver. The unit below is similar except that the air pump separation chamber and condensate receiver are separate units, connected as shown in Figure 4. The operation for both types of construction is identical.
AIR EVACUATION CYCLE
The independent air evacuation cycle begins when the vacuum
switch, responding to system requirements, starts the centrifu­gal air pump. This pump circulates hurling water from the separation chamber through the multi-jet nozzle, venturi and returns it to the separation chamber. The water, forced at high velocity across the gap between nozzle and venturi, entrains air and gases in multiple jet streams, creating a smooth, steady vacuum in the condensate receiver and system. The mixture is discharged through the venturi into the separation chamber where the air and gases separate from the hurling water and are vented. When the desired vacuum has been produced in the system, the vacuum switch stops the pump, and the check valve at air inlet to separation chamber closes. preventing the return of air to the system.
Replacement of the hurling water evaporated from the separa­tion chamber is controlled by a solenoid valve connected to the water supply and actuated by a float switch.
CONDENSATE RETURN CYCLE
The condensate return cycle begins when a float switch starts
a water pump on condensate rise. The condensate is pumped into the boiler feed system until the preset low float switch set­ting has been reached.
DUPLEX PUMPS
The second or lag pump of duplex water and/or air pumps
functions if the first or lead pump fails and automatically oper­ates to double the capacity in the event of abnormal demand.
TEMPERATURE LIMIT SWITCH
Some units may be equipped with temperature limit switches.
When located on the separation chamber, it is used to admit cooling water if the hurling temperature exceeds a predeter­mined limit.
A condition may be encountered where the temperature of the condensate fluctuates intermittently to critically high levels, where operation under vacuum could cause the condensate to vaporize. A temperature limit switch can be installed on the condensate receiver to prevent the air pump(s) from operating where such a condition exists. Upon temperature drop the vac­uum switch(es) will again control operation of the air pump(s).
VACUUM SWITCH ADJUSTMENTS
The vacuum switches are adjusted and tested at the factory for
proper operation. The vacuum switch on the single unit and the lead switch of the duplex unit is set to close at 3" Hg vacuum and open at 8". The lag switch of a duplex unit is set to close at 2" and open at 8".
These settings are suitable for all normal installations including those having an accumulator tank or lift fitting when properly piped. If settings must be readjusted, refer to manufacturer’s instruction.
4
FIG. 4 100 & 150 VCD LIFT PIPE ASSEMBLIES
FIG. 3
CUT-AWAY VIEW OF VCD PUMP WITH 50 VCD RECEIVER
25 VCD RECEIVERS ARE SIMILAR
CUT-AWAY VIEW OF VCD PUMP WITH 100 VCD
OR 150 VCD RECEIVERS
Loading...
+ 8 hidden pages