Bell & Gossett DN0132F User Manual

Domestic® Pump Vented Boiler Feed Units Series CM,™ CSM,™ CBEM,™ CBM,™ CMED,™ and
CMHD
INSTRUCTION MANUAL
DN-0132
REVISION F
TM
CMED Boiler Feed Unit
CBEM Boiler Feed Unit
CBM Boiler Feed Unit
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on
the unit safety instruction decals to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
WARNING
EXPLOSIBLE
ISOLATE TANK
DURING LEAK TEST
(2) All Units DN0485 (Small) DN0486 (Large)
EXPLOSIBLE
(2) All Units
DN0483 (Small) - DN0484 (Large)
WARNING
DO NOT PRESSURIZE TANK. ISOLATE TANK DURING LEAK TEST. DO NOT RESTRICT VENT. DO NOT PLUG OVERFLOW. OPEN INLET VALVES SLOWLY. DO NOT USE AS A FLASH TANK.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
If the decals as noted below are missing or are illegible contact
your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in accordance with all National, State and Local codes.
2. Motor must have properly sized starter with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at extremely high or low temperatures, guarding or insulation is required.
4. Operating personnel should be trained in the operation of boiler feed units.
TM
SERIES
MODEL
SERIAL
GPM PSI PUMP
CFM IN HG. PUMP
DWGS
POWER V. PH. HZ 60
CONTROL V. PH. 1 HZ 60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
DN0016
TM
Morton Grove, Illinois 60053
DN0116
Units with Panel
SERIES
MODEL
SERIAL
GPM PSI PUMP
POWER V. PH. HZ60
CONTROL V. PH. 1 HZ60
TOTAL LARGEST MOTOR F.L. AMP F.L. AMP
TM
TM
Morton Grove, Illinois 60053
DN0019
Units Less/Panel
CAUTION
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARLY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
P70644
All Units
P70644
OPERATION AND MAINTENANCE
Operators must be familiar with all sections of this manual to
understand the operation of the unit. Hot water, steam and electricity can be hazardous.
Check motor nameplate for any lubrication requirements. Pumps require no lubrication.
NOTICE / AUTO RESTART
Single phase motors will restart automatically after thermal
overload protector trips. Overload thermal relays in starters must be reset manually.
A properly installed unit should function unattended for long periods of time. Periodic checks to assure proper operations are highly recommended. Refer to trouble shooting section when necessary.
A variety of control options are available and are furnished in accordance with user specifications. Refer to wiring diagrams (when furnished) to determine control switch settings.
The inlet strainer (when furnished) is intended to protect the pump and system. Periodic cleaning should be included in the maintenance schedule. Check frequently in new systems.
PUTTING THE UNIT INTO SERVICE
1. Assure that the unit is piped in accordance with instructions
on page 2.
2. Isolate tank before performing any system leak test. Do not pressurize the tank as part of the leak test. Failure to do this can result in serious injury or death.
3. Check floats and alternators for free operation.
4. Check power leads in accordance with wiring diagram enclosed in control cabinet (when furnished).
5. Install drain plugs.
6. Fill receiver half full of water to prime pump(s) and prevent possible damage to pump seals. Avoid freezing conditions after unit receiver has been filled.
7. Check for proper rotation of all three phase motors. Rotation must be clockwise looking down on the motor as indicated by directional arrow on pump casting. If pump runs backwards, interchange two wires (3 phase only).
8. Throttle plug cock in discharge line until pressure at pump (while pump is discharging) approaches pump rated pres­sure. Tighten plug nut to secure adjustment.
9. Connect the water make-up assembly to city water. Use piping at least as large as valve piping provided. Provide a manual fill valve if not included on the unit.
10.
Boiler Level Controls
Assure that the controls on and related to the boiler match
the control systems provided on the unit (see the wiring dia­gram furnished) (applicable when electrical control panel is furnished).
11. Check that the pump discharge pressure exceeds the max­imum operating pressure of the boiler.
12. Manually move the make-up water float indicator and assure that the make-up solenoid admits water.
13. Manually move the low water cut-off float switch indicator to check for pump shut-off.
14. Remove start-up label (below) from panel (if applicable) after complying with instructions.
15. If possible, observe operation thru several cycles.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.
Inspect pump seal regularly for leaks. Replace as required.
Failure to follow these instructions could result in injury or property damage.
CAUTION: DO NOT REVERSE
Reverse operation can cause extensive damage to
pumps. Jog the motor to test for direction of rotation. Failure to follow these instructions could result in injury or property damage.
WARNING: EXPLOSIBLE
Do not pressurize receiver. Isolate receiver during leak
test. Do not plug overflow. Do not restrict vent opening to atmosphere. Open valves slowly. Failure to follow these instructions could result in serious injury or death.
WARNING: HIGH VOLTAGE
Disconnect and lock out power before connecting or
servicing unit. Failure to follow these instructions could result in serious injury or death.
CAUTION: SUBSEQUENT DAMAGE
A unit showing symptoms of possible problems
(overflow, noise, leaks, vibrations, continual operation, etc.) must be corrected immediately. Failure to follow these instructions may result in full liability for subsequent injury or property damage.
SAFETY INSTRUCTIONS
SEE COVER OF THIS MANUAL
ELECTRICIAN/INSTALLER/OPERATOR
REMOVE AND DESTROY THIS TAG AFTER
1. ASSURING THAT ALL PUMPS ROTATE CLOCKWISE PER ARROWS CAST ON VOLUTES. (JOG PUMP MOMENTARILY TO TEST – INTERCHANGE ANY TWO MOTOR POWER WIRES TO REVERSE 3PH MOTORS.)
2. ASSURING THAT SHIPPING LOCKS HAVE BEEN REMOVED FROM ALL FLOAT SWITCHES.
WARNING: EXPLOSIBLE
The installed boiler feed unit becomes an integral part
of the boiler system. Boiler operation and maintenance requires specific skills and training and may require licensing or certification. The boiler feed unit must be operated and maintained so as not to jeopardize the boiler operation. Failure to follow these instructions could result in serious injury, death or extensive property damage.
WARNING: MAINTAIN BOILER SAFETY FEATURES
When connecting the boiler feed unit to the boiler,
assure that all boiler safety controls (burner cutoff, etc.) are and remain operational. With certain control arrangements, dedicated boiler controllers are required for the boiler feed pumps. Failure to follow these instructions could result in serious injury, death or extensive property damage.