LS Condensate Removal Pump
INSTRUCTION MANUAL
6-71-075-115
REVISION A

CAUTION: Combustible liquids may not be pumped! The condensate pump may not be run dry, as this can
destroy the bearings in a very short period.
Applications
The LS is designed for condensate from:
• Gas or oil condensing boiler (maximum heating capacity 682,000 BTU/h) with pH of 2.7 or higher
• Air conditioning systems, cooling, and refrigeration systems.
• Air dehumidifiers and evaporators
Specifications
Supply voltage 100 - 240 V
Frequency 50 / 60 Hz
P1 power supply capacity 20 Watt
Current consumption 0.2 – 0.1 A
Degree of protection IP 44 / Class F
Max. delivery head 45 kPa
Max. pump capacity 450 l/h
Noise level (L
) 46 dB(A)
w
Acid resistance pH 2 or higher
Max. media temperature + 140°F (60°C)
Min. ambient temperature Not freezing 50°F (10°C)
Floating contact Break contact, switching capacity 250 VA
Tank volume 0.7 l (usable volume 0.5 l)
Packaging dimensions 8.5” x 8.5” x 7.1” (215x215x180 mm)
Packaging weight 3.52 lbs (1.6 kg)
Subject to technical changes due to product modifications
Dimensional Drawings Fig.3
Fig.2
4.65” (118)
5.83” (148)
3.54” (90)