Bell & Gossett 210667C Z-6B User Manual

INSTRUCTION MANUAL
210667C
Bell & Gossett®ZoneTrol II
Models Z-4, Z-4B, Z-4M, Z-6, Z-6B, Z-6M
McDonnell & Miller ZoneSmart
U
L
®
C US
LISTED
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual and on the unit safety instructions decal to draw attention to safety related instructions. When used, the safety alert symbol means ATTEN-
TION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
DESCRIPTION
The Bell & Gossett ZoneTrol II and McDonnell & Miller Zone­Smart Pump Controllers are circulating pumps in hydronic systems.
Model Current Zones HP/Pump
Z-4 / ZS-4
Z-6 / ZS-6 6
20 amps maximum combined load.
T-stat Number of Max.
0.085
FEATURES
• Indicator lights visible without removing cover.
Power LED will illuminate when input power is applied to the controller. Zone LEDs will illuminate when relay is energized.
• PRIORITY: This is typically used in domestic hot water applications where it may be desirable to give hot water production a priority over space heating requirements for a certain period of time. Zone 1 is the priority zone and the functionality is enabled via DIP switch 1. The priority timer is selectable for 30 or 60 minutes, via DIP switch 3.
• PURGE: In normal operation, the last circulator will stop and the boiler will shut down as soon as there is no longer a call for heat. If the purge functionality is enabled via DIP switch 2, the boiler will shut down, but the circulator will continue to run for 90 seconds to extract additional BTUs from the boiler.
designed to control 120 VAC
Max.
4
Models ZS-4, ZS-4B, ZS-4M, ZS-6, ZS-6B, ZS-6M
1/3
• EXERCISE: When the exercise functionality is enabled via DIP switch 4, each circulator will run for 10 seconds after every 72 hours of inactivity. This prevents scale and other deposits from accumulating around the rotating parts and ensures a trouble free start up at the beginning of each heating season.
DIP SWITCH SETTINGS
Switch ON OFF
1
2 Purge On Purge Off 3 Priority 30 minutes Priority 60 minutes 4 Exercise On Exercise Off 5 Reset Normal 6 Power Delay On Power Delay Off
Slave Master
Priority Off Priority On
OUTDOOR RESET
For controll ers with intergal outdoor reset con troller, please refer to Instruction Manual 210668. This document can be downloaded at www.bellgossett.com or www.mcdonnellmiller.com.
MECHANICAL INSTALLATION INSTRUCTIONS
The pump controller should be securely mounted on a wall near the pumps using four #8 screws (not included).
WARNING: Electrical Shock Hazard
Electrical connections are to be made by a qualified electrician in accordance with all applicable codes, ordi­nances and good practices Disconnect and lock out the power before making electrical connections. Failure to fol­low these instructions could result in serious personal injury and/or death.
ELECTRICAL INSTAL LATION INSTRUCTIONS
1. Disc onnect the electr ica l supply to the pump bef ore installing the controller.
2. Refer to the applicable wiring diagram
- Figure 1A: Cold Start Boiler
- Figure 1B: Tankless Coil
3. Verify that the circulator(s) do not exceed the electrical rat­ing of the controller.
Used only with optional reset
RW
LNG
4. Make electrical connections according to the applicable wiring diagram. Run the pump power through the holes in the controller chassis to the applicable L/N terminals. Keep 120 VAC and 24 VAC wiring separate. All 120 VAC wiring should be 14 AWG (minimum) copper electrical wi re. Perform all wiring in accordance with applicable codes.
5. If the priority function is to be enabled, the priority zone (e.g., Domestic Hot Water) pump should be wired to the Zone 1 L/N terminals.
6. Run the thermostat wires through the grommet(s) in the controller chassis and connect to the appropriate R/W ter­minals. If the priority function is to be enabled, the priority zone (e.g., Domestic Hot Water) T-Stat should be wired to the Zone 1 R/W terminals. Keep 24 VAC wiring separate from 120 VAC wiring.
NOTE: During the initial power-up
of the zone controller, some “power stealing” thermostats may require up to 3 minutes to function properly. If the installation requires the
pump relays and X-X relay to be held open during this power-up sequence, the installer can position DIP switch 6 to the “ON” position. This will cause the controller to suspend relay operation during the thermostat power-up period. Normal operation and cycling of the heating system will resume after the 3 minute time period. This applies to initial power-up only and does not affect normal system operation.
EXPANSION
The 4 and 6 zone controllers can be connected together to accommodate larger systems. A six conductor straight pinned cable with two male RJ-11 terminations is required for con­nection of multiple controllers. This cable can be ordered from your distributor as McDonnell & Miller part number 109454.
The “master” controller should have DIP switch 1 set to the OFF position. “Slave” controllers should have DIP switch 1 set to the ON position. If the Priority function is to be enabled (e.g., domestic hot water production) Zone 1 on the Master controller will be the priority zone.
GENERAL WIRING DIAGRAM
Refer to Instruction Manual 210688 for units with outdoor reset controller.
For connection
of additional
controllers
EXPANSION
Figure 1A: Cold Start Boiler
control - refer to
instruction
manual 210668
for details
BOIL OUT SUP COM
INSOLATED END
SWITCH
X X ZC ZR
Refer to Fig 1A for cold start or
Fig. 1B for tankless coil application
X X ZC ZR
}
Jumper
To TT
on boiler
When a thermostat calls for heat,
the corresponding circulator will
start and the XX end switch will
close to enable the boiler.
RW
RW
ZONE 1
HN
24 VAC
ZONE 2LNZONE 3LNZONE 4LNZONE 5LNZONE 6
ZONE 1
LN
ZONE 2
CIRCULATORS
To zone
circulators
Figure 1B: Tankless Coil
When a thermostat calls for heat,
the corresponding circulator will
start when the boiler temperature
reaches the low limit setting.
}
RW
ZONE 3
THERMOSTATS
ZC ZR
To ZC on aquastat
To
thermostats
RW
RW
ZONE 4
ZONE 5
LN
To ZR on
aquastat
ZONE 6
General Wiring Diagram (6 zone controller shown)
120 VAC
Input Power
120/1/60
WARNING: Electrical Shock Hazard
When wiring per the Tankless Coil Application, pump controller and boiler aquastat must be on the same circuit and have a common disconnect. Failure to fol­low these instructions may introduce a secondary source of power resulting in personal injury or death.
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett
Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. 210667C May 2012
Loading...