Bellfires RDL3 R LF, RDL3 R CF, RDL3 L LF, RDL3 L CF, RDL3 LF Installation Instructions & Manual For Maintenance

...
This document is an essential part of your gas fi re.
Read it carefully before installation and maintenance of the
gas fi re and keep it in a safe place!
Bellfi res wishes you many cosy evenings with your new Bellfi res gas fi re
Serial number:
Production date:
INSTALLATION INSTRUCTIONS &
ROOM DIVIDER LARGE 3 CF/LF
ROOM DIVIDER LARGE 3 L/R CF/LF
Gas fi res with closed combustion system
3
Bellfi res
English
Installation instructions
BELLFIRES GAS FIRE WITH CLOSED COMBUSTION SYSTEM:
Room Divider Large 3 CF (Centre Fire) (RDL3 CF) Room Divider Large 3 LF (Line Fire) (RDL3 LF)
Room Divider Large 3 Left CF (Centre Fire) (RDL3 L CF) Room Divider Large 3 Left LF (Line Fire) (RDL3 L LF)
Room Divider Large 3 Right CF (Centre Fire) (RDL3 R CF) Room Divider Large 3 Right LF (Line Fire) (RDL3 R LF)
Also available as a
wall mounted gas fi re.
4
Bellfi res
English
Installation instructions
IMPORTANT
These Installation Instructions form part of the documentation pack supplied with the appliance.
The complete documentation, necessary for the installation of the appliance,
consists of:
1. INSTALLATION INSTRUCTIONS & MANUAL FOR MAINTENANCE
2. CONCENTRIC COMPONENTS SUITABLE FOR THE INSTALLATION
OF A BELLFIRES GAS FIRE WITH CLOSED COMBUSTION
3. INSTRUCTIONS FOR USE & MANUAL DAILY MAINTENANCE
5
Bellfi res
English
Installation instructions
CONTENTS
Page
1. INSTALLATION INSTRUCTIONS .............................................................. 7
2. MAINTENANCE ......................................................................................... 58
3. FAULTS ...................................................................................................... 60
4. DISMANTLING
/ ASSEMBLING OF THE GLASS ....
..............................
... 61
5. DIAGRAM ELECTRICITY AND GAS ...........................
.................
............ 63
6. DIMENSIONS ............................................................................................ 64
7. TECHNICAL DETAILS/REGULATIONS .................................................... 75
8. REPLACEMENT PARTS LIST .................................................................. 79
9. DISPOSAL OF PACKAGING AND APPLIANCE ....................................... 82
The installation must only be carried out by a
“Gas Safe Register” registered installation engineer.
IMPORTANT
6
Bellfi res
English
Installation instructions
7
Bellfi res
English
Installation instructions
1 INSTALLATION INSTRUCTIONS
1.1 GENERAL
The gas fi re must be positioned and connected as a “room sealed system” (balance fl ue) appliance by a “Gas Safe Register” registered gas installation engineer in accordance with the following installation instructions, nationally and locally applicable regulations (see “Technical Details/ Regulations” at the rear of this manual). If you have any queries regarding the installation, please consult your local gas company.
Important: Before beginning the installation, check that the details on the rating plate correspond to the gas type and pressure to which the appliance will be connected.
The appliance is supplied with a “Centre Fire” or “Line Fire” double burner, as ordered. These burners each have their own specifi c fl ame image which is defi ned by the perforation pattern in the burner cover.
See Chapter 5 and the Instructions for use.
The appliance is factory set to the correct nominal heat input. The pilot light is set to the correct level of consumption.
Depending on the requested version, the appliance will be delivered from the factory with a Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm concentric connection for extracting the fl ue gases and supply of combustion air.
It is possible to install the gas fi re with either a wall or roof outlet.
The roof connection must be carried out using the concentric fl ue system Ø100 mm ­Ø150 mm. The fumes are exhausted naturally to the outside environment through the inner Ø100 mm pipe whereas the combustion air supply passes between the Ø100 mm and Ø150 mm pipes.
The wall connection must be carried out using the concentric fl ue system Ø130 mm ­Ø200 mm. The fl ue gases are evacuated outside by means of natural draft through the internal pipe of Ø130 mm, whereas the combustion air is supplied between the pipes of Ø130 mm and Ø200 mm. The wall outlet itself is, depending on the concentric fl ue gas
system confi guration, Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm. (In some cases,
with a wall connection, a complete concentric fl ue system Ø100 mm - Ø150 mm is also possible (see Chapter 1.6.1).)
The gas fi re can be installed in a completely sealed or mechanically ventilated house without extra ventilation and/or fume extraction.
The appliance is fi tted into a fi replace surround as a built-in appliance. The appliance can be positioned on the fl oor or suspended on the wall.
In order to prevent the ! replace heating up excessively, it must be properly ventilated by installing vents at the top and bottom of the fi replace.
8
Bellfi res
English
Installation instructions
The appliance can be fi tted with a convection package as an optional extra. This is a “convection jacket” (convection casing) for around and above the appliance, two fl exible aluminium pipes and two built-in convection vents. This enables hot air to be circulated into the room. If required, two additional convector grills can be fi tted (= 1x extra convection set).
If an existing chimney is to be used, please consult your installer fi rst. If the chimney was previously used for a wood or coal fi re, then it should be cleaned by an expert.
1.2 CONCENTRIC FLUE SYSTEMS Ø100 MM - Ø150 MM AND Ø130 MM - Ø200 MM: • Bell! res - Muelink & Grol System
• Poujoulat - PGI Ssystem
• Ontop - Metaloterm US System
• Jeremias/STB - H-Twin System (STB = Chimney­ Technics Brummen NL)
• Jeremias - TWIN-GAS System
The gas fi re, in combination with the concentric fl ue system [Ø100 mm - Ø150 mm] and/or [Ø130 mm - Ø200 mm] (rigid and/or fl exible)
for the brand types mentioned above, has been approved in accordance with the European CE-norm for gas appliances and may therefore be used only with these systems. The permitted components for these systems are listed in instructions enclosed: CONCENTRIC COMPONENTS SUITABLE FOR THE INSTALLATION OF A BELLFIRES GAS FIRE WITH CLOSED COMBUSTION. The guarantee on the appliance lapses if it is installed, fully or partially, with other components or a different fl ue system. The concentric fl ue [Ø100 mm - Ø150 mm] and [Ø130 mm - Ø200 mm] systems can be used with either a newly-built or existing chimney.
N.B. If any part is missing, please contact your dealer.
1.3 INCLUDED
Set documentation - Installation instructions & Manual for maintenance
- Instructions for Concentric Components
- Instructions for use & Manual daily maintenance
Attributes - Ceramic log set, or marble pebbles white or marble pebbles grey
9
Bellfi res
English
Installation instructions
1.4 OPTIONS AND ACCESSORIES
The following options and accessories can be supplied by your dealer:
Part no. Option
Room Divider Large 3
RDL3 RDL3 L RDL3 R
Without Frame X X
Hidden Door (4 cm frame) X X
Hidden Door + 10 cm (10 cm frame) X X incl. mantle iron and draw bars
Wall-mounting (Wall mounted gas fi re): X
• Wall support, for mounting the appliance on the wall as a wall-mounted gas fi re
• Wall support, gas regulator block and receiver on the bottom side of the appliance
Convection package Room Divider Large 3 X X 341672 • 1x Convection top plate 312829 • 1x Convection set General
341678 Black mirror rear wall X X
341679 Black mirror side wall X
341735 Steel panel rear wall X X
341785 Steel panel side wall X
10
Bellfi res
English
Installation instructions
Part no Accessorie Room Divider Large 3
RDL3 RDL3 L RDL3 R
302092 Adapter receiver 6 VDC X X
312829 Convection set General: X X (for convection air extraction)
302188 • 1x Flexible aluminium pipe Ø125 mm, L= 3 m (max.) 310178 • 2x Fitting box 135 x 135 mm 309872 • 2x Convection exit grid, white, 145x145 mm 309730 • 2x Collar adaptor Ø125 mm
304040 • 4x Hose clamp Ø125 mm
337670 Set high altitude kit (incl. adapters) 4 pieces X X
329874 Set carrying brackets 2 pieces X X
3......... Bellfi res - Muelink & Grol concentric X X
fl ue system (*)
3......... Poujoulat - PGI concentric X X
fl ue system (*)
3......... Ontop - Metaloterm US concentric X X
fl ue system (*)
3......... Jeremias/STB - H-TWIN concentric X X
fl ue system (*)
3......... Jeremias - TWIN-GAS concentric X X
fl ue system (*)
(*) Please refer to the instructions enclosed:
CONCENTRIC COMPONENTS SUITABLE
FOR THE INSTALLATION OF A bellfi res GAS FIRE WITH CLOSED combustion
11
Bellfi res
English
Installation instructions
1.5 PREPARATION FOR INSTALLATION
The following preparation must be carried out before the gas fi re can be installed.
1.5.1 Instructions for positioning the outlet
1.5.1.1 Positioning the outlet for correct operation:
Roof-mounted outlet:
Figure 1: Roof-mounted outlet
This must be positioned at least 0.5 m from the roof edge; the apex of the roof can be disregarded.
Wall-mounted outlet:
Figure 2: Wall-mounted outlet
This must be positioned at least 0.5 m from:
• the corner of the building.
• the roof overhang, the rain gutter.
• balconies etc., unless the exhaust construction extends to at least the face of the protruding section.
>0.5 m
>0.5 m
12
Bellfi res
English
Installation instructions
1.5.1.2. Positioning the outlet to avoid affecting the surrounding area
All listed “distances” in this section are no more than guidelines. For the exact minimum “distances”, please consult your national and local directives.
“Distance” = minimum distance required for positioning of the outlet to avoid adverse effects with respect to:
A. A ventilation opening serving an occupied room, a toilet or a bathroom.
B. A heating air supply, when the supply fl ows through an occupied room.
C. A window that can be opened and that is near an occupied room, a toilet or a bathroom.
Roof-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At the same roof level. >3 m (*)
At a different roof level. >1 m (*)
At a lower positioned wall. >1 m
At a higher sloping surface. >3 m (**)
(*) If the required distance cannot be achieved, the outlet position rules take precedence.
(**) If the required distance cannot be achieved, the position of the outlet must be at least 1 m above the highest facade/roof.
13
Bellfi res
English
Installation instructions
Wall-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At walls in buildings with staggered Not permitted if A, B, or C are located heights. above the outlet.
On a wall - general. (*) Above the outlet: >2 m Below the outlet: >0.75 m Left and right of the outlet: >0.75 m
At <1 m from the roof overhang. >2 m
Beneath balconies, walkways etc. >2 m from the underside of the protruding balcony or walkway.
Beneath balconies, walkways >2 m etc. where the outlet extends to the front.
To the garden or on the terrace. >2 m to the outside space. (**)
With respect to a facing wall. >2 m (if the distance from the facing wall is less, the criteria detailed for “On a wall - general” apply).
Enquire at your local gas company for the regulations relating to outlets
positioned opposite each other and outlet(s) in facade(s) that form an angle.
(*) These minimum distances do not apply if there is an obstruction between the outlet and A, B and C that protrudes at least 0.5 m from the wall and has a length exceeding the distance.
(**) This distance is not required if the outlet is situated at least 1 m higher than the intended area of the outside space.
If the outlet has a clearance of less than 0.5 m from the hard surface of a public area at
a height of less than 2 m, it must be fi tted with an effective protector. The mesh size of the guard must not affect the correct operation of the appliance.
14
Bellfi res
English
Installation instructions
Figure 3: Application universal wall/fl oor support Ø150 mm
1.6 GENERAL SERVICES
1.6.1 The Fume Channel/Combustion Air Intake
The combined fume channel and combustion air intake requires one of the following concentric fl ue system confi gurations.
Important: Due to the high temperature of the outer walls (approx. 150°C), no fl ammable materials may be located or used in the vicinity of the fl ue system. The complete fl ue system, must therefore be sleeved with a heat resistant material after assembly.
Ventilate the covered concentric fl ue by fi tting a grid near the fl oor and ceiling (on each fl oor).
Do not insulate the concentric fl ue.
Use the universal wall/fl oor support Ø150 mm to attach the covering of the concentric fl ue system [Ø100 mm - Ø150 mm], see 1.6.2, drawing number 36.
Use as a wall support Use as a fl oor support
36
36
15
Bellfi res
English
Installation instructions
Figure 4: Vertical roof-mounted outlet without bend
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
18
10, 11, 12, 13
1
4
Y
28
16
17
16
24
23
24
23
(100)
RIGID CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES
Appliance: Concentric fl ue connection Ø100-Ø150 mm or Ø130-Ø200 mm
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Room Divider Large 3 (L/R)
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
16
Bellfi res
English
Installation instructions
Figure 5: Vertical roof-mounted outlet with bend
(*) : (Y1 + Y2) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
16
23
Y
2
X
10, 11, 12, 13
14, 15
Y
1
4
1
28
23
23
17
24
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*) Distance Y1 + Y2 (*) Concentric Concentric (min.-max.) (min.-max.) (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
Room Divider
1.0 - 11.0 m 0 - 3.0 m 2.0 - 11.0 m
-
Width:
Large 3 (L/R)
B = 40 mm
17
Bellfi res
English
Installation instructions
Figure 6: Vertical chimney outlet using an existing lined chimney (Flexible Ø100 mm and/or rigid Ø100 mm / Ø150 mm)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
(100)
1
4
28
32
18
23
25
26
29
7
5
29
30
10, 11, 12, 13
Y
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Room Divider Large 3 (L/R)
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
Appliance: Concentric fl ue connection Ø100-Ø150 mm or Ø130-Ø200 mm
FLEXIBLE CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES
18
Bellfi res
English
Installation instructions
Figure 7: Vertical chimney outlet using a lined chimney with a bend > 45° (Flexible Ø100 mm and/or rigid Ø100 mm / Ø150 mm)
(*) : (Y1 + Y2+ Y3) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
2
Y
1
10, 11, 12, 13
> 45°
X
Y
3
32 18 30
29
5
7
29 26
25
23
28
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*) Distance Y1 + Y2 + Y3 (*) Concentric Concentric (min.-max.) (min.-max.) (min.-max.) connection connection on
appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
Room Divider
1.0 - 11.0 m 0 - 3.0 m 2.0 - 11.0 m
-
Width:
Large 3 (L/R) B = 40 mm
19
Bellfi res
English
Installation instructions
Figure 8: Vertical chimney outlet using an existing unsound lined chimney or when no chimney liners are present (Flexible Ø100 mm / Ø150 mm)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
7
6
8
1832
31
29
30
29
26
29
27
28 29
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Room Divider Large 3 (L/R)
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
20
Bellfi res
English
Installation instructions
Figure 9: Vertical chimney outlet using an existing unsound lined chimney or when the chimney is unlined; with a bend >45
o
(Flexible Ø100 mm / Ø150 mm)
(*) : (Y1 + Y2+ Y3) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
3
Y
2
Y
1
X
> 45°
6
8
7
31 29
32 18
30 29
26
29
27
28 29
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*) Distance Y1 + Y2 + Y3 (*) Concentric Concentric (min.-max.) (min.-max.) (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
Room Divider
1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m
-
Width:
Large 3 (L/R)
B = 40 mm
21
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Wall
Termination Position
100
4
28
1
Y
X
19
14
10, 11, 13
0.16 m
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection on (min.-max.) (min.-max.) appliance is Ø130-Ø200 mm
2.0 - 3.0 m 0 - 0.6 m -
Room Divider Large 3 (L/R)
3.0 - 4.0 m 0 - 1.6 m -
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
RIGID CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
Figure 10: Horizontal wall termination
Item descriptions:
see 1.6.2
22
Bellfi res
English
Installation instructions
Figure 11: Horizontal wall termination
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Wall
Termination Position
100
4
128
1
Y
X
19
14
110, 111, 113
0.16 m
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Item descriptions:
see 1.6.2
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection on (min.-max.) (min.-max.) appliance is Ø130-Ø200 mm
Room Divider Large 3 (L/R) 1.0 - 2.0 m 0 - 2.6 m -
23
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 12: Horizontal wall termination
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Item descriptions:
see 1.6.2
100
4
128
1
Y
X
19
114
110, 111, 113
0.25 m
123
Wall
Termination Position
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection on (min.-max.) (min.-max.) appliance is Ø130-Ø200 mm
Room Divider Large 3 (L/R) 1.0 - 3.0 m 1.6 - 4.6 m -
24
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 13: Horizontal wall termination
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y1 Distance X1 Distance Y2 Distance X2 Concentric connection on (min.-max.) (min.-max.) (min.-max.) (min.-max.) appliance is Ø130-Ø200 mm
0 - 0.5 m 0 - 0.5 m 0.5 - 1.0 m 0 - 0.6 m -
Room
Divider
0.5 - 1.0 m 0 - 0.5 m 0 - 0.5 m 0 - 0.6 m -
Large 3
1.0 - 3.0 m 0 - 1.0 m 0.5 - 2.0 m 0 - 0.6 m ­(L/R)
1.0 - 3.0 m 0 - 3.0 m 1.0 - 3.0 m 0 - 0.6 m -
Item descriptions:
see 1.6.2
110, 111, 113
128
4
1
114
14
114
110, 113
110, 111, 113
100
19
0.16 m
Y
2
X
2
Y
1
X
1
Wall
Termination Position
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
25
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 14: Horizontal wall termination
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection on (min.-max.) (min.-max.)
appliance is Ø130-Ø200 mm
0 - 0.5 m 0 - 0.6 m -
Room Divider Large 3 (L/R)
0.5 - 3.0 m 0 - 3.6 m -
1.0 - 3.0 m 3.6 - 8.6 m -
Item descriptions:
see 1.6.2
4
128
1
Y
X
119
114
110, 111, 113
0.25 m
123
Wall
Termination Position
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø130 mm - Ø200 mm
26
Bellfi res
English
Installation instructions
1.6.2 Item descriptions for ! gures 4 t/m 14
FIG. NO. DESCRIPTION
1 Gas fi re; Concentric fl ue connection Ø130/Ø200 mm or Ø100/Ø150 mm
2 -
3 -
4 Restriction plate
(The different sizes restriction plates are supplied with every appliance)
5 Chimney, min. Ø150 mm internal, totally gas tight.
6 Chimney or fi reproof sleeving. Min. Ø160 mm internal.
7 Ø100 mm internal fl exible stainless steel gas vent chimney liner AISI 316TI.
8 Ø150 mm internal fl exible stainless steel gas vent chimney liner AISI 316TI.
9 -
• The room-sealed gas appliances have been approved in
combination with the components of the concentric fl ue systems listed in this instruction book, according to the European CE norm for gas appliances and may therefore be used only with these components.
• The components of the concentric fl ue system of:
* Bellfi res - Muelink & Grol System * Poujoulat - PGI System * Ontop - Metaloterm US System * Jeremias/STB - H-Twin System (STB = Chimney Technic Brummen NL) * Jeremias - TWIN-GAS systeem may not be used together in one installation.
• Check whether the wall or roof termination kit to be used exactly
matches one of those listed in this instruction book.
For the suitable and available components for concentric chimney systems, please consult the “Concentric Components” booklet.
1.6.3 Gas connection
Built-in appliance: Operation (gas regulator block (and receiver)) outside the appliance (in the operating unit):
The gas connection Ø12 mm (3/8”) is situated where the operating
unit is built in near to the appliance.
27
Bellfi res
English
Installation instructions
Figure 15: A clearence of at least 1 cm must be maintained between
the bottom of the appliance and the fl oor.
Min.1 cm
Wall-mounted appliance: Operation (gas regulator block (and receiver)) under the appliance:
The gas connection Ø12 mm (3/8”) is situated on the underside of the appliance.
Use only gas piping with a minimum diameter of 1/2” and a shut-off valve.
1.6.4 Operating unit (Built-in appliance)
If the appliance is fi tted with an operating unit comprising gas control block and receiver, this will be located, once it has been built in, at a maximum of 50 cm from the left or right hand side of the appliance.
1.6.5 Convection package connections
When fi tting a convection package (= convection casing and convection set (1x or 2x)), consideration should be given to the openings at approximately 1 meter above the appliance for the warm air exiting grids.
1.7 POSITIONING THE APPLIANCE
Important: BUILT-IN APPLIANCE:
The appliance may only be installed in a fi replace consisting
of non-fl ammable material.
• The fi replace is constructed on a suffi ciently solid fl oor that can bear the weight of the appliance.
• Ensure a free space of at least 1 cm between the bottom of the appliance and the fl oor.
28
Bellfi res
English
Installation instructions
• Never position the appliance directly against the rear wall,
but always place an nonfl ammable insulation plate, at least 12 mm thick, between the appliance and the rear wall, with free space on either side of 2 cm. (Total ± 5 cm.) The rear wall must be made of nonfl ammable material. For the left or right variant (L / R), the metal panel on the side of the appliance must be insulated in the same manner.
• Never use combustible materials during the installation.
• Ensure that the fi replace does not rest on the appliance. If necessary, use a mantle iron
(accessorie).
• Ventilate the fi replace, by allowing vents above and below the fi replace.
WALL-MOUNTED APPLIANCE:
• The appliance may only be installed on a wall constructed from non-fl ammable material.
• To suspend the appliance, use the correct fi xing method appropriate to the wall in question.
• The total weight of the appliance is 90 kg.
• The cove, above and under the appliance, must be made of
non-fl ammable material.
• Ventilate the cove over the appliance by fi tting with vents at the top of the appliance.
• Ensure that the cove does not rest on the appliance.
If necessary, use a mantle iron (accessorie).
GENERAL:
• Ensure that the temperature of the fl oor under and in front of the appliance can never rise above 85°C! Make use of a temperature protection plate (of nonfl ammable material) on the fl oor if necessary. Take care with a fl oor made of a fl ammable material.
• During installation of the gas fi re, a clearance of 3 mm should be maintained on all sides of the appliance to allow for expansion of the appliance during operation.
• Do not insulate the appliance! Only the top and sides may be fi tted with a strip of white, loose insulation wool (heat-resistant to 1000°C), width 15 cm max. to protect the wall.
• Do not use fi breglass or Rockwool, or any other sort of insulating material. These emit a pungent odour. This is considered extremely unpleasant. They may also cause discolouring of the column.
• Flammable materials, such as curtains, should not be placed in the vicinity of the gas fi re. Minimum safe distance: 100 cm.
If desired, fi t a convection package to the appliance. (See chapter 1.1)
29
Bellfi res
English
Installation instructions
• The appliance can be easily installed • Room Divider Large 3 with options: using a set of carrying brackets * 10 cm kader frame (4 sided) and (accessory). After installing: mantle iron
remove carrying brackets! * convection package
30
Bellfi res
English
Installation instructions
Figure 16: Appliance installed in ventilated chimney breast
Horizontal outlet of the fl ue gas exhaust /combustion air supply via the wall. Fitted with the options / accessories:
• convection package (= convection casing and 1x convection set)
• 1x extra convection set
1
Inlet opening (appliance) convection air 2 Natural convection in the chimney breast 3 Outlet opening (grate) (chimney breast) natural convection air 4
Outlet opening (appliance) convection air / connection convection set (2x or 4x) 5
Outlet opening (grill convection set) (chimney breast) convection air (2x or 4x) 6 Concentric fl ue connection appliance; Ø130-200 mm for a horizontal wall outlet 7 Horizontal wall outlet 8 Built in operating unit with gas regulator block and receiver
31
Bellfi res
English
Installation instructions
1 Inlet opening (appliance) convection air 2 Natural convection in the chimney breast 3 Outlet opening (grate) (chimney breast) convection air (2x) 4 Concentric fl ue connection appliance; Ø100-150 mm for a vertical roof outlet 5 Concentric fl ue system; Ø100-150 mm for a vertical roof outlet 6 Built in operating unit with gas regulator block and receiver
Figure 17: Appliance installed in ventilated chimney breast
Vertical outlet of the fl ue gas exhaust / combustion air supply via the roof.
Fitted without convection package
32
Bellfi res
English
Installation instructions
BUILT-IN APPLIANCE:
Fitting the appliance
When fi tting the appliance, it can be levelled with the adjustable feet
.
These adjustable feet can be reached via the openings (4x), after removing the protective covers, in the corners of the fl oor of the combustion chamber. The adjustable feet on the bottom side of the appliance can also be adjusted using an Allen key. The fl oor of the combustion chamber can be reached after the window and the grill around the burner have been removed (see chapter 4). Using an Allenkey (no. 5), the appliance can be adjusted to the required height.
• Adjust height with Allenkey no. 5. • Adjustable feet seen from the bottom
of the appliance.
After adjusting the appliance, the
protection caps should be replaced.
• Remove the grill (See also Chapter 4). • Remove protecting cover.
33
Bellfi res
English
Installation instructions
Fitting the extended adjustable feet:
The extended adjustable feet can be used to position the appliance at an extra height to a maximum of 52 cm. These feet should be mounted on the bottom side of the appliance using the pre-mounted adapters underneath the appliance.
• Saw the 4 extended adjustable feet • Mount the legs on the pre-mounted to the desired length. adapters for the extended adjustable feet.
34
Bellfi res
English
Installation instructions
Position the gas supply pipe such that it can be easily mounted after installation.
Because the control system is outside the appliance, the gas pipe must lead to where the operating unit (built in), the gas regulator block (and the receiver) assembly are
fi tted.
Move the appliance until it is ± 5 cm from the rear wall and ensure it is level. Place the nonfl ammable insulation plate (min. 12 mm) between the appliance and rear wall. The appliance may not be installed against a fl ammable rear wall.
Attach the appliance to the rear wall with 2 wedge bolts.
35
Bellfi res
English
Installation instructions
WALL-MOUNTED APPLIANCE: Hanging the appliance
• Screw the M8x16 bolts into the wall • Turn the fl ange nuts on the inside on support at the desired height. the screws.
• Leave room between the wall support • Screw the wall support to the wall using and the nut. the expansion bolts supplied.
• Make sure that the wall support is • … and in this direction. level in this direction...
36
Bellfi res
English
Installation instructions
• If not, the appliance can be adjusted using the 2 adjustable feet on the bottom side.
• Raise the appliance and slide it over • Slide the appliance downwards. the bolts.
• Tighten the nuts properly. • Check that the appliance is level.
37
Bellfi res
English
Installation instructions
• The vertical stone strip or steel strip • Make sure that the distance between must be removable, so that the glass the stone and glass is a minimum can still be removed. of 4 mm.
Fitting the natural stone plateau
If the appliance is fi nished with a natural stone plateau, please consider the following:
Max. 30 mm
Max. 15 mm
Max. 5 mm
Natural stone plateau dimensions
Natural stone strip (removable)
Natural stone plateau
4 mm gap between the stone and glass
1.7.1 Gas connection operating unit - BUILT-IN APPLIANCE
Note: If the appliance is being installed as a hanging gas ! re, the gas regulator block will be mounted under the appliance during production.
Important: During gas connection, take care not to twist the gas regulator block. Make sure that both the gas regulator block and the supply pipes are not subjected to stresses.
The appliance is supplied with a built-in operating unit.
38
Bellfi res
English
Installation instructions
Figure 18: Operating unit


Operating unit
Frame with door (white)
Remove the decorative edging and door of the operating unit. Fit the separate operating unit, where the gas regulator block and receiver will be placed, on max. 50 cm from the appliance.
The burner, gas regulator block and receiver have been fully factory assembled.
Disconnect the bracket with the gas regulator block and receiver from the appliance. Carefully move the bracket with the gas regulator block, receiver, pipes and cables to the operating unit. Mount the bracket at the bottom of the operating unit.
Important: Take care that no pipes get damaged and no compression ! ttings come loose when moving the gas regulator block. Prevent twisting the " exible pipes# Check all compression ! ttings for leaks afterwards#
Mount the receiver in the top of the operating unit. Check afterwards that all electric connections are properly connected.
General: Route all piping and cables from the operating unit to the appliance through an easily accessible hollow cavity. During subsequent installation of the operating unit, protect the gas regulator block and piping against encasement by cement etc.
Important : Cement and chalk can damage the piping and can, in turn, lead to gas leaks.
39
Bellfi res
English
Installation instructions
Gas pipe “rear burner” Ø8 mm Flex.
Gas valve “rear burner”
Gas pipe “front burner” Ø8 mm Flex.
Gas supply connection
Gas regulator block
Thermocouple
Pilot light
pipe
Ø4 mm Flex.
Thermocouple
interrupter
Figure 19: Gas regulator block and gas valve: Gas and thermocouple
connections
Disassembly and assembly of pipes and cables:
If necessary for mounting, all pipe compression fi ttings and cable connectors can be temporarily disassembled. After mounting, carefully reassemble all pipes and cables. Check afterwards all compression fi ttings for leaks and that all electric connections are properly connected.
Important : Screw the thermocouple connection (and thermocouple interrupter) manually into the gas regulator block. Afterwards, carefully fasten a half turn with a spanner.
Note : Check that the fl exible burner pipes are correctly connected!
The gas connection of the gas valve “rear burner” must be connected to the “rear burner”! See Chapter 5. Switching over the fl exible burner pipes during assembly can lead to an explosive ignition. Prevent this at all costs!
40
Bellfi res
English
Installation instructions
Figure 20: Gas regulator block - Front
Inlet
Pressure Tap
Outlet
Pressure Tap
Gas supply connection
Gas connection for to the “front burner”
Gas connection for gas valve to the “rear burner”
Thermocouple interrupter connection
Adjustment Screw Minimum Burner pressure
Pilot light connection
Figure 21: Gas regulator block - Rear
Pilot Gas Adjustment Screw (Pierce the housing with a small screwdriver)
Adjustment Screw Maximum Burner pressure
Motor-knob
Microswitch8 Wire connecting
cable receiver
41
Bellfi res
English
Installation instructions
Figure 22: Receiver - Top
Figure 23: Receiver - AUX connection - RESET button
Thermocouple
voltage / current
OUT - connection (yellow)
Piezo cable connection
RESET button
AUX: Electrical connection for gas valve “rear burner”
TCSW
Thermocouple voltage / current IN - connection (red)
6 VDC Adapter connection (option)
Connection 8 wire cable gas regulator block
Connection for external operating (option)
RESET button
AUX: Electrical connection for gas valve “rear burner”
42
Bellfi res
English
Installation instructions
1.7.2 Connecting the concentric fl ue
Assemble the concentric fl ue system according to one of the examples in section 1.6.1, fi gure 4 to 14 inclusive. Make sure that all connections are completely gas tight.
1.7.2.1 Mounting the convection
package (option)
The convection package (option) consists of a convection casing and a convection set. The convection set is supplied separately and consists of two fl exible aluminium pipes, hose clamps and two built-in convection grills (fi tting box and grill).
Mount the aluminium pipes on the collar adaptors of the convection top plate. Use the supplied hose clamps. The fl exible aluminium pipes are
stretchable to a length
of + 3 meter.
43
Bellfi res
English
Installation instructions
Position the two fi tting boxes in the fi replace, at a minimum distance of 30 cm under the ceiling. Mount the other end of the aluminium pipes onto the fi tting boxes. To do this use the hose clamps supplied. When the fi replace is completely fi nished, mount the grilles onto the fi tting boxes.
Within a range of 30 cm either side and 50 cm above the escape opening, there must be no fl ammable materials (e.g. wooden ceiling, fi tted furniture).
1.7.3 Building in the appliance
Remove the front of the casing, if applicable. (See Chapter 4: Dismantling / Assembling of the glass.) Decide on positions of the vents (grilles above and below the fi replace) and, if applica­ble, the hot air grids of the convection package.
The brickwork must be built up around the appliance. In connection with the appliance expanding during burning: there must be at least 3 mm clearance on either side of the appliance. Do not build up the brickwork farther than the angle irons/brackets (keep in mind the thickness of any plastering!).
Do not use masking tape on the appliance when installing and plastering. Tape can damage the ! nish of the appliance.
Connect up the convection package, if applicable. See 1.7.2.1.
44
Bellfi res
English
Installation instructions
Mantle iron in combination with the 10 cm frame (option). The mantle iron is screwed on the top panel of the 4 sided 10 cm frame at the factory.
Do not unscrew this connection !
Bar set: • 4x draw bars
• 2x tension sleeves
• 2x M6 hooks
• 2x brass expansion plugs M6
Mantle iron (option).
The optional mantle iron is intended for supporting the brickwork above the appliance. The mantle iron must rest on the brickwork on both sides so that upward building is possible. Level the mantle iron with the supplied bar set.
Fix the mantle iron to the rear wall with the bar set. Place the draw bars at an angle of about 60˚ (between the appliance and the wall). Level the mantle iron with the tension sleeves. Ensure that the height between the mantle iron and the underside of the glass is the same at left, middle and right.
45
Bellfi res
English
Installation instructions
Keep a clearance of 2 mm between the mantle iron and the top of the side panels. The side panels should always be easily removable. Check that the mantle iron is at right angles to the side panels, both left and right.
Put ceramic felt on the top of the mantle iron, before laying bricks or using other heat­resistant structural materials.
If using other materials, such as stone or heat-resistant plating, you should follow the supplier’s instructions.
Installing the appliance as a built-in appliance:
Once the fi replace has been fi nished, you can now, fi t the frame with the small door to the operating unit.
After installation in a new ! replace and/or applying new cement work, the appliance cannot be used for at least four weeks.
2 mm
46
Bellfi res
English
Installation instructions
1.7.4 Checking the gas connection
After connection of the gas supply, check that all connections are completely gas tight using soapy water or a leak tester.
1.7.5 Positioning the ceramic log set or marble pebbles
The appliance can be supplied with:
• Ceramic log set + embers
• Marble pebbles white (small, white marble stones)
• Marble pebbles grey (small, grey marble stones)
Important: • Carefully place the
chips of wood/embers/vermiculite granules/
log set or marble pebbles, on and around the main burner according to the directions in this chapter.
• Do not place any chips of wood/embers/vermiculite granules/ log set or marble pebbles against the pilot light burner. For that reason, the main burner has a protective pilot-light cowl.
Never remove this cowl! Make sure that the pilot fl ame can burn at all times freely over the main burner. Only in this way is proper ignition of the main burner ensured. Ignoring these directions could lead to a dangerous situation.
• Make sure that all burner orifi ces remains free at all times!
• The burner bed (with chips of wood/embers/vermiculite granules) and the positioning of the logs or marble pebbles must not be changed.
• Only use those items supplied! These been rigorously checked and the quantities adapted to the appliance.
• Replacement parts, including the ceramic mat are available from your dealer.
• Fitting may only be carried out by a qualifi ed person.
Remove the glass according to the instructions in chapter 4; DISMANTLING / ASSEMBLING OF THE GLASS.
47
Bellfi res
English
Installation instructions
1.7.5.1 Ceramic log set + chips of wood + embers + vermiculite granules
1 Place the ceramic mat on the burner in such a way that the holes in the mat are in
line with the burner openings.
2 Remove the embers carefully from their packaging and spread them evenly over the
burner mat and the grate around the burner.
3 Distribute the vermiculite granules (50 gram) evenly over the burner.
48
Bellfi res
English
Installation instructions
Note ! : Small embers and their residue should not be scattered on
the burner. This can cause a blockage on the burner orifi ces.
• Embers and vermiculite granules must not be placed next to the pilot light burner.
• Important: make sure that all burner openings remain free !!
Burner orifi ces, which are not open, could lead to a dangerous
situation.
4 Place the logs on the burner:
Appliance
Natural gas-burner Propane / Butane-burner
see fi gure: see fi gure:
Room Divider Large 3 CF/LF 24 26
Room Divider Large 3 L/R CF/LF 25 27
Keep the burner orifi ces unblocked !!!
5 Place the chips of wood around the burner.
49
Bellfi res
English
Installation instructions
Logs:
Log no u Log no v
Log no w Log no x
Log no y Log no z
Log no { Log no |
50
Bellfi res
English
Installation instructions
Figure 24: Log set Room Divider Large 3 CF/LF Position natural gas burner
Keep the burner orifi ces unblocked!
Figure 25: Log set Room Divider Large 3 L/R CF/LF Position natural gas burner
Embers must not be placed next to the pilot light burner
Keep the burner orifi ces unblocked!
Embers must not be placed next to the pilot light burner
y
z
u
v
x
w
|
v
y
z
v
x
w
|
u
v
51
Bellfi res
English
Installation instructions
Figure 26: Log set Room Divider Large 3 CF/LF Position propane/butane burner
Keep the burner orifi ces unblocked!
Figure 27: Log set Room Divider Large 3 L/R CF/LF Position propane/butane burner
Keep the burner orifi ces unblocked!
Embers must not be placed next to the pilot light burner
Embers must not be placed next to the pilot light burner
y
z
u
v
x
w |
v
y
z
v
x
w
|
u
v
52
Bellfi res
English
Installation instructions
1.7.5.2 Marble pebbles
1 Place the ceramic mat on the burner in such a way that the holes in the mat are in
line with the burner openings.
2 Spread the pebbles over the whole burner bed (burner and grid around the burner).
Make sure that the pilot light remains free.
Room Divider Large 3 CF/LF : see fi gure 29
Room Divider Large 3 L/R CF/LF : see fi gure 29
Figure 28: Marble pebbles-set natural gas and propane/butane-burner
IMPORTANT: Open area, in order to ensure free
accessibility of the pilot fl ame to the burner
Keep the burner orifi ces unblocked
53
Bellfi res
English
Installation instructions
Keep the burner orifi ces unblocked!
Figure 29: Marble pebbles
Room Divider Large 3 CF/LF
Room Divider Large 3 L/R CF/LF Position natural gas and propane/butane burner
Marble pebbles must not be placed next to the pilot light burner
: Keep all burner orifi ces free of marmersplit!
54
Bellfi res
English
Installation instructions
Figure 30: Marble pebbles Room Divider Large 3 CF/LF Marble pebbles Room Divider Large 3 L/R CF/LF Position natural gas burner
Figure 31: Marble pebbles Room Divider Large 3 CF/LF Marble pebbles Room Divider Large 3 L/R CF/LF Position propane/butane burner
: Keep all burner orifi ces free of marmersplit!
: Keep all burner orifi ces free of marmersplit!
Marble pebbles must not be placed next to the pilot light burner
Marble pebbles must not be placed next to the pilot light burner
55
Bellfi res
English
Installation instructions
Important: • Do not place any marble pebbles in front of the pilot light. Make sure that the pilot light can burn freely over the main burner.
Keep the burner ori! ces unblocked.
Only this way a proper ignition of the main burner is ensured.
Once the logs / marble pebbles have been positioned, replace the glass in the appliance, following the instructions in chapter 4: DISMANTLING / ASSEMBLING OF THE GLASS.
1.7.6 Mounting " ue gas restriction plate
Depending on the length and shape of the concentric fl ue system and the chimney construction, you should, if indicated, fi t a restriction plate with a certain width (B) into the ceiling of the combustion chamber. To do this, see the set-up options as listed in fi gure 4 through 14.
Important: Ensure that the correct " ue gas restriction plate is mounted. Use of the correct " ue gas restriction plate will provide optimum ef! ciency, " ame effect and combustion. Mounting an incorrect " ue gas restriction plate can result in damage to the gas ! re.
56
Bellfi res
English
Installation instructions


%

[
Figure 32: Positioning restriction plate
Assembly restriction plate Screw fastening (2x)
The following restriction plates are supplied:
Concentric fl ue connection appliance
[Ø130 - 200 mm]
[Ø100 - 150 mm]
Restriction plate: Horizontal wall outlet Roof-mounted outlet
Width: - B = 30 mm Width: B = 40 mm B = 40 mm Width: B = 50 mm B = 50 mm Width: B = 65 mm B = 65 mm Width: B = 80 mm -
57
Bellfi res
English
Installation instructions
1.7.7 Check overpressure hatches
There are four overpressure hatches in the roof of the combustion chamber.
Check that the hatches are loose, by lifting a little and carefully letting them come down again. Check if the gasket under the hatches is sealed. If necessary, the gasket can be replaced by lifting the hatch, tilting it and removing via the opening.
1.7.8 Checking the appliance following installation
After installation, visually check the gas fl ame. When the fi re is ignited, the fl ames should be short and blue/yellow in colour. These fl ames should gradually increase in height and become more yellow. When all fl ames are yellow, the gas fi re has reached the correct temperature.
THE GAS FIRE IS NOW READY FOR USE
58
Bellfi res
English
Installation instructions
2 MAINTENANCE
2.1 ANNUAL MAINTENANCE
It is essential that the appliance, the complete
concentric fl ue system (where possible) and the outlet are cleaned and inspected annually
by a recognised fi tter/gas specialist. The safe operation of the appliance will thus remain guaranteed.
Maintenance consists of the following:
• Remove fi rst the embers, vermiculite granules, logs set or pebbles from the main
burner and carefully clean these with a soft brush.
• Clean and inspect (visually) the main burner, pilot light, combustion chamber,
fl ue system and combustion air intake. Dust can be removed using a vacuum cleaner.
• Clean the glass on the inside of the appliance with glass spray or ceramic hob
cleaner. This also applies to the black mirror rear wall and side panels, if the appliance is fi tted with these.
CAUTION !! : If the appliance has anti-refl ective glass, please follow the cleaning instructions in Chapter 4 of the “Operating Instructions and Daily Maintenance Manual” booklet. Failure to follow these
instructions may result in damage to the anti-refl ective glass.
• After cleaning; Carefully replace the embers, vermiculite granules, logs set or pebbles on and
around the main burner according to the installation directions in this instruction booklet.
Do not place any embers, vermiculite granules, logs or pebbles against the
pilot light burner. Make sure that the pilot fl ame can burn at all times freely over the main burner. Only in this way is proper ignition of the main burner ensured.
Ignoring these directions could lead to a dangerous situation.
• Check the gas supply, fl ue system, and combustion air supply route for leaks.
• Check the correct operation of the gas regulator block, thermocouple
circuit and the ignition of the main burner.
59
Bellfi res
English
Installation instructions
• Check the gas inlet-pressure (both when the appliance is off and when it burns at maximum) and the burner pressure.
• Check if the overpressure hatches are correctly positioned and check if the
gasket seals are properly positioned under the hatches.
• Check the complete concentric fl ue system including the outlet construction.
A camera can be used to inspect the whole length of the fl ue gas outlet and the
combustion air intake. Also check that all connections are secure.
60
Bellfi res
English
Installation instructions
3 FAULTS
3.1 POSSIBLE REASONS
Possible reasons for the gas fi re going out are:
• The concentric fl ue system is not installed according to one of the methods detailed in Paragraph 1.6.
• An incorrect “fl ue gas restriction plate” is fi tted.
• The pilot light extinguishes if fumes are not exhausted or are insuffi ciently exhausted.
• The pilot light is either dirty or defective.
• Insuffi cient gas pressure.
• (Internal) leak of the concentric fl ue system.
• Thermocouple voltage is too low. This is usually caused by insuffi cient heating of the thermocouple by the pilot light.
• Dirty electrical contacts in the thermo-electrical system; for example, the thermocouple connection.
• Batteries in receiver or remote control are fl at.
3.2 SAFETY MEASURES IN THE APPLIANCE
3.2.1 Thermo-electric pilot light shut off
The appliance is protected by means of a thermo-electric pilot light shut off in the event of a gas escape from the main burner.
3.2.2 Over pressure safety system
The appliance is fi tted with a patented safety system, whereby the door will extract any over-pressure that arises in a controlled way. In this, a spring system briefl y causes the door to hinge forward a few centimetres. A loud noise can occur. A safety strip limits the maximum degree to which the door can be tilted.
If an over-pressure situation occurs, the appliance should be thoroughly checked by the installer.
61
Bellfi res
English
Installation instructions
4 DISMANTLING / ASSEMBLING OF THE GLASS
4.1 ROOM DIVIDER LARGE 3 HIDDEN DOOR (10 cm frame)
Dismantling of the glass: Place paperboard on the chimney breast, under the appliance.
This helps prevent damage.
• Room Divider Large 3 • Unscrew the glass holder at the top a little and leave it in place.
• Pull the side panel forwards along • Remove the lower strip. the glass and remove it.
62
Bellfi res
English
Installation instructions
Assembling of the glasses:
The assembly of the glass takes place in reverse order.
Important:
• The glass panes fi t together well. There must be no gaps between the glass panes,
or there will be a danger of fl ue leakage.
• The glass panes must fi t properly all round the edges of the combustion chamber.
• Check if the fastening strips have been properly mounted all round.
• Check if the compression springs has been replaced in the correct position.
All fastening strips on the top
side remain in position!
• Carefully push the glass upwards. • Pull the glass at the bottom side slightly
outwards.
The glass at the front can be removed in the same way as the glass at the sides.
• Lower the glass... • and remove it.
63
Bellfi res
English
Installation instructions
5 DIAGRAM ELECTRICITY AND GAS
Gas supply connection
Thermocouple
Ignition(piezo)cable
2 Wire cable
Motor­knob
Gas pipe “Rear burner”
GAS
REGULATOR
BLOCK
“red”
“black”
AUX
“red”
“yellow”
Pilot light
“Front burner”
“Rear burner”
Pilot light gas pipe
Thermocouple interruptor
8 Wire connecting cable
Gas pipe “Front burner”
Gas valve
“Rear burner”
AC power adapter 230 VAC (option)
Button “RESET”
Receiver (with battery compartment for 4 AA-batteries)
Connection cable (option) for external operating (i.a. Domotica systems)
Thermo-electrical cable TC
Thermo-electrical cable SW
Double burner: : Perforation pattern “Centre Fire” double burner.
+ : Perforation pattern “Line Fire” double burner.
64
Bellfi res
English
Installation instructions
6 DIMENSIONS
6.1 ROOM DIVIDER LARGE 3 - Without Frame
65
Bellfi res
English
Installation instructions
6.2 ROOM DIVIDER LARGE 3 - Hidden Door
Fitted with the option: Convection casing
66
Bellfi res
English
Installation instructions
6.3 ROOM DIVIDER LARGE 3 - Hidden Door+ 10 cm Frame
67
Bellfi res
English
Installation instructions
6.4 ROOM DIVIDER LARGE 3 - WALL-MOUNTED Hidden Door
Operating unit
Operating unit
68
Bellfi res
English
Installation instructions
6.5 ROOM DIVIDER LARGE LEFT 3 - Without Frame
69
Bellfi res
English
Installation instructions
6.6 ROOM DIVIDER LARGE LEFT 3 - Hidden Door
Fitted with the option: Convection casing
70
Bellfi res
English
Installation instructions
6.7 ROOM DIVIDER LARGE LEFT 3 - Hidden Door+ 10 cm Frame
71
Bellfi res
English
Installation instructions
6.8 ROOM DIVIDER LARGE RIGHT 3 - Without Frame
72
Bellfi res
English
Installation instructions
6.9 ROOM DIVIDER LARGE RIGHT 3 - Hidden Door
Fitted with the option: Convection casing
73
Bellfi res
English
Installation instructions
6.10 ROOM DIVIDER LARGE RIGHT 3 - Hidden Door+ 10 cm Frame
74
Bellfi res
English
Installation instructions
6.11 OPERATING UNIT
75
Bellfi res
English
Installation instructions
7 TECHNICAL DETAILS/REGULATIONS
National installation regulations:
Gas safety installation and use regulations 1998 plus all relevant safety and building regulations concerning ! re installation
Document J: Combustion appliances and fuel storage systems
Model : ROOM DIVIDER LARGE 3 CF (Centre Fire) ROOM DIVIDER LARGE 3 L/R CF (Centre Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Product identifi cation no : 0063CM3684 : 0063CM3684 Type of appliance under CE-norm : C11 / C31 / C91 : C11 / C31 / C91 Category of appliance : I2H natural gas G20 : I
3B/P
butane/propane G30/G31
Nominal heat input : 12.0 kW : Butane (G30) : 11.2 kW (Gross calorifi c value) Propane (G31) : 9.4 kW
Nominal heat output : 9.2 kW : 7.2 - 8.6 kW Effi ciency class : 1 (85%) : 1 (85%) NOx-class : 5 : 5
Gas rate (max.) : 1.14 m
3
s
/hr. : Butane (G30) : 860 gr/hr.
Propane (G31) : 710 gr/hr.
Supply pressure : 20.0 mbar : Butane (G30) : 37.0 mbar Propane (G31) : 37.0 mbar
Burner pressure (max.) Hot : 13.6 mbar(*) : 29.0 mbar(*)
Burner pressure (max.) Cold : 12.9 mbar(**) : 29.0 mbar(**)
Burner pressure (min.) : 1.5 mbar(***) : 2.1 mbar(***)
Primary air inlet burner Rear : 1x Ø10.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Primary air inlet burner Front : 1x Ø10.0 mm : 1x Ø20,0
+corner
mm +
2x Ø5.0 mm
Gas regulator block (remote control) : Mertik GV 60 : Mertik GV 60 Main burner : Centre Fire 960x130 mm : Centre Fire 960x130 mm Main burner injector Rear : no 190 (= 1x Ø1.90 mm) : no 110 (= 1x Ø1.10 mm) Main burner injector Front : no 210 (= 1x Ø2.10 mm) : no 130 (= 1x Ø1.30 mm)
76
Bellfi res
English
Installation instructions
Model : ROOM DIVIDER LARGE 3 CF (Centre Fire) ROOM DIVIDER LARGE 3 L/R CF (Centre Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Pilot light burner : SIT 0.145.019 : SIT 0.145.019 Pilot light burner injector : nr. 36 (SIT 0.977.091) : nr. 23 (SIT 0.977.150) Gas connection : 3/8” G / Ø12 mm : 3/8” G / Ø12 mm Concentric fl ue system : Ø100 mm - Ø150 mm or : Ø100 mm - Ø150 mm or connection Ø130 mm - Ø200 mm Ø130 mm - Ø200 mm
Batteries remote control
- Receiver : 4x 1.5V AA : 4x 1.5V AA
- Hand-transmitter : 2x 1.5V AAA : 2x 1.5V AAA
Weight:
- Basis model : 140 kg : 140 kg
- Including all options : 188 kg : 188 kg
(*) : Both burners at maximum. Appliance is on temperature. (**) : Both burners at maximum. Appliance is cold. (***) : Both burners at minimum.
Flue gas exhaust and combustion air supply: Roof-mounted outlet : Concentric fl ue system Ø100 mm - Ø150 mm. Rigid and/or fl exible. Horizontal wall outlet : Concentric fl ue system Ø130 mm - Ø200 mm. Rigid. With wall outlet, depending on the fl ue confi guration; Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm.
77
Bellfi res
English
Installation instructions
Model : ROOM DIVIDER LARGE 3 LF (Line Fire) ROOM DIVIDER LARGE 3 L/R LF (Line Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Product identifi cation no : 0063CM3684 : 0063CM3684 Type of appliance under CE-norm : C11 / C31 / C91 : C11 / C31 / C91 Category of appliance : I2H natural gas G20 : I
3B/P
butane/propane G30/G31
Nominal heat input : 12.3 kW : Butane (G30) : 12.2 kW (Gross calorifi c value) Propane (G31) : 10.1 kW
Nominal heat output : 9.4 kW : 7.8 - 9.4 kW Effi ciency class : 1 (85%) : 1 (85%) NOx-class : 5 : 5
Gas rate (max.) : 1.17 m
3
s
/hr. : Butane (G30) : 930 gr/hr.
Propane (G31) : 760 gr/hr.
Supply pressure : 20.0 mbar : Butane (G30) : 37.0 mbar Propane (G31) : 37.0 mbar
Burner pressure (max.) Hot : 11.9 mbar(*) : 29.0 mbar(*)
Burner pressure (max.) Cold : 11.2 mbar(**) : 29.0 mbar(**)
Burner pressure (min.) : 1.7 mbar(***) : 2.1 mbar(***)
Primary air inlet burner Rear : 1x Ø8.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Primary air inlet burner Front : 1x Ø8.0 mm : 1x Ø20,0
+corner
mm +
2x Ø5.0 mm
Gas regulator block (remote control) : Mertik GV 60 : Mertik GV 60 Main burner : Line Fire 960x130 mm : Line Fire 960x130 mm Main burner injector Rear : no 190 (= 1x Ø1.90 mm) : no 115 (= 1x Ø1.15 mm) Main burner injector Front : no 230 (= 1x Ø2.30 mm) : no 135 (= 1x Ø1.35 mm) Pilot light burner : SIT 0.145.019 : SIT 0.145.019 Pilot light burner injector : nr. 36 (SIT 0.977.091) : nr. 23 (SIT 0.977.150) Gas connection : 3/8” G / Ø12 mm : 3/8” G / Ø12 mm
Concentric fl ue system : Ø100 mm - Ø150 mm or : Ø100 mm - Ø150 mm or connection Ø130 mm - Ø200 mm Ø130 mm - Ø200 mm
78
Bellfi res
English
Installation instructions
Model : ROOM DIVIDER LARGE 3 LF (Line Fire) ROOM DIVIDER LARGE 3 L/R LF (Line Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Batteries remote control
- Receiver : 4x 1.5V AA : 4x 1.5V AA
- Hand-transmitter : 2x 1.5V AAA : 2x 1.5V AAA
Weight:
- Basis model : 140 kg : 140 kg
- Including all options : 188 kg : 188 kg
(*) : Both burners at maximum. Appliance is on temperature. (**) : Both burners at maximum. Appliance is cold. (***) : Both burners at minimum.
Flue gas exhaust and combustion air supply: Roof-mounted outlet : Concentric fl ue system Ø100 mm - Ø150 mm. Rigid and/or fl exible. Horizontal wall outlet : Concentric fl ue system Ø130 mm - Ø200 mm. Rigid. With wall outlet, depending on the fl ue confi guration; Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm.
79
Bellfi res
English
Installation instructions
8 REPLACEMENT PARTS LIST
When requesting service or ordering replacement parts, please quote the model type and serial number. All parts listed in this manual may be ordered from a Bellfi res dealer.
No Article no Description
1 334974 Main burner “Centre Fire” 960 x 130 mm Natural gas G20 / Butane/Propane G30/G31 G20: 1x Ø10.0 mm front + 1x Ø10.0 mm rear G30/G31: 1x Ø20.0
+corner
mm + 2x Ø5.0 mm front and
1x Ø20.0
+corner
mm + 2x Ø5.0 mm rear 2 334977 Burner mat L = 960 mm “Centre Fire” 3 334876 Burner injector Natural gas; Front: no 210 (1x Ø2.10 mm) 4 334988 Burner injector Natural gas; Rear: no 190 (1x Ø1.90 mm) 5 301928 Burner injector Butane/Propane; Front: no 130 (1x Ø1.30 mm) 6 334992 Burner injector Butane/Propane; Rear: no 110 (1x Ø1.10 mm)
7 334976 Main burner “Line Fire” 960 x 130 mm Natural gas G20 / Butane/Propane G30/G31 G20: 1x Ø8.0 mm front + 1x Ø8.0 mm rear G30/G31: 1x Ø20.0
+corner
mm + 2x Ø5.0 mm front and 1x Ø20.0
+corner
mm + 2x Ø5.0 mm rear 8 334978 Burner mat L = 960 mm “Line Fire” 9 334989 Burner injector Natural gas; Front: no 230 (1x Ø2.30 mm) 10 334988 Burner injector Natural gas; Rear: no 190 (1x Ø1.90 mm) 11 334991 Burner injector Butane/Propane; Front: no 135 (1x Ø1.35 mm) 12 334990 Burner injector Butane/Propane; Rear: no 115 (1x Ø1.15 mm)
13 333597 Gas regulator block; GV 60 (M10 Thermocouple connection) 14 302122 3/8” male x 12 Compression fi tting 15 302084 Nut Ø8 mm for burner supply GV 60 for “front burner” 16 302089 Olive Ø8 mm for burner supply GV 60 for “front burner” 17 333607 Gas valve “rear burner” 18 333608 Adapter 3/8”bsp x 3/8”+ O-ring 19 333610 Nut Ø8 mm for gas valve “rear burner” 20 333611 Olive Ø8 mm for gas valve “rear burner” 21 302086 Cut-off nipple Ø4 mm GV 60 22 333601 Cable (sw): Receiver - Thermocouple interrupter, L = 500 mm 23 333602 Cable (tc): Receiver - Thermocouple interrupter, L = 500 mm 24 341204
Hand-held transmitter:
Bellfi res Symax 1-8 25 339907 Receiver GV 60 - Symax 1 26 302068 8 Wire connecting cable Gas regulator block - Receiver, L = 500 mm 27 302421 Piezo ignition cable, 2x 2.8 x 0.8 mm, L = 1500 mm
80
Bellfi res
English
Installation instructions
No
Article no Description
28
321926 Thermocouple M10 - 1500 mm
29 333604 Thermocouple interrupter M10
30 310908 Pilot light set outer casing, Double fl ame 31 310909 Packing pilot light set outer casing 32 310910 Pilot light injector; Natural gas; no 36 33 310912 Pilot light injector; Butane/Propane; no 23 34 310907 Piezo electrode for pilot light, 2.8 x 0.5 mm 35 302062 Nut piezo electrode 36 319842 Nut thermocouple 37 332552 Pilot light olive; Ø4 mm, steel 38 332553 Pilot light nut; Ø4 mm, steel 39 322552 Pilot light pipe; Ø4 mm, L = 1500 mm, Flexible, Stainless steel 40 325750 Burner pipe; Ø8 mm, L = 1500 mm, Flexible, Stainless steel - 10 kW+, “front burner” 41 325750 Burner pipe; Ø8 mm, L = 1500 mm, Flexible, Stainless steel - 10 kW+, “rear burner”
42 326055 Nut; Ø8 mm, compression elbow main burner 43 326054 Olive; Ø8 mm, compression elbow main burner
44 334902 Packing pilot light holder (CF/LF) 45 334259 Packing double burner (CF/LF)
46 341676 Glass
Room Divider Large 3 (L/R) side (493 x 1067.5 x 4 mm) 47 341675 Glass Room Divider Large 3 (L/R) front side (493 x 372 x 4 mm) 48 341677 Glass
Room Divider Large 3 (L/R) side (493 x 462 x 4 mm)
49
301669 Tube ceramic glue
50 301593 Black fi bre glass tape 15 x 3 mm, adhesive 51 319664 Black fi bre glass tape 30 x 2 mm, adhesive 52 311006 Black fi bre glass tape 20 x 2 mm, adhesive 53 301617 Black fi bre glass cord Ø10 mm
81
Bellfi res
English
Installation instructions
Logs - Chips of wood - Embers -
Vermiculite granules - Marble
pebbles
Chips of
Embers with Vermiculite no 4
wood set
Glow-effect black
Anthracite fi ltered
Appliance Log set
Marble pebbles Marble pebbles
set (white) set (grey)
Set Log no
Art. no:
C 325292
Room Divider Large 3 (L/R) CF/LF
1
331357
1x
2
331358
2x
3
331359
1x
4
331360
1x
6
331362
1x
7
331363
-
8
331364
1x
5
331361
1x
3 pieces
xxxxxx
2x
Bag: 125 gr.
301863
4x
Bag: 50 gr.
332583
1x
Bag: 2.5 kg.
310937
3x
Bag: 2.5 kg.
325758
3x
82
Bellfi res
English
Installation instructions
9 DISPOSING OF PACKAGING AND APPLIANCE
The appliance comes in recyclable packaging. This can include:
• Cardboard
• Wood
• Plastic
• Paper
Such materials must be disposed of responsibly, in line with local regulations.
Batteries should be disposed of as chemical waste. Batteries must be disposed of responsibly, in line with local regulations.
The authorities or fi tter can provide you with information on responsible disposal of obsolete appliances.
83
Bellfi res
English
Installation instructions