Bellfires DERBY LARGE 3 CF, DERBY LARGE 3 LF Installation Instructions Manual

This document is an essential part of your gas fi re. Read it carefully before
installation and use of the gas fi re and keep it in a safe place!
INSTALLATION INSTRUCTIONS
&
MANUAL FOR MAINTENANCE
DERBY LARGE 3 CF/LF
Gas fi re with closed combustion system
Serial number:
Production date:
3
Bellfi res
English
Installation instructions
BELLFIRES GAS FIRE WITH CLOSED COMBUSTION SYSTEM:
Derby Large 3 CF (Centre Fire) (DYL3 CF)
Derby Large 3 LF (Line Fire) (DYL3 LF)
4
Bellfi res
English
Installation instructions
5
Bellfi res
English
Installation instructions
CONTENTS
Page
1. INSTALLATION INSTRUCTIONS .............................................................. 7
2. MAINTENANCE .....................................................................
...................
. 67
3. FAULTS ...................................................
.................................
.......
..........
. 68
4. DISMANTLING
/ ASSEMBLING OF THE GLASS ........................
...
.......
... 69
5. DIAGRAM ELECTRICITY AND GAS ........................
........................
......... 75
6. DIMENSIONS ......................................................
..............................
....
....
. 76
7. TECHNICAL DETAILS/REGULATIONS .....................................
.......
......... 84
8. REPLACEMENT PARTS LIST .........................................
..................
........ 88
9. DISPOSAL OF PACKAGING AND APPLIANCE .........
......................
...
.....
. 91
The installation must only be carried out by a
“Gas Safe Register” registered installation engineer.
IMPORTANT
6
Bellfi res
English
Installation instructions
7
Bellfi res
English
Installation instructions
1 INSTALLATION INSTRUCTIONS
1.1 GENERAL
The gas fi re must be positioned and connected as a “room sealed system” (balance fl ue) appliance by a “Gas Safe Register” registered gas installation engineer in accordance with the following installation instructions, nationally and locally applicable regulations (see “Technical Details/ Regulations” at the rear of this manual). If you have any queries regarding the installation, please consult your local gas company.
Important: Before beginning the installation, check that the details on the rating plate correspond to the gas type and pressure to which the appliance will be connected.
The appliance is supplied with a “Centre Fire” or “Line Fire” double burner, as ordered. These burners each have their own specifi c fl ame image which is defi ned by the perforation pattern in the burner cover.
See Chapter 5 and the Instructions for use.
The appliance is factory set to the correct nominal heat input. The pilot light is set to the correct level of consumption.
Depending on the requested version, the appliance will be delivered from the factory with a Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm concentric connection for extracting the fl ue gases and supply of combustion air.
It is possible to install the gas fi re with either a wall or roof outlet.
The roof connection must be carried out using the concentric fl ue system Ø100 mm ­Ø150 mm. The fumes are exhausted naturally to the outside environment through the inner Ø100 mm pipe whereas the combustion air supply passes between the Ø100 mm and Ø150 mm pipes.
The wall connection must be carried out using the concentric fl ue system Ø130 mm ­Ø200 mm. The fl ue gases are evacuated outside by means of natural draft through the internal pipe of Ø130 mm, whereas the combustion air is supplied between the pipes of Ø130 mm and Ø200 mm. The wall outlet itself is, depending on the concentric fl ue gas
system confi guration, Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm. (In some cases,
with a wall connection, a complete concentric fl ue system Ø100 mm - Ø150 mm is also possible (see Chapter 1.6.1).)
The gas fi re can be installed in a completely sealed or mechanically ventilated house without extra ventilation and/or fume extraction.
The gas fi re can be installed as an insertion into an existing open fi replace or as a built-in appliance in a new fi replace.
In order to prevent the fi replace heating up excessively, it must be properly ventilated by installing vents at the top and bottom of the fi replace.
8
Bellfi res
English
Installation instructions
Set documentation - Instructions for use
- Installation instructions
Attributes - Ceramic log set, or marble pebbles white or marble pebbles grey
- Hook (for opening the frame and the glass)
The appliance can be fi tted with a convection package as an optional extra. This is a “convection jacket” (convection casing) for around and above the appliance, two fl exible aluminium pipes and two built-in convection vents. This enables hot air to be circulated into the room. If required, two additional convector grills can be fi tted (= 1x extra convection set).
If an existing chimney is to be used, please consult your installer fi rst. If the chimney was previously used for a wood or coal fi re, then it should be cleaned by an expert.
1.2 CONCENTRIC FLUE SYSTEMS Ø100 MM - Ø150 MM AND Ø130 MM - Ø200 MM : • Bellfi res (Muelink & Grol system)
• Poujoulat (PGI system)
• Ontop (Metaloterm US system)
The gas fi re, in combination with the concentric fl ue system [Ø100 mm - Ø150 mm] and/ or [Ø130 mm - Ø200 mm] (rigid and/or fl exible)
for the brands Bellfi res (Muelink & Grol system), Poujoulat (PGI system) or Ontop (Metaloterm US system), has been approved in accordance with the European CE-norm for gas appliances and may therefore be used only with these systems. The permitted components for these systems are listed in Chapter 1.6.2. The guarantee on the appliance lapses if it is installed, fully or partially, with other components or a different fl ue system. The concentric fl ue [Ø100 mm - Ø150 mm] and [Ø130 mm - Ø200 mm] systems can be used with either a newly-built or existing chimney.
N.B. If any part is missing, please contact your dealer.
1.3 INCLUDED
9
Bellfi res
English
Installation instructions
1.4 OPTIONS AND ACCESSORIES
The following options and accessories can be supplied by your dealer:
Part no Accessorie
312829 Convection set General: (for convection air extraction) 302188 • 1x Flexible aluminium pipe Ø125 mm, L= 3 m (max.)
310178 • 2x Fitting box 135 x 135 mm 309872 • 2x Convection exit grid, white, 145 x 145 mm 309730 • 2x Collar adaptor Ø125 mm 304040 • 4x Hose clamp Ø125 mm
329874 Set carrying brackets (2 pieces)
3........ Bellfi res (M&G) concentric fl ue system
See component summary
3........ Poujoulat (PGI) concentric fl ue system
See component summary
3........ Ontop (Metaloterm US) concentric fl ue system
See component summary
Part no Option
Convection package Derby Large 3
329703 • 1x Convection casing 329704 • 1x Top plate Convection 312829 • 1x Convection set General
330361 Set of high adjustable feet (4 pieces)
311967 Mantle iron L = 1250 mm
10
Bellfi res
English
Installation instructions
1.5 PREPARATION FOR INSTALLATION
The following preparation must be carried out before the gas fi re can be installed.
1.5.1 Instructions for positioning the outlet
1.5.1.1 Positioning the outlet for correct operation:
Roof-mounted outlet:
Figure 1: Roof-mounted outlet
This must be positioned at least 0.5 m from the roof edge; the apex of the roof can be disregarded.
Wall-mounted outlet:
Figure 2: Wall-mounted outlet
This must be positioned at least 0.5 m from:
• the corner of the building.
• the roof overhang, the rain gutter.
• balconies etc., unless the exhaust construction
extends to at least the face of the protruding section.
>0.5 m
>0.5 m
11
Bellfi res
English
Installation instructions
1.5.1.2. Positioning the outlet to avoid affecting the surrounding area
All listed “distances” in this section are no more than guidelines. For the exact minimum “distances”, please consult your national and local directives.
“Distance” = minimum distance required for positioning of the outlet to avoid adverse effects with respect to:
A. A ventilation opening serving an occupied room, a toilet or a bathroom.
B. A heating air supply, when the supply fl ows through an occupied room.
C. A window that can be opened and that is near an occupied room, a toilet or a bathroom.
Roof-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At the same roof level. >3 m (*)
At a different roof level. >1 m (*)
At a lower positioned wall. >1 m
At a higher sloping surface. >3 m (**)
(*) If the required distance cannot be achieved, the outlet position rules take precedence.
(**) If the required distance cannot be achieved, the position of the outlet must be at least 1 m above the highest facade/roof.
12
Bellfi res
English
Installation instructions
Wall-mounted outlet:
To avoid adverse effects Distance: outlet - A, B or C
At walls in buildings with staggered Not permitted if A, B, or C are located heights. above the outlet.
On a wall - general. (*) Above the outlet: >2 m Below the outlet: >0.75 m Left and right of the outlet: >0.75 m
At <1 m from the roof overhang. >2 m
Beneath balconies, walkways etc. >2 m from the underside of the protruding balcony or walkway.
Beneath balconies, walkways >2 m etc. where the outlet extends to the front.
To the garden or on the terrace. >2 m to the outside space. (**)
With respect to a facing wall. >2 m (if the distance from the facing wall is less, the criteria detailed for “On a wall - general” apply).
Enquire at your local gas company for the regulations relating to outlets
positioned opposite each other and outlet(s) in facade(s) that form an angle.
(*) These minimum distances do not apply if there is an obstruction between the outlet and A, B and C that protrudes at least 0.5 m from the wall and has a length exceeding the distance.
(**) This distance is not required if the outlet is situated at least 1 m higher than the intended area of the outside space.
If the outlet has a clearance of less than 0.5 m from the hard surface of a public area at
a height of less than 2 m, it must be fi tted with an effective protector. The mesh size of the guard must not affect the correct operation of the appliance.
13
Bellfi res
English
Installation instructions
1.6 GENERAL SERVICES
1.6.1 The Fume Channel/Combustion Air Intake
The combined fume channel and combustion air intake requires one of the following concentric fl ue system confi gurations.
Important: Due to the high temperature of the outer walls
(approx. 150°C), no fl ammable materials may be located or used in the vicinity of the fl ue system. The complete fl ue system, must therefore be sleeved with a heat resistant material after assembly.
Ventilate the covered concentric fl ue by fi tting a grid near the fl oor and ceiling (on each fl oor).
Do not insulate the concentric fl ue.
Use the universal wall/fl oor support Ø150 mm to attach the covering of the concentric fl ue system [Ø100 mm - Ø150 mm], see 1.6.2, drawing number 36.
Figure 3: Application universal wall/fl oor support Ø150 mm
Use as a wall support Use as a fl oor support
36
36
14
Bellfi res
English
Installation instructions
RIGID CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES
18
10, 11, 12, 13
1
4
Y
28
16
17
16
24
23
24
23
(100)
Appliance: Concentric fl ue connection Ø100-Ø150 mm or Ø130-Ø200 mm
Figure 4: Vertical roof-mounted outlet without bend
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Derby Large 3
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
15
Bellfi res
English
Installation instructions
Figure 5: Vertical roof-mounted outlet with bend
(*) : (Y1 + Y2) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
16
23
Y
2
X
10, 11, 12, 13
14, 15
Y
1
4
1
28
23
23
17
24
(100)
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*) Distance Y1 + Y2 (*) Concentric Concentric (min.-max.) (min.-max.) (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
Derby
1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m
-
Width:
Large 3 B = 40 mm
Item descriptions:
see 1.6.2
16
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
(100)
1
4
28
32
18
23
25
26
29
7
5
29
30
10, 11, 12, 13
Y
Appliance: Concentric fl ue connection Ø100-Ø150 mm or Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Derby Large 3
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
Item descriptions:
see 1.6.2
Figure 6: Vertical chimney outlet using an existing lined chimney (Flexible Ø100 mm and/or rigid Ø100 mm / Ø150 mm)
FLEXIBLE CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES
17
Bellfi res
English
Installation instructions
(*) : (Y1 + Y2+ Y3) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
2
Y
1
10, 11, 12, 13
> 45°
X
Y
3
32
18
30 29
5
7
29 26
25
23
28
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y1 (*) Distance X (*)
Distance Y1 + Y2 + Y3 (*) Concentric Concentric
(min.-max.) (min.-max.) (min.-max.) connection connection
on appliance is on appliance is
Ø100-Ø150 mm Ø130-Ø200 mm
Derby Large 3 1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m
-
Width:
B = 40 mm
Figure 7: Vertical chimney outlet using a lined chimney with a bend > 45° (Flexible Ø100 mm and/or rigid Ø100 mm / Ø150 mm)
18
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
7
6
8
1832
31
29
30
29
26
29
27
28 29
4
1
(100)
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Concentric Concentric (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 4.0 m
Width: Width:
B = 30 mm B = 65 mm
Derby Large 3
4.0 - 12.0 m
Width: Width:
B = 40 mm B = 80 mm
Figure 8: Vertical chimney outlet using an existing unsound lined chimney or when no chimney liners are present (Flexible Ø100 mm / Ø150 mm)
19
Bellfi res
English
Installation instructions
(*) : (Y1 + Y2+ Y3) : X > 2 : 1 (Vertical to horizontal ratio (or 45° upwards) is always at least 2 to 1)
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Y
3
Y
2
Y
1
X
> 45°
6
8
7
31 29
32 18
30 29
26
29
27
28 29
4
1
(100)
Item descriptions:
see 1.6.2
Figure 9: Vertical chimney outlet using an existing unsound lined chimney or when the chimney is unlined; with a bend >45
o
(Flexible Ø100 mm / Ø150 mm)
Assemble restriction plate:
Appliance:
Distance Y1 (*) Distance X (*) Distance Y1 + Y2 + Y3 (*) Concentric Concentric (min.-max.) (min.-max.) (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
Derby Large 3 1.0 - 11.0 m 0 - 3.0 m 1.0 - 11.0 m
-
Width:
B = 40 mm
20
Bellfi res
English
Installation instructions
Figure 10: Horizontal wall termination
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Item descriptions:
see 1.6.2
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric Concentric (min.-max.) (min.-max.) connection connection on appliance is on appliance is Ø100-Ø150 mm Ø130-Ø200 mm
2.0 - 3.0 m 0 - 0.6 m - - Derby Large 3
3.0 - 4.0 m 0 - 1.6 m - -
Wall
Termination
Position
(100)
4
28
1
Y
X
19
14
10, 11, 13
0.16 m
Appliance: Concentric fl ue connection
Ø100-Ø150 mm or Ø130-Ø200 mm
RIGID CONCENTRIC FLUE Ø100 mm - Ø150 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
21
Bellfi res
English
Installation instructions
Item descriptions:
see 1.6.2
Figure 11: Horizontal wall termination
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection (min.-max.) (min.-max.) on appliance is Ø130-Ø200 mm
0.5 - 1.0 m 0 - 0.6 m ­Derby Large 3
1.0 - 2.0 m 0 - 2.6 m -
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
100
4
128
1
Y
X
19
14
110, 111, 113
0.16 m
Wall
Termination Position
22
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 12: Horizontal wall termination
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection (min.-max.) (min.-max.) on appliance is Ø130-Ø200 mm
0.5 - 3.0 m
0 - 2.6 m Width: B = 40 mm
Derby Large 3
0.5 - 3.0 m 2.6 - 4.6 m -
Item descriptions:
see 1.6.2
100
4
128
1
Y
X
19
114
110, 111, 113
0.25 m
123
Wall
Termination Position
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
23
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 13: Horizontal wall termination
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y1 Distance X1 Distance Y2 Distance X2 Concentric connection (min.-max.) (min.-max.) (min.-max.) (min.-max.)
on appliance is Ø130-Ø200 mm
0 - 0.5 m 0 - 0.5 m 0.5 - 1.0 m 0 - 0.6 m -
0.5 - 1.0 m 0 - 0.5 m 0 - 0.5 m 0 - 0.6 m ­Derby
Large 3
1.0 - 3.0 m 0 - 1.0 m 0.5 - 2.0 m 0 - 0.6 m -
1.0 - 3.0 m 0 - 3.0 m 1.0 - 3.0 m 0 - 0.6 m -
Item descriptions:
see 1.6.2
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø100 mm - Ø150 mm
110, 111, 113
128
4
1
114
14
114
110, 113
110, 111, 113
100
19
0.16 m
Y
2
X
2
Y
1
X
1
Wall
Termination Position
24
Bellfi res
English
Installation instructions
ALL SIZES INCLUDE THE LENGTH OF THE ROOF OR WALL TERMINATION
Figure 14: Horizontal wall termination
Appliance: Concentric fl ue connection
Ø130-Ø200 mm
Assemble restriction plate:
Appliance: Distance Y Distance X Concentric connection (min.-max.) (min.-max.)
on appliance is Ø130-Ø200 mm
0 - 0.5 m 0 - 0.6 m Width: B = 40 mm
Derby Large 3 0.5 - 3.0 m 0 - 3.6 m Width: B = 50 mm
0.5 - 3.0 m 3.6 - 8.6 m -
Item descriptions:
see 1.6.2
4
128
1
Y
X
119
114
110, 111, 113
0.25 m
123
Wall
Termination Position
RIGID CONCENTRIC FLUE Ø130 mm - Ø200 mm SYSTEM CONNECTION POSSIBILITIES and with wall outlet Ø130 mm - Ø200 mm
47
Bellfi res
English
Installation instructions
Min. 6 cm
Figure 15: A clearence of at least 6 cm must be maintained between the bottom plate of the appliance and the fl oor.
1.6.3 Gas connection
Operation (gas regulating block (and receiver)) outside the appliance
(in the operating
unit): The gas connection is situated where the operating unit is built in near to the appliance.
Use only gas piping with a minimum diameter of 1/2” and a shut-off valve.
1.6.4 Operating unit
If the appliance is fi tted with an operating unit comprising gas control block and receiver, this will be located, once it has been built in, at a maximum of 50 cm from the left or right hand side of the appliance.
1.6.5 Convection package connections
When fi tting a convection package (= convection casing and convection set (1x or 2x)), consideration should be given to the openings at approximately 1 meter above the appliance for the warm air exiting grids.
1.7 POSITIONING THE APPLIANCE
Important: The fi replace is constructed on a suffi ciently solid fl oor that can bear the weight of the appliance.
Ensure a free space of at least 6 cm between the bottom plate of the appliance and the fl oor.
Ensure that the temperature of the fl oor under and in front of the appliance can never rise above 85°C! Make use of a temperature protection plate (of nonfl ammable material) on the fl oor if necessary. Take care with a fl oor made of a fl ammable material.
48
Bellfi res
English
Installation instructions
Never position the appliance directly against the rear wall, but always place an nonfl ammable insulation plate, at least 12 mm thick, between the appliance and the rear wall, with free space on either side of 2 cm. (Total ± 5 cm.) The rear wall must be made of nonfl ammable material.
Never use combustible materials during the installation.
Ventilate the fi replace, by allowing vents above and below the fi replace.
During installation of the gas fi re, a clearance of 3 mm should be maintained on all sides of the appliance to allow for expansion of the appliance during operation.
Do not insulate the appliance! Only the top and sides may be fi tted with a strip of white, loose insulation wool (heat-resistant to 1000°C), width 15 cm max. to protect the wall.
Do not use fi breglass or Rockwool, or any other sort of insulating material. These emit a pungent odour. This is considered extremely unpleasant. They may also cause discolouring of the column.
Flammable materials, such as curtains, should not be placed in the vicinity of the gas fi re. Minimum safe distance: 100 cm.
If desired, fi t a convection package to the appliance.
(See chapter 1.1)
The appliance can be easily installed using a set of
carrying brackets (accessory).
After installing: remove carrying brackets!
49
Bellfi res
English
Installation instructions

Figure 16: Appliance installed in ventilated chimney breast Horizontal outlet of the fl ue gas exhaust /combustion air supply via the wall. Fitted with the options / accessories:
• convection package (= convection casing and 1x convection set)
• 1x extra convection set
• high adjustable feet
1 Inlet opening (appliance) convection air 2 Inlet opening (grate) (chimney breast) convection air 3 Natural convection in the chimney breast 4 Outlet opening (grate) (chimney breast) natural convection air 5
Outlet opening (appliance) convection air / connection convection set (2x or 4x)
6
Outlet opening (grill convection set) (chimney breast) convection air (2x or 4x) 7 ­ 8 Concentric fl ue connection appliance; Ø130-200 mm for a horizontal wall outlet 9 Horizontal wall outlet 10 Built in operating unit with gas regulating block and receiver
50
Bellfi res
English
Installation instructions
Figure 17: Appliance installed in ventilated chimney breast Vertical outlet of the fl ue gas exhaust / combustion air supply via the roof.
Fitted without convection package
1 Inlet opening (appliance) convection air 2 Inlet opening (grate) (chimney breast) convection air 3 Natural convection in the chimney breast 4 Outlet opening (grate) (chimney breast) convection air (2x) 5 Concentric fl ue connection appliance; Ø100-150 mm for a vertical roof outlet 6 Concentric fl ue system; Ø100-150 mm for a vertical roof outlet 7 Built in operating unit with gas regulating block and receiver
51
Bellfi res
English
Installation instructions
- Position 4 protecting covers. - Protecting cover.
Press the 4 protecting covers back into the fl oor.
When fi tting the appliance, it can be levelled with the adjustable feet
. These adjustable feet can be reached via the openings (4x), after removing the protective covers, in the corners of the fl oor of the combustion chamber. The fl oor of the combustion chamber can be reached after the window and the grill around the burner have been removed (see chapter 4). Using an Allenkey (no. 5), the appliance can be adjusted to the required height.
- Adjustable feet seen from the bottom
- Adjust height with Allenkey no. 5.
of the appliance.
52
Bellfi res
English
Installation instructions
- 2x Mounting bracket.
Position the gas supply pipe such that it can be easily mounted after installation.
Because the control system is outside the appliance, the gas pipe must lead to where the operating unit (built in), the gas regulating block (and the receiver) assembly are
fi tted.
Move the appliance until it is ± 5 cm from the rear wall and ensure it is level. Place the nonfl ammable insulation plate (min. 12 mm) between the appliance and rear wall. The appliance may not be installed against a fl ammable rear wall.
Attach the appliance to the rear wall with 2 wedge bolts. Use the adjustable mounting brackets at the side of the appliance for this.
53
Bellfi res
English
Installation instructions
Figure 18: Operating unit
Frame with
door (white)
Operating unit
1.7.1 Gas connection operating unit
Important: During gas connection, take care not to twist the gas regulator block. Make sure that both the gas regulator block and the supply pipes are not subjected to stresses.
The appliance is supplied with a built-in operating unit.
Remove the decorative edging and door of the operating unit. Fit the separate operating unit, where the gas regulator block and receiver will be placed, on max. 50 cm from the appliance.
The burner, gas regulator block and receiver have been fully factory assembled.
Disconnect the bracket with the gas regulator block and receiver from the appliance. Carefully move the bracket with the gas regulator block, receiver, pipes and cables to the operating unit. Mount the bracket at the bottom of the operating unit..
Important: Take care that no pipes get damaged and no compression fi ttings come loose when moving the gas regulator block. Prevent twisting the fl exible pipes! Check all compression fi ttings for leaks afterwards!
Mount the receiver in the top of the operating unit. Check afterwards that all electric connections are properly connected.
General: Route all piping and cables from the operating unit to the appliance through an easily accessible hollow cavity. During subsequent installation of the operating unit, protect the gas regulator block and piping against encasement by cement etc.
54
Bellfi res
English
Installation instructions
Gas pipe
“rear burner”
Ø8 mm Flex.
Gas valve
“rear burner”
Gas pipe
“front burner”
Ø8 mm Flex.
Gas supply
connection
Gas regulator block
Thermocouple
Pilot light
pipe
Ø4 mm Flex.
Thermocouple
interrupter
Figure 19: Gas regulator block and gas valve: Gas and thermocouple connections
Important : Cement and chalk can damage the piping and can, in turn, lead to gas leaks.
Disassembly and assembly of pipes and cables:
If necessary for mounting, all pipe compression fi ttings and cable connectors can be temporarily disassembled. After mounting, carefully reassemble all pipes and cables. Check afterwards all compression fi ttings for leaks and that all electric connections are properly connected.
Important : Screw the thermocouple connection (and thermocouple interrupter) manually into the gas regulator block. Afterwards, carefully fasten a half turn with a spanner.
Note : Check that the fl exible burner pipes are correctly connected!
The gas connection of the gas valve “rear burner” must be connected to the “rear burner”! See Chapter 5. Switching over the fl exible burner pipes during assembly can lead to an explosive ignition. Prevent this at all costs!
55
Bellfi res
English
Installation instructions
Figure 20: Gas regulator block - Front
Inlet
Pressure Tap
Outlet
Pressure Tap
Gas supply connection
Gas connection for to the “front burner”
Gas connection for gas valve to the “rear burner”
Thermocouple interrupter connection
Adjustment Screw Minimum Burner pressure
Pilot light connection
Figure 21: Gas regulator block - Rear
Pilot Gas Adjustment Screw (Pierce the housing with a small screwdriver)
Adjustment Screw Maximum Burner pressure
Motor-knob
Microswitch8 Wire connecting
cable receiver
56
Bellfi res
English
Installation instructions
Figure 22: Receiver - Top
Figure 23: Receiver - AUX connection - RESET button
Thermocouple
voltage / current
OUT - connection (yellow)
Piezo cable connection
RESET button
AUX: Electrical connection for gas valve “rear burner”
TCSW
Thermocouple voltage / current IN - connection (red)
6 VDC Adapter connection (option)
Connection 8 wire cable gas regulator block
Connection for external operating (option)
RESET button
AUX: Electrical connection for gas valve “rear burner”
57
Bellfi res
English
Installation instructions
1.7.2 Connecting the concentric fl ue
Assemble the concentric fl ue system according to one of the examples in section 1.6.1, fi gure 4 to 14 inclusive. Make sure that all connections are completely gas tight.
1.7.3 Building in the appliance
Remove the front of the casing, if applicable. (See Chapter 4: DISMANTLING
/ ASSEMBLING OF THE GLASS.) Decide on positions of the vents (grilles above and below the fi replace) and, if applicable, the hot air grids of the convection package.
The brickwork must be built up around the hearth. In connection with the hearth expanding during burning: there must be at least 3 mm clearance on either side of the appliance. Do not build up the brickwork farther than the angle irons/brackets (keep in mind the thickness of any plastering!).
Do not use masking tape on the appliance when installing and plastering. Tape can damage the fi nish of the hearth.
Connect up the convection package, if applicable.
The optional mantle iron is intended for supporting the brickwork above the hearth. The mantle iron must rest on the brickwork on both sides so that upward building is possible. The brickwork therefore must not rest on the fi replace; there must be approx. 3 mm clearance in connection with the weight.
If using other materials, such as stone or heat-resistant plating, you should follow the supplier’s instructions.
Once the fi replace has been fi nished, you can now, fi t the frame with the small door to the operating unit.
After installation in a new fi replace and/or applying new cement work, the appliance cannot be used for at least four weeks.
58
Bellfi res
English
Installation instructions
1.7.4 Checking the gas connection
After connection of the gas supply, check that all connections are completely gas tight using soapy water or a leak tester.
1.7.5 Positioning the ceramic log set or marble pebbles
The appliance can be supplied with:
• Ceramic log set + embers
• Marble pebbles white (small, white marble stones)
• Marble pebbles grey (small, grey marble stones)
Important: • Carefully place the
chips of wood/embers/vermiculite granules/
log set or marble pebbles, on and around the main burner according to the directions in this chapter.
• Do not place any chips of wood/embers/vermiculite granules/ log set or marble pebbles against the pilot light burner. For that reason, the main burner has a protective pilot-light cowl.
Never remove this cowl! Make sure that the pilot fl ame can burn at all times freely over the main burner. Only in this way is proper ignition of the main burner ensured. Ignoring these directions could lead to a dangerous situation.
• Make sure that all burner orifi ces remains free at all times!
• The burner bed (with chips of wood/embers/vermiculite granules) and the positioning of the logs or marble pebbles must not be changed.
• Only use those items supplied! These been rigorously checked and the quantities adapted to the appliance.
• Replacement parts, including the ceramic mat are available from your dealer.
• Fitting may only be carried out by a qualifi ed person.
Remove the glass according to the instructions in chapter 4; DISMANTLING / ASSEMBLING OF THE GLASS.
59
Bellfi res
English
Installation instructions
1.7.5.1 Ceramic log set + chips of wood + embers + vermiculite granules
1 Place the ceramic mat on the burner in such a way that the holes in the mat are in
line with the burner openings.
2 Remove the embers carefully from their packaging and spread them evenly over the
burner mat and the grate around the burner.
3 Distribute the vermiculite granules (50 gram) evenly over the burner.
60
Bellfi res
English
Installation instructions
Note ! : Small embers and their residue should not be scattered on
the burner. This can cause a blockage on the burner orifi ces.
• Embers and vermiculite granules must not be placed next to the pilot light burner.
• Important: make sure that all burner openings remain free !!
Burner orifi ces, which are not open, could lead to a dangerous
situation.
4 Place the logs on the burner:
Appliance
Natural gas-burner Propane / Butane-burner
see fi gure: see fi gure:
Derby Large 3 CF/LF 24 25
Keep the burner orifi ces unblocked !!!
5 Place the chips of wood around the burner.
61
Bellfi res
English
Installation instructions
Logs:
Log no u Log no v
Log no w Log no x
Log no y Log no z
Log no { Log no |
62
Bellfi res
English
Installation instructions
Keep the burner orifi ces unblocked!
Figure 24: Log set Derby Large 3 CF/LF Position natural gas burner
Embers must not be placed next to the pilot light burner
Embers must not be placed next to the pilot light burner
Keep the burner orifi ces unblocked!
Figure 25: Log set Derby Large 3 CF/LF Position propane/butane burner
u
x
y
z
{
v
u
x
y
z
{
v
63
Bellfi res
English
Installation instructions
1.7.5.2 Marble pebbles
1 Place the ceramic mat on the burner in such a way that the holes in the mat are in
line with the burner openings.
2 Spread the pebbles over the whole burner bed (burner and grid around the burner).
Make sure that the pilot light remains free.
Derby Large 3 CF/LF : see fi gure 27
Figure 26: Marble pebbles-set natural gas and propane/butane-burner
IMPORTANT: Open area, in order to ensure free
accessibility of the pilot fl ame to the burner
Keep the burner orifi ces unblocked
64
Bellfi res
English
Installation instructions
Keep the burner orifi ces unblocked!
Figure 27: Marble pebbles Derby Large 3 CF/LF Position natural gas and propane/butane burner
Important: • Do not place any marble pebbles in front of the pilot light. Make sure that the pilot light can burn freely over the main burner.
Keep the burner orifi ces unblocked.
Only this way a proper ignition of the main burner is ensured.
Once the logs / marble pebbles have been positioned, replace the glass in the appliance, following the instructions in chapter 4: DISMANTLING
/ ASSEMBLING OF THE
GLASS.
1.7.6 Mounting fl ue gas restriction plate
Depending on the length and shape of the concentric fl ue system and the chimney
construction, you should, if indicated, fi t a restriction plate with a certain width (B) into the ceiling of the combustion chamber. To do this, see the set-up options as listed in fi gure 4 through 14.
Keep the burner orifi ces unblocked!
Marble pebbles must not be placed next to the pilot light burner
65
Bellfi res
English
Installation instructions
Important: Ensure that the correct fl ue gas restriction plate is mounted. Use of the correct fl ue gas restriction plate will provide optimum effi ciency, fl ame effect and combustion. Mounting an incorrect fl ue gas restriction plate can result in damage to the gas fi re.
Figure 28: Positioning restriction plate
Assembly restriction plate
66
Bellfi res
English
Installation instructions


%
[
The following restriction plates are supplied:
1.7.7 Checking the appliance following installation
After installation, visually check the gas fl ame. When the fi re is ignited, the fl ames should be short and blue/yellow in colour. These fl ames should gradually increase in height and become more yellow. When all fl ames are yellow, the gas fi re has reached the correct temperature.
THE GAS FIRE IS NOW READY FOR USE
Concentric fl ue connection appliance
[Ø130 - 200 mm]
[Ø100 - 150 mm]
Restriction plate: Horizontal wall outlet Roof-mounted outlet
Width: - B = 30 mm Width: B = 40 mm B = 40 mm Width: B = 50 mm B = 50 mm Width: B = 65 mm B = 65 mm Width: B = 80 mm -
67
Bellfi res
English
Installation instructions
2 MAINTENANCE
2.1 ANNUAL MAINTENANCE
It is essential that the appliance, the complete concentric fl ue system (where possible) and the outlet are cleaned and inspected annually by a recognised fi tter/gas specialist. The safe operation of the appliance will thus remain guaranteed.
Maintenance consists of the following:
• Remove fi rst the embers, vermiculite granules, logs set or pebbles from the main burner and carefully clean these with a soft brush.
• Clean and inspect (visually) the main burner, pilot light, combustion chamber, fl ue system and combustion air intake. Dust can be removed using a vacuum cleaner.
• Clean the glass on the inside of the appliance with glass spray or ceramic hob cleaner. This also applies to the black mirror rear wall and side panels, if the appliance is fi tted with these.
• After cleaning;
Carefully replace the embers, vermiculite granules, logs set or pebbles on and
around the main burner according to the installation directions in this instruction booklet.
Do not place any embers, vermiculite granules, logs or pebbles against the
pilot light burner. Make sure that the pilot fl ame can burn at all times freely over the main burner. Only in this way is proper ignition of the main burner ensured.
Ignoring these directions could lead to a dangerous situation.
• Check the gas supply, fl ue system, and combustion air supply route for leaks.
• Check the correct operation of the gas regulating block, thermocouple circuit and the ignition of the main burner.
• Check the gas inlet-pressure (both when the appliance is off and when it burns at maximum) and the burner pressure.
• Check the complete concentric fl ue system including the outlet construction.
A camera can be used to inspect the whole length of the fl ue gas outlet and the
combustion air intake.
Also check that all connections are secure.
68
Bellfi res
English
Installation instructions
3 FAULTS
3.1 POSSIBLE REASONS
Possible reasons for the gas fi re going out are:
• The concentric fl ue system is not installed according to one of the methods detailed in Paragraph 1.6.
• An incorrect “fl ue gas restriction plate” is fi tted.
• The pilot light extinguishes if fumes are not exhausted or are insuffi ciently exhausted.
• The pilot light is either dirty or defective.
• Insuffi cient gas pressure.
• (Internal) leak of the concentric fl ue system.
• Thermocouple voltage is too low. This is usually caused by insuffi cient heating of the thermocouple by the pilot light.
• Dirty electrical contacts in the thermo-electrical system; for example, the thermocouple connection.
• Batteries in receiver or remote control are fl at.
3.2 SAFETY MEASURES IN THE APPLIANCE
3.2.1 Thermo-electric pilot light shut off
The appliance is protected by means of a thermo-electric pilot light shut off in the event of a gas escape from the main burner.
3.2.2 Over pressure safety system
The appliance is fi tted with a patented safety system, whereby the door will extract any over-pressure that arises in a controlled way. In this, a spring system briefl y causes the door to hinge forward a few centimetres. A loud noise can occur. A safety strip limits the maximum degree to which the door can be tilted.
If an over-pressure situation occurs, the appliance should be thoroughly checked by the installer.
69
Bellfi res
English
Installation instructions
4 DISMANTLING / ASSEMBLING OF THE GLASS
4.1 DERBY LARGE 3 FLOATING FRAME
Dismantling of the glass:
- Derby Large 3 - Use the hook supplied (see photo) for Floating Frame opening the frame and the glass.
- With the hook, pull the thin, metal spring strips on the top left and right from the studs on the frame.
Note ! : When loosening the frame and after it has been loosened, sup­ port it with your hand to prevent it falling forward !
70
Bellfi res
English
Installation instructions
stud (right)
- Detail of the stud (right). - Place paperboard on the chimney
breast, under the frame. This helps prevent damage.
- Dismantle the safety strip from the frame.
71
Bellfi res
English
Installation instructions
- Frame and glass are now removed from the appliance.
- Carefully tilt the frame and the window - Take hold of the frame and the glass forwards. clamped together and pull these
Note ! : Frame and window are upwards.
two separate parts !
Assembling of the glass:
The assembly of the glass takes place in reverse order.
Important:
• Check whether the frame is properly positioned underneath in the 2 holes of the front.
• Check whether the frame is placed in the middle of the front.
• Check whether the safety strip is securely fastened to the top of the frame (middle).
The glass (frame) must fi t tightly all round to the edge of the combustion chamber.
• Check that the spring strips, on the top, remain in their proper place.
72
Bellfi res
English
Installation instructions
4.2 DERBY LARGE 3 HIDDEN DOOR
Dismantling of the glass:
- Derby Large 3 Hidden Door.
- Use the hook to pull the frame at the top forward and hold the frame fi rmly.
- Use the hook supplied for opening the
frame (including glass).
73
Bellfi res
English
Installation instructions
- Dismantle the safety strip from the frame.
- With the hook, pull the thin, metal spring strips on the top left and right from the studs on the frame.
Note ! : When loosening the frame and after it has been loosened, support it with your hand to prevent it falling forward !
74
Bellfi res
English
Installation instructions
- Carefully tilt the frame and the glass forwards at the top. Prevent damage by laying paperboard on the chimney breast, under the frame. Pull the frame upwards and remove it from the appliance.
Assembling of the glass:
The assembly of the glass takes place in reverse order.
Important:
• Check whether the frame is properly positioned underneath in the 2 holes of the front.
• Check whether the frame is placed in the middle of the front.
• Check whether the safety strip is securely fastened to the top of the frame (middle).
The glass (frame) must fi t tightly all round to the edge of the combustion chamber.
• Check that the spring strips, on the top, remain in their proper place.
75
Bellfi res
English
Installation instructions
5 DIAGRAM ELECTRICITY AND GAS
Gas supply connection
Thermocouple
Ignition(piezo)cable
2 Wire cable
Motor­knob
Gas pipe “Rear burner”
GAS
REGULATOR
BLOCK
“red”
“black”
AUX
“red”
“yellow”
Pilot light
“Front burner”
“Rear burner”
Pilot light gas pipe
Thermocouple interruptor
8 Wire connecting cable
Gas pipe “Front burner”
Gas valve
“Rear burner”
AC power adapter 230 VAC (option)
Button “RESET”
Receiver (with battery compartment for 4 AA-batteries)
Connection cable (option) for external operating (i.a. Domotica systems)
Thermo-electrical cable TC
Thermo-electrical cable SW
Double burner: : Perforation pattern “Centre Fire” double burner.
+ : Perforation pattern “Line Fire” double burner.
76
Bellfi res
English
Installation instructions
6 DIMENSIONS
6.1 DERBY LARGE 3
6.1.1 DERBY LARGE 3 - Hidden Door
77
Bellfi res
English
Installation instructions
6.1.2 DERBY LARGE 3 - Floating Frame
78
Bellfi res
English
Installation instructions
6.2 DERBY LARGE 3 Fitted with the options: - Convection casing
- High adjustable feet
6.2.1 DERBY LARGE 3 - Hidden Door
* With the high adjustable feet (option), the appliance can be installed till 350 mm above the fl oor.
79
Bellfi res
English
Installation instructions
6.2.2 DERBY LARGE 3 - Floating Frame
* With the high adjustable feet (option), the appliance can be installed till 350 mm above the fl oor.
80
Bellfi res
English
Installation instructions
6.3 DERBY LARGE 3 Hidden Door Plus (+)
6.3.1 DERBY LARGE 3 - Hidden Door Plus (+) 7 cm Frame
* With the high adjustable feet (option), the appliance can be installed till 350 mm above the fl oor.
81
Bellfi res
English
Installation instructions
6.3.2 DERBY LARGE 3 - Hidden Door Plus (+) 10 cm Frame
* With the high adjustable feet (option), the appliance can be installed till 350 mm above the fl oor.
82
Bellfi res
English
Installation instructions
* With the high adjustable feet (option), the appliance can be installed till 350 mm above the fl oor.
6.3.3 DERBY LARGE 3
Hidden Door Plus (+) 10 cm Frame & Decorative Stone
Fitted with the options: -
Convection casing
- High adjustable feet
With this model the remote control receiver and the gas regulating block are located in the fi re and can be accessed via the metal cover, under the stone. The gas fi re does not have a separate operating unit !!
83
Bellfi res
English
Installation instructions
OPERATING UNIT
84
Bellfi res
English
Installation instructions
7 TECHNICAL DETAILS/REGULATIONS
National installation regulations:
Gas safety installation and use regulations 1998 plus all relevant
safety and building regulations concerning fi re installation
Document J: Combustion appliances and fuel storage systems
Model : DERBY LARGE 3 CF (Centre Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Product identifi cation no : 0063CM3684 : 0063CM3684 Type of appliance under CE-norm : C11 / C31 / C
31S
: C11 / C31 / C
31S
Category of appliance : I2H natural gas G20 : I
3B/P
butane/propane G30/G31
Nominal heat input : 11.5 kW : Butane (G30) : 10.0 kW (Gross calorifi c value) Propane (G31) : 8.5 kW
Nominal heat output : 8.8 kW : 6.6 - 7.7 kW Effi ciency class : 1 (85%) : 1 (85%) NOx-class : 5 : 5
Gas rate (max.) : 1.10 m
3
s
/hr. : Butane (G30) : 780 gr/hr.
Propane (G31) : 640 gr/hr.
Supply pressure : 20.0 mbar : Butane (G30) : 37.0 mbar Propane (G31) : 37.0 mbar
Burner pressure (max.) Hot : 13.0 mbar(*) : 29.0 mbar(*)
Burner pressure (max.) Cold : 12.3 mbar(**) : 29.0 mbar(**)
Burner pressure (min.) : 0.5 mbar(***) : 2.0 mbar(***)
Primary air inlet burner Rear : 1x Ø10.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Primary air inlet burner Front : 1x Ø10.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Gas regulator block (remote control) : Mertik GV 60 : Mertik GV 60 Main burner : Centre Fire 561x130 mm : Centre Fire 561x130 mm Main burner injector Rear : no 200 (= 1x Ø2.00 mm) : no 95 (= 1x Ø0.95 mm) Main burner injector Front : no 200 (= 1x Ø2.00 mm) : no 125 (= 1x Ø1.25 mm) Pilot light burner : SIT 0.145.019 : SIT 0.145.019 Pilot light burner injector : no 36 (SIT 0.977.091) : no 23 (SIT 0.977.150) Gas connection : 3/8” G / Ø12 mm : 3/8” G / Ø12 mm Concentric fl ue system connection : Ø100 mm - Ø150 mm or : Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm Ø130 mm - Ø200 mm
85
Bellfi res
English
Installation instructions
Model : DERBY LARGE 3 CF (Centre Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Batteries remote control
- Receiver : 4x 1.5V AA : 4x 1.5V AA
- Hand-transmitter : 1x 9V block : 1x 9V block
Weight:
- Basis model :
98 kg :
98 kg
- Including all options : 115 kg : 115 kg
(*) : Both burners at maximum. Appliance is on temperature. (**) : Both burners at maximum. Appliance is cold. (***) : Both burners at minimum.
Flue gas exhaust and combustion air supply: Roof-mounted outlet : Concentric fl ue system Ø100 mm - Ø150 mm. Rigid and/or fl exible. Horizontal wall outlet : Concentric fl ue system Ø130 mm - Ø200 mm. Rigid. With wall outlet, depending on the fl ue confi guration; Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm.
Heat changing surface: Entire front of the appliance.
86
Bellfi res
English
Installation instructions
Model : DERBY LARGE 3 LF (Line Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Product identifi cation no : 0063CM3684 : 0063CM3684 Type of appliance under CE-norm : C11 / C31 / C
31S
: C11 / C31 / C
31S
Category of appliance : I2H natural gas G20 : I
3B/P
butane/propane G30/G31
Nominal heat input : 12.0 kW : Butane (G30) : 11.5 kW (Gross calorifi c value) Propane (G31) : 9.5 kW
Nominal heat output : 9.2 kW : 7.3 - 8.8 kW Effi ciency class : 1 (85%) : 1 (85%) NOx-class : 5 : 5
Gas rate (max.) : 1.15 m
3
s
/hr. : Butane (G30) : 890 gr/hr.
Propane (G31) : 700 gr/hr.
Supply pressure : 20.0 mbar : Butane (G30) : 37.0 mbar Propane (G31) : 37.0 mbar
Burner pressure (max.) Hot : 12.0 mbar(*) : 29.0 mbar(*)
Burner pressure (max.) Cold : 11.3 mbar(**) : 29.0 mbar(**)
Burner pressure (min.) : 0.8 mbar(***) : 1.7 mbar(***)
Primary air inlet burner Rear : 1x Ø10.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Primary air inlet burner Front : 1x Ø10.0 mm : 1x Ø20.0
+corner
mm +
2x Ø5.0 mm
Gas regulator block (remote control) : Mertik GV 60 : Mertik GV 60 Main burner : Line Fire 561x130 mm : Line Fire 561x130 mm Main burner injector Rear : no 190 (= 1x Ø1.90 mm) : nr. 110 (= 1x Ø1.10 mm) Main burner injector Front : no 230 (= 1x Ø2.30 mm) : nr. 130 (= 1x Ø1.30 mm) Pilot light burner : SIT 0.145.019 : SIT 0.145.019 Pilot light burner injector : no 36 (SIT 0.977.091) : no 23 (SIT 0.977.150) Gas connection : 3/8” G / Ø12 mm : 3/8” G / Ø12 mm Concentric fl ue system connection : Ø100 mm - Ø150 mm or : Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm Ø130 mm - Ø200 mm
87
Bellfi res
English
Installation instructions
Model : DERBY LARGE 3 LF (Line Fire)
Gas : NATURAL GAS : BUTANE / PROPANE
Country :
GB; G
reat Britain
/IE;
Ireland :
GB; G
reat Britain
/IE;
Ireland
Batteries remote control
- Receiver : 4x 1.5V AA : 4x 1.5V AA
- Hand-transmitter : 1x 9V block : 1x 9V block
Weight:
- Basis model :
98 kg :
98 kg
- Including all options : 115 kg : 115 kg
(*) : Both burners at maximum. Appliance is on temperature. (**) : Both burners at maximum. Appliance is cold. (***) : Both burners at minimum.
Flue gas exhaust and combustion air supply: Roof-mounted outlet : Concentric fl ue system Ø100 mm - Ø150 mm. Rigid and/or fl exible. Horizontal wall outlet : Concentric fl ue system Ø130 mm - Ø200 mm. Rigid. With wall outlet, depending on the fl ue confi guration; Ø100 mm - Ø150 mm or Ø130 mm - Ø200 mm.
Heat changing surface: Entire front of the appliance.
88
Bellfi res
English
Installation instructions
8 REPLACEMENT PARTS LIST
When requesting service or ordering replacement parts, please quote the model type and serial number. All parts listed in this manual may be ordered from a Bellfi res dealer.
No Article no Description
1 335118 Main burner “Centre Fire” 561 x 130 mm Natural gas G20 / Butane/Propane G30/G31 G20: 1x Ø10.0 mm front + 1x Ø10.0 mm rear G30/G31: 1x Ø20.0
+corner
mm + 2x Ø5.0 mm front and
1x Ø20.0
+corner
mm + 2x Ø5.0 mm rear 2 335114 Burner mat L = 561 mm “Centre Fire” 3 334875 Burner injector Natural gas; Front: no 200 (1x Ø2.00 mm) 4 334875 Burner injector Natural gas; Rear: no 200 (1x Ø2.00 mm) 5 335122 Burner injector Butane/Propane; Front: no 125 (1x Ø1.25 mm) 6 335120 Burner injector Butane/Propane; Rear: no 95 (1x Ø0.95 mm)
7 335119 Main burner “Line Fire” 561 x 130 mm Natural gas G20 / Butane/Propane G30/G31 G20: 1x Ø10.0 mm front + 1x Ø10.0 mm rear G30/G31: 1x Ø20.0
+corner
mm + 2x Ø5.0 mm front and 1x Ø20.0
+corner
mm + 2x Ø5.0 mm rear 8 335115 Burner mat L = 561 mm “Line Fire” 9 334989 Burner injector Natural gas; Front: no 230 (1x Ø2.30 mm) 10 334988 Burner injector Natural gas; Rear: nr. 190 (1x Ø1.90 mm) 11 301928 Burner injector Butane/Propane; Front: nr. 130 (1x Ø1.30 mm) 12 334992 Burner injector Butane/Propane; Rear: nr. 110 (1x Ø1.10 mm)
13 333597 Gas regulator block; GV 60 (M10 Thermocouple connection) 14 302122 3/8” male x Ø12 Compression fi tting 15 302084 Nut Ø8 mm for burner supply GV 60 for “front burner” 16 302089 Olive Ø8 mm for burner supply GV 60 for “front burner” 17 333607 Gas valve “rear burner” 18 333608 Adapter 3/8”bsp x 3/8”+ O-ring 19 333610 Nut Ø8 mm for gas valve “rear burner” 20 333611 Olive Ø8 mm for gas valve “rear burner” 21 302086 Shear-off nut & olive Ø4 mm GV 60 22 333601 Cable (sw): Receiver - Thermocouple interrupter, L = 500 mm 23 333602 Cable (tc): Receiver - Thermocouple interrupter, L = 500 mm 24 333598
Hand-held transmitter: Display screen: Temperature and two programmes 25 333599 Cover battery compartment hand-held transmitter - with imprint: Operating double burner 26 333600 Receiver GV 60 - EU 27 302068 8 Wire connecting cable Gas regulator block - Receiver, L = 500 mm 28 302421 Piezo ignition cable, 2x 2.8 x 0.8 mm, L = 1500 mm
89
Bellfi res
English
Installation instructions
No Article no Description
29
321926 Thermocouple M10 - 1500 mm
30 333604 Thermocouple interrupter M10
31 310908 Pilot light set outer casing, Double fl ame 32 310909 Packing pilot light set outer casing 33 310910 Pilot light injector; Natural gas; no 36 34 310912 Pilot light injector; Butane/Propane; no 23 35 310907 Piezo electrode for pilot light, 2.8 x 0.5 mm 36 302062 Nut piezo electrode 37 319842 Nut thermocouple 38 332552 Pilot light olive; Ø4 mm, steel 39 332553 Pilot light nut; Ø4 mm, steel 40 322552 Pilot light pipe; Ø4 mm, L = 1500 mm, Flexible, Stainless steel 41 325750 Burner pipe; Ø8 mm, L = 1500 mm, Flexible, Stainless steel - 10 kW+, “front burner” 42 325750 Burner pipe; Ø8 mm, L = 1500 mm, Flexible, Stainless steel - 10 kW+, “rear burner”
43 326055 Nut; Ø8 mm, compression elbow main burner 44 326054 Olive; Ø8 mm, compression elbow main burner
45 329701 Glass Derby Large 3 Hidden Door (796 x 642 x 4 mm) 46 329700 Glass Derby Large 3 Floating Frame (788 x 648.5 x 4 mm)
47 301669 Tube ceramic glue
48 301593 Black fi bre glass tape 15 x 3 mm, adhesive 49 319664 Black fi bre glass tape 30 x 2 mm, adhesive 50 311006 Black fi bre glass tape 20 x 2 mm, adhesive 51 301617 Black fi bre glass cord Ø10 mm
90
Bellfi res
English
Installation instructions
Logs - Chips of wood - Embers - Vermiculite granules - Marble pebbles
Appliance Log set
Marble pebbles
Marble pebbles
set (white) set (grey)
Set Log no
Art. no: F 328349
Derby Large 3
Chips of
Embers with Vermiculite no 4
wood set
Glow-effect black
Anthracite fi ltered
1
331357
1x
2
331358
1x
3
331359
-
4
331360
1x
6
331362
1x
7
331363
1x
8
331364
-
5
331361
1x
3 pieces
xxxxxx
1x
Bag: 125 gr.
301863
3x
Bag: 50 gr.
332583
1x
Bag: 2.5 kg.
310937
2x
Bag: 2.5 kg.
325758
2x
91
Bellfi res
English
Installation instructions
9 DISPOSING OF PACKAGING AND APPLIANCE
The appliance comes in recyclable packaging. This can include:
• Cardboard
• Wood
• Plastic
• Paper
Such materials must be disposed of responsibly, in line with local regulations.
Batteries should be disposed of as chemical waste. Batteries must be disposed of responsibly, in line with local regulations.
The authorities or fi tter can provide you with information on responsible disposal of obsolete appliances.