Rack Mount UPS
Input
Output
Protection &
Filtering
Battery
Alarm
Environment
Physical
Front Panel
Model
Capacity 1100 1500 2300 3200
Max Load 660 900 1380 1920
Voltage Range
Frequency
Voltage Regulation (AVR)
AVR Detection Tolerance
AVR Output Voltage Range
AVR Response Time
Voltage (On battery)
Frequency (On battery)
Waveform
Spike Protection
EMI/RFI Filter
Overload Protection
Unit Input
Telecommunication
Short Circuit in AC Mode or
Battery Mode
Voltage / Amps 12V/4.5Ah (4 pcs.) 12V/7.2 Ah (4 pcs.) 12V/12Ah (4 pcs.) 12V/12Ah (4 pcs.)
Battery Protection 40A/32V Fuse (2 Pcs.) 40A/32V Fuse (1 Pcs.)
Type
Typical Recharge Time
Protection
Battery Run Time
On Battery
Battery Low
Overload
Fault
Battery Test
Communication Port
Ambient Operation
Audible Noise
Weight (kgs/lbs) 23/50 25/55.11 30/66.13 41.5/91.48
H x W x D (cm) 13.2 x 56.5 x 57
H x W x D (in.) 5.19 x 17 x 16
Compliance
AC Power On (1 Beep)
Power Off (1 Beep)
Cold Start (Turns DC Power
On)
F6C110-RKM-2U F6C150-RKM-2U F6C230-RKM-2U F6C320-RKM-3U
80 ~ 150 Vac
Auto Sensing 50/60Hz ± 6Hz
AVR Boost Increases 17% of Voltage if input is 91 ~ 145 Vac
AVR Buck Reduces 13% of Voltage if input is 132 ~ 145 Vac.
± 6Vac
On-line operation for input between 91 ~ 145 Vac. Output will be 101 ~ 136 Vac.
<200ms
110/120/127 DIP Switch Selectable
Auto Sensing 50/60Hz ± 3Hz
True Sine Wave
500 Joules
FCC Part 15 Class B Certified
UPS Low to high voltage switch to battery: 91 ~ 145 ± 3 Vac
Electronic overload and short circuit protector
1 In, 1 Out (RJ45/RJ11) jacks
UPS shuts down
16A/250V
Sealed, maintenance free lead acid
< 8 Hours
Automatic self discharge protection, replace battery indicator LED
Solid Red LED and Intermittent Audible Alarm
Flashing Yellow LED and Intermittent Audible Alarm
Flashing Red LED and Intermittent Audible Alarm
Solid Red LED Light
Flashing Yellow LED and Intermittent Audible Alarm
RS232 Serial Ports
0 ~ 95% Relative Humidity (Non-condensing)
0 ~ 40º C Operating Temperature
< 45 dBA at 1 meter
8.8 x 56.5 x 57
3.46 x 17 x 16
UL 1778, cUL, UL 497A, UL 497B, Meets UL 1449, CSA22.1, CE EMC, CE Safety, TUV, EMI (FCC Class
B), EN55022, EN50081-1, EN50082-1, EN50091-2, IEC 801-2 Level 4, IEC 801-4 Level 3; IEC 801-5 Level
3, FCC Part 68,
Press button and hold longer than 1 sec.
Press button and hold longer than 1 sec.
Press button and hold longer than 1 sec.
Battery Test (On AC Mode)
Buzzer Silence
Press button and hold less than 0.5 sec.
Press button and hold less than 0.5 sec.