Brief description
Applications
Technical data sheet ZEV
The ZEV adjustment tool enables the operating volumetric flow settings in VAV and CAV systems with conventional control to be adjusted on site. It is not suitable for systems with an MP
bus connection.
The ZEV is connected to the VAV-Compact using the PP (peer-to-peer) interface of the VAV
controller.
As well as using the service socket on the VAV-Compact, it is also possible to connect the ZEV
to easily accessible connection points such as the service plug on the CR24-B room temperature controller or on the terminals in the control cabinet. This means there is no need for direct
access to the VAV controller.
The 24 V supply to the ZEV comes via the service socket of the VAV, CR24 controller or from a
local 24 V supply, e.g. connection terminals of the VAV controller.
The VAV-Compact devices do not have any operating elements such as switches or setpoint
potentiometers. If necessary, the operating parameters are set using the ZEV or another adjustment tool, e.g. the PC-Tool with additional functions such as trend, etc.
In the VRD2(-L), it is possible to set the mode appropriately for the selected 0…10 V or 2...10 V
room temperature controller.
1)
Mode setting 0 ... 10 V / 2 ... 10 V
2)
See mode setting
3)
Devices manufactured before 8/2006 need a modified scale sticker
Nominal voltageAC 24 V, 50/60 Hz, DC 24 V
Power supply rangeAC 19.2 ... 28.8 V, DC 21.6 ... 26.4 V
Power consumption1 W
PP communicationDC 1.0/12.5 V max. DC 15 V
bidirectional 1200 baud
ConnectionScrew terminals for 2 x 1.5 mm2
Connection cableseparate obtainable, see «Accessories» on page 4
Protection classIII Safety extra-low voltage
Degree of protectionIP42
EMCCE according to 89/336/EEC
Ambient temperature range0 ... +50 °C
Non-operating temperature range-20 ... +80 °C
Moisture testAccording to EN 60730-1
DimensionsSee «Dimensions» on page 3
WeightApprox. 500 g
www.belimo.comT4-ZEV • en • v1.3 • 09.2007 • Subject to changes1 / 4
Page 2
ZEV
VAV adjustment tool
2 / 4T4-ZEV • en • v1.3 • 09.2007 • Subject to changeswww.belimo.com
~
T
T
5 5 1
U/PP
AC 24 V
T
~
1 2 3 4
– + DC 24 V
T
PP
1
2
3
5
Y
U
~
T
51 2
AC 24 V
T
~
– + DC 24 V
51 2
1
2
3
5
Y
U
~
T
51 2
AC 24 V
T
~
– + DC 24 V
!
!
Products no longer available
Safety notes
Electrical installation
Note
Connection via safety transformer!
• The device is not allowed to be used outside the specified field of application, especially in
aircraft or in any other airborne means of transport.
• Only for Belimo VAV devices with 24 V safety extra-low voltage.
Wiring diagrams
The ZEV is connected to connections 1 and 5 of the corresponding controller. The ZEV supply (AC/DC 24 V) comes directly from
connection 2.
When the system is being wired up, it is advantageous for the
actual value signal U5 (terminal 5) of the VAV controller to be fed
back to the room temperature controller or into the control cabinet.
Communication is via a peer-to-peer connection (PP).
Connection options
Note
• When an operating device (e.g. ZEV) is connected via the U/-PP connection (terminal 5) of
the VAV controller, the voltage signal of output
U5 does not correspond to the current actual
value signal.
When using the service socket of an LMV-D2MP, NMV-D2-MP or SMV-D2-MP, the U5 signal
is not impaired.
• The maximum communication level is DC 15 V.
To prevent damage to third-party equipment, it
may have to be disconnected from terminal 5
under certain circumstances – for the duration of
communication.
Connection via service socket (Cable see «Accessories» on page 4)
ZEV devices manufactured before 8/2006 need a
modified scale sticker. Please contact your Belimo
branch.
OperationQueryProgramming
VAV adjustment tool
AB
CD
Operating volumetric flow
A
Operating volumetric flow
B
Mode setting for reference and volumetric flow actual value signal
C
Functional check of control loop nominal/actual value comparison
D
E
Reset
min.
-/
setting to original OEM values
max.
min
max
E
for VRD2(-L), NMV-D2,
LMV-D2M, NMV-D2M
for LMV-D2-MP, NMV-D2-MP,
SMV-D2-MP
Leg
end
Yellow LED lights up
LED dark
Turn the rotary button slowly until
the check LED lights up.
– Flashing LED:
Value in VAV controller is lower
– LED dark:
Value in VAV controller is higher
Turn the rotary button slowly until
the check LED flashes.
LED Vmin
LED Vmax
3 - 4s
– The following flashing sequence indica-
tes that the value in the VAV controller is
greater.
LED Vmin
LED Vmax
3 - 4s
Set the value at the corresponding rotary button:
Press and hold the «Set» button for 2 seconds. The
write procedure is acknowledge by the LED lighting
up (see application table on page 4).
Set the value with the corresponding rotary button:
Press the «Set» button repeatedly until the following
flashing sequence indicates that the value has been
accepted.
LED Vmin
LED Vmax
3 - 4s
– LED dark:
Value in VAV controller is higher.
Functional checkVAV control loop
www.belimo.comT4-ZEV • en • v1.3 • 09.2007 • Subject to changes3 / 4
Green LED lights up
Green LED flashes
– Dark
– Bright
→ Actual value same as nominal value
→ Actual value not same as nominal value
→ Volumetric flow not reached
→ Volumetric flow too high
Page 4
ZEV
4.5
130
140
153
45
43
88
5
54
Products no longer available
Dimensions [mm]
Dimensional diagrams
Application with different VAV versions
VAV adjustment tool
VersionLMV-D2-MP
VRD2
VRD2-L
Note
1)
Technical data
Nominal voltageAC 24 V, 50/60 Hz
Connection of operating devices
setting
min.
setting
max.
Mode
Feedback LED«Mode» LED lights upThe set mode is not displayed on the LED but the
Reset operating volumetric flow setting
Range
Range30 ... 100% of
RangeConstant
min./max.
Current devicePhased out by NMV-
Terminals
«Mode» LED lights up
No functionReset to (OEM) factory setting
No functionReset to (OEM) factory setting
NMV-D2LMV-D2M
NMV-D2M
Phased out by NMV-D2-
D2M in 2000
MP in 2006
LMV-D2-MP
NMV-D2-MP
NMV-D2-MP
SMV-D2-MP
SMV-D2-MP
Current device
TerminalsTerminals, socketTerminals, socket
0 2) ... 100% of
Constant4) / 2 ... 10 V / 0 ... 10 V
02) ... 100% of
max
30 ... 100% of
4)
/ 2 ... 10 V / 0 ... 10 V
nom
nom
The set mode is not displayed on the LED but the
write command
write command
5)
5)
is performed correctly
is performed correctly
to original factory setting
Functional check
Control loop
w = xGreen LED lights up
w ≠ xGreen LED flashes
Green LED lights up
Green LED flashes
5)
nom
3)
Communication
Normal LED functionData transmission
Normal LED functionData transmission is
is displayed by brief
displayed by brief flash-
flashes of the three
es of the three LEDs
5)
LEDs
1)
See product information for VAV-Compact and VAV-Universal
2)
Lowest setting depends on the creep flow suppression. See VAV product information documents or refer to data from the VAV manufacturer.
3)
ZEV devices (manufactured before 8/2006) need a modified scale sticker. Please contact your Belimo branch.
4)
The "Constant" option is irrelevant for the current VRD2, L/NMV-D2M and L/N/SMV-D2-MP versions.
5)
If the LED constantly displays low-power "dark" flashes (> 3 min), this means the actuator is most probably at a limit position.
Accessories
Type Use
Cable
4 / 4T4-ZEV • en • v1.3 • 09.2007 • Subject to changeswww.belimo.com