NMX24-3-F-T Technical Data Sheet
On/Off, Floating Point, Non-Spring Return, 24 V
Torque min. 90 in-lb, for control of damper surfaces up to 22 sq. ft.
Technical Data
Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Power consumption in operation 2 W
Power consumption in rest
position
Transformer sizing 4 VA (class 2 power source)
Electrical Connection Screw terminal (for 26 to 14 GA wire)
Overload Protection electronic throughout 0...95° rotation
Input Impedance 600 Ω
Angle of rotation Max. 95°, adjustable with mechanical stop
Torque motor 90 in-lb [10 Nm]
Direction of motion motor selectable with switch
Position indication Mechanically, 30...65 mm stroke
Manual override external push button
Running Time (Motor) 95 s, constant, independent of load
Ambient humidity max. 95% r.H., non-condensing
Ambient temperature -22...122°F [-30...50°C]
Storage temperature -40...176°F [-40...80°C]
Degree of Protection IP20, NEMA 1, UL Enclosure Type 1
Housing material UL94-5VA
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA
Noise level, motor 45 dB(A)
Servicing maintenance-free
Quality Standard ISO 9001
Weight 1.2 lb [0.53 kg]
0.2 W
E60730-1:02, CE acc. to 2014/30/EU and
2014/35/EU
68873
Date created, 02/10/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

NMX24-3-F-T Technical Data Sheet
On/Off, Floating Point, Non-Spring Return, 24 V
Wiring Diagrams
Actuators with appliance cables are numbered.
A
Provide overload protection and disconnect as required.
Actuators may also be powered by 24 VDC.
Actuators Hot wire must be connected to the control board common.
Only connect common to neg. (-) leg of control circuits. Terminal
models (-T) have no-feedback.
Actuators may be connected in parallel if not mechanically linked. Power
consumption and input impedance must be observed.
Actuators are provided with a numbered screw terminal strip instead of
16
a cable.
24 VAC Transformer
olts
On/Off
olts
Floating Point
olts
A
1 3
11 16
(1) Common
(2) + Hot
(3) + Input
A
1 3
11 16
(1) Common
(2) + Hot
(3) + Input
A
ComHot
1 3 11
Blk (1) Common
Floating Point - Triac Source
olts
ComHot
Floating Point - Triac Sink
Red (2) + Hot
Wht (3) Y Input
A
1
6
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
11
Date created, 02/10/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.