Belimo NM24A-MOD Technical Data Sheet

Page 1
Communicative damper actuator for adjusting dampers in technical building installations
• Torque motor 10 Nm
• Nominal voltage AC/DC 24 V
• Control modulating, communicative, hybrid mode
• Communication via BACnet MS/TP, Modbus RTU, Belimo-MP-Bus or conventional control
Technical data
Electrical data Nominal voltage AC/DC 24 V
Functional data
Safety
Technical data sheet NM24A-MOD
Nominal voltage frequency 50/60 Hz Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V Power consumption in operation 3.5 W Power consumption in rest position 1.4 W Power consumption for wire sizing 6 VA Connection supply / control Cable 1 m, 6 x 0.75 mm²
Nominal torque Min. 10 Nm Torque variable 25%, 50%, 75% reduced Communicative control BACnet MS/TP
Modbus RTU (ex works)
MP-Bus Operating range Y DC 2...10 V Operating range Y variable DC 0.5...10 V Position feedback U DC 2...10 V Position feedback U note Max. 1 mA Position feedback U variable Start point DC 0.5...8 V
End point DC 2...10 V Position accuracy ±5% Direction of motion motor selectable with switch 0 / 1 Direction of motion note Y = 0%: At switch position 0 for ccw rotation or
1 for cw rotation, respectively Direction of motion variable electronically reversible Manual override with push-button, can be locked Angle of rotation Max. 95° Angle of rotation note can be limited on both sides with adjustable
mechanical end stops Running time motor 150 s / 90° Running time motor variable 43...173 s Adaption setting range manual Adaption setting range variable No action
Adaption when switched on
Adaption after pushing the gear disengagement
button Override control, controllable via bus communication
Override control variable MAX = (MIN + 32%)...100%
Sound power level Motor 35 dB(A) Damper spindle Universal spindle clamp 8...26.7 mm Position indication Mechanically, pluggable
Protection class IEC/EN III Safety Extra-Low Voltage (SELV) Protection class UL UL Class 2 Supply Degree of protection IEC/EN IP54 Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2 EMC CE according to 2014/30/EU Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position) = 50%
MIN = 0%...(MAX – 32%)
ZS = MIN...MAX
www.belimo.com
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
1
Page 2
!
NM24A-MOD
Technical data
Safety notes
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
Safety Certification UL cULus according to UL60730-1A, UL60730-2-
14 and CAN/CSA E60730-1:02 Mode of operation Type 1 Rated impulse voltage supply / control 0.8 kV Control pollution degree 3 Ambient temperature -30...50°C Non-operating temperature -40...80°C Ambient humidity Max. 95% r.h., non-condensing Maintenance Maintenance-free
Weight
Weight 0.92 kg
• The device must not be used outside the specified field of application, especially not
in aircraft or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea)water, snow, ice, insolation
or aggressive gases interfere directly with the actuator and that is ensured that the ambient conditions remain at any time within the thresholds according to the data sheet.
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The device may only be opened at the manufacturer’s site. It does not contain any
parts that can be replaced or repaired by the user.
• Cables must not be removed from the device.
• To calculate the torque required, the specifications supplied by the damper
manufacturers concerning the cross-section, the design, the installation site and the ventilation conditions must be observed.
• The device contains electrical and electronic components and must not be disposed
of as household refuse. All locally valid regulations and requirements must be observed.
Product features
Mode of operation
Converter for sensors
Parameterisable actuators
Combination analogue - communicative
(hybrid mode)
Simple direct mounting
Manual override
Adjustable angle of rotation
High functional reliability
The actuator is fitted with an integrated interface for BACnet MS/TP, Modbus RTU and MP-Bus. It receives the digital positioning signal from the control system and returns the current status.
Connection option for a sensor (passive, active or with switching contact). In this way, the analogue sensor signal can be easily digitised and transferred to the bus systems BACnet, Modbus or MP-Bus.
The factory settings cover the most common applications. Single parameters can be modified with the Belimo Service Tools MFT-P or ZTH EU. The communication parameters of the bus systems (address, baud rate etc.) are set with the ZTH EU. Pressing the “Address” button on the actuator while connecting the supply voltage, resets the communication parameters to the factory setting. Quick addressing: The BACnet and Modbus address can alternatively be set using the buttons on the actuator and selecting 1 to 16. The value selected is added to the «Basic address» parameter and results in the effective BACnet and Modbus address.
With conventional control by means of an analogue positioning signal, BACnet or Modbus can be used for the communicative position feedback
Simple direct mounting on the damper spindle with an universal spindle clamp, supplied with an anti-rotation device to prevent the actuator from rotating.
Manual override with push-button possible (the gear is disengaged for as long as the button is pressed or remains locked).
Adjustable angle of rotation with mechanical end stops.
The actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached.
2
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
www.belimo.com
Page 3
NM24A-MOD
Product features
Home position
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out a synchronisation. The synchronisation is in the home position (0%). The actuator then moves into the position defined by the positioning signal.
Adaption and synchronisation
Accessories
Electrical accessories
Mechanical accessories
0
1
Y = 0%
Y = 0%
ccw
cw
An adaption can be triggered manually by pressing the “Adaption” button or with the PC-Tool. Both mechanical end stops are detected during the adaption (entire setting range). Automatic synchronisation after pressing the gearbox disengagement button is configured. The synchronisation is in the home position (0%). The actuator then moves into the position defined by the positioning signal. A range of settings can be adapted using the PC-Tool (see MFT-P documentation)
Description Type
Auxiliary switch, add-on, 1 x SPDT S1A
Auxiliary switch, add-on, 2 x SPDT S2A Feedback potentiometer 140 Ohm, add-on P140A Feedback potentiometer 140 Ohm, add-on, grey P140A GR Feedback potentiometer 200 Ohm, add-on P200A Feedback potentiometer 500 Ohm, add-on P500A Feedback potentiometer 500 Ohm, add-on, grey P500A GR Feedback potentiometer 1 kOhm, add-on P1000A Feedback potentiometer 1 kOhm, add-on, grey P1000A GR Feedback potentiometer 2.8 kOhm, add-on P2800A Feedback potentiometer 2.8 kOhm, add-on, grey P2800A GR Feedback potentiometer 5 kOhm, add-on P5000A Feedback potentiometer 5 kOhm, add-on, grey P5000A GR Feedback potentiometer 10 kOhm, add-on P10000A Feedback potentiometer 10 kOhm, add-on, grey P10000A GR Connecting cable 5 m, A+B: RJ12 6/6, To ZTH EU ZK1-GEN Connection cable 5 m, A: RJ11 6/4, B: Free wire end, To ZTH EU ZK2-GEN
Description Type
Actuator arm, for one-sided spindle clamp K-ENSA AH-25
Shaft extension 240 mm, for damper spindles Ø 8...25 mm or Ø
10...25 mm
Angled ball joint with M8, suitable for damper crank arm KH8 KG8 Straight ball joint with M8, suitable for damper crank arm KH8 KG10A Damper crank arm, for damper spindles KH8 Spindle clamp, one side for NM..A K-ENMA Spindle clamp, one side for NM..A, SM..A K-ENSA Spindle clamp, reversible for NM..A and LMQ.. K-NA Form fit insert 8x8 mm, for NM..A ZF8-NMA Form fit insert 10x10 mm, for NM..A / SM..A ZF10-NSA Form fit insert 12x12 mm, for NM..A / SM..A ZF12-NSA Form fit insert 15x15 mm, for NM..A / SM..A ZF15-NSA Form fit insert 16x16 mm, for NM..A / SM..A ZF16-NSA Mounting kit for linkage operation, NM..A for flat installation ZG-NMA Anti-rotation mechanism 180 mm Z-ARS180 Base plate extension from NM..A to NM.. Z-NMA Position indication for LM..A, NM..A, SM..A, GM..A Z-PI
AV8-25
www.belimo.com
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
3
Page 4
GND
NM24A-MOD
Accessories
Service Tools
Electrical installation
!
Wiring diagrams
BACnet MS/TP / Modbus RTU
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
Description Type
Service tool for parametrisable and communicative Belimo actuators / VAV controller and HVAC performance devices
Belimo PC-Tool, software for adjustments and diagnostics MFT-P Adapter to Service Tool ZTH MFT-C
Notes • Connection via safety isolating transformer.
• The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance with applicable RS485 regulations.
• Modbus / BACnet: Supply and communication are not galvanically isolated. Connect earth signal of the devices with one another.
ZTH EU
D – D
+
3
T
+
AC/DC 24 V
~
12
5
67
D
+
D
T
AC/DC 24 V
12
~
+
Connection with passive sensor, e.g. Pt1000, Ni1000, NTC
T
~
+
D– D+
12
3
5
MFT
67
D
D
Ni1000
–28...+98°C
PT1000
NTC
–35...+155°C
–10...+160°C
+
850...1600 Ω
850...1600 Ω
1)
200 Ω...60 kΩ
2)
2)
2)
Connection with active sensor, e.g. 0...10 V @ 0...50°C
T
~
+
D-
D+
3
5
67
D
D
1) depending on type
2) Resolution 1 Ohm
Cable colours: 1= black 2 = red 3 = white 5 = orange 6 = pink 7 = grey
+
Signal assignement Modbus: C1 = D– = A C2 = D+ = B
3
12
4
5
MFT
67
D
+
D -
Possible voltage range:
0...32 V (resolution 30 mV)
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
www.belimo.com
Page 5
GND
V
~
NM24A-MOD
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
Electrical installation
Connection with switching contact, e.g. Δp monitor
T
~
+
D­D+
∆p
3
12
5
MFT
67
D
+
D -
Modbus RTU / BACnet MS/TP with analog setpoint (hybrid mode)
D+ D-
AC/DC 24 V
3
12
T
~
+
5
67
D+
D-
Y U
DC (0)2…10 DC 2…10 V
Requirements for switching contact: The switching contact must be able to accurately switch a current of 16 mA @ 24 V.
Operation on the MP-Bus
T
+
Y U
12356D-7
MFT
D+
Sensor MP
www.belimo.com
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
5
Page 6
NM24A-MOD
Operating controls and indicators
0
1
1
Adaption
Address
4
5
2
Power
3
Status
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
1
Direction of rotation switch
Switch over: Direction of rotation changes
2
Push-button and LED display green
Off: On: Flashing:
Press button:
3
Push-button and LED display yellow
Off: On:
Flickering: Press button:
4
Gear disengagement button
Press button: Release button:
5
Service plug
For connecting parameterisation and service tools
Check power supply connection
2
Off and 3 On
No power supply or malfuntion In operation In address mode: Pulses according to set address (1...16) When starting: Reset to factory setting (Communication) In standard mode: Triggers angle of rotation adaptation In address mode: Confi rmation of set address (1...16)
Standard mode Adaptation or synchronising process active or actuator in address mode (LED display green fl ashing) BACnet / Modbus communication active In operation (>3 s): Switch address mode on and off In address mode: Address setting by pressing several times When starting (>5 s): Reset to factory setting (Communication)
Gear disengages, motor stops, manual override possible Gear engages, synchronisation starts, followed by standard mode
Possiple wiring error in power supply
Service
Quick adressing
Service Tools connection
1. Press the “Address” button until the green “Power” LED is no longer illuminated. LED flashes in accordance with the previously set address.
2. Set the address by pressing the “Address” button the corresponding number of times (1-16).
3. The green LED flashes in accordance with address that has been entered (1-16). If the address is not correct, then this can be reset in accordance with Step 2.
4. Confirm the address setting by pressing the green “Adaption” button. If no confirmation occurs for 60 seconds, then the address procedure is ended. Any address change that has already been started will be discarded. The resulting BACnet MS/TP and Modbus RTU address is made up of the set basic address plus the short address (e.g. 100+7=107).
The actuator can be parameterised by ZTH EU via the service socket. For an extended parameterisation the PC tool can be connected.
T
~
AC 24 V
+
DC 24 V
MP USB
ZTH EU
esc OK
12
i
3
5
67
MFT
D
+
D
USB
BELIMO PC-Tool
6
NM24A-MOD • en-gb • 2018-04-26 • subject to changes
www.belimo.com
Page 7
52
4112125
80
NM24A-MOD
Dimensions [mm]
Spindle length
Damper actuator, modulating communicative hybrid mode, AC/DC 24 V, 10 Nm,
Dimensional drawings
L
Min. 40
Min. 20
8...26.7 ≥8 ≤26.7
*
8...20 ≥8 ≤20
*Option: Spindle clamp mounted below (accessories K-NA needed)
Further documentation
62
124
Tool connections
• Description Protocol Implementation Conformance Statement PICS
• Description Modbus register
• Overview MP Cooperation Partners
• MP Glossary
• Introduction to MP-Bus Technology
www.belimo.com
NM24A-MOD • en-gb • 2018-04-26 • subject to changes