User Manual Installation
Industrial Ethernet Rail Switch SPIDER Standard Line PoE
Installation SPIDER-SL PoE Technical support
Release 01 05/2019 https://hirschmann-support.belden.com
Page 2
The naming of copyrighted trademarks in this manual, even when not specially indicated, should not be taken to mean that these names may be considered as free in the sense of the trademark and tradename protection law and hence that they may be freely used by anyone.
© 2019 Hirschmann Automation and Control GmbH Manuals and software are protected by copyright. All rights reserved. The copying,
reproduction, translation, conversion into any electronic medium or machine scannable form is not permitted, either in whole or in part. An exception is the preparation of a backup copy of the software for your own use.
The performance features described here are binding only if they have been expressly agreed when the contract was made. This document was produced by Hirschmann Automation and Control GmbH according to the best of the company's knowledge. Hirschmann reserves the right to change the contents of this document without prior notice. Hirschmann can give no guarantee in respect of the correctness or accuracy of the information in this document.
Hirschmann can accept no responsibility for damages, resulting from the use of the network components or the associated operating software. In addition, we refer to the conditions of use specified in the license contract. Hirschmann
You can get the latest version of this manual on the Internet at the Hirschmann product site
(www.hirschmann.com).
Hirschmann Automation and Control GmbH Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany
Installation SPIDER-SL PoE
2 Release 01 05/2019
Page 3
Contents
Safety instructions................................................................................ 4
About this Manual ................................................................................. 8
Legend ................................................................................................... 8
1 Description ....................................................................................... 9
1.1 General device description ........................................................ 9
1.2 Device name and product code ................................................. 9
1.3 Device view ............................................................................. 11
1.3.1 Front view ........................................................................ 11
1.4 Power supply ........................................................................... 13
1.5 Ethernet ports .......................................................................... 13
1.5.1 10/100/1000 Mbit/s twisted pair port ................................ 13
1.5.2 10/100/1000 Mbit/s PoE port ........................................... 13
1.5.3 10/100 Mbit/s twisted pair port ......................................... 14
1.5.4 10/100 Mbit/s PoE port .................................................... 14
1.5.5 100/1000 Mbit/s F/O port ................................................. 14
1.5.6 100 Mbit/s F/O port .......................................................... 14
1.6 Pin assignments ...................................................................... 15
1.7 Display elements ..................................................................... 16
1.7.1 Power supply state .......................................................... 16
1.7.2 Port state ......................................................................... 17
1.7.3 PoE state ......................................................................... 17
2 Installation ..................................................................................... 18
2.1 Checking the package contents ............................................... 18
2.2 Mounting the device ................................................................ 19
2.2.1 Installing the device onto the DIN rail ............................... 19
2.2.2 Grounding the device....................................................... 19
2.3 Installing an SFP transceiver (optional) ................................... 20
2.4 Adjust DIP switch settings ....................................................... 21
2.5 Wiring the terminal block for the supply voltage and the grounding
................................................................................................ 22
2.6 Operating the device ............................................................... 23
2.7 Connecting data cables ........................................................... 23
3 Monitoring the ambient air temperature ...................................... 24
4 Maintenance and service .............................................................. 25
5 Disassembly .................................................................................. 26
5.1 Removing an SFP transceiver (optional) ................................. 26
5.2 Removing the device ............................................................... 26
6 Technical data ................................................................................ 27
A. Further Support ............................................................................. 33
Installation SPIDER-SL PoE
Release 01 05/2019 3
Page 4
Safety instructions
General safety instructions
You operate this device with electricity. Improper usage of the device entails the risk of physical injury or significant property damage. The proper and safe operation of this device depends on proper handling during transportation, proper storage and installation, and careful operation and maintenance procedures. Before connecting any cable, read this document, and the safety
instructions and warnings.
Operate the device with undamaged components exclusively. The device is free of any service components. In case of a
damaged or malfunctioning the device, turn off the supply voltage and return the device to Hirschmann for inspection.
Certified usage
Use the product only for the application cases described in the
Hirschmann product information, including this manual.
Operate the product only according to the technical specifications.
See “Technical data” on page 27
Connect to the product only components suitable for the
requirements of the specific application case.
Installation site requirements
Install the device in a fire enclosure according to EN 60950-1.
Device casing
Only technicians authorized by the manufacturer are permitted to open the casing. Never insert pointed objects (narrow screwdrivers, wires, etc.) into
the device or into the connection terminals for electric conductors. Do not touch the connection terminals.
Install the device in the vertical position.
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as
practical knowledge and experience make up their qualifications. This is the prerequisite for grounding and labeling circuits, devices, and systems in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their
Installation SPIDER-SL PoE
4 Release 01 05/2019
Page 5
work.
General requirements for connecting electrical wires
The following requirements apply without restrictions:
The electrical wires are voltage-free. The cables used are permitted for the temperature range of the application case. This device must be operated with a separate power supply or DC/DC converter with
galvanically separated SELV/PELV output voltages.
Requirements for connecting the supply voltage
The following requirements apply alternatively:
Alternative 1
The power supply complies with the requirements for a limited power source as per EN 60950-1.
Alternative 2
All of the following requirements are complied with:
The power supply complies with the requirements for a safety
extra-low voltage (SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the plus conductor of
the power supply. The minus conductor is on ground potential. Otherwise, a fuse is also located in the minus conductor. Regarding the properties of this fuse:
See “General technical data” on page 27
Qualified personnel are familiar with appropriate measures
against these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable safety regulations.
Grounding the device
The device is grounded by means of a separate ground screw.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the requirements listed are complied with.
Supply voltage
The supply voltage is only connected with the ground connection via protective elements.
Installation SPIDER-SL PoE
Release 01 05/2019 5
Page 6
CE marking
The labeled devices comply with the regulations contained in the following European directive(s):
2011/65/EU (RoHS) Directive of the European Parliament and of the Council on the restriction of the use of certain hazardous substances in electrical and electronic equipment.
2014/30/EU (EMC) Directive of the European Parliament and the council for standardizing the regulations of member states with regard to electromagnetic compatibility.
In accordance with the above-named EU directive(s), the EU conformity declaration will be available to the relevant authorities at the following address:
Hirschmann Automation and Control GmbH Stuttgarter Str. 45-51 72654 Neckartenzlingen Germany
The device can be used in the industrial sector.
Interference immunity: EN 61000-6-2 Emitted interference: EN 55032
You find more information on technical standards here:
“Technical data” on page 27
The assembly guidelines provided in these instructions must be strictly adhered to in order to observe the EMC threshold values.
Warning! This is a class A device. This device can cause interference in living areas, and in this case the operator may be required to take appropriate measures.
Installation SPIDER-SL PoE
6 Release 01 05/2019
Page 7
FCC note:
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference; (2) this device must accept any interference received, including interference that may cause undesired operation. Appropriate testing has established that this device fulfills the requirements of a class A digital device in line with part 15 of the FCC regulations. These requirements are designed to provide sufficient protection against interference when the device is being used in a business environment. The device creates and uses high frequencies and can also radiate these frequencies. If it is not installed and used in accordance with this operating manual, it can cause radio transmission interference. The use of this device in a residential area can also cause interference, and in this case the user is obliged to cover the costs of removing the interference.
Recycling note
After usage, this device must be disposed of properly as electronic waste, in accordance with the current disposal regulations of your county, state, and country.
Installation SPIDER-SL PoE
Release 01 05/2019 7
Page 8
About this Manual
Listing
Work step
Subheading
The “Installation User Manual” document contains a device description,
safety instructions, a display description and further information that you require to install the device.
Legend
The symbols used in this manual have the following meanings:
Installation SPIDER-SL PoE
8 Release 01 05/2019
Page 9
1 Description
Item
Characteristic
Characteristic value
Description
1 ... 9
Product
SPIDER-SL
SPIDER Standard Line
10
(hyphen)
-
11
Data rate 2
10/100 Mbit/s
4
10/100/1000 Mbit/s
12
Power over Ethernet (PoE)
4
PoE+ support 13
(hyphen)
-
14 ... 17
Number Twisted pair ports 04T1
4 × Twisted Pair TX, RJ45
05T1
5 × Twisted Pair TX, RJ45
08T1
8 × Twisted Pair TX, RJ45
18 ... 19
Optical fiber port 1
M2
DSC multimode socket for 100 Mbit/s F/O connections
S2
DSC singlemode socket for 100 Mbit/s F/O connections
M4
ST multimode socket for 100 Mbit/s F/O connections
S4
ST singlemode socket for 100 Mbit/s F/O connections
1.1 General device description
The SPIDER-SL PoE devices are designed for the special requirements of industrial automation. They meet the relevant industry standards, provide very high operational reliability, even under extreme conditions, and also long-term reliability and flexibility.
The SPIDER-SL PoE is a power sourcing equipment (PSE), provides up to 8 Power-over-Ethernet ports. Through a twisted-pair cable connected to the 10/100/1000 Mbit/s PoE port, the device provides power for a powered device (PD) such as a WLAN access point, an IP camera or an IP telephone. With the presence of the PoE power supply, a separate power supply for the powered device is unnecessary.
You have numerous options of combining the device characteristics. You can determine the possible combinations using the configurator which is available in the Belden E-Catalog (www.e-catalog.beldensolutions.com) on the web page of the device.
1.2 Device name and product code
The device name corresponds to the product code. The product code is made up of characteristics with defined positions. The characteristic values stand for specific product properties.
Installation SPIDER-SL PoE
Release 01 05/2019 9
Page 10
Item
Characteristic
Characteristic value
Description
O6
SFP slot for 100/1000 Mbit/s F/O connections
99
without
20 ... 21
Optical fiber port 2 O6
SFP slot for 100/1000 Mbit/s F/O connections
99
without
22 ... 23
Optical fiber port 3
99
without
24
Temperature range
T
Extended
-40 °C ... +70 °C (-40 °F ... +158 °F)
25 ... 26
Certificates and declarations
Z9
CE, FCC, EN61131
27 ... 28
Customer-specific version
HH
Hirschmann standard 29 ... 30
Configuration
HH
Hirschmann standard
Table 1: Device name and product code
10 Release 01 05/2019
Installation SPIDER-SL PoE
Page 11
1.3 Device view
SPIDER-SL-44-05T1O6...
SPIDER-SL-44-05T199...
SPIDER-SL-44-08T19999...
SPIDER-SL-44-08T1O6O6...
Front view using example of device variants SPIDER-SL-44...
SPIDER-SL-44-05T1O6...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for port status
5
1 × SFP slot for 100/1000 Mbit/s F/O connections
6
1 × RJ45 socket for 10/100/1000 Mbit/s Twisted Pair connections
7 ... 10
4 × RJ45 socket for 10/100/1000 Mbit/s PoE+ port
11
LED display elements for PoE status
SPIDER-SL-44-05T199...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for port status
5
1 × RJ45 socket for 10/100/1000 Mbit/s Twisted Pair connections
6 ... 9
4 × RJ45 socket for 10/100/1000 Mbit/s PoE+ port
10
LED display elements for PoE status
SPIDER-SL-44-08T19999...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for PoE status
5 ... 12
8 × RJ45 socket for 10/100/1000 Mbit/s PoE+ port
SPIDER-SL-44-08T1O6O6...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for PoE status
5
2 × SFP slot for 100/1000 Mbit/s F/O connections
6 ... 13
8 × RJ45 socket for 10/100/1000 Mbit/s PoE+ port
1.3.1 Front view
Installation SPIDER-SL PoE
Release 01 05/2019 11
Page 12
SPIDER-SL-24-04T1...
SPIDER-SL-24-05T1...
Front view using example of device variants SPIDER-SL-24...
SPIDER-SL-24-04T1...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for port status
5
depending on device variant
DSC multimode socket for 100 Mbit/s F/O connections DSC singlemode socket for 100 Mbit/s F/O connections ST multimode socket for 100 Mbit/s F/O connections ST singlemode socket for 100 Mbit/s F/O connections
6 ... 9
4 × RJ45 socket for 10/100 Mbit/s PoE+ port
10
LED display elements for PoE status
SPIDER-SL-24-05T1...
1
LED display elements for power supply status
2
4-pin, pluggable terminal block for power supply
3
DIP
4
LED display elements for port status
5
1 × RJ45 socket for 10/100 Mbit/s twisted pair connections
6 ... 9
4 × RJ45 socket for 10/100 Mbit/s PoE+ port
10
LED display elements for PoE status
12 Release 01 05/2019
Installation SPIDER-SL PoE
Page 13
1.4 Power supply
You have the following options to supply your device with voltage:
Power supply via a 4-pin terminal block
For the power supply of the device, a 4-pin terminal block is available. For further information see “Wiring the terminal block for the supply
voltage and the grounding” on page 22.
1.5 Ethernet ports
You can connect end devices and other segments to the device ports using twisted pair cables or optical fibers (F/O). The PoE port of the device (Endpoint PSE) supplies voltage to the twisted pair cables via the wire pairs carrying the signal (Alternative A) You find information on pin assignments for making patch cables here:
“Pin assignments” on page 15
1.5.1 10/100/1000 Mbit/s twisted pair port This port is an RJ45 socket.
The 10/100/1000 Mbit/s twisted pair port offers you the ability to connect network components This port supports:
Autonegotiation Autopolarity Autocrossing 1000 Mbit/s full duplex 100 Mbit/s half-duplex mode, 100 Mbit/s full duplex mode 10 Mbit/s half-duplex mode, 10 Mbit/s full duplex mode
1.5.2 10/100/1000 Mbit/s PoE port This port is an RJ45 socket.
The 10/100/1000 Mbit/s PoE port allows you to connect network components such as a powered device (PD) This port supports:
Autonegotiation Autopolarity Autocrossing 1000 Mbit/s full duplex
Installation SPIDER-SL PoE
Release 01 05/2019 13
Page 14
100 Mbit/s half-duplex mode, 100 Mbit/s full duplex mode 10 Mbit/s half-duplex mode, 10 Mbit/s full duplex mode Power over Ethernet (PoE/PoE+)
1.5.3 10/100 Mbit/s twisted pair port This port is an RJ45 socket.
The 10/100 Mbit/s twisted pair port offers you the ability to connect network components This port supports:
Autonegotiation Autopolarity Autocrossing 100 Mbit/s half-duplex mode, 100 Mbit/s full duplex mode 10 Mbit/s half-duplex mode, 10 Mbit/s full duplex mode
1.5.4 10/100 Mbit/s PoE port This port is an RJ45 socket.
The 10/100 Mbit/s PoE port allows you to connect network components such as a powered device (PD) This port supports:
Autonegotiation Autopolarity Autocrossing 100 Mbit/s half-duplex mode, 100 Mbit/s full duplex mode 10 Mbit/s half-duplex mode, 10 Mbit/s full duplex mode Power over Ethernet (PoE/PoE+)
1.5.5 100/1000 Mbit/s F/O port This port is an SFP slot. The 100/1000 Mbit/s F/O port offers you the
ability to connect network components. This port supports:
100 Mbit/s full duplex when using a Fast Ethernet SFP transceiver 1000 Mbit/s full duplex when using a Gigabit Ethernet SFP
transceiver
1.5.6 100 Mbit/s F/O port The 100 Mbit/s F/O port offers you the ability to connect network
components.
Installation SPIDER-SL PoE
14 Release 01 05/2019
Page 15
This port supports:
RJ45
Pin
10/100 Mbit/s
1000 Mbit/s
PoE voltage
MDI mode
1 TX+
BI_DA+
Plus terminal
2
TX-
BI_DA-
Plus terminal
3
RX+
BI_DB+
Minus terminal
4 - BI_DC+
5 - BI_DC-
6
RX-
BI_DB-
Minus terminal
7 - BI_DD+
8 -
BI_DD-
Full duplex mode
1.6 Pin assignments
Pin assignment of a TP/TX interface in MDI mode, RJ45 socket
Installation SPIDER-SL PoE
Release 01 05/2019 15
Page 16
1.7 Display elements
LED
Color
Activity
Meaning
P1
Green Lights up
The operating voltage 1 is on
None
The operating voltage 1 is off
P2
Green Lights up
The operating voltage 2 is on
None
The operating voltage 2 is off
After the supply voltage is switched on, the device performs a self-test. During this process, various LEDs light up.
1.7.1 Power supply state
This LED provides information on the status of the power supply.
16 Release 01 05/2019
Installation SPIDER-SL PoE
Page 17
1.7.2 Port state
LS/DA (link status/data)
Color
Activity
Meaning
Green Lights up
Device detects a valid link
Flashing
Device is transmitting and/or receiving data
None
Device detects an invalid or missing link
LED
Color
Activity
Meaning
Green Lights up
The PoE power supply is active
None
The PoE power supply is inactive
These LEDs provide port-related information.
1.7.3 PoE state These LEDs provide information on the status of the PoE.
Installation SPIDER-SL PoE
Release 01 05/2019 17
Page 18
2 Installation
The devices have been developed for practical application in a harsh industrial environment. On delivery, the device is ready for operation.
To configure a subdomain, follow these steps:
Checking the package contents Mounting the device Installing an SFP transceiver (optional) Wiring the terminal block for the supply voltage and the grounding Operating the device Connecting data cables
2.1 Checking the package contents
Check whether the package includes all items named in the section
“Scope of delivery” on page 30.
Check the individual parts for transport damage.
Installation SPIDER-SL PoE
18 Release 01 05/2019
Page 19
2.2 Mounting the device
Installing the device onto the DIN rail
2.2.1 Installing the device onto the DIN rail Prerequisite:
The device is for mounting on a 35 mm DIN rail in accordance with DIN EN 60715.
Proceed as follows:
Slide the upper stiff metal spring of the device into the DIN rail. Press the device downwards onto the clip-in bar. Snap in the device.
2.2.2 Grounding the device
The device has a functional ground connection. The device is grounded via the separate ground screw.
Note: Ground the device before connecting any other cables.
Installation SPIDER-SL PoE
Release 01 05/2019 19
Page 20
2.3 Installing an SFP transceiver (optional)
Prerequisite:
Use only Hirschmann SFP transceivers which are suitable for usage
with the device.
See “Accessories” on page 31.
Proceed as follows:
Remove the protection cap from the SFP transceiver. Push the transceiver with the lock closed into the slot until it latches
in.
Installation SPIDER-SL PoE
20 Release 01 05/2019
Page 21
2.4 Adjust DIP switch settings
Device
DIP Switch
Setting
Description
SPIDER-SL-44-05T1O6... 100/1GSFP
ON
Supports 1000M SFP module
OFF
Supports 100M SFP module
Jumbo ON
Enable Jumbo frame function
OFF
Disable Jumbo frame function
SPIDER-SL-44-05T199... N.C.
--
Serves no function
Jumbo ON
Enable Jumbo frame function
OFF
Disable Jumbo frame function
SPIDER-SL-44­08T19999...
N.C.
--
Serves no function
Jumbo
ON
Enable Jumbo frame function
OFF
Disable Jumbo frame function
SPIDER-SL-44­08T1O6O6... N.C.
--
Serves no function
Jumbo ON
Enable Jumbo frame function
OFF
Disable Jumbo frame function
SPIDER-SL-24-... N.C.
--
Serves no function
Jumbo ON
Enable Jumbo frame function
OFF
Disable Jumbo frame function
The 2-pin DIP switch on the top of the device gives you the following options:
Note: For the SPIDER-SL-44-05..., you must restart the device for the changes to take effect after modifying the DIP switch.
Before starting operation of the device, check whether the default
settings of the DIP switch correspond to your requirements.
Installation SPIDER-SL PoE
Release 01 05/2019 21
Page 22
2.5 Wiring the terminal block for the supply
WARNING
ELECTRIC SHOCK
Connect only a supply voltage that corresponds to the type plate of your device. Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals for the supply voltage, and do not touch the terminals.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Type of the
voltages that can
be connected
Specification of the
supply voltage
Connections
DC voltage
Rated voltage range DC 12 V ... 57V +
Plus terminal of the supply voltage
-
Minus terminal of the supply voltage
voltage and the grounding
A 4-pin terminal block is used for connecting the supply voltage and it is a redundant power. A grounded screw is used for the grounding.
Figure 1: 4-pin, pluggable terminal block for power supply
Table 2: Type and specification of the supply voltage and pin assignment on the device
The operating voltage can be connected redundantly. Both inputs are
uncoupled. There is no distributed load. With redundant supply, the power supply unit with the higher output voltage supplies the device on its own.
22 Release 01 05/2019
Installation SPIDER-SL PoE
Page 23
Proceed as follows:
Ensure the required conditions for connecting the supply voltage. See “Requirements for connecting electrical wires” on page 4.  Pull the terminal block off the device. Connect the ground connection. Connect the power supply cables. Plug the terminal block into the connection on the housing.
2.6 Operating the device
By connecting the supply voltage via the terminal block, you start the operation of the device.
2.7 Connecting data cables
Note the following general recommendations for data cable connections in environments with high electrical interference levels:
Keep the length of the data cables as short as possible. Use optical data cables for the data transmission between the
buildings.
When using copper cables, provide a sufficient separation between
the power supply cables and the data cables. Ideally, install the cables in separate cable channels.
Verify that power supply cables and data cables do not run parallel
over longer distances, and that ideally they are installed in separate cable channels. If reducing the inductive coupling is necessary, verify that the power supply cables and data cables cross at a 90° angle.
Use shielded cables (SF/UTP cables as per ISO/IEC 11801:2002). Beware of possible short circuits when connecting a cable section
with conductive shielding braiding.
Connect the data cables according to your requirements.
Installation SPIDER-SL PoE
Release 01 05/2019 23
Page 24
3 Monitoring the ambient air
temperature
Operate the device below the specified maximum ambient air temperature exclusively.
See “General technical data” on page 27.
The ambient air temperature is the temperature of the air at a distance of 2 in (5 cm) from the device. It depends on the installation conditions of the device, e.g. the distance from other devices or other objects, and the output of neighboring devices.
NOTE: We recommend the installation environment for the equipment is:
0.8 in (2 cm) left and right spacing, 2 in (5 cm) up and down
Installation SPIDER-SL PoE
24 Release 01 05/2019
Page 25
4 Maintenance and service
CAUTION
RISK OF TRANSIENTS OR ELECTROSTATIC DISCHARGES
Do not open the housing.
Failure to follow these instructions can result in injury or equipment damage.
When designing this device, Hirschmann largely avoided using high­wear parts. The parts subject to wear and tear are dimensioned to last longer than the lifetime of the product when it is operated normally. Operate this device according to the specifications. Depending on the degree of pollution in the operating environment, check at regular intervals that the ventilation slots in the device are not obstructed.
Note: You will find information about the complaints and returns procedures on the Internet under
http://www.beldensolutions.com/en/Service/Repairs/index.phtml .
Installation SPIDER-SL PoE
Release 01 05/2019 25
Page 26
5 Disassembly
5.1 Removing an SFP transceiver (optional)
Proceed as follows:
Pull the SFP transceiver out of the slot by means of the opened lock. Close the SFP transceiver with the protective cap.
5.2 Removing the device
Proceed as follows:
Disconnect the data cables. Disable the supply voltage. Remove the power connector from the device. Press the device downwards. Pull it device from under the DIN rail.
Installation SPIDER-SL PoE
26 Release 01 05/2019
Page 27
6 Technical data
Dimensions W × H × D
SPIDER Standard Line PoE
See “Dimension drawings” on page 28.
Power supply
2 voltage input 4-pin terminal block Safety extra-low voltage (SELV)
Rated voltage range DC
24 V
Voltage range DC incl. maximum tolerances
12 V ... 57 V
PoE power output 12-18.9V 60W1
19-57V 120W1
Power loss buffer
10ms at 20.4V DC (no PoE buffer)
Back-up fuse
≤ 15 A, quick acting
Peak inrush current
2.77A2s
Climatic conditions during operation
Ambient air temperature2
-40 °C ... +70 °C (-40 °F ... +158 °F) Derating3
Humidity
10 % ... 95 % (non-condensing)
Air pressure
minimum 795 hPa (+6562 ft; +2000 m)
Climatic conditions during storage
Ambient air temperature2
-40 ºC ... +85 ºC (-40 ºF ... +185 ºF)
Humidity
10 % ... 95 % (non-condensing)
Air pressure
minimum 795 hPa (+6562 ft; +2000 m)
Pollution degree
2
Protection classes
Degree of protection
IP 30
General technical data
1. When the total PoE output power exceeds Max. PoE power output, the device stops working.
2. Temperature of the ambient air at a distance of 2 inches (5 cm) from the device.
3. Derating: -40°C … +65°C at Uin < 24VDC combined with PoE load > 90W.
Installation SPIDER-SL PoE
Release 01 05/2019 27
Page 28
Dimension drawings
Figure 2: Dimensions of device variants SPIDER-SL-24...
Figure 3: Dimensions of device variants SPIDER-SL-44...
Installation SPIDER-SL PoE
28 Release 01 05/2019
Page 29
EMC and immunity
EMC interference emission
Radiated emission
FCC 47 CFR Part 15
Class A
EN 55032
Class A
Conducted emission
FCC 47 CFR Part 15
Class A
EN 55032
Class A
EMC interference immunity
Electrostatic discharge
EN 61000-4-2 IEEE C37.90.3
Contact discharge
± 6 kV
EN 61000-4-2 IEEE C37.90.3
Air discharge
± 8 kV
Electromagnetic field
EN 61000-4-3
80 MHz ... 6000 MHz
10 V/m
Fast transients (burst)
EN 61000-4-4 IEEE C37.90.1
DC supply connection
± 2 kV
EN 61000-4-4 IEEE C37.90.1
Data line
± 2 kV
Voltage surges - DC supply connection
EN 61000-4-5
line/earth
± 2 kV
EN 61000-4-5
line/line
± 1 kV
Voltage surges - data line
EN 61000-4-5
line/earth
± 1 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
Stability
IEC 60068-2-6, test Fc Vibration
5 Hz ... 8.4 Hz with
3.5 mm amplitude
8.4 Hz ... 150 Hz with 1 g
IEC 60068-2-27, test Ea
Shock
15 g at 11 ms
10/100/1000 Mbit/s twisted pair port
Length of a twisted pair segment
max. 109 yards (100 m) (for Cat5e cable)
Network range
Installation SPIDER-SL PoE
Release 01 05/2019 29
Page 30
Power consumption/ power output at 24V DC
Device name
Max. power consumption
Power output
SPIDER-SL-44-05T1...
6.8W
20.3 BTU(IT)/h
SPIDER-SL-44-08T1
7.6W
25.8 BTU(IT)/h
SPIDER-SL-24-04T1
4.1W
13.9 BTU(IT)/h
Device name
Max. power consumption
Power output
SPIDER-SL-44-05T1...
139.7W
476.7 BTU(IT)/h
SPIDER-SL-44-08T1
134.5W
457.3 BTU(IT)/h
SPIDER-SL-24-04T1
134.2W
456.3 BTU(IT)/h
Number
Article
1 ×
Device
1 ×
4-pin, pluggable terminal block for power supply
1 ×
General safety instructions
Device
SPIDER-SL-44-05T1O69999TZ9HHHH
942-274-001
SPIDER-SL-44-05T1999999TZ9HHHH
942-274-002
SPIDER-SL-44-08T1999999TZ9HHHH
942-274-003
SPIDER-SL-44-08T1O6O699TZ9HHHH
942-274-004
SPIDER-SL-24-04T1M29999TZ9HHHH
942-274-005
SPIDER-SL-24-04T1M49999TZ9HHHH
942-274-006
SPIDER-SL-24-04T1S29999TZ9HHHH
942-274-007
SPIDER-SL-24-04T1S49999TZ9HHHH
942-274-008
SPIDER-SL-24-05T1999999TZ9HHHH
942-274-009
Without PoE output
With 120W PoE output
Scope of delivery
Order number
30 Release 01 05/2019
Installation SPIDER-SL PoE
Page 31
Accessories
Fast-Ethernet-SFP-Transceiver
Order number
M-FAST SFP-TX/RJ45
942 098-001
M-FAST SFP-TX/RJ45 EEC
942 098-002
M-FAST SFP-MM/LC
943 865-001
M-FAST SFP-MM/LC EEC
943 945-001
M-FAST SFP-SM/LC
943 866-001
M-FAST SFP-SM/LC EEC
943 946-001
M-FAST SFP-SM+/LC
943 867-001
M-FAST SFP-SM+/LC EEC
943 947-001
M-FAST SFP-LH/LC
943 868-001
M-FAST SFP-LH/LC EEC
943 948-001
SFP-FAST-MM/LCa
942 194-001
SFP-FAST-MM/LC EECa
942 194-002
SFP-FAST-SM/LCa
942 195-001
SFP-FAST-SM/LC EECa
942 195-002
Bidirectional Gigabit Ethernet SFP transceiver
Order number
M-SFP-BIDI Type A LX/LC EEC
943 974-001
M-SFP-BIDI Type B LX/LC EEC
943 974-002
M-SFP-BIDI Type A LH/LC EEC
943 975-001
M-SFP-BIDI Type B LH/LC EEC
943 975-002
M-SFP-BIDI Bundle LX/LC EEC (type A + B)
943 974-101
M-SFP-BIDI Bundle LH/LC EEC (type A + B)
943 975-101
Gigabit Ethernet SFP transceiver
Order number
M-SFP-TX/RJ45
943 977-001
M-SFP-SX/LC
943 014-001
M-SFP-SX/LC EEC
943 896-001
M-SFP-MX/LC EEC
942 108-001
M-SFP-LX/LC
943 015-001
M-SFP-LX/LC EEC
943 897-001
M-SFP-LX+/LC
942 023-001
M-SFP-LX+/ LC EEC
942 024-001
M-SFP-LH/LC
943 042-001
M-SFP-LH/LC EEC
943 898-001
M-SFP-LH+/LC
943 049-001
SFP-GIG-LX/LCa
942 196-001
SFP-GIG-LX/LC EECa
942 196-002
Note that products recommended as accessories may have different characteristics to those of the device, which may limit the application range of the overall system. For example, if you add an accessory with IP 20 to a device with IP 65, the IP of the overall system is reduced to
20.
a. You will find further information on the certificates on the Internet on the Hirschmann
product pages (www.hirschmann.com).
Installation SPIDER-SL PoE
Release 01 05/2019 31
Page 32
Underlying technical standards
Name
EN 55032
Information technology equipment Radio disturbance characteristics – Limits and methods of measurement
EN 61000-6-2
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
EN 61131-2
Programmable controllers – Part 2: Equipment requirements and tests
FCC 47 CFR Part 15
Code of Federal Regulations
Table 3: List of the technical standards
The device has an approval based on a specific standard only if the approval indicator appears on the device casing. The device generally fulfills the technical standards named in their current versions.
32 Release 01 05/2019
Installation SPIDER-SL PoE
Page 33
A. Further Support
Technical Questions
For technical questions, please contact any Hirschmann dealer in your area or Hirschmann directly. You will find the addresses of our partners on the Internet at
http://www.hirschmann.com.
A list of local telephone numbers and email addresses for technical support directly from Hirschmann is available at
https://hirschmann-support.belden.com.
This site also includes a free of charge knowledge base and a software download section.
Hirschmann Competence Center
The Hirschmann Competence Center is ahead of its competitors:
Consulting incorporates comprehensive technical advice, from
system evaluation through network planning to project planning.
Training offers you an introduction to the basics, product briefing
and user training with certification. The current technology and product training courses can be found at http://www.hicomcenter.com
Support ranges from the first installation through the standby
service to maintenance concepts.
With the Hirschmann Competence Center, you have decided against making any compromises. Our client-customized package leaves you free to choose the service components you want to use. Internet:
http://www.hicomcenter.com
Installation SPIDER-SL PoE
Release 01 05/2019 33
Page 34