Belden Hirschmann OZD Profi G12DU ATEX 1, Hirschmann OZD Profi G12DE ATEX 1, Hirschmann OZD Profi G12DK ATEX 1 User Manual

Page 1
Manual
PROFIBUS Fiberoptic Repeater OZD Profi G12DU ATEX 1 OZD Profi G12DK ATEX 1 OZD Profi G12DE ATEX 1
Hirschmann. Simply a good Connection.
System
CH1
CH2
CH3
CH3
CH2
24V*24VDIBDI
A
0V0V FG FG
DOBDOACH0VFNCFNOCH3CH
2
F
NICHT UNTER SPANNUNG ÖFFNEN DO NOT OPEN WHILE EN ERGISED
NE PAS OUVRIR SOUS TE NSION
NON APRIRE SOTTO TENSIONE
NÃO ABRIR QUANDO ENERGIZADO
943881321000000001
Ser.-No.: 0123456789
Page 2
The specified performance characteristics are binding only if these have been expressly agreed at the time of contract conclusion. We have checked the contents of the brochure for com plia nce with the specified hardware and software. However, devia tions cannot be ruled out, we hence do not guarantee complete compliance. Details in the brochure are checked regularly. Necessary corrections are included in the subsequent editions. Sug ­gestions for improvement are welcome.
Technical changes reserved.
Transfer and copying of this docum ment, utilisation and disclosure of the contents is not permitted, unless expressly conceded. Contraven tions are liable for com­pensation. All rights reserved, particularly for the case of granting of patents or regsitration of utility model.
© Hirschmann Automation and Control GmbH
All Rights Reserved
Note
We would like to emphasise that the contents of this operating manual are not a part of an earlier or existing agreement, commitment or legal relationship or an amendment thereof. All obligations of Hirschmann arise from the purchase contract, which also include the com­plete and exclusively applicable guarantee regulations. These contract ual warranty agreements are neither extended or limited by the versions of this operat ing man­ual.
Moreover, we would like to emphasise that in the interest of clarity in this operating manual, not every imaginable problem related to the use of this device can be described. Should you require more information or should other problems occur, which have not been dealt with in detail in the operating manual, you can get the required information about the Hirsch mann partner in your vicinity or directly request the same from Hirschmann (see address in section “information on CE marking“.
Order numbers
OZD Profi G12DU ATEX 1 943 881-321
OZD Profi G12DK ATEX 1 943 882-321
OZD Profi G12DE ATEX 1 943 883-321
Manual 039 677-001 PROFIBUS Fiberoptic Repeater OZD Profi G12DU ATEX 1 OZD Profi G12DK ATEX 1 OZD Profi G12DE ATEX 1
Page 3
3
Contents
OZD Profi G12D... ATEX 1 V. 03 07/2014
1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Safety guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Operator of the system and personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Relevant laws, standards, guidelines and other documentation . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Information on marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.7 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.7.1 General information on assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.7.2 Assembly in zone 1 or zone 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.7.3 Assembly in zone 2 or zone 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.8 Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.9 Installation and startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.10 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.11 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.12 Delivery, Transport and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.13 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.14 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3 General functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1 Functions independent of the mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2 Functions dependent on the mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 Network topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 Line topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1 Line topology with fibre optic path monitoring and segmentation . . . . . . . . . . . . . . . . . . . . 20
4.1.2 Line topology without fibre optic path monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2 Star topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.3 Redundant optical ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.4 Combination with network topologies of ex-zone 2, 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1 Design guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1.1 Assembly in zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1.2 Assembly in zone 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1.3 Assembly in safe area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1.4 Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.1.5 Suppression of switched inductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.1.6 Spatial arrangement of devices and lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.1.7 Model/design/version of shield connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Contents
Page 4
Contents
4
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.2 Startup process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.3 Assemble/disassemble repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.1 Assembly of OZD Profi G12DU ATEX 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.2 Assembly of OZD Profi G12DK ATEX 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3.3 Assembly OZD Profi G12DE ATEX 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4 Setting the mode, connection/disconnection of terminating resistors . . . . . . . . . . . . . . . . . . . . . 34
5.4.1 Setting the mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.4.2 Connection/disconnection of internal terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . 35
5.5 Connect optical bus cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.6 Connect electrical bus cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.7 Connect functional earth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.8 Connect signal contact cables (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.9 Define reception level of optical channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.10 Connect operating voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.11 Monitor LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6 Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.1 LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2 Fault finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3 Problem report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4 Contact address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.1 Configuration of redundant optical rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
8 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
9 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
A.1 Define reception level of optical channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Page 5
5
2 Safety
OZD Profi G12D... ATEX 1 V. 03 07/2014
1 Safety
The safety chapter is applicable as an operating manual Different procedures and instructions in this operating manual require special precautionary measures for ensuring safety of the involved persons.
1.1 Validity
This manual contains guidelines, which must be observed for your personal safety and for avo iding property damage. The information is high lighted by a warning triangle and depending upon the degree of risk is presented as follows:
z
Danger!
means death, serious inj ury or extensive damage to property may occur, if the appropriate precautions are not taken.
z
Warning!
means death, serious inj ury or extensive damage to property may occur, if appropriate precau­tions are not taken.
z
Caution!
means a minor inj ury or property dam age may occur , if appropriate precautions are not taken.
Note:
is important information on the product, handling of the product or the respective part of documentation, which must be paid special attention .
1.2 Safety guidelines
Responsibility with respect to planning, assembly, start­up, operation and maintenance is that of the operator of the system. Assembly, installation, startup, maintenance and opera­tion of all devices must be done by qualified personnel only. The operating manual must be read and under­stood.
1.3 Operator of the system and personnel
Page 6
2 Safety
6
OZD Profi G12D... ATEX 1 V. 03 07/2014
Laws, standards or guidelines applicable for the usage and/or the planned intended use must be complied with just like the appropriate data sheets, declarations of con­formity, EC-type examination certificates and certificates where applicable.
Guideline 94/9 EC must be observed for explosive haz­ardous areas.
1.4 Relevant laws, standards, guidelines and other documentation
7
The devices comply with the regulations of the following European directive:
89/336/EEC Council directive for approximation of legal pro visio ns of member states for electromagnetic compatibility (changed by directive 91/263/EEC, 92/31/EEC and 93/68/EEC).
Prerequisite for the compliance of EMC limits is the strict compliance of guidelines specified in the description and operating manual.
Records of the EC declarations of conformity are kept in accordance with the above mentioned EC directive for the compe tent authorities at:
Hirschmann Automation and Control GmbH Stuttgarter Strasse 45-51 72654 Neckartenzlingen Germany Telefon +49 (0)1805 14-1538 E-Mail HAC.Support@Belden.com
The product is usable in the residential area (residential area, business and commercial areas, small enterprises) as well as in the industrial area.
– Interference immunity:
EN 61000-6-2:2001
– Emitted immunity:
EN 55022:1998+A1:2000+A2:2003 Class A
z
Note!
This equipment belongs to class A. This may cause radio interference in the residential area. In this case the operator may request execution of appropriate measures and pay for the same.
Marking of devices
OZD Profi G12DU devices are marked as per EU-type examination certificate PTB 09 ATEX 2044 X as follows:
II 2 G Ex e mb op is [ib] IIC T4 Gb
OZD Profi G12DK and OZD Profi G12DE devices are marked as per EU-type examination certificate PTB 09 ATEX 2045 as follows:
II 2 G Ex e mb [ib] op is IIC T4
II 2 D Ex tD A21 IP 66 T 130 °C
1.5 Information on marking
Page 7
7
2 Safety
OZD Profi G12D... ATEX 1 V. 03 07/2014
The PROFIBUS Fiberoptic Repeater in plastic or stain­less steel protective housing is intended for use in explo­sive hazardous area. The PROFIBUS Fiberoptic Repeater (DIN-rail module) without plastic or stainless steel protective housing must be used only as a replacement for a defective PROFIBUS Fiberoptic Repeater in plastic or stainless steel protective housing. Another use is possible after joint ATEX approval with an approved protective housing.
The PROFIBUS Fiberoptic Repeater is used as an inter ­face between electrical PROFIBUS signals from the explosive hazardous area (ex-area) and the safe area (non-ex-area). Bus and auxiliary power circuits are isolat­ed galvanically.
PROFIBUS Fiberoptic Repeater are intended for use in the optical PROFIBUS networks. They enable implemen­tation of electrical PROFIBUS interfaces (RS 485 level) in optical PROFIBUS interfaces and vice-versa.
By using the known advantages of the optical transmis­sion technology, the devices can be integrated in the existing PROFIBUS fieldbus networks. Likewise, com­plete structure of a PROFIBUS fieldbus network with devices in line, star and ring topology is possible in any combination.
Applicable laws, standards or guidelines must be observed for usage or the planned purpose. The devices are approved only for proper and intended use. Any guarantee and producer responsibility becomes void in case of infringement.
The devices are not suitable for separation of signals in power measurement, unless stated specifically in the appropriate data sheet.
Protection of operating personnel and system is not guaranteed if the component is not used in accordance with its intended purpose.
1.6 Intended use
1.7 Assembly
1.7.1 General information on assembly
Familiarise yourself with the device prior to assembly, installation and startup and read this manual carefully. The device must not be installed on places with aggres­sive vapours. Observe BGR A3 (the Federal Institute for Geosciences and Natural Resources) when working under voltage. Installation requirements in accordance with IEC/EN 60079-14 / IEC/EN 60079-25 and national deviations must be com plied with. The devices are designed for use in pollution degree 1 and overvoltage category II as per IEC/EN 60664-1 .
If devices are used in general electrical systems, these must not be used thereafter in electrical systems, which are connected to explosive hazardous areas. The in-built PROFIBUS Fiberoptic Repeater in ex-e­housing contains non-intrinsic circuits. The non-intrinsic circuits must be covered so that the optical fibre connec­tions are accessible during ongoing operation. The cover must attain protection class IP30 as per IEC/EN 60529.
The devices are designed according to protection class encapsulation as per IEC/EN 60079-18. The housing, the seal and the sealing agent must not be damaged.
The equipment must not be operated with dust deposits >_ 5 mm thickness as per IEC/EN 61241-1. Terminals in increased safety are covered. The cover may be removed any time during assembly in safe area.
The device types can be installed outside the ex-area. The housing cover may be opened for servicing during ongoing operation.
Non-used inlet openings are to be sealed securely with certified sealing plugs in order to comply with the IP pro­tection class. Likewise, seal inserts appropriate for the respective cable diameter must be used.
Page 8
2 Safety
8
OZD Profi G12D... ATEX 1 V. 03 07/2014
Excessive force on the glands may endanger the protec­tion class. For ensuring protection class IP 54:
all seals must be fitted intact and correctly,
all screws of the housing/housing cover must be tightened with the appropriate torque,
only cables of appropriate sizes must be used in the cable glands,
all cable glands must be tightened with the appropri­ate torque,
all free cable glands must be sealed with sealing plugs.
The PROFIBUS Fiberoptic Repeater are delivered in housings of protection class IP 66. The same provisions are applicable for this.
1.7.2 Assembly in zone 1 or zone 21
The devices must be installed in a housing with minimum protection class IP 54 as per gas-ex in zone 1.
IP 6* must be complied for conductive and non-conduc-
tive dust.
Temperature class T4 specified in the EC-type examina­tion certification PTB 04 ATEX 1030 must be maintained at maximum ambient temperature of the housing of <_60 °C.
The housing cover may be opened in zone 1 for servicing during ongoing operation.
Terminals in increased safety are covered.
The cover may be removed only if there is no explosion hazard circuits are switched to zero potential before­hand.
1.7.3 Assembly in zone 2 or zone 22
The devices must be installed in a housing with minimum protection class IP 54 as per gas-ex in zone 2. For the assembly, besides devices in housing design, even DIN rail modules are available as per the data sheet. The modules must be installed as asso ciated equipment in safe area or in su itable housing in zone 2.
IP 6* must be complied for conductive and non-conduc-
tive dust.
Temperature class T4 specified in the statement of con­formity must be maintained at maximum ambient ­temperature of the housing of <_ 60 °C under normal operating conditions.
The housing cover may be opened in zone 2 for servicing during ongoing operation. In Zone 22 the housing cover may be opened only in the current-free state.
All terminals are covered.
The cover may be removed in zone 2 and also in the safe area for servicing. The terminals are then accessible.
Select the assembly location such that climatic limit val­ues specified in the technical data are maintained.
Page 9
9
2 Safety
OZD Profi G12D... ATEX 1 V. 03 07/2014
If the device is installed in zone 1, the housing, in which the device is installed, must be suitable for the intended use. Examination certificate as per directive 94/9/EC must be obtained for the housing.
Installation in housing not examined by Hirschmann together with the fibre optic coupler is not permitted. For this, separate certification of a notified body may be obtained. Following points must be observed/ evaluated:
IP protection class as per IEC/EN 60529
resistance to light as per IEC/EN 60079-0
impact strength as per IEC/EN 60079-0
chemical resistance as per IEC/EN 60079-0
heat resistance as per IEC/EN 60079-04
electrostatics as per IEC/EN 60079-0
If the seal of the housing cover or a seal of the cable entry is damaged, it should be replaced with a new hous­ing cover or cable entries of the manufacturer.
1.8 Housing
The device must be zero-potential during installation and maintenance. Voltage must be applied only after com­plete assembly and connection of all circuits required for the operation.
The devices must be connected only to the supply volt­age printed on the type plate. The devices are designed only for operation with the safety low voltage. According­ly, only PELV circuits or optionally SELV circuits with voltage restrictions as per IEC/EN 60950 must be con­nected to the supply voltage connections and the sig­nalling contact. In case that you operate the module with external voltage: supply the system only with a safety low voltage as per IEC/EN 60950.
The optical fibres have an inherently safe optical radia­tion and must be interconnected only with other inherent­ly safe optical equipment. For this, preferably a similar device of type OZD Profi G12D... ATEX 1 must be used.
Installation regulations as per IEC/EN 60079-14 (VDE 0165-1) for zone 1 or IEC/EN 60079-15 for zone 2 as well as directive 99/92 EC must be complied with.
The devices must be installed by a qualified electrician in consensus with the nationally applicable standards in zone 1 or zone 2 or zone 21 and zone 22.
Explosion group specified on the housing, the tempera­ture class and special ambient conditions must be com­plied with!
Modifications and changes to the device are not permit­ted.
The device must be operated as per the intended pur­pose in undamaged and perfect condition!
Only original parts from the manufacturer must be used as spares.
If foreign bodies enter, these must be removed from the device before the initial startup!
When carrying any work on the device, observe the national safety and accident prevention regulations and warnings specially marked in the operating manual!
For installation and operation of associated equipment, comply with the applicable safety regulations as per the ordinance on industrial safety and health and equipment and Product Safety Act and the generally recognised rules of the technology!
Before starting the device with the help of technical data, convince yourself that the operating conditions have been complied with and all polarities of the connections have been selected correctly. Also check the auxiliary power supply and your work area.
1.9 Installation and startup
Page 10
2 Safety
10
OZD Profi G12D... ATEX 1 V. 03 07/2014
z
Warning!
LASER CLASS 1 as per IEC/EN 60825-1 (2001).
The devices must not be repaired, changed or mani ­pulated. In case of defect, the product must be always replaced by an original one.
If the seal of the housing cover or a seal of the cable entry is damaged, it should be replaced with a new hous­ing cover or cable entries of the manufacturer.
The insulation must reach up to the terminal. The con­ductor itself must not be damaged.
Fine-wired cables must be secured with a cable lug. If two cables must be led to a common terminal, a double cable lug must be used.
Generally only certified cable entries and sealing plugs must be used. Trumpet shaped cable glands or other suitable entries with additional stress relief must be used for flexible cables. Assembly guidelines, which are signif­icant for cable entries, must be observed. When using cable entry with an IP protection class, which is lower than the one applicable for the device, IP protection class of the entire device must be reduced. Non-used inlet openings must be sealed with a certified sealing plug for getting the minimum protection class. When installing the cable entries, ensure that seal inserts suit­able for the cable diameter are used during installation. For excisable seal inserts ensure that the insert is suit­able for the cable diameter. All non-used cable entries must be sealed with sealing plugs certified for cable entries. The fibre optic cables are introduced through glands with slotted seals so that
pre-assembled fibre optic cables can be used. Permissi­ble cladding diameter of the fibre optic cable must be complied with. (for this see technical data, cable glands, page 54).
Cable entries must be tightened for ensuring the required minimum protection class (for this see technical data, test torque, page 55). Excessive tightening may impair the protection class. When tightening the cap nut of the metal cable entries (type E1WF/e), the gland must be secured against rota­tion with the help of a suitable tool.
The device must be operated only at the specified ambi­ent temperature and at the specified relative humidity (not condensing).
The housing may be opened under voltage in zone 1. The IP30 cover of the terminals must not be opened under voltage. The IP-30 cover must be replaced after repairs or maintenance. All non­covered control elements such as switches may be actuated. The fibre optic cable may be plugged or removed under voltage.
The devices must not be repaired, changed or manipulat­ed. In case of defect, the device must be always replaced by an original one. For dust explosion protection, safety measures, which are same as gas explosion protection are applicable. The housing must not be opened under voltage if there is dust explosion hazard. Before opening the housing, the dust deposits must be removed and electric voltages must be switched off.
1.10 Operation
The national regulations are applicable for service, main­tenance and testing of associated equipment.
No maintenance is required if the device is operated properly taking into consideration the assembly instruc­tions and ambient conditions.
According to the ordinance on industrial health and safe­ty the operator of the electrical systems in explosion haz­ard areas is obliged to get these tested from a qualified electrician for their proper condition.
1.11 Maintenance
Page 11
11
2 Safety
OZD Profi G12D... ATEX 1 V. 03 07/2014
National regulations applicable for the maintenance/ ser­vice of electrical equipment in explosion hazard areas must be complied with. The required maintenance intervals are application-spe­cific and hence must be determined depending upon the operating conditions. As part of maintenance, primarily parts on which the type of ignition protection is depen­dent, must be tested (e.g. intactness and tightness of the housing, integrity of the seals and the cable entries as well as the required potential equalisation).
If one determines the need for servicing during mainte­nance, kindly take the “Operation” chapter 1.10, page 10 into consideration. The devices must not be repaired, changed or manipulat­ed. In case of defect, the device must be always replaced by an original one.
Check the packaging and contents for damage. In case of damage, notify the post and/or the forwarding agent and the supplier. Check the delivery scope based on the order and the delivery documents for completeness and correctness. Preserve the original packaging. The device should always be stored or transported in the original packaging.
Always store the device in dry and clean surroundings. Note the permissible storage temperature (see technical data, page 54).
1.12 Delivery, Transport and Storage
The devices must not be repaired, changed or manipulat­ed. In case of defect, the product must be always replaced by an original one.
1.13 Repairs
The devices and packaging material must be disposed in accordance with the relevant laws and regulations in the respective country. Batteries are not included in the devices, these must be disposed off separately.
1.14 Disposal
Page 12
2 Safety
12
OZD Profi G12D... ATEX 1 V. 03 07/2014
Page 13
13
2 Introduction
OZD Profi G12D... ATEX 1 V. 03 07/2014
2 Introduction
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
DO NOT OPEN WH ILE ENERGISED
DO NOT OPEN WH ILE ENERGISED
NE PAS OUVRIR S OUS TENSION
NON APRIR E SOTTO TENSIONE
NÃO ABRIR QU ANDO ENERGIZA DO
943881321000000001
Ser. No.: 0123456789
Terminal blocks with connections for CH1 (electrical channel), functional earth, signalling contact and operating voltage supply and with measuring points for the receive level of the optical channels
LED indicators
Switch for operating mode and internal terminating resistors
Channel 2 and 3 optical, BFOC/2.5 sockets
PROFIBUS Fiberoptic Repeater
OZD Profi G12DU ATEX 1,OZD Profi G12DK ATEX 1 andOZD Profi G12DE ATEX 1
are planned for use in optical PROFIBUS fieldbus net­works. They enable implementation of electrical PROFIBUS interfaces (RS 485 level) in optical PROFIBUS interfaces and vice-versa.
By using the known advantages of the optical transmis­sion technology, the devices can be integrated in the existing PROFIBUS fieldbus networks. Likewise, com­plete structure of a PROFIBUS fieldbus network with devices in line, star and ring topology is possible in any combination.
Explosion protection
The devices have been approved for operation in the explosion protection zones 1, 21, 2 and 22 as per AT. They are thus interfaces between electrical Profibus-sig­nals from the explosion hazard areas (ex-area) and the safe area (non-ex-area). The electronic circuits are separated by encapsulation as per EN 50028/VDE 0170/0171 part 9 from the explosive atmosphere. The electrical connections are lead from the electronic circuits through the encapsulation and placed on the
front side of the housing on the terminals of a terminal block.
Device variants
The repeater
- OZD Profi G12DU ATEX 1 has no protective housing
- OZD Profi G12DK ATEX 1 has a plastic protective hous­ing (i. e. it conforms to a OZD Profi G12DU ATEX 1 with plastic protective housing)
- OZD Profi G12DE ATEX 1 has stainless steel protective housing (i. e. it conforms to a
OZD Profi G12DU ATEX 1 with stainless steel protective housing)
Application area
The device has electromagnetic compatibility as per EN 61326 and NAMUR recommendation NE21. It is planned for use in the industrial area.
Channels
Each device has three independent channels (ports), which in turn comprise a transmitter and receiver.
The electric channel (port 1) is placed on 4 terminals of the terminal block. For types OZD Profi … DK … and OZD Profi … DE … with connection cables are led out­wards via PG cable glands.
Fig. 1: OZD Profi G12DU ATEX 1 with location of each port, the terminal blocks and the LED indicators
Page 14
2 Introduction
14
OZD Profi G12D... ATEX 1 V. 03 07/2014
Fig. 2: OZD Profi G12DK ATEX 1 with location of cable entries and grounding screw
Fig. 3: OZD Profi G12DE ATEX 1 with location of cable entries and grounding screw
Page 15
15
2 Introduction
OZD Profi G12D... ATEX 1 V. 03 07/2014
A RS 485 bus segment as per PROFIBUS standard EN 50170 can be connected to the electrical channel.
The optical channels (CH2 and 3) are designed as optical BFOC/2.5 (ST®) sockets. For types OZD Profi … DK … and OZD Profi … DE …the fibre optics are led outwards via the PG cable glands. A slotted seal enables the installation of fibre optic cables with an add-on connector.
Voltage supply
Operating voltage supply is through the 24 V d.c. volt­age. A redundant power feed is available for increasing the operational safety.
The operating voltage supply is placed on 3 terminals of the terminal block. For types OZD Profi … DK … and OZD Profi … DE … with connection cables, these are led outwards via PG cable glands.
The operating voltage connections are below eachother and are galvanically separated from the remaining electrical connections.
Signalling contact
Various interferences of the repeater can be signaled through a signalling contact (relays with potential-free contacts) .
The signalling contact is placed on 3 terminals of the ter­minal block. For types OZD Profi … DK … and OZD Profi … DE … with connection cables are led outwards via PG cable glands.
The signalling contact connections are below each other and galvanically separated from the remaining electrical connections.
LEDs
Four multi-coloured LEDs signalise the current operating status and possible malfunctions.
Configuration
The device is configured with eight easily accessible switches.
Fibre optics
Use of fibre optics allows very large ranges and ensure optimum protection from EMC influences not only on the transmission paths but also due to electrical isolation on the repeater itself.
Transmission speed
The PROFIBUS Fiberoptic Repeater OZD Profi G12D… ATEX 1 supports data rates of
9.6 kbit/s to 12 MBit/s NRZ.
Network extension
Permissible network extension for the line, ring or star topology is up to 3000 m.
Redundance
Very high transmission security is ensured by the redun­dant ring. Operational safety can be further increased by redundant operating voltage supply.
Measurement output
A measurement output, on which the optical input power can be determined with a standard voltmeter, is available for every optical channel. For this, a hot work permit is required in the ex-area.
Standards / Directives
OZD Profi G12D… ATEX 1 comply with the standard EN 50170 as well as the technical guideline “optical trans­mission technology for PROFIBUS” issued by the PROFIBUS user organisation PNO .
Page 16
2 Introduction
16
OZD Profi G12D... ATEX 1 V. 03 07/2014
Page 17
3.1 Functions independent of the mode of operation
17
3 General functions
OZD Profi G12D... ATEX 1 V. 03 07/2014
3 General functions
Transmission speed
OZD Profi G12D... ATEX 1 supports all transmission speeds (transmission rates) defined in EN 50170:
9.6 kBit/s, 19.2 kBit/s, 45.45 kBit/s, 93.75 kBit/s,
187.5 kBit/s, 500 kBit/s, 1.5 MBit/s, 3 MBit/s, 6 MBit/s and 12 MBit/s.
Transmission speed is set automatically once OZD Profi G12D... ATEX 1 telegrams are received. Adjustment or conversion depends upon the transmission speed and the set operating mode and may last up to several sec­onds for each OZD Profi G12D...ATEX 1 .
If the transmission speed is not recog nised, outputs are blocked for all channels. If the trans mission speed changes during operation, the repeater recognises it and reconfigures the same. Brief transmission faults may occur during the changeover time.
Signal regeneration
The repeater regenerates the signal form and amplitude of the received data. It is thus possible to cascade up to 122 OZD Profi G12D... ATEX 1 (limited by the address space for PROFIBUS networks).
Startup aid
During the installation, at least one active bus station is required for checking the fibre optic connections. This bus station is used as a source for telegrams. After switching on, the OZD Profi G12D... ATEX 1 behave pas­sively. You can recognise the transmission speed from the telegrams transmitted by the bus station. Optical startup aid is possible with the help of flashing channel LED.
Operating mode for the
- OZD Profi G12DU ATEX 1 with DIP switches is set on the upper side of the repeater
- for OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX 1 after opening the protective housing with DIP switches on the upper side of the repeater
. Adjustment help is on the label besides the DIP switches.
3.1 Functions independent of the mode of operation
3.2 Functions dependent on the mode of operation
Segment monitoring of the RS-485 channel
If the operating mode “electrical channel with segment monitoring” is set, every receiver monitors each RS 485 bus segment connected to it for erroneous telegrams or constant network allocation. If erroneous telegrams arrive at the receiver or allocations exceed the maximum permissible transmitting time,
transfer of received signals is blocked, till error-free telegrams are received again or no signal was received for a period of one second.
Page 18
3 General functions 3.2 Functions dependent on the mode of operation
18
OZD Profi G12D... ATEX 1 V. 03 07/2014
In the operating mode “electrical channel without seg­ment monitoring, connected RS 485 bus segments are not monitored. Interferences of the electrical segment affect the entire network.
Kindly observe the installation information in chapter 5.6 “Connect electrical bus cables” on page 37.
Following functions are available only for the optical channels. Activation of the functions is independent of the set operating mode. Kindly refer to the following chapters for detailed infor­mation.
Line monitoring via Echo
The repeater enables active monitoring of the connected optical paths for interruptions of the fibre optic cable through the “send echo”, “monitor echo” and “suppress echo” functions.
Send echo
If the repeater receives a telegram through any channel, the same is send to all other channels. If the receiver is an optical channel, the repeater sends the telegram back to the related optical transmitter.
Monitor echo
If the repeater transmits a telegram - no echo! – to an optical channel, the Repeater expects an echo. If echo does not arrive after a specified time, echo monit oring error is signalled with a red LED belonging to a channel.
Suppress echo
The rele vant receiver is separated from he remaining channels from the start of transmission of the telegram up to complete reception of the echo.
Segmentation
If an echo monitoring error or distortion occurs on an optical channel, the repeater assumes a line fault and blocks this channel for user data. The connected fieldbus subnetwork is thus segmented (detached). Due to this segmentation, the repeater on the opposite side of fibre optic is also segmented. Both repeaters connected to the segmented fieldbus subnetwork transmit test telegrams to the segmented channel. Both repeaters can check the status of the field­bus subnetwork through these test telegrams to be received regularly. Segmentation is automatically cancelled as soon as both the repeaters detect the segmented fieldbus subnetwork with the help of test telegrams.
If all active bus stations in a previously active network are switched off, the repeaters are segmented in cycles for checking the fibre optic paths for neighbouring modules. In the absence of telegram traffic but intact fibre optic paths, the channel LEDs of the optical channels blink yel­low in cycles.
Page 19
4.1 Line topology
19
4 Network topologies
OZD Profi G12D... ATEX 1 V. 03 07/2014
4 Network topologies
Following network topologies are possible with OZD Profi G12D... ATEX 1:
Point to point connectionLine topologyStar topologyRedundant optical ring
Even combinations from these basic types are possible. For building up fibre optic paths of these network topologies lines with two optical fibres are used.
If a fault occurs – e. g. breakage of fibre optic line – high failure safety of the fieldbus network is required, availability of the network is increased by a redundant network configuration.
Kindly note:
Individual terminal equipments or complete
PROFIBUS segments with max. 31 stations can be connected to OZD Profi G12D...ATEX 1.
Lay only fibre optic cables in severe EMC-risk
areas in order to rule out EMC influences in the entire network.
Optical channels, which are connected to each
other via fibre optic cable, must have the same operating mode set.
4.1 Line topology
CH 2
SE
CH 3
SE
CH 2
SE
CH 3
SE
CH 2
SE
CH 3
SE
OZD Profi G12D...
ATEX 1
OZD Profi G12D...
ATEX 1
CH 1
CH 1
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
Terminal equipment/
bus segment
Terminal equipment/
bus segment
CH 2
SE
CH 3
SE
OZD Profi G12D...
ATEX 1
CH 1
Terminal equipment/
bus segment
RS 485-type bus
Optical fibre
Fig. 4: Network structure in the optical line topology
Page 20
4 Network topologies 4.1 Line topology
20
OZD Profi G12D... ATEX 1 V. 03 07/2014
4.1.1 Line topology with fibre optic path monitoring and segmentation
Use this operating mode preferably if a faulty fibre optic segment should be separated from the remaining net­work.
Monitoring mechanisms:
Transmit echo: yes Monitor echo: yes Suppress echo: yes Monitor: yes Segmentation: yes
In this operating mode, individual fibre optic paths are monitored by both the modules connected to it.
If a repeater breaks down or an optical fibre breaks or there is a fault in the optical transmission path , fibre optic path between both OZD Profi G12D... ATEX 1 is broken (segmented). The PROFIBUS network disintegrates into two subnet­works, which each in itself - remains operational. Fault is signalled by switching the channel LED to red and activation of the signalling contact of both OZD Profi
Line topology can be implemented with and without fibre optic path monitoring. If both operating modes are used within a fibre optic line, the operating mode “line topolo­gy without fibre optic path monitoring” determines the availability of this fibre optic line. In homogenous OZD Profi networks, it is recommended to use the fibre optic path monitoring (factory setting).
Kindly note that following basic conditions must be com­plied with for a proper operation during network configuration:
Parameters MIN T
SDR
specified in the PROFIBUS standard EN 50170 must be set at value >_11 for all terminal equipment. This is generally the case, however, it must be checked at occurrence of per­manent communication interferences.
When configuring your network, select possibly
low bus station addresses, in order to keep poten­tial master time-outs small.
For changing the settings, kindly refer to the manufactur­ers documentation related to connected terminal equip­ment.
4.1.2 Line topology without fibre optic path monitoring
Use this operating mode, if you connect a OZD Profi G12D... ATEX 1 with another fibre optic network com ­ponent as per PROFIBUS directive (optical/electrical con verter), which does not transmit a telegram echo and does not expect or take any telegram echo.
G12D... connected to the faulty fibre optic path. Seg­mentation is automatically can celled as soon as both the repeaters detect the uninterrupted segmented fieldbus subnetwork with the help of test telegrams.
Note that in case of fault, two logical token rings are formed for networks with several active bus stations. Each interconnection of the two sub networks may thus lead to temporary network failure due to double token or telegram collisions.
Note:
If a line repeater with two optical channels is used at the beginning or the end, the non-allocated optical channel must be switched to the operating mode “line without fibre optic path monitoring”, so that it does not lead to a fibre breakage signalling. Note that optical channels, which are not connected must be always protected with protective caps from external light incidence and dirt.
Monitoring mechanisms:
Transmit echo: no Monitor echo: no Suppress echo: no Monitor: no Segmentation: no
Individual fibre optic paths are not monitored in this operating mode.
Page 21
4.2 Star topology
21
4 Network topologies
OZD Profi G12D... ATEX 1 V. 03 07/2014
4.2 Star topology
Fig. 5: Network structure in the optical star topology
CH 2
SE
CH 3
SE
CH 2
SE
CH 3
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
CH 2
SE
Terminal equipment/
bus segment
Terminal equipment/
bus segment
Terminal equipment/
bus segment
Terminal equipment/
bus segment
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 2
SE
CH 3
SE
OZD Profi G12D...
ATEX 1
CH 1
CH 2
SE
CH 3
SE
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
OZD Profi G12D...
ATEX 1
CH 1
Electrical star segment
S0 = 1 S0 = 1 S0 = 1 S0 = 1
RS 485-type bus
Optical fibre
Several repeaters are combined to form an active PROFIBUS star coupler. Other repeaters are connected to this via double-wire fibre optic lines. The repeaters of the star coupler are connected below each through electrical channels (electrical star segment).
Kindly note:
For all OZD Profi G12D... ATEX 1, which are con-
nected to the electrical star segment, CH1 must switched to “Monitor off“ mode (S0 = 1). Segmen­tation function of RS 485 channel is thus switched off for this OZD Profi G12D... ATEX 1, for high availability of the electric star.
Page 22
4 Network topologies 4.2 Star topology
22
OZD Profi G12D... ATEX 1 V. 03 07/2014
Fig. 6: Network structure in the redundant optical ring topology
RS 485-type bus
Optical fibre
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
4.3 Redundant optical ring
Ensure that the electrical star segment is carefully
wired. Keep its ex tension as short as possible, in order to prevent interferences in the electrical star segment and from there in the entire network. You may attain this by placing the OZD Profi G12D... ATEX 1 in the star segment directly adjacent to each other on a top-hat rail.
Energise the terminating resistors on both the ends
of the electrical star segments (see chapter 5.4.2, “connection/disconnection of internal terminating resistors”, page 35).
Do not possibly connect any bus station to the
electric star segment.
For enabled path monitoring on the optical channels, monitoring of fibre optic paths is provided by the respec­tively connected OZD Profi G12D... ATEX 1.
Note:
Non-allocated optical channels, which example are pro­vided for subsequent extensions, lead to fibre optic line signalling during enabled path monitoring. You can avoid this error message, wherein, you switch the non-allocated channels to the operating mode “line without fibre optic path monitoring”. Kindly note that optical channels, which are not connect­ed must be always protected with protection caps against external light incidence and dirt.
Page 23
4.3 Redundant optical ring
23
4 Network topologies
OZD Profi G12D... ATEX 1 V. 03 07/2014
This network topology presents a special form of line ­topo logy. High operational safety of the network can be attained by “closing” the optical line.
Monitoring mechanisms:
Transmit echo: yes Monitor echo: yes Suppress echo: yes Segmentation: yes
Interruptions of one or both optical fibres between two repeaters is recognised from the OZD Profi G12D... ATEX 1 and the ring becomes an optical line.
If the repeater breaks down, only terminal equipment or the RS 485 segment connected to this repeaterare uncou­pled from the ring. The rest of the network itself remains functional as a line. Error reporting is done by the LED of both the OZD Profi G12D... ATEX 1 connected to the faulty fibre optic path and through its signalling contact. Segmentation is automatically cancelled as soon as both the repeaters recognise the uninterrupted segmented fieldbus subnetwork with the help of test telegrams. The line again closes to form a ring.
Kindly note:
Following basic conditions must be complied with for proper operation:
Operating mode “redundant optical ring” must be
set on both the optical channels of all OZD Profi G12D... ATEX 1.
All repeaters in the course of ring must be con-
nected to each other via fibre optic lines. There should be no RS 485 bus cable during the course of a ring.
Parameter MIN T
SDR
described in the PROFIBUS standard EN 50170 must be set at value < 11 for all terminal equipment. This is generally the case, however, it must be checked at occurrence of substantial communication interferences.
When configuring your network, select possibly
low bus station addresses, in order to keep poten­tial master time-outs small.
If there is redundancy (e.g. line breakage), it results
into a switching time, during which correct data trans­mission may not be possible. For ensuring shock-free overbridging of the application, it is recommended to set the number of repetitions (retry) of the telegram at minimum 3 for the PROFIBUS master. For ensuring shock-free switching back of the optical line to the optical ring after eliminating the fault, there must be no telegram at this point in the network. This state occurs if a master addresses a device, whose address is configured but is not actually available. The master tries to address this device in cycle and waits for a response (“GAP query”) maximum up to expira­tion of the configured slot time. OZD Profi G12D... ATEX 1 recognises this state and closes the optical line in the middle of this query sequence to the optical ring. Two configuration requirements are produced for the redundant optical ring: – The value of parameters HSA (Highest Station
Address) must be set such for all terminal equip­ment, that between the bus address 0 and the value HSA at least one address in the network is not allo­cated by a bus station, there is at least one address gap. You can get this address gap simply by setting the value of the parameter HSA by at least one high­er than the highest station bus address occurring in the network. Attention: If this requirement is not and/or cannot be fulfilled any longer, the optical line cannot be closed for a redundant optical ring after a segmen­tation. The fault message (LED and signal contact) of the two concerned OZD Profi G12D... ATEX 1 is not taken back after rectification of the fault.
– The slot time must be set at double the value than
for a non-redundant network. Other information is in chapter 6, “configuration”, page 51. Kindly refer to the manufacturers documentation for change in settings of the terminal equipment or con­figuration software.
Page 24
4 Network topologies 4.4 Combination with network topologies of ex-zone 2, 22
24
OZD Profi G12D... ATEX 1 V. 03 07/2014
For transitions between the ex-zones 1, 21 and 2, 22 an optical cable for ex-zone 1, 21 a repeater OZD Profi G12D... ATEX 1 must be used in the ex-zone 1 ,21. Other network segments outside the zone 1, 21 can be imple­mented through its second optical interface with repeaters OZD Profi 12M G11 (PRO), OZD Profi 12M G12 (PRO) or OZD Profi 12M G12 EEC (PRO. All topologies as per chapter 3.1, 3.2 and 3.3 are applied in the individ­ual networks.
4.4 Combination with network topologies of ex-zone 2, 22
RS 485-type bus
Optical fibre
Terminal equipment/
bus segment
OZD Profi 12M ...
PRO
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
Terminal equipment/
bus segment
OZD Profi G12D...
ATEX 1
CH 1
CH 3
SE
CH 2
SE
OZD Profi G12D...
ATEX 1
OZD Profi G12D...
ATEX 1
OZD Profi G12D...
ATEX 1
OZD Profi G12D...
ATEX 1
Building B Ex-Zone 2, 22 OZD Profi G12D... ATEX 1 and OZD Profi 12M ... PRO
Building A Ex-Zone 1, 21 OZD Profi G12D... ATEX 1
RS 485-type bus
Optical fibre
Fig. 7: Example for a transition from the ex-zone 1, 21 to ex-zone 2, 22
Page 25
5.1 Design guidelines
25
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5 Startup
5.1.2 Assembly in zone 2
OZD Profi G12DU ATEX 1 devices shall be installed into an enclosure that complies with one of the following types of protection as a minimum according to the respective field of application : "lncreased Safety", "Flameproof Enclosure" or "Protec­tion by Enclosure". OZD Profi G12DK/DE ATEX 1 devices may be installed in gas-ex in zone 2 or for dust-ex in zone 22.
IP5* must be complied with for non-conductive dust and
IP6* for conductive dust.
The housing cover may be opened for servicing during ongoing operation.
All terminals are covered. The cover may be removed in zone 2 and also in the safe area for servicing. The terminals are then accessible. Non-used inlet openings are to be sealed securely with certified sealing plugs in order to comply with the IP pro­tection class. Likewise, seal inserts appropriate for the respective cable diameter must be used. Excessive force on the glands may endanger the protection class.
5.1.3 Assembly in safe area
The device types can be installed outside the ex-area. The housing cover may be opened for servicing during ongoing operation. Terminals in increased safety are covered. The cover may be removed any time during assembly in safe area.
5.1.1 Assembly in zone 1
OZD Profi G12DU ATEX 1 devices shall be installed into an enclosure that complies with one of the following types of protection as a minimum accord­ing to the respective field of application : "lncreased Safety", "Flameproof Enclosure" or "Protec­tion by Enclosure". OZD Profi G12DK/DE ATEX 1 devices may be installed in gas-ex in zone 1 or for dust-ex in zone 21.
The housing cover may be opened in zone 1 for servicing during ongoing operation. The housing cover for dust-ex in zone 21 is opened only in currentless state or with hot work permit.
Terminals in increased safety are covered. The cover may be removed only if there is no explosion hazard (hot work permit) or circuits are switched to zero potential beforehand. Non-used inlet openings are to be sealed securely with certified sealing plugs in order to comply with the IP pro­tection class. Likewise, seal inserts appropriate for the respective cable diameter must be used. Excessive force on the glands may endanger the protec­tion class.
5.1 Design guidelines
Page 26
5 Startup 5.1 Design guidelines
26
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.1.6 Spatial arrangement of devices and cables
Reduce interference by distance. Likewise a simple as well as effective alternative for reducing interferences is in the spatial separation of interfering and susceptible devices and cable. Inducti­ve and capacitive interferences decrease in the qua­drate of the distance of the involved elements. That means, doubling the distance reduces the effects of the interference by factor 4. If layout considerations right in the planning phase of a building or a control cabinet can generally be very cost-effective.
Standard recommendations for spatial arrangement of devices and cables Recommendations for spatial arrangement of de vices and cables with the aim of ensuring a possibly low mutual inter ference, includes EN 50174–2.
5.1.5 Suppression of switched inductors
Switch switched inductors with suppressors Switching of inductors e.g in relays and fans causes interference voltages, the amount of which is much more than the switched operating voltage. These interference voltages may affect electronic devices. The interference voltages of inductors must be limited to the emission source by switching with suppressors (diodes or RC wiring). Use only interference suppres­sors, which are intended for the relays or fans used by you.
Cabinet lighting Use bulbs for cabinet lighting, e. g. LINESTRA lamps. Avoid using fluorescent lamps as these lamps create interference fields. If fluorescent lamps cannot be used, measures shown in figure 8 must be taken.
Shield grid over the lamp
Shielded cable
metal-encased Switch
Mains filter or shielded mains cable
Fig. 8: Measures against suppression of fluorescent lamps in
the cabinet
5.1.4 Electromagnetic Compatibility (EMC)
The electromagnetic compatibility (EMC) comprises all queries of the electrical, magnetic and electro magnetic spinning and spin-off effects. for avoiding electromagnetic interferences in electrical systems , these effects must be restricted
to a minimum. Limitation measures mainly in clude design and pro per connection of bus cables and the supp ression of switched inductors.
z
Warning!
Interference suppressor must comply with the ATEX directives in the explosive hazard area.
Page 27
5.1 Design guidelines
27
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
Handling sheaths for the bus cables Follow the following measures when sheathing the cables:
- Use universally sheathed cables. The sheaths of these cables must feature sufficient coverage den­sity of the sheath , for complying with the legal requirements for interference emissions and inter­ference immunity.
- Always place the sheaths on both sides of the bus cables. You can fulfill the legal requirements for inter-
ference emission and interference immunity of your device (CE sign) only by connecting both-sided con­nection of the sheath.
- Remove the insulation of the sheath of the bus cable without interruption and place it on a potential equalisation bar. This in turn must be connected via a short cable with the functional earth of
OZD Profi G12D… ATEX 1.
Data transmission line
Potential equalisation
Potential equalisation
Switch panel 1
Switch panel 2
Fig. 9: Laying a potential equalisation cable parallel to the bus cable
Note:
For potential differences between the grounding points an unauthorised high equalising current may flow through the sheath connected on both sides. Do not in any case separate the sheath of the bus cable for rectifying the fault! Following solution is permitted: Lay an additional potential equalisation cable parallel to the bus cable, which accepts the sheath current. For this note “PROFIBUS, technical direc tive, design guidelines PROFIBUS-DP/FMS” (issuer: PROFIBUS Nutzer organisation e.V.).
Page 28
5 Startup 5.1 Design guidelines
28
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.1.7 Execution of sheath connections
Kindly consider following points when laying the cable sheaths:
Fix braid cable sheath with metal cable clamps.
The clamps must extensively enclose the sheath and have a good contact (see Figure 10).
Contact the cables only through the copper braid sheath and not through the aluminium foil sheath. The foil sheath is placed on a plastic foil for increasing the tensile strength and thus non-conductive!
All cable sheaths leading from outside to the protecti­ve housing must be intercepted at the entry point of the protective housing and extensively contacted with the earth of the protective housing.
When removing the cable sheaths ensure that the braid sheath of the cables is not damaged. Tinned or galvanically stabilised surfaces are ideal for a good mutual contact of grounding elements. For tinned sur­faces, the required contacts must be ensured with a suitable gland. Painted surfaces at the point of contact are not suitable.
Sheath catching/contacts must not be used as strain relief. Contact to the shielding bus may deteriorate or tear.
Fig. 10: Fixing sheathed cables with cable clamps and hose clip
(schematic presentation)
Page 29
5.2 Startup process
29
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.2 Startup process
Startup of PROFIBUS Fiberoptic Repeater OZD Profi G12D… ATEX 1 is done in following steps:
Assemble/disassemble repeater
Setting the operating mode, connecting/disconnec­ting the terminating resistors
Connect optical bus cables
Connect electrical bus cables
Connect functional earth
Connect signal contact cables (optional)
Define reception level of optical channels
Connect operating voltage supply
Monitor LED indicators
Page 30
5 Startup 5.3 Assemble/disassemble repeater
30
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.3.1 Assembly of OZD Profi G12DU ATEX 1
The Fiberoptic Repeater OZD Profi G12DU ATEX 1 can be assembled on
- a 35 mm top-hat rail as per IEC 60715: 1981 + A1: 1995 or
- a flat surface (pre-assembled top-hat rail must be unscrewed beforehand).
Assembly on top-hat rail
Select the assembly location such that climatic limit val­ues specified in the technical data are maintained.
Consider adequate space for the connection of bus and supply cables.
For easy installation of the optical fibre connect this to the repeater before the assembly.
Assemble the repeater on the top-hat rail. For this, mount the top latch of the repeater on the top­hat rail and press the lower side
- as shown in figure 11 - on the rail, till the latch engages.
Note:
You may disassemble the repeater from the top-hat rail, wherein, you unlock the snap device as shown in figure 12 with a screwdriver .
5.3 Assemble/disassemble repeater
click !
Fig. 11: Assembling the repeater on a top-hat rail
Fig. 12: Disassembling the repeater from a top-hat rail
Page 31
5.3 Assemble/disassemble repeater
31
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
Assembly on an even base
The repeaters are provided with three mounting brack­ets. These enable assembly on an even base - e.g. on the assembly plate of a control cabinet. It can be installed horizontally or vertically.
Select the assembly location such that climatic limit values specified in the technical data are maintained.
Unscrew the pre-assembled top-hat rail adapter.
Drill three holes in the assembly plate as per the drilling dimensions in figure 14.
Screw the repeater on the base.
Screw Spacer sleeve Washer
Nut
Screw Washer
Nut
Fig. 13: Assembling the repeater on an assembly plate
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
943881321000000001
Ser.-No.: 0123456789
80 30
70 70
30
115
Fig. 14: Drilling dimension OZD Profi G12DU ATEX 1
Page 32
5 Startup 5.3 Assemble/disassemble repeater
32
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.3.2 Assembly of OZD Profi G12DK ATEX 1
The repeater is provided with four semi-circular cutouts at the bottom. These enable assembly on an even base. It can be installed horizontally or vertically.
Select the assembly location such that climatic limit val­ues specified in the technical data are maintained.
Drill four holes in the assembly plate as per the drilling dimensions in figure 16.
Unscrew the housing cover.
Remove the four holders for the cover screws.
Screw the repeater on the base.
Reinstall the four holders for the cover screws.
If required, screw on the housing cover again.
141
152
Fig. 16: Drilling dimension OZD Profi G12DK ATEX 1
Screw
Washer
Fig. 15: Assembling the repeater on an even base
Page 33
5.3 Assemble/disassemble repeater
33
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.3.3 Assembly OZD Profi G12DE ATEX 1
The repeater is provided with two brackets at the bot­tom. These enable assembly on an even base. It can be installed horizontally or vertically.
Select the assembly location such that climatic limit values specified in the technical data are maintained.
Drill two holes in the assembly plate as per the drilling dimensions in figure 18.
Screw the repeater on the base.
215
9797
Fig. 18: Drilling dimension OZD Profi G12DE ATEX 1
Screw
Washer
Fig. 17: Assembling the repeater on an even base
Page 34
5 Startup 5.4 Setting the mode, connection/disconnection of terminating resistors
34
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.4 Setting the mode, connection/disconnection of terminating resistors
Setting of the operating mode and the connection/dis­connection of the terminating resistors is done with the DIP switches. These are on the front side of the OZD Profi G12DU ATEX 1 (see figure 19).
Note: For OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX 1 the DIP switches are accessible after removing the cover.
Note:
The DIP switches S5 and S6 are without functions.
5.4.1 Setting the mode
Kindly note:
If the operating voltage for the repeater is already applied e.g for subsequent reconfiguration, then the operating voltage must be switched off for setting the operating mode.
With the DIP switch S0 the operating mode of the electrical channel CH1 is set.
With the DIP switch S1 and S2 the operating mode of the optical channel CH2 is set.
With the DIP switch S3 and S4 the operating mode of the optical channel CH3 is set.
With the DIP switch S7 the internal terminating resis-
tors are connected and disconnected.
5.4.1.1 Setting the operating mode of the electri-
cal channel (CH1)
Operating mode “electrical channel with segment
monitoring“
CH1 is connected in this operating mode, if S0 is in the OFF position.
Operating mode “electrical channel without
segment moni toring“
CH1 is connected in this operating mode, if S0 is in
the ON position.
Kindly note that the operating
mode should be set only in the star
segment of the star topology.
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
S0S1 S2 S3 S4 S5 S6S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
NICHT UNT ER SPANNUNG ÖFFNEN DO NOT OPEN WH ILE ENERGISED
NE PAS OUVRIR S OUS TENSION
NON APRIR E SOTTO TENSIONE
NÃO ABRIR QU ANDO ENERGIZA DO
943881321000000001
Ser. No.: 0123456789
DIL switch for operating mode and internal terminating resistors
Fig. 19: Location of the DIP switch for OZD Profi G12DU ATEX
1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
Page 35
5.4 Setting the mode, connection/disconnection of terminating resistors
35
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.4.1.2 Setting the operating mode of the optical channels (CH2, CH3)
Operating mode can be set separately for each optical channel. Combinations of the operating modes “Line with and line without fibre optic path monitoring” are possible. Kindly note that operating mode of both the optical chan­nels connected to each other via the fibre optic cable must be always set similar! The operating mode “redundant optical ring” must be always set on both the optical channels.
Operating mode “Line with fibre optic path moni-
toring and segmentation“
CH3 is connected in this operating mo de, if S3 and S4 are in the OFF position. CH2 is connected in this operating mode, if S1 and S2 are in the OFF position.
Operating mode “Line without fibre optic path
moni toring“
CH3 is connected in this operating mode, if S3 is in the ON position and S4 is in OFF position. CH2 is connected in this operating mode, if S1 is in the ON position and S2 is in the OFF position.
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
Operating mode “redundant optical ring“
CH3 is connected in this operating mode, if S3 and S4 are in the ON position. CH2 is connected in this operating mode, if S1 and S2 are in the ON position.
Kindly note that this operating mode must be always set on both optical channels of a module.
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
5.4.2 Connection/disconnection of
internal terminating resistors
If the repeater is at the beginning or end of the bus seg­ment, the internal terminating resistors must be set.
Note: The repeater must not be disconnected when con­necting/disconnecting the terminating resistors.
Internal terminating resistors are connected
if S7 is in the OFF position.
Internal terminating resistors are disconnected
if S7 is in the ON position.
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
S0 S1 S2 S3 S4 S5 S6 S7
CH1 CH2 CH3
1234 567 8
ON OFF
Page 36
5 Startup 5.5 Connect optical bus cables
36
OZD Profi G12D... ATEX 1 V. 03 07/2014
The repeaters are equipped with two optical ports.
Connect the individual repeaters via a duplex fibre optic cable with BFOC/2.5 (ST®) plug-in connectors.
Note the maximum length of the fibre optic cable and the possible fibre types specified in the technical data.
Always ensure that an optical input a and an optical output J are conn ected to each other (cross connec­tion). Associated BFOC sockets of both the ports are iden­tified on the lateral adhesive label.
Lead the fibre optic cable for OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX 1 as shown in figure 20 and figure 21 via cable entries (PG glands).
Note: The PG-glands have slotted seals. The fibre optic connector must not be lead through the seal, however, you can bend open the seal and lay it around the fibre optic cable.
Ensure adequate stress relief of fibre optic cable and note its minimum bending radii.
Do not close the non-allocated BFOC sockets with the provided protective caps. Incident am bient light may interfere with the network, particularly at high ambient light. Penetrating dust may make the optical components unusable.
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
NICHT UNT ER SPANNUNG ÖFFNEN DO NOT OPEN WH ILE ENERGISED
NE PAS OUVRIR S OUS TENSION
NON APRIRE SOTTO TENSIONE
NÃO ABRIR QUANDO ENERGIZADO
943881321000000001
Ser.-No.: 0123456789
Fig. 20: Cable routing of the fibre optic cable for
OZD Profi G12DK ATEX 1
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCF
NOCH3CH2
F
NICHT UNTER SPANNUNG ÖFFNEN DO NOT OPEN WH ILE ENERGISED
NE PAS OUVRIR S OUS TENSION
NON APRIRE SOTTO TENSIONE
NÃO ABRIR QUANDO ENERGIZADO
943881321000000001
Ser.-No.: 0123456789
Fig. 21: Cable routing of the fibre optic cable for
OZD Profi G12DK ATEX 1
5.5 Connect optical bus cables
Page 37
5.6 Connect electrical bus cables
37
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.6 Connect electrical bus cables
z
Warning!
Work on ex-e cables in zone 1 is permitted only with hot work permit or in the current-free state.
The repeaters are equipped with an electrical port with RS 485 level.
The RS 485 bus cables are designed in the protection class ex-e EN 60079-7:2007. They are placed on the front side of the OZD Profi G12DU ATEX 1 on four sepa­rate single terminals (DI A, DI B, DO A and DO B). The terminals have a valid type approval certificate. The con­nections are in duplicate in order to loop through the bus cable through the device.
Note: The terminals are accessible for OZD Profi … DK … and OZD Profi … DE … after opening the protective housing.
Note: If the terminating resistors are not connected, data cable is looped through without signal regeneration through the device.
The RS 485 bus cables RxD/TxD–N and RxD/TxD–P are galvanically separated (functional separation) vis-a-vis the 24 V supply voltage within the SELV limits.
The RS 485 interface is galvanically connected to the potential equalisaton connection.
Connect the RS 485 bus cable and its cable shield to the terminal block, see fig 22.
Note:
Ensure that bus segments connected to the 485 inter face are terminated on both the ends.
Use only shielded pair cables as RS 485 bus cable
Ensure adequate stress relief of RS 485 bus cable and consider its minimum bending radii.
Remove RS 485 bus cable from OZD Profi, if no device is connected on the other cable-end or the same has been switched currentless. The open cable otherwise works as an antennae and can couple interferences.
Follow the following sequence when connecting a RS 485 bus cable to the OZD Profi G12D… ATEX 1 for an active network, in order to minimise the disturbances : attach 1. RS 485 bus connector to the device to be connected (e.g. on the programming unit) and screw on tightly.
2. Install RS 485 bus cables on OZD Profi G12D… ATEX 1 . Proceed in the reverse sequence when removing a repeater from the network.
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
943881321000000001
Ser. No.: 0123456789
Shield
Incoming
Bus line
Outgoing Bus line
Shield
Fig. 22: Terminal block - connections of the electrical bus
cables for OZD Profi G12DU ATEX 1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
Page 38
5 Startup 5.6 Connect electrical bus cables
38
OZD Profi G12D... ATEX 1 V. 03 07/2014
z
Warning!
OZD Profi G12DU ATEX 1: The sheath of the data cable must be connected in the control cabinet together with the functional earth connection to a potential equalisation bar. OZD Profi … DK … and OZD Profi … DE … : The connection for the functional earth on the housing must be connected to the potential equal­isation bar. The potential equalisation bars of the control cabi­nets, which are mutually connected via an electri­cal RS 485, must be connected mutually at low­resistance.
z
Warning!
Do not connect any RS 485 bus cables, which are laid wholly or partially outside the building. Otherwise, lightning strikes in the area may destroy the repeater. Establish the bus connections, leave the build ing with fibre optic cable!
z
Warning!
There is no galvanic separation between the bus cables and the functional earth connection. Hence follow the follow ing safety infor mation:
Do not connect the repeater via bus cables with system parts, having a different earth potential. The potential differences may lead to destruction of the repeater!
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
943881321000000001
Ser.-No.: 0123456789
Fig. 23: Cable lead-through of the electrical bus cables for OZD
Profi G12DK ATEX 1 (OZD Profi ... DE ... : analog)
Lead both the RS 485 cables OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX as shown in figure 23 through the two cable entries (PG-glands).
Page 39
5.7 Connect functional earth
39
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
Functional earth
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
943881321000000001
Ser. No.: 0123456789
5.7 Connect functional earth
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
Functional earth
Fig. 24: Terminal block - connection of functional earth for
OZD Profi G12DU ATEX 1
Fig. 25: Connection of the functional earth for OZD Profi G12DK
ATEX 1 (OZD Profi ... DE ... : analog)
z
Warning!
Work on ex-e cables in zone 1 is permitted only with hot work permit or in the current-free state.
The repeaters are equipped with connection for the func­tional earth.
The functional earths are designed in the protection class ex-e EN 60079-7:2007. It is placed on the front side of the OZD Profi G12DU ATEX 1 on a separate single termi­nal (FG). The terminal has a valid type approval certifi­cate.
Note: For OZD Profi … DK … and OZD Profi … DE … the cables are lead on a terminal accessible from outside (see fig 25).
Connect the cable for the functional earth for OZD Profi … DK …to the terminal block (see fig 24), for OZD Profi G12DK ATEX 1 and OZD Profi G12DU ATEX 1 (see fig 25) to the terminal accessible from outside.
Ensure adequate stress relief of the cables and note its minimum bending radii.
Page 40
5 Startup 5.8 Connect signal contact cables (optional)
40
OZD Profi G12D... ATEX 1 V. 03 07/2014
5.8 Connect signal contact cables (optional)
z
Warning!
Work on ex-e cables in zone 1 is permitted only with hot work permit or in the current-free state.
The repeaters are equipped with a signalling contact connection.
The signalling contact connection is designed in the igni­tion protection ex-e EN 60079-7:2007. The connection cables are placed on the front side of the OZD Profi G12DU ATEX 1 on three separate single terminals (F NO, F NC and F). The terminals have a valid type approval certificate.
Note: The terminals are accessible for OZD Profi … DK … and OZD Profi … DE … after opening the protective housing.
Connect the signalling contact cable to the terminal block, see fig 26.
Lead the signalling contact cable for OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX as shown in figure 27 through the cable entries (PG-glands).
Ensure adequate stress relief of the cables and note its minimum bending radii.
z
Warning!
Limit values of the relay contact – maximum switching voltage:32 V – maximum switching current: 1.0 A – maximum switching capacity: 30 W
Voltage connected to the relay must be a safety low voltage as per IEC 950/EN 60 950/ VDE 0805 and according to the UL/CSA approval must com­ply with the regulations of NEC, class 2.
Kindly ensure correct connection allocation of the terminal block. Ensure adequate electrical iso lation of the connection cables of the signalling contacts. Faulty allocation may destroy the repeater.
Breakdowns of the network and the repeater can be sig­nalled by the signalling contact connection.
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
FAU LT
F
F
NO
F
NC
FAULT
Fig. 26: Terminal block - connection of the signalling contact
cables for OZD Profi G12DU ATEX 1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
Fig. 27: Cable lead-through of the signalling contact for OZD
Profi G12DK ATEX 1 (OZD Profi ... DE ... : analog)
S0S1 S2 S3 S4 S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
943881321000000001
Ser.-No.: 0123456789
Page 41
5.8 Connect signal contact cables (optional)
41
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
z
Warning!
Work on ex-e cables in zone 1 is permitted only with hot work permit or in the current-free state.
The repeaters are equipped with measuring points for two analog voltage for diagnosis.
The analog voltage outputs are designed in the protecti­on class ex-e EN 60079-7:2007. They are placed on the front side of the OZD Profi G12DU ATEX 1 on three separate single terminals (CH 2, CH 3 and CH 0V). The terminals have a valid type approval certificate.
Note: The terminals are accessible for OZD Profi … DK … and OZD Profi … DE … after opening the protective housing.
The reception level of the two optical channels CH 2 and CH 3 can be determined with a standard volt meter on the terminal block (see fig 27 and 28). The OZD Profi G12D… ATEX 1 is protected against a short-circuit on the terminals, brief interruption of data transmission is however possible*.
With that – the incoming optical power is documented , e.g. for subsequent measurements (aging, dam age) – a good/bad check can be conducted (limit value).
Further information is in appendix A.1, “Determine recep­tion level of the optical channels“ page 57.
* Measurement is done with a floating, high impedance
voltmeter. The reference potential socket must not be connected to the housing of the OZD Profi 12M ….
5.9 Define reception level of optical channels
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
CH 2
Fig. 28: Terminal block - reception level for CH 2 for OZD Profi
G12DU ATEX 1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
CH 3
Fig. 29: Terminal block - reception level for CH 3 for OZD Profi
G12DU ATEX 1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
In an error-free operation, the connections F and FNC (NC -> normally connected) are connected mutually by an internal relay contact. At occurrence of an error or dis­connected supply voltage, F and FNO (NO -> normally open) are mutually connected.
Kindly refer to chapter 6.1 “LED indicators“, page 45 for breakdowns signalled with the signalling contact.
Page 42
5 Startup 5.10 Connect operating voltage supply
42
OZD Profi G12D... ATEX 1 V. 03 07/2014
z
Warning!
Work on ex-e cables in zone 1 is permitted only with hot work permit or in the current-free state.
The repeaters are equipped with a connection for two independent operating voltages.
The supply voltage connection is designed in the ignition protection ex-e EN 60079-7:2007. The connection cables are placed on the front side of the OZD Profi G12DU ATEX 1 on three separate single termi­nals (24 V, 24 V* and 0V). The terminals have a valid type approval certificate. The 4 connections of the double terminal for the 0V con ­nection are galvanically connected to each other, colour gray, ex-e.
Note: The terminals are accessible for OZD Profi … DK … and OZD Profi … DE … after opening the protective housing.
Connect the cables for the operating voltage supply to the terminal block, see fig 30.
Lead the RS cable for the operating voltage for OZD Profi G12DK ATEX 1 and OZD Profi G12DE ATEX as shown in figure 31 through the cable entries (PG glands).
Ensure adequate stress relief of the cables and note its minimum bending radii.
z
Warning! Supply the module only with a stable safety low voltage as per IEC 950/EN 60 950/VDE 0805 of
maximum +32 VDC (typ. +24 VDC). Voltage source must comply with NEC, class 2 as per the UL/CSA approval.
For increasing the operational safety, the module can be supplied redundant through terminals 0 V and 24 V* . At breakdown of the reg ul ar supply voltage the module automatically switches to the redundant operating vol ­tage supply. There is no load distribution between indi­vidual supply options. The signalling contact does not signal the breakdown of an individual 24 V supply. For monitoring, like the sig­nalling contact, both the supplies must be placed on an input module.
5.10 Connect operating voltage supply
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
0 V /
+24 V
0 V / +24 V*
Fig. 30: Terminal block - connection of the supply voltage for
OZD Profi G12DU ATEX 1 (OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
S0S1 S2 S3 S4S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
24V*24
V
DIBDI
A
0V0V FG FG
DOBDO
A
CH 0V
FNCFNOCH3CH
2
F
943881321000000001
Ser.-No.: 0123456789
Fig. 31: Cable lead-through of the supply voltage for OZD Profi
G12DK ATEX 1 (OZD Profi ... DE ... : analog)
Page 43
5.11 Monitor LED indicators
43
5 Startup
OZD Profi G12D... ATEX 1 V. 03 07/2014
LEDs for diagnosis are on the front side of the device of OZD Profi G12DU ATEX 1 . You can find the meaning in chapter 6.1, LED­indicators, page 45.
Note: For OZD Profi … DK … and OZD Profi … DU … the LEDs are visible after opening the protective housing.
Note: For the OZD Profi … DK … a housing cover with a window is provided as an accessory, so that the LEDs are always visible.
5.11 Monitor LED indicators
Page 44
5 Startup
44
OZD Profi G12D... ATEX 1 V. 03 07/2014
Page 45
6.1 LED indicators
45
6 Troubleshooting
OZD Profi G12D... ATEX 1 V. 03 07/2014
6 Troubleshooting
Fig. 32: LED indicators for OZD Profi G12DU ATEX 1
(OZD Profi ...DK ... and OZD Profi ... DE ... : after opening the housing)
S0 S1 S2 S3 S4 S5 S6 S7
System
CH1
CH2
CH3
CH3
CH2
943881321000000001
Ser.-No. : 0123456789
Possible reasons
– The transmission speed was detected and the voltage supply is ok
– Breakdown of the voltage supply (total breakdown*) – Supply voltage wrongly connected – Defective module
Transmission rate not yet detected – No transmitting bus station available – No connection to a telegram transmitting partner module – Transmitting and receiving fibre optics are swapped – Transmission rate does not comply with the PROFIBUS standard – Only one active bus station is connected, which transmits token only to itself.
After connecting a second bus station the indicator must change (token tele ­grams alone are not adequate for setting the transmission rate).
– The connected RS 485 segment is closed only on one side
Transmission rate detected but – The slot time of the network could not be determined (network parameter
HSA set very low, no transmitting bus station avail able)
– An optical channel is set at mode “redundant optical ring“, but not the sec-
ond one (this operating mode must be always set at both optical channels)
– The slot time of the network is set at a very low value
* for redundant supply breakdown of both supply voltages
LED indicators
System
glows greendoes not glow
blinks red
blinks red/green
Signalling contact
does not respond
responds
does not respond
does not respond
6.1 LED indicators
Page 46
6 Troubleshooting 6.1 LED indicators
46
OZD Profi G12D... ATEX 1 V. 03 07/2014
Possible reasons
Signals are received on RS 485 bus cable.
– Bus station is not connected – Connected bus station is not switched on – Interruption of one or both wires of the RS 485 bus cable
Sporadic interferences through – Inadequate sheathing of the RS 485 bus cable – Open, i.e. RS 485 bus cable connected only on one side to the module – RS 485 segment not connected or connected only on one side – Pull/insert a RS 485 bus terminal or terminal plug Constant interference due to – Wires A and B of the RS 485 bus cable are swapped – Short circuit on the RS 485 bus cable – Transmission timeout caused by a bus station, which is in a bus segment
connected to channel 1
– Module and a bus station connected through channel 1 transmit simulta -
neously (e.g. due to duplicate address allocation or very little set slot time or when removing the segmentation in the optical line, see chap. 4.1.1, page 20)
– RS 485 driver of the module is defective (e.g. after lightning)
PROFIBUS telegrams are received on the optical channel
Operating mode “Line with fibre optic path monitoring“ and
“redundant optical ring“
Transmission rate is not yet detected - “LED” blinks red – No transmitting bus station available – Transmitting and receiving fibre optics are swapped – No partner module connected or partner module is not switched on – Connected partner module defective
Transmission rate is detected - LED “system” glows green – If operating mode “redundant optical ring“ is set, the
optical channel functions as standby channel There is no malfunction in the OZD Profi or on the fibre optic
– If one of the operating modes “Line fibre optic path monitoring …“ is set, no
PROFIBUS telegrams are received on the optical channel. There is no mal­function in the OZD Profi or on the fibre optic.
Transmission rate is detected - LED “system” glows green or blinks red/green – There is no transmitting bus station (fibre optic connection is ok)
– Transmitting and receiving fibre optics are swapped – No partner module connected or partner module is not switched on – Connected partner module defective – Transmission timeout of the connected partner module – Interruption of a fibre optic cable – Fibre optic path to partner module is longer than allowed – Loose connection on a fibre optic connector – Optical fibre in the fibre optic connector is loose – If on a redundant optical ring the channel LED glows red even after rectifica-
tion of fibre optic failure, check whether setting of parameter HSA described in chap. 4.3 page 22 has been complied with.
– Periodically occurring error (see above) – Loose connection on a fibre optic connector – Optical fibre in the fibre optic connector is loose – Only one active bus station is connected, which transmits token only to itself.
After connecting a second station, no error should be displayed
Operating mode “Line without fibre optic path monitoring”
Signals are received on the optical channel
– No transmitting bus station available – Transmitting and receiving fibre optics are swapped – No partner module connected or partner module is not switched on – Connected partner module defective
LED indicators
CH1
glows yellow
electric
does not glow
blinks/glows red
CH2, CH3
glows yellow
optical
does not glow
blinks yellowglows red
blinks red/yellow
glows yellow does not glow
Signalling contact
does not respond
does not respond
responds
does not respond
does not respond
does not respond
does not respond
responds
responds
does not respond
does not respond
Table 1: Meaning of LED indicators and signalling by signal contact
Page 47
6.1 LED indicators
47
6 Troubleshooting
OZD Profi G12D... ATEX 1 V. 03 07/2014
This chapter provides you help to locate the location of error after error signalling (LED or signal contact). For this kindly note the description of the LED indicators in chapter 6.1, pag 45.
6.2 Fault finding
Error display in the system LED
See description of LED indicators in chapter 6.1, page 45.
Error display on CH1
Check whether
the DIP switch is in the ON position, if the OZD Profi on the electric star segment is on a star topology. (see chapter 4.2, “Star topology“, page 21)
the error pattern can be seen even after disconnecting the electrical bus stations. Also: device defective”. Replace the OZD Profi. No longer exists: The interference is from the RS485 bus segment.
Check – the structure and the shielding of the RS485
bus segment
– the RS485 bus segment with a PROFIBUS bus
monitor
– configuration of all bus stations.
* Is not applicable, if the monomaster of a PROFIBUS network is connected to a RS485 bus segment that is to be checked In this case replace the conspicuous OZD profi with another OZD Profi of the network and subsequently execute the above test.
If the error migrates with the OZD Profi, there is a defect in the device. Replace the OZD Profi.
If the error does not migrate with the OZD Profi, then the interference is from the RS485 bus segment. Execute measures as described above.
Error display on CH2 / CH3
1. Check whether
optically only repeaters of the same type are connect­ed mutually (see chapter 4, “network topologies” page 19).
he optical fibre is permitted for the used module type and the permitted length is not exceeded
optical channels, which are mutually connected, have the same operating mode set. (see chapter 5.4; “set­ting the operating mode, connect/disconnect termi­nating resistors“, page 34)
when connecting and laying the optical bus cables, specifications in 5.5 “connect optical bus cables” page 36 were complied with.
2. Determine the optical reception level (see Appendix A.1,”determine reception level of the optical chan­nels“, page 57):
– Level is in the range “Function not guaranteed“.
Check the optical fibre attenuation with an opti­cal level measuring device. very high: Replace optical fibre within the One of the two OZD Profi of the valid range: faulty fibre optic segment is defective.
First replace the other OZD Profi of the faulty fibre optic segment (i.e. the OZD Profi, which delivers the transmission ­signal to the above measurement). If the error persists, instead of this replace the other OZD Profi.
– Level is in the range “optical system reserve
reduced“ or “normal operation“.
As described above, check the optical reception level of the other OZD Profi of the faulty fibre optic segment on the appropriate channel.
Page 48
6 Troubleshooting 6.1 LED indicators
48
OZD Profi G12D... ATEX 1 V. 03 07/2014
If the transmission in the RS 485 network is not satisfacto­ry even after clarification of points in chapter 6.2 , “fault finding”, page 47, send your replies to the following queries as well as the requested documents to our ser­vice hotline (contact address: see chapter 6.4, page 49):
1. Precise type description of OZD Profi G12D… ATEX
1. Kindly specify the 18 digit number printed on the device for clear identification.
2. Does the bus system to be transmitted comply with standard RS 485 in the physical interface?
3. Does the bus access method of the used bus system ensure that only station on the bus can be accessed at any point of time? Attention! collision-afflicted access methods (e.g. CAN) are not permitted!
4. Does the fieldbus system work in “half duplex-“ or “full duplex“ procedure?
5. Give a possibly detailed error description in your own words.
6. Send a detailed network plan with – the fibre type and the fibre length – the location and the length of the electrical
seg ments,
– the values, the type and the position of the
termination on the electrical bus segment.
7. Which data rate is used?
8. How are the DIP switches set for the individual OZD Profi G12D… ATEX 1 ?
9. What is the status of the LEDs on the concerned OZD Profi G12D… ATEX 1?
10. Specify the voltage value of the analog voltage out­puts (terminal Ua2 and Ua3 on the 3 pole terminal block on the front side of the device) of the con­cerned port.
11. Name and manufacturer of the fieldbus system?
Important!
We cannot process your request without complete details on questions 1 to 11!
Note:
The current version of this manual is on the Internet under http://www.hirschmann.com/ through the product search for product. The version of the manual is on every page of the manual at the bottom opposite the page number.
6.3 Problem report
– Level is on both OZD Profi of the faulty fibre optic
segment in the range “optical system reserve reduced“ or “normal operation“: one of the two OZD Profi of the faulty fibre optic segment is defective.
First replace a OZD Profi of the faulty fibre optic segment. If the error persists, instead of this replace the other OZD Profi.
Page 49
6.3 Problem report
49
6 Troubleshooting
OZD Profi G12D... ATEX 1 V. 03 07/2014
Contact address for technical support
Hirschmann Automation and Control GmbH Stuttgarter Strasse 45 - 51 72654 Neckartenzlingen Germany
Tel.: +49 (0)1805 14 1538 E-Mail: HAC.Support@Belden.com Internet: http://www.hirschmann.com
6.4 Contact address
Page 50
6 Troubleshooting
50
OZD Profi G12D... ATEX 1 V. 03 07/2014
Page 51
7.1 Configuration of redundant optical rings
51
7 Configuration
OZD Profi G12D... ATEX 1 V. 03 07/2014
7 Configuration
Due to the telegram delays through cables and network components and through monitoring mechanism in the network components, when configuring the PROFIBUS
network parameter “slot time“ must be adapted to the network extension, network topology and the data rate.
In the redundant optical ring following config uration con­ditions must be fulfilled (details see chapter 4.3, “redun­dant optical ring“, page 22):
(1) Configuration of a non-available bus station
(2) Increase in retry value to minimum value 3
(3) Reviewing and adjusting the slot time
For setting the parameter under (2) and (3) use user-spe­cific profile of the configuration tools.
Calculate the slot time according to the following equation:
Slot time = a + (b .Length
of the fibre optic
) + (c .number
OZD
)
“Slot time” is the monitoring time in bit times
“Length
fibre optic
“ is the total of all fibre optic
cables (segment lengths) in the network. Length specification must in km !
“Number
OZD
is the number ofOZD Profi
G12D... ATEX 1 in the network.
Factors a, b and c depend upon the transmission speed and can be inferred from the following table.
7.1 Configuration of redundant optical rings
Data rate a b c
12 MBit/s
1)
1651 240 28
6 MBit/s
1)
951 120 24
3 MBit/s
1)
551 60 24
1,5 MBit/s 351 30 24 500 kBit/s 251 10 24 187,5 kBit/s 171 3,75 24
93,75 kBit/s 171 1,875 24 45,45 kBit/s 851 0,909 24 19,2 kBit/s 171 0,384 24
9,6 kBit/s 171 0,192 24
Table 2a: Constants for calculating the slot time for
DP standard (redundant optical ring)
Data rate a b c
12 MBit/s
1)
1651 240 28
6 MBit/s
1)
951 120 24
3 MBit/s
1)
551 60 24
1,5 MBit/s 2011 30 24 500 kBit/s 771 10 24 187,5 kBit/s 771 3,75 24
93,75 kBit/s 451 1,875 24 45,45 kBit/s 851 0,909 24 19,2 kBit/s 181 0,384 24
9,6 kBit/s 171 0,192 24
Table 2b: Constants for calculating the slot time for DP/FMS
(“Universal“) and DP with S595U (redundant optical ring)
Page 52
7 Configuration 7.1 Configuration of redundant optical rings
52
OZD Profi G12D... ATEX 1 V. 03 07/2014
The slot time calculation considers only the optical net­work and the connection of bus stations to the OZD Profi through max. 20 m length RS 485 bus segment. Longer RS 485 bus segments must be calculated additionally, wherein, they are added to the Length
fibre optic
.
Note:
If the slot time is calculated with a very low value, it may lead to malfunctions and error displays on OZD Profi 12M …. The system LED blinks red/green.
Page 53
53
8 Technical data
OZD Profi G12D... ATEX 1 V. 03 07/2014
OZD Profi G12 … DU ATEX 1 DK ATEX 1 DE ATEX 1
power supplies
Operating voltage 18 V to 32 VDC, typ. 24 VDC, (redundant inputs decoupled),
Safety low voltage, galvanically separated Power consumption max. 200 mA Power input 5 W Signalling contact
Maximum witching voltage 60 VDC; 42 VAC safety low voltage), galvanically separated from
housing and all electric connections
Maximum switching current 1.0 A
Signal transmission
Transmission speed 9.6; 19.2; 45.45; 93.75; 187.5; 500 kBit/s
1.5; 3; 6; 12 Mbit/s Adjustment of transmission speed automatic Bit error rate <10
-9
Signal processing time (any input/output) < 6.5 t
bit
Retimer
Input channel 1 to 3
Signal distortion ±30 % Bit length ±0,12 %
Output channel 1 to 3
Medium bit length ±0,01 %
Electric channel
Input/output signal RS 485 level Input resistance –10 V to + 15 V
Optical channels
Wave length 860 nm Launchable optical power
– in glass fibre G 50/125 –15 dBm – in glass fibre G 62.5/125 –13 dBm
Optical input min. –28 dBm Transmission limit receiver –3 dBm Bridgeable distance
– with glass fibre G 50/125 0 - 3000 m
1)
(860 nm: 3.0 dB/km)
– with glass fibre G 62.5/125 0 - 3000 m
1)
(860 nm: 3.5 dB/km)
Plug-in connector B/2.5
8 Technical data
Page 54
8 Technical data
54
OZD Profi G12D... ATEX 1 V. 03 07/2014
OZD Profi G12 … DU ATEX 1 DK ATEX 1 DE ATEX 1
Electromagnetic Compatibility (EMC)
Emitted immunity Limit class A (EN 55022), FCC CFR 47 part 15, Class A Interference immunity against static discharge on shield connection and housing parts: ±4 kV contact discharge
(EN 61000-4-2)
Interference immunity against high – 10 V/m at 80% amplitude modulation with 1 kHz, frequency radiation – 80 MHz - 1 GHz (EN 61000-4-3)
–10 V/m with 50% duty cycle at 900 MHz (ENV 50204) –10 V/m at 80% amplitude modulation with 1 kHz,
10 kHz - 80 MHz
Interference immunity against conducted On power supply lines and sheathed disturbances (burst) RS 485 bus cables: ±2 kV (EN 61000-4-4)
Interference immunity against conducted – On power supply lines: ±1 kV symmetric disturbances (surge voltage, surge) – On sheathed RS 485 bus cables:: ±2 kV asymmetric
(EN 61000-4-5)
Climatic ambient conditions
Ambient temperature –20 °C to + 60 °C (IEC 60068-2-1, IEC 60068-2-2) Storage temperature –40 °C to + 70 °C (IEC 60068-2-14) Relative humidity 10 % - 100 % Air pressure Operation: to 2000 m (795 hPa)
Transport and storage: to 3,000 m (700 hPa)
Pollution degree 2
Explosion protection
EC-type examination certification PTB 09 ATEX 2044 X PTB 09 ATEX 2045 PTB 09 ATEX 2045 Fibre optic inherent safe Ignition protection II 2 (1) G Ex mb e [ia] opis II, IIC, IIB T4/T6
- II 2 (1) D Ex tD A21 II 2 (1) D Ex tD A21 IP 66 T 130 °C IP 66 T 130 °C
Cable glands
Supply voltage
Number of glands - 2 2 Diameter of gland - M 20 M 20 Permissible cable diameter - 5.5 - 13 mm 5.5 - 13 mm
Signalling contact
Number of glands - 1 Diameter of gland - M 16 M 16 Permissible cable diameter - 5.5 - 10 mm 5.5 - 10 mm
RS 485 bus cable
Number of glands - 2 2 Diameter of gland - M 16 M 16 Permissible cable diameter - 5.5 - 10 mm 5.5 - 10 mm
Optical connections
Number of glands - 2 2 Diameter of gland - M 20 M 20 Permissible cable diameter - 6.4 - 13 mm 6.4 - 13 mm
Not used
Number of glands - 1 1 Diameter of gland - M 16 M 16 Permissible cable diameter - 5.5 - 10 mm 5.5 - 10 mm
Functional earth - fixed mount fixed mount
connection connection
Page 55
55
8 Technical data
OZD Profi G12D... ATEX 1 V. 03 07/2014
OZD Profi G12 … DU ATEX 1 DK ATEX 1 DE ATEX 1
Test torques
Cover screws - 2.50 Nm 2.50 Nm Pressure screw of cable entry M12 - 1.65 Nm ­Pressure screw of cable entry M16 - M20 - 2.50 Nm ­Pressure screw of cable entry M25 - 3.50 Nm ­Pressure screw of metal ex-e cable entry M16 - - 7.5 Nm
Type E1WF/e, (ex-e)
Pressure screw of metal ex-e cable entry M20 - - 10 Nm
Type E1WF/e, (ex-e)
Pressure screw of metal ex-e cable entry M25 - - 15 Nm
Type E1WF/e, (ex-e)
Protection class IP 40 IP 66 IP 66 Dimensions (B x H x T) see chapter 5.3, page 31 Housing Encapsulation cup Plastic housing Stainless steel
housing
Mass approx. 1.5 kg approx. 2.4 kg approx. 3.7 kg
1) Depending upon the optical performance record, the path length between two OZD Profi must not be exceeded in any case.
Page 56
8 Technical data
56
OZD Profi G12D... ATEX 1 V. 03 07/2014
9 Accessories
OZD SFK ATEX, Order no. 943 884-001
Housing cover with window for OZD Profi G12DK ATEX 1.
For replacing the housing cover (without window) of OZD Profi G12 DK ATEX 1.
Page 57
A.1 Define reception level of optical channels
57
8 Technical data
OZD Profi G12D... ATEX 1 V. 03 07/2014
A Appendix
A.1 Define reception level of optical channels
Fig. 33: Relation between the output voltage on the terminals CH2 and CH3 and the signal quality at port 2 or port 3
Normal operation
0 100 200 300 400 500 600 700 800 900
Output voltage [mV]
Signal
quality
good
critical
bad
Optical system reserve reduced
Function not guaranteed
Warning threshold, defined by software
Fixed alarm level of the relay
Note:
For a valid measuring value it is necessary that the partner-OZD Profi transmits regular PROFIBUS telegrams at the other end of fibre optic. This can be recognised from the LED image of the partner-OZD Profi (see chap. 6.1, “LED­indica tors“, page 45).
Output voltages on the measuring outlets are influenced by many influence factors like e.g.:
Strength of the transmission power of the partner OZD ProfiAmbient temperature of the optical transmitter and the receiverAttenuation of the transmission pathUsed transmission rate
The measuring outlets are hence not planned as replacement of calibrated level measuring device with calibrated light. The read-out value is only used for classifying the received optical signal in the 3 classes
good (Normal operation)critical (Optical system reserve reduced)bad (Function not guaranteed)
Measurement must be done with a standard floating and high impedance voltmeter. A connection to the housing of OZD Profi G12D... ATEX 1 is permitted neither by the measuring outputs nor the reference potential.
Page 58
Hirschmann Automation and Control GmbH Stuttgarter Strasse 45 - 51 72654 Neckartenzlingen Germany
Tel.: +49 (0)1805 14 1538 E-Mail: HAC.Support@Belden.com Internet: http://www.hirschmann.com
039 677-001-E-03-0714 Printed in Germany
Loading...