BEKA BA304NE, BA324NE User Manual

Page 1
BA304NE & BA324NE
Type n
loop-powered
field mounting indicators
14
th
December 2011
Issue: 2
Page 2
2
CONTENTS
1. Description
2. Operation
2.1 Controls
3. Certification
3.1 ATEX Ex nA certification
3.2 Zones, gas groups & T rating
3.3 4/20mA input
3.4 Certification label information
4. System Design for Zone 2 Gas Hazardous Areas
4.1 Transmitter loops
4.2 Remote indication
5. Installation
5.1 Location
5.2 Installation procedure
5.3 EMC
6. Configuration and Calibration
6.1 Summary of configuration functions.
6.2 Indicator function
6.3 Resolution
6.4 Position of decimal point
6.5 Calibration using an external current source.
6.6 Calibration using internal reference.
6.7 Bargraph format and calibration
6.8 Function of the P push button
6.9 Tare function
6.10 Security code
6.11 Reset to factory defaults
6.12 Under and over-range
8. Maintenance
8.1 Fault finding during commissioning
8.2 Fault finding after commissioning
8.3 Servicing
8.4 Routine maintenance
8.5 Guarantee
8.6 Customer comments
9. Accessories
9.1 External keypad
9.2 Units of measurement and instrument identification.
9.3 Alarms
9.3.1 Solid state output
9.3.2 Type nA certification
9.3.3 Configuration and adjustment.
9.3.4 Alarm enable
9.3.5 Setpoint adjustment
9.3.6 Alarm function
9.3.7 Alarm output status
9.3.8 Hysteresis
9.3.9 Alarm delay
9.3.10 Alarm silence time
9.3.11 Flash display when alarm
occurs.
9.3.12 Access setpoint in display
mode.
9.3.13 Adjusting alarm setpoint from
the display mode.
9.3.14 Displaying setpoints on
BA324NE bargraph.
9.4 Display backlight
9.4.1 Loop powering the backlight
9.4.2 Separately powering the
backlight.
9.5 Pipe mounting kits
7. Lineariser
Appendix 1 ATEX dust certification
7.1 Lineariser calibration using an external current source.
Appendix 2 IECEx gas and dust certification
7.2 Lineariser calibration using internal reference.
7.3 Lineariser error message
7.4 Under and over-range
7.5 Lineariser default configuration
The BA304NE & BA324NE are CE marked to show compliance with the European Explosive Atmospheres
Directive 94/9/EC and the European EMC Directive 2004/108/EC
Page 3
3
1. DESCRIPTION
These field mounting, Type nA certified, digital indicators display the current flowing in a 4/20mA loop in engineering units. They are loop powered but only introduce a 1.2V drop, which allows them to be installed into almost any 4/20mA current loop. No additional power supply or battery is required.
The two models are electrically similar, but have different size displays.
Model Display
BA304NE 4 digits 15mm high
BA324NE 5 digits 11mm high and 31 segment
bargraph.
This instruction manual supplements the instruction sheet supplied with each instrument.
The main application of both models is to display a measured variable or control signal in a Zone 2 gas hazardous area or a Zone 22 dust hazardous process area. The zero and span of the display are independently adjustable so that the indicator can be calibrated to display any variable represented by the 4/20mA current, e.g. temperature, flow, pressure or level.
2. OPERATION
Fig 1 shows a simplified block diagram of both models. The 4/20mA input current flows through resistor R1 and forward biased diode D1. The voltage developed across D1, which is relatively constant, is multiplied by a switch mode power supply and used to power the instrument. The voltage developed across R1, which is proportional to the 4/20mA input current, provides the input signal for the analogue to digital converter.
Each time a 4/20mA current is applied to the instrument, initialisation is performed during which all segments of the display are activated, after five seconds the instrument displays the input current using the calibration information stored in the instrument memory. If the loop current is too low to power the instrument the indicator will display the error message ‘LPLo’.
Both models have Ex nA and Ex tc certification issued by Notified Body Intertek Testing and Certification Ltd which has been used to confirm complance with the European ATEX Directive 94/9/EC.
For international applications the two indicators have IECEx certification which is described in Appendix 2.
Fig 1 Indicator block diagram
Page 4
4
2.1 Controls
The indicators are controlled and calibrated via four push button switches located behind the instrument control cover, or as an option on the control cover. In the display mode i.e. when the indicator is displaying a process variable, these push buttons have the following functions:
P While this button is pushed the
indicator will display the input current in mA, or as a percentage of the instrument span depending upon how the indicator has been conditioned. When the button is released the normal display in engineering units will return. The function of this push button is modified when optional alarms are fitted to the indicator.
▼ While this button is pushed the
indicator will display the numerical value and analogue bargraph* the indicator has been calibrated to display with a 4mA
Φ
input. When released the normal display in engineering units will return.
3. CERTIFICATION
Both models have ATEX and IECEx gas and dust certification. This section of the instruction manual describes ATEX gas certification. ATEX dust approval is described in Appendix 1 and IECEx certification in Appendix 2.
3.1 ATEX Ex nA certification
Notified Body Intertek Testing and Certification Ltd have issued both instruments with a common Type Examination Certificate number ITS11ATEX47255. This has been used to confirm compliance with the European ATEX Directive for Group II, Category 3GD equipment. The indicators bear the community mark and subject to local codes of practice may be installed in any of the European Economic Area (EEA) member countries. ATEX certificates are also acceptable for installations in Switzerland.
This section of the instruction manual describes ATEX installations in explosive gas atmospheres conforming with EN60079-14 Electrical Installations in Hazardous Areas. When designing systems for installation outside the UK the local Code of Practice should be consulted.
▲ While this button is pushed the
indicator will display the numerical value and analogue bargraph* the indicator has been calibrated to display with a 20mA
Φ
input. When released the normal display in engineering units will return.
E No function in the display mode unless
the tare function is being used.
P + ▼ Indicator displays firmware number
followed by version.
P + ▲ Provides direct access to the alarm
setpoints when optional alarms are fitted to the indicator and the ‘ACSP’ access setpoints in display mode function has been enabled.
P + E Provides access to the configuration
menu via optional security code.
Notes: * BA324NE only
Φ
If the indicator has been calibrated using the CAL function, calibration points may not be 4 and 20mA.
3.2 Zones, gas groups and T rating
The indicators have been certified as Group II Category 3G Ex nA ic IIC T5 Gc apparatus with a Ta of –40ºC to +70ºC. This is non-sparking apparatus complying with EN 60079-15 that minimises the risk of arcs or sparks capable of creating an ignition hazard occurring during conditions of normal operation.
The IEC guidance on maintenance procedures IEC 60079-17 permits live maintenance in Zone 2 if a risk analysis demonstrates that this does not introduce an unacceptable risk. The removal of covers is permitted if this can be done without contaminating the interior of the instrument with dust or moisture. Since the relevant circuits are ‘ic’ [as indicated by the certificate] the adjustment and calibration procedures listed in this document may be carried out in Zone 2 or 22. Some end-users may prefer not to permit live maintenance to minimise risk.
Page 5
5
When connected to a suitable system the indicators may be:
Installed in:
Zone 2 explosive gas air mixture not
likely to occur, and if it does will only exist for a short time.
Be used with gases in groups:
Group A propane Group B ethylene Group C hydrogen
Having a temperature classification of:
T1 450 T2 300 T3 200 T4 135 T5 100
At ambient temperatures between -40 and +70
o
o
o
o
o
C C C C C
o
C.
This allows use with all industrial gases except carbon disulphide CS
.
2
3.3 4/20mA input
The input safety parameters for the 4/20mA input, terminals 1 and 3 are:
Ii = 100mA
4. SYSTEM DESIGN FOR ZONE 2 GAS HAZARDOUS AREAS
4.1 Transmitter loops
Both models may be connected in series with almost any Ex n protected 4/20mA current loop and calibrated to display the measured variable or control signal in engineering units. There are four design requirements:
1. The current flowing in the 4/20mA loop, must not exceed 100mA in normal operation.
2. Wiring must comply with Clause 9 of EN 60079-14 Electrical installation in hazardous areas.
3. The instrument enclosure must be fitted with Ex n or Ex e certified glands, conduit fittings or blanking plugs.
4. The loop must be able to tolerate the additional 1.2V required to operate the indicator. This increases to 5.0V if the indicator is fitted with an optional backlight which is loop powered. See 9.4.1
Figs 2 illustrate a typical application in which an indicator is connected in series with a 2-wire Ex n transmitter.
The indicators are current input instruments incorporating an internal protection circuit that defines the voltage developed between the input terminals 1 and 3, therefore the ATEX certificate does not specify a maximum safety input voltage Ui.
3.4 Certification label information
The certification label is fitted in a recess on the top outer surface of the instrument enclosure. It shows the ATEX certification information and BEKA associates' name and location. Non European certification information may also be shown. The instrument serial number and date of manufacture are recorded on a separate label inside the terminal compartment.
BA304NE certification label
BA324NE certification label
Fig 2 Typical Zone 2 transmitter loop
To strictly comply with the requirements of EN 60079:14 Electrical installations design, selection and erection, each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often considered adequate.
Page 6
4.2 Remote indication
The BA304NE and the BA324NE may be driven directly from a safe area instrument with a 4/20mA output to provide a remote display within a Zone 2 hazardous area.
There are four design requirements:
1. The current flowing in the 4/20mA loop, must not exceed 100mA in normal operation.
2. Wiring must comply with Clause 9 of
EN60079-14 Electrical installation in hazardous areas.
3. The instrument enclosure must be fitted with Ex n or Ex e certified glands, conduit fittings or blanking plugs.
4. The safe area 4/20mA output from the safe area instrument must be able to supply the
1.2V required to operate the indicator. This increases to 5.0V if the indicator includes an optional loop powered backlight. See 9.4.1
6
Fig 3 shows a typical application.
Fig 3 Remote indication in Zone 2 hazardous area
To strictly comply with the requirements of EN 60079:14 Electrical Installation in Hazardous Areas, each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often considered adequate.
Page 7
5. INSTALLATION
5.1 Location
The BA304NE and BA324NE indicators are housed in robust IP66 glass reinforced polyester (GRP) enclosures incorporating an armoured glass window and stainless steel fittings making them suitable for exterior mounting in most industrial installations, including off-shore and waste water treatment. The indicator should be positioned where the display is not in direct sunlight.
Both indicators are surface mounting, but may be pipe mounted using one of the accessory kits described in section 9.5 of this manual. The field terminals and the two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly.
Terminals 2 and 4 are internally joined and may be used for linking the return 4/20mA wire - see Fig 2. Similarly terminals 5 and 6 are internally joined and may be used for linking cable screens. The indicator’s earth terminal is connected to the carbon loaded GRP enclosure. If this enclosure is not bolted to an earthed post or structure, the earth terminal should be connected to the plant potential equalising conductor.
7
Fig 4 BA304NE & BA324NE installation procedure
The enclosures are fitted with a bonding plate to ensure electrical continuity between the three conduit / cable entries.
5.2 Installation Procedure
Fig 4 illustrates the instrument installation procedure.
a. Remove the instrument terminal cover by
unscrewing the two captive 'A' screws.
b. Mount the instrument on a flat surface and
secure with screws or bolts through the two 'B' holes. Alternatively use one of the pipe or stem mounting kits described in section 9.5.
c. Remove the temporary dust seals from the
three cable entries and install Ex n or Ex e certified glands, conduit fittings or blanking plugs.
Note: The temporary dust seals do not provide IP66 protection and must not be used in Zone 2.
d. Connect the field wiring to the terminals as
shown in Fig 5.
e. Replace the instrument terminal cover and
evenly tighten the two 'A' screws.
Fig 5 Dimensions and terminal connections
5.3 EMC
Both instruments compy with the requirements of the European EMC Directive 2004/108/EC. For specified immunity all wiring should be in screened twisted pairs, with the screens earthed in the safe area.
Page 8
8
6. CONFIGURATION AND CALIBRATION
Both indicators are configured and calibrated via four push buttons which are located behind the control cover. An optional external keypad mounted on the outside of the control cover allows the indicator to be configured live without removing the cover. All the configuration functions are contained in an easy to use intuitive menu that is shown diagrammatically in Fig 6.
Each menu function is summarised in section 6.1 and includes a reference to more detailed information. When the indicator is fitted with alarms additional functions are added to the menu which are described in section 9.3 Throughout this manual push buttons are shown as P, E, ▼ or ▲, and legends displayed by the indicator are shown within inverted commas e.g. 'CAL' and ' ALr2'.
Access to the configuration menu is obtained by operating the P and E push buttons simultaneously. If the indicator security code is set to the default 0000 the first parameter 'FunC' will be displayed. If a security code other than the default code 0000 has already been entered, the indicator will display 'CodE'. Pressing the P button will clear this prompt allowing each digit of the code to be entered using the ▲ and ▼ push buttons and the P button to move control to the next digit. When the correct four digit code has been entered pressing E will cause the first parameter 'FunC' to be displayed. If the code is incorrect, or a button is not pressed within twenty seconds, the indicator will automatically return to the display mode.
Once within the configuration menu the required parameter can be reached by scrolling through the menu using the ▲ and ▼ push buttons as shown in Fig 6. When returning to the display mode following recalibration or a change to any function, the indicator will display ‘dAtA’ followed by ‘SAVE’ while the new information is stored in non-volatile memory.
All new indicators are supplied calibrated as requested at the time of ordering. If calibration is not requested, indicators will be supplied with the following default configuration:
6.1 Summary of configuration functions
This section summarises each of the main configuration functions and includes a cross reference to a more detailed description. Fig 6 illustrates the location of each function within the configuration menu. The lineariser and the optional factory fitted alarms are described separately in sections 7 and 9.3 of this manual.
Display Summary of function
'FunC' Indicator function
Defines the relationship between the 4/20mA input current and the indicator display. May be set to:
‘Std’ Standard linear relationship
‘root’ Square root extraction ‘Lin’ 16 segment adjustable
lineariser – see section 7.
See section 6.2
'rESn' Display resolution
Defines the resolution of the least significant display digit. May be set to ‘1’, ‘2’, ‘5’ or ‘10’ digits. See section 6.3
'dP' Decimal point
Positions a dummy decimal point between any of the digits or turns it off. See section 6.4
'CAL' Calibration of the digital display
using an external current source.
Enables the zero and span of the indicator to be adjusted using an external current source such as a calibrator. When used with an accurate traceable current source this is the preferred method of calibration. See section 6.5
'SEt' Calibration of display using internal
references.
Enables the zero and span of the indicator to be adjusted without the need for an accurate input current or disconnection from the 4/20mA loop. See section 6.6
Default Configuration
BA304NE BA324NE
Access code ‘CodE’ 0000 0000 Function ‘FunC’ Linear Linear Display at 4mA ‘Zero’ 0.0 0.00 Display at 20mA ‘SPAn’ 100.0 100.00 Resolution ‘rESn’ 1 digit 1 digit Bargraph start ‘BarLo’ ----- 0.00 Bargraph finish ‘BarHi’ ----- 100.00 P button in display mode ‘C-P’ % % Tare ‘tArE’ Off Off
'bAr' Bargraph format and claibration
Only the BA324NE has a bargraph
The bargraph may be conditioned to start from left, right or centre of the display, or it may be disabled. When optional alarms are fitted it can also display both alarm setpoints and the measured value. The bargraph may be calibrated to start and finish at any value within the indicator’s calibrated digital display. See section 6.7
Page 9
9
Page 10
10
Display Summary of function
'C - - P' Function of P push button
The indicator may be configured to display the input current in milliamps, or the input current as a percentage of the 4/20mA input when the P push button is operated in the display mode. See section 6.8
'tArE' Tare function
When enabled the tare function sets the indicator display to zero when the E push button is operated in the display mode. See section 6.9
'CodE' Security code
Defines a four digit numeric code that must be entered to gain access to the configuration menu. Default code 0000 disables this security function and allows unrestricted access to all conditioning functions. See section 6.10
'rSEt' Reset
Contains two sub-functions, ‘ConF’ which returns the indicator to the default conditions shown in section 6.0 and ‘LtAb’ which returns the lineariser to the default conditions shown in section 7.3. To prevent accidental use both resets must be confirmed by entering ‘5urE’ before they will be executed. See section 6.11
6.2 Indicator function: ‘FunC’
This configuration function defines the relationship between the indicator’s 4/20mA input current and the indicator’s display. Three alternatives are available:
‘Std’ Standard linear relationship
‘root’ Square root extraction ‘Lin’ 16 segment adjustable lineariser
To reveal the existing indicator function select 'FunC' from the configuration menu and press P. If the function is set as required, press E to return to the menu, or press the ▲ or ▼ button to change the setting, followed by the E button to return to the configuration menu.
‘Std’ Linear
Provides a linear relationship between the 4/20mA indicator input current and the indicator display.
‘root’ Square root extraction
Primarily intended to linearise the square law 4/20mA output from differential flowmeters.
For reference, the following table shows the output current from a non-linearised differential flowmeter.
% of full flow Current output mA
2.5 4.01
10.0 4.16
25.0 5.00
50.0 8.00
75.0 13.00
100.0 20.00 When the root function is selected the indicator will display flow in linear units.
‘Lin’ 16 segment adjustable lineariser
Enables non linear variables to be displayed by the indicator in linear engineering units. Use of the lineariser is described in section 7 of this instruction manual.
6.3 Resolution: rESn
This function defines the resolution of the least significant display digit. Decreasing the display resolution can improve the readability of a noisy signal. Select ''rESn' from the menu and press P which will reveal the current display resolution. To change the resolution press the ▲ or ▼ button to select 1, 2, 5 or 10 digits, followed by the E button to enter the selection and return to the configuration menu.
Page 11
11
6.4 Position of the decimal point: ‘dP’
A dummy decimal point can be positioned between any of the digits or it may be absent. To position the decimal point select 'dP' from the menu and press P. The decimal point can be moved by pressing the ▲ or ▼ push button. If a decimal point is not required it should be positioned beyond the most or least significant digit. When positioned as required press the E button to enter the selection and return to the configuration menu.
6.5 Calibration using an external current source: ‘CAL’
This function enables the zero and span of the indicator to be adjusted using an external calibrated current source. When used with an accurate traceable current source this is the preferred method of calibration.
Zero is the indicator display with 4mA input Span is the indicator display with 20mA input
To calibrate the indicator select 'CAL' from the configuration menu and press P. The indicator will display 'ZEro' which is a request for a 4mA input current. Adjust the external current calibrator to
4.000mA and again press P which will reveal the current zero display. The flashing digit of the indicator display can be changed by pressing the ▲ or ▼ buttons, when set as required pressing P will transfer control to the next digit. When all the digits have been adjusted, press E to enter the new zero and return to the 'ZEro' prompt .
Pressing the ▲ button will cause the indicator to display 'SPAn' which is a request for a 20mA input current. Adjust the external current calibrator to
20.000mA and again press P which will reveal the existing span display. The flashing digit of the indicator display can be changed by pressing the ▲ or ▼ buttons, when set s required pressing P will transfer control to the next digit. When all the digits have been adjusted press E to enter the new span and return to the 'SPAn' prompt. Finally press E again to return to the configuration menu.
Notes:
a. The indicator input current must be adjusted to
the required value before the zero and span functions are entered by pressing the P button.
6.6 Calibration using internal reference: ‘SEt’
Using the ‘SEt’ function the indicator can be calibrated without the need to know the value of the 4/20mA input current, or to disconnect the indicator from the 4/20mA loop.
When using the ‘Set’ function the indicator’s internal reference is used to simulate a 4mA and 20mA input current.
Zero is the display with a simulated 4mA input Span is the display with a simulated 20mA input
To calibrate the indicator display select 'SEt' from the configuration menu and press P. The indicator will display 'ZEro', pressing
P again will reveal the
current display at 4mA. The flashing digit can be adjusted by pressing the ▲ or ▼ buttons, when the flashing digit is correct pressing P will transfer control to the next digit. When all the digits have been adjusted, press E to return to the 'ZEro' prompt.
To adjust the display at 20mA, press the ▲ button which will cause the indicator to display 'SPAn', pressing P will then reveal the indicator’s existing display at 20mA. The flashing digit can be adjusted by pressing the ▲ or ▼ buttons, when the flashing digit is correct pressing P will transfer control to the next digit. When all the digits have been adjusted press E to return to the 'SPAn' prompt followed by E to return to the ‘SEt’ prompt in the configuration menu.
6.7 Bargraph format and calibration: ‘bAr’
Only the BA324NE has a bargraph
In addition to a five digit numerical display the BA324NE has a 31 segment analogue bargraph which may be configured to start and finish anywhere within the indicator’s numerical display range.
To configure the bargraph select 'bAr' from the configuration menu and press P. The indicator will display 'tYPE', pressing P again will reveal the existing bargraph justification which can be changed to one of the following four or five options using the ▲ or ▼ button:
b. Indicators may be calibrated at currents other
than 4 and 20mA, withiin the range 3.8 to
21.0mA providing the difference between the two currents is greater than 4mA. If these conditions are not complied with, the indicator displays ‘FaiL’ and aborts the calibration.
c. If the zero current is greater than the span
current the instrument will be reverse acting i.e. an increasing input current will cause the display to decrease.
Bargraph justification starts from
‘LEFt’ Left end of display ‘CEntr’ Centre of display ‘riGHT’ Right end of display ‘AlrSP’ Only with alarms – see section 9.3 ‘oFF’ Bargraph disabled
When set as required press E to return to the ‘tYPE’ sub-function prompt.
Page 12
12
The indicator’s digital display at which the bargraph starts is defined by the ‘bArLo’ sub­function which is selected by pressing the ▲ button followed by the P button which will reveal the current indicator display at which the bargraph starts. The flashing digit can be adjusted by pressing the ▲ or ▼ buttons, when set as required pressing P will transfer control to the next digit. When all the digits have been adjusted, press E to return to the 'bArLo' prompt from which ‘bArHi’ which defines the finishing point of the bargraph can be selected by pressing the ▲ button. ‘bArHi’ is adjusted in the same way as ‘bArLo’. When set as required, pressing E twice will return the display to the ‘bAr’ prompt in the configuration menu.
Note: ‘bArLo’ must be set lower than ‘bArHi’, incorrect setting is indicated by the bargraph scale flashing with a single bargraph segment activated.
6.8 Function of the P push button: ‘C - - P’
When the indicator is in the display mode, operating the P push button will display the input current in milliamps, or the displayed value as a percentage of the difference between the displayed values at 4mA and 20mA inputs.
To check or change the function of the P push button select 'C - -P' from the configuration menu and press P to reveal the current setting. Pressing the ▲ or ▼ button will toggle the setting between '4-20' the current display in milliamps and 'PC' the percentage display. When set as required press E to return to the ‘C - - P’ prompt in the configuration menu.
6.9 Tare function: ‘tArE’
The tare function is primarily intended for use with weighing system. When the indicator is in the display mode and the tare function is activated, pressing the E button for more than three seconds will zero the indicator display and activate the tare annunciator. Subsequent operation of the E push button for less than 3 seconds will return the indicator to the gross display and deactivate the tare annunciator.
To check or change the tare function select 'tARE' from the configuration menu and press P to reveal the current setting. Pressing the ▲ or ▼ button will toggle the setting between 'on' and 'oFF'. When set as required press E to return to the ‘tARE’ prompt in the configuration menu.
6.10 Security code: ‘CodE’
Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access. New instruments are configured with the default security code 0000
which allows unrestricted access to all configuration functions.
To enter a new security code select 'CodE' from the configuration menu and press P which will cause the indicator to display the existing security code with one digit flashing. The flashing digit can be adjusted using the
▲ and ▼ push buttons,
when set as required operating the P button will transfer control to the next digit. When all the digits have been adjusted press E to return to the ‘CodE’ prompt in the configuration menu. The revised security code will be activated when the indicator is returned to the display mode.
Please contact BEKA associates sales department if the security code is lost.
6.11 Reset to factory defaults: ‘rSEt’
This function enables the indicator and the lineariser to be quickly returned to the factory default configurations shown in sections 6.0 and
7.3
To reset the indicator or lineariser select ‘rSEt’ from the configuration menu and press P, the indicator will display one of the reset options ‘ConF’ or ‘LtAb’.
‘ConF’ Resets the indicator to defaults ‘LtAb’ Resets the lineariser to defaults
Using the ▲ or ▼ push button select the required sub-function and press P. To prevent accidental resetting the request must be confirmed by entering ‘5urE’. Using the ▲ button set the first flashing digit to ‘5’ and press P to transfer control to the second digit which should be set to ‘u’. When ‘5urE’ has been entered pressing the E button will reset the selected configuration menus and return the display to the ‘rSEt’ function in the configuration menu.
6.12 Under and over-range
If the numerical display range of the indicator is exceeded, all the decimal points will flash as shown below:
BA304NE BA324NE
Underrange -9.9.9.9 -9.9.9.9.9 Overrange 9.9.9.9 9.9.9.9.9
Although not guaranteed, most indicators will continue to function normally with an input current between 1.8mA and 4mA, at lower currents the instrument will display ‘LPLo’ before it stops functioning.
Under or overrange of the BA324NE bargraph is indicated by an activated arrow at the appropriate end of the bargraph and a flashing bargraph scale.
Page 13
13
7. LINEARISER
A sixteen segment, seventeen breakpoint (0 to 16) lineariser may be selected in the ‘FunC’ section of the configuration menu. The starting point and slope of each straight line segment are fully adjustable allowing the indicator to display most non-linear process variables in linear engineering units. Each break-points must occur at a current greater than the preceeding break-point and less than the following break-point, in the range 3.8 to
21.0mA Fig 8 shows a typical linearised indicator characteristic. Fig 7 shows a typical linearised indicator characteristic.
variable to be displayed. e.g. the output from a level sensor in an irregular tank may be displayed in linear volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break-point.
The number of break-point required should first be entered using the 'Add' and 'dEL' functions. In both these sub-functions the indicator initially displays the current break-point and the total number of break-points being used as shown below.
Display Description of function
'Add' Add a break-point
Adds a new break-point before the displayed break-point. The calibration of existing break-points is not changed, but the identification number of all subsequent break-points is increased by one.
Fig 7 shows a typical linearising characteristic
Selecting ‘Lin’ in the ‘FunC’ section of the configuration menu activates the lineariser, this does not change the configuration menu shown in Fig 6, but the 'CAL' and 'SEt' functions are extended as shown in Fig 8. As with a linear indicator, calibration may be performed with an external current source using the 'CAL' function, or with the internal reference using the 'SEt' function.
The lineariser configuration is retained irrespective of how the the indicator function ‘FunC’ is subsequently changed. It is therefore possible to select and deselect the lineariser without having to reconfigure it each time.
7.1 Lineariser calibration using an external current source.
This method allows direct calibration of the lineariser with an exteral current source and is the preferred method when traceability is required. If the exact system non-linearity is unknown, this method also allows direct calibration from the
'dEL' Remove a break-point
Removes the displayed break-point and joins the preceding break-point to the following break-point with a straight line. The identification number of all subsequent break-points is decreased by one.
To add a break-point use the ▲ or ▼ button to select 'CAL' from the configuration menu and press P which will result in the 'Add' sub-function prompt being displayed. To enter the sub-function press P which will reveal the current break-point and the total number of break-points which have already been entered. Each subsequent operation of the P push button will introduce an additional break­point up to the maximum of 17. When adding a break-point to a calibrated indicator, the insertion position for the new segment can be selected using the ▲ and ▼ push buttons.
The delete break-point sub-function 'dEL' operates in exactly the same way as the 'Add' sub-function described above. Once within the ‘dEL’ sub­function each time the P button is pressed a break­point is removed. When deleting a break-point from a calibrated indicator, the break-point to be deleted can be selected using the ▲ and ▼ push buttons. The minimum number of break-point is 2, break-points 0 and 1.
Page 14
14
Page 15
15
When the required number of linearising break­points have been entered, return to the linearisation sub-menu by pressing E. The indicator will display the 'Add' or 'dEL' prompt depending upon the last function used. The break­point of each segment, which is its finishing point, as shown in Fig 7, can now be defined using the ‘Pts’ sub-function.
Using the ▲ or ▼ button select 'PtS' from the sub­menu and press P which will select the starting point for the first segment '0 : n', where n is the total number of linearising break-points entered. The selected linearising break-point can be changed using the ▲ and ▼ buttons. When the required linearising break-point has been selected set the indicator input current to the exact value at which the break-point is required and press P. Using the ▲ and ▼ buttons and the P button to move between digits, enter the required indicator display at this break-point.
When set as required, press the E push button to enter the required indicator display and return to the sub-menu from which the next beak-point can be selected.
'dEL' Remove a break-point
Removes the displayed break-point and joins the preceding segment to the following segment with a straight line. The identification number of all subsequent break-points is decreased by one.
'in' Defines the current at which break-
point occurs.
Enables the required current at each break-point to be defined without having to input an accurate input current to the indicator.
'diSP' Defines indicator display at break-
point.
Enables the indicator display at each break-point to be defined.
The number of break-point required should first be entered using the 'Add' and 'dEL' sub-functions. In both these sub-functions the indicator initially displays the current break-point and the total number of break-point being used as shown below.
When all the break-points have been calibrated pressing E twice will return the indicator to the ‘CAL’ function in the configuration menu.
Note: The indicator input current must be adjusted to the required value before the P button is operated to enter the required indicator display.
7.2 Lineariser calibration using the internal
reference.
The ‘SEt’ function enables the lineariser to be calibrated without the need for an accurate external current source. Throughout the calibration the indicator input current may be any value between 4 and 20mA.
The ‘SEt’ functions contains four sub-functions.
Display Description of function
'Add' Add a break-point
Adds a new break-point before the displayed break-point. The calibration of existing break-points is not changed, but the identification number of all subsequent break-point is increased by one.
To add a break-point using the ▲ or ▼ button select 'SEt' from the configuration menu and press P which will result in the 'Add' sub-function prompt being displayed. To enter the sub-function press P which will reveal the current break-point and the total number of break-point which have already been entered. Each subsequent operation of the P push button will introduce an additional break­point up to the maximum of 17. When adding a break-point to a calibrated indicator, the insertion position for the new segment can be selected using the ▲ and ▼ push buttons.
The delete break-point, sub-function 'dEL' operates in exactly the same way as the 'Add' sub-function described above. Once within the ‘dEL’ function each time the P button is pressed a break-point is removed. When deleting a break-point from a calibrated indicator, the break-point to be deleted can be selected using the ▲ and ▼ push buttons. The minimum number of break-point is 2, break­points 0 and 1.
Page 16
16
When the required number of linearising break­point has been entered, return to the linearisation sub-menu by pressing E. The indicator will display the 'Add' or 'dEL' prompt depending upon the last sub-function used. The indicator input current and corresponding indicator display at each break­point, which is the segment finishing point as shown in Fig 8, can now be entered using the ‘in’ and ‘diSP’ sub-functions.
Using the ▲ or ▼ button select 'in' from the sub­menu and press P which will reveal the starting point for the first segment '0 : n', where n is the total number of break-point entered. Press P and use the ▲ and ▼ buttons and the P button to move between digits, to enter the input current at which the first break-point is required, usually
4.000mA. When set as required, press E to return
to the ‘0 : n’ prompt from which the the next break-point can be selected using the ▲ and ▼ buttons. When the required break-point has been selected press P and set the indicator input current at this break-point. Repeat this procedure until the indicator input current at all the the break-points has been defined and then return to the ‘in’ sub­function by pressing the E button.
7.4 Under and over-range
The lineariser does not change the under and over-range indication described in section 6.12. At input currents below that specified for the first break-point (0), the indicator will continue to use the specified slope of the first segment. Although not guaranteed, most indicators will continue to function normally with an input current between
1.8mA and 4mA, at lower currents the instrument will display ‘LPLo’ before it stops functioning.
At input currents above that specified for the last break-point, the indicator will continue to use the slope specified for the last lineariser segment.
7.5 Lineariser default configuration
When the lineariser is reset to the default conditions using the ‘rSEt’ reset function described in section 6.11, the defaults conditions are:
BA304NE BA324NE
First break-point 4mA 0.0 0.00 Second break-point 20mA 100.0 100.00
The corresponding indicator display at each of the break-points can now be defined using the ‘diSP’ sub-function Using the ▲ and ▼ buttons select the ‘diSP’ sub-function and press P which will reveal the starting point for the first break-point '0 : n', where n is the total number of break-points entered. Press P and use the ▲ and ▼ buttons and the P button to move between digits, to enter the required indicator display at the first break­point. When set as required, press E to return to the ‘0 : n’ prompt from which the the next break­point can be selected using the ▲ or ▼ buttons. When the required break-point has been selected press P and set the required indicator display at this break-point.
Repeat this procedure until the indicator display at all the break-points has been defined and then return to the ‘SEt’ function in the configuration menu by pressing the E button twice.
7.3 Lineariser error message
If an attempt is made to position a break-point at a current which is not greater than the current of the preceeding break-point, or at a current which is not less than the current of the following break-point, the error message ‘FaiL’ will be displayed. This error message will also be displayed if an attemp[t is made to position a break-point outside the current range 3.8 to 21.0mA.
Page 17
17
8. MAINTENANCE
8.1 Fault finding during commissioning
If an indicator fails to function during commissioning the following procedure should be followed:
Symptom Cause Solution
No display Incorrect wiring Check wiring
There should be
0.6 to 1.2V between terminals 1 & 3 with terminal 1 positive.
With an optional loop powered backlight, there should be 3.4 to 5V between terminals 1 & 13 with terminal 1
No display 0V between terminals 1 & 3.
All decimal points flashing.
Unstable display 4/20mA input is
Unable to enter configuration menu.
Incorrect wiring or no power supply
Underrange if –ve sign displayed or overrange.
noisy.
Incorrect security code entered.
positive. Check supply voltage and voltage drop caused by all the instruments in the loop. Recalibrate the numerical display.
Eliminate ripple on 4/20mA power supply and/or decrease indicator resolution. Enter correct security code, or contact BEKA if the code has been lost.
8.2 Fault finding after commissioning
ENSURE PLANT SAFETY BEFORE
STARTING MAINTENANCE
If an indicator fails after it has been functioning correctly follow the procedure shown in section
8.1. If this does not reveal the cause of the fault, it is recommended that the instrument is replaced.
8.3 Servicing
All BA304NE and BA324NE loop powered indicators are interchangeable if the required optional backlight and alarms are fitted. A single spare instrument may quickly be recalibrated to replace any instrument that is damaged or fails. No attempt should be made to repair instruments at component level.
We recommend that faulty instruments are returned to BEKA associates or to your local BEKA agent for repair.
8.4 Routine maintenance
The mechanical condition of the instrument and electrical calibration should be regularly checked. The interval between inspections depends upon environmental conditions. We recommend that initially instrument calibration should be checked annually.
8.5 Guarantee
Indicators which fail within the guarantee period should be returned to BEKA associates or our local agent. It is helpful if a brief description of the fault symptoms is provided.
8.6 Customer comments
BEKA associates is always pleased to receive comments from customers about our products and services. All communications are acknowledged and whenever possible, suggestions are implemented.
Live maintenance within the hazardous area should only be performed when it is permitted by risk analysis or when there is no risk of a flammable atmosphere being present.
Page 18
18
9. ACCESSORIES
9.1 External keypad
For applications requiring the indicator to be adjusted or calibrated in Zone 2 or 22, without the need for a gas clearance certificate, an optional control cover fitted with an external intrinsically safe keypad is available.
This keypad maintains the enclosure ingress protection and accidental push button activation can be prevented by use of a menu security access code, see section 6.10.
9.2 Units of measurement & instrument
identification.
Both the BA304NE and the BA324NE indicators are fitted with a blank escutcheon around the liquid crystal display. This can be supplied printed with any units of measurement and tag information specified at the time of ordering. Alternatively, the information may be added on-site via an embossed strip, dry transfer or a permanent marker.
9.3 Alarms
CAUTION
These alarms outputs should not be used for critical safety applications such as an emergency shut down system.
Both models can be supplied with factory fitted dual solid state, single pole alarm outputs. Each alarm output may be independently conditioned as a high or low alarm with a normally open or normally closed output in the non-alarm condition.
When the 4/20mA current powering the indicator is removed both alarm outputs will open irrespective of configuration. The open circuit condition should therefore be chosen as the alarm condition when designing an alarm system. Fig 9 illustrates the conditions available and shows which are fail safe.
When an alarm occurs an alarm annunciator on the indicator front panel is activated and if required the numerical display can alternate between the measured value and the alarm channel identification ‘ALr1’ or ‘ALr2’.
To gain access to the display label remove the terminal cover by unscrewing the two 'A' screws which will reveal two concealed 'D' screws. If the instrument is fitted with external keypad, also unscrew the two 'C' screws securing the buttons and un-plug the five way connector. Finally unscrew all four 'D' screws and carefully lift off the front of the instrument. The location of all the screws is shown in Fig 4.
Add the required legend to the display escutcheon, or stick a new pre-printed self-adhesive escutcheon, which is available from BEKA associates, on top of the existing escutcheon. Do not remove the original escutcheon.
Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure. This plate can accommodate:
1 row of 9 alphanumeric characters 10mm high
or 1 row of 11 alphanumeric characters 7mm high
CAUTION
The alarms are activated by the indicator’s numerical display. Use of the Tare Function ‘tArE’ will change the numerical display, the alarms will continue to function at the original displayed value, but this will correspond to a different input current.
or 2 rows of 18 alphanumeric characters 5mm high
Fig 9 Alarm outputs
Configurable functions for each alarm include adjustable setpoint, hysteresis, alarm delay and alarm accept.
Page 19
9.3.1 Solid state output
Each alarm output is a galvanically isolated single pole solid state switch as shown in Fig 10. The output is polarised and current will only flow in one direction, terminals 8 and 10 should therefore be connected to the positive side of the circuit being switched.
Ron = less than 5Ω + 0.7V Roff = greater than 1MΩ
Fig 10 Equivalent circuit of each alarm output
19
9.3.2 Type nA certification
Each alarm output is a separate galvanically isolated Ex nA circuit with the following input parameters:
Ui = 30V dc Ii = 200mA
This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 200mA.
Fig 11 shows a typical application in which a BA304NE or BA324NE indicator is displaying the output from a 2-wire transmitter in Zone 2. Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located in the safe area.
The BA304NE and BA324NE indicators have Ex nA protection but when mounted in Zone 2 the alarm outputs may be used to switch Ex nC Protected Sparking and Ex nR Restricted Breathing apparatus in addition to Ex nA apparatus.
Fig 11 Typical alarm application
(Shown without recommended screened cables)
To strictly comply with the requirements of EN 60079:14 Electrical Installation in Hazardous Areas, each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply that can be switched off is often considered adequate.
Page 20
20
Page 21
21
9.3.3 Configuration and adjustment
When optional alarms are fitted to a loop powered indicator the configuration menu is extended as shown in Fig 12. The additional functions appear between the ‘SEt’ and the ‘C- - P’ functions for the BA304NE and between ‘bAr’ and ‘C- -P’ for the BA324NE indicator. For simplicity, Fig 12 only shows the additional functions for alarm 1, but alarm 2 has identical functions.
The following table summaries each of the alarm configuration functions and includes a cross reference to more detailed information.
Summary of alarm configuration functions
Display Description of function
'EnbL’ Alarm enable
Enables or disables the alarm without changing the alarm parameters. See section 9.3.4
'SP1' Alarm setpoint 1
Adjusts the alarm setpoint. The alarm is activated when the indicator display equals the setpoint. See section 9.3.5
'Hi.Lo' Alarm function
Defines the alarm function as High or Low. See section 9.3.6
'no.nC' Normally open or normally closed
output
Sets the alarm output open or closed in the non-alarm condition. See section 9.3.7
'HStr' Hysteresis
Adjusts the alarm hysteresis. See section 9.3.8
'dELA' Alarm delay time
Introduces adjustable delay between the display equalling the setpoint and the alarm output being activated. See section 9.3.9
'SiL' Alarm silence time
Defines the time that the alarm output remains in the non-alarm condition following acceptance of an alarm. See section 9.3.10
‘FLSH’ Flash display when alarm occurs
When enabled, alternates the numerical display between process value and alarm reference, ‘ALr1’ or ‘ALr2’, when an alarm output is activated. See section 9.3.11
'ACSP' Access setpoint
Sub-menu which enables direct access to the alarm setpoints from the indicator display mode, and defines a separate security code. See section 9.3.12
Page 22
22
9.3.4 Alarm enable: ‘EnbL’
This function allows each alarm to be enabled or disabled without altering any of the alarm parameters. To enable or disable the alarm select 'EnbL' from the alarm menu and press P which will reveal the current setting ‘on’ or ‘oFF’. The function can be changed by pressing the ▲ or ▼ button followed by the E button to return to the alarm menu.
9.3.5 Setpoint adjustment: ‘SP1’ and ‘SP2’
The setpoint of each alarm may be positioned anywhere in the numerical display of the indicator providing that this corresponds to an input current between 3.8 and 20.2mA. e.g. If the indicator has been calibrated to display 0 with 4mA input and 10000 with 20mA input, the two alarm setpoints may be positioned anywhere between -125 and
10125.
To adjust the setpoint select 'SP1' or 'SP2' from the alarm configuration menu and press P which will reveal the existing alarm setpoint. The flashing digit of the setpoint can be adjusted using the ▲ and ▼ push buttons, and the P button to move control to the next digit. When the required setpoint has been entered press E to return to the alarm configuration menu. The alarm setpoints may also be adjusted when the indicator is in the display mode, see section
9.3.12.
9.3.6 Alarm function: ‘Hi.Lo’
Each alarm can be independently conditioned as a high alarm or as a low alarm. To check or change the alarm function select 'Hi.Lo' from the alarm menu and press P to reveal the current setting. The function can be changed by pressing the ▲ or ▼ button followed by the E button to return to the alarm menu.
To check or change the alarm output status, select 'no.nC' from the alarm configuration menu and press P to reveal the setting. The function may be changed by pressing the ▲ or ▼ button followed by the E button to return to the alarm configuration menu.
9.3.8 Hysteresis: HStr
Hysteresis is shown in the units that the indicator has been calibrated to display. To adjust the hysteresis select 'HStr' from the alarm menu and press P which will reveal the existing figure. The flashing digit can be adjusted using the ▲ and ▼ push buttons, and the P button will move control to the next digit. When the required hystersis has been entered press E
to
return to the alarm configuration menu.
e.g. An indicator calibrated to display 0 to 10000, with a high alarm set at 9000 and hysteresis of 200 will perform as follows:
The high alarm will be activated when increasing indicator display equals 9000, but will not reset until the indicator display falls below 8800.
9.3.9 Alarm delay: dELA
This function delays activation of the alarm output for an adjustable time following the alarm condition occurring. The delay can be set in 1 second increments between 0 and 3600 seconds. If a delay is not required zero should be entered. To adjust the delay select 'dELA' from the alarm configuration menu and press P which will reveal the existing delay. The flashing digit of the delay can be adjusted using the ▲ and ▼ push buttons, and the P button to move control to the other digits. When the required delay has been entered press E to return to the alarm menu.
9.3.7 Alarm output status: ‘no.nC’
Configures the solid state alarm output to be open ‘no’ or to be closed ‘nC’ in the non-alarm condition. When deciding which is required, care should be taken to ensure that the alarm output is fail safe as illustrated in Fig 9.
‘no’ Alarm output open in non-alarm condition
‘nC’ Alarm output closed in non-alarm condition
CAUTION When the 4/20mA supply is removed from the loop powered indicator, both alarm outputs will open irrespective of conditioning. Therefore for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition ‘nC’.
e.g. An indicator with a high alarm set at 9000 and an alarm delay of 30 seconds will perform as follows:
The alarm annunciator will start to flash when an increasing indicator display equals 9000, but the alarm output will not be activated until the alarm condition has existed continuously for 30 seconds. When the alarm output is activated, the alarm annunciator will stop flashing and become permanently activated.
If the ‘FLSH’ function, which flashes the indicator display when an alarm occurs, has been enabled, it will not start to function until the alarm output is activated. See section 9.3.11
Page 23
23
9.3.10 Alarm silence time: SiL
This function is primarily intended for use in small installations where the alarm output directly operates an alarm annunciator such as a sounder or beacon. When the alarm silence time, which is adjustable between 0 and 3600 seconds in 1 second increments, is set to any figure other than zero, the P push button becomes an alarm accept button. After an alarm has occurred, operating the P button will cause the alarm output to revert to the non-alarm condition for the programmed alarm silence time. If the alarm condition still exists at the end of the silence time, the alarm output will be reactivated. During the silence time the indicator alarm annunciator will flash until the silence time expires or the alarm is cleared.
If the ‘FLSH’ function, which flashes the indicator display when an alarm occurs has been enabled, it will only function when the alarm output is activated, not during the silence time. See section
9.3.11
To adjust the alarm silence time select 'SiL' from the alarm configuration menu and press P which will reveal the existing silence time. The flashing digit of the silence time can be adjusted using the ▲ and ▼ push buttons, and the P button to move control to the other digits. When the required silence time has been entered press E to return to the alarm menu.
indicator is in the display mode is provided by a separate security code.
This direct setpoint access menu is enabled and the separate security code entered from the 'ACSP' function in the alarm configuration menu as shown in Fig 12. To change the menu parameters select 'ACSP' from the configuration menu and press P which will display the enable prompt 'EnbL'. Press P again to reveal if the direct access menu is 'on' or 'oFF'. The ▲ or ▼ button will toggle the display between the two conditions.
If 'oFF' is selected, the operator will not have access to the setpoints from the display mode. Return to the 'ACSP' prompt in the main menu by pressing E twice.
If 'on' is selected, the operator will have direct access to the alarm setpoints from the display mode via a separate optional security code. To define this four digit security code press P to return to the 'Enbl' prompt followed by the ▲
or ▼ button
to select the access code prompt 'ACCd'. Pressing P will reveal the current security code. Each digit of the code may be changed by operating the ▲ and ▼ push buttons, and the P button to move control to the next digit. When the required code has been entered, press E twice to return to the 'ACSP' prompt in the configuration menu.
9.3.11 Flash display when alarm occurs ‘FLSH’ In addition to the two alarm annunciators on the top left hand corner of the indicator display which show the status of both alarms, this function provides an even more conspicuous indication that an alarm condition has occurred.
When enabled, the function alternates the indicator display between the numerical value and the alarm reference, ‘ALr1’ or ‘ALr2’, when the alarm output is activated. If both alarm outputs are activated, the alarm references are displayed in sequence.
To enable or disable the function select 'FLSH' from the alarm menu and press P which will reveal the current setting ‘on’ or ‘oFF’. The function can changed by pressing the ▲ or ▼ button followed by the E button to return to the alarm menu.
9.3.12 Access setpoint in display mode: ACSP
This function enables a separate menu providing access to the alarm setpoints from the display mode by simultaneously operating the P and ▲ push buttons. An operator can therefore adjust the alarm setpoints without having access to the indicator configuration menu. Protection against accidental adjustment of the setpoints when the
Default code 0000 will disable the security code allowing direct access to the setpoints in the display mode by pressing the P and ▲ buttons simultaneously. Unless otherwise requested new instruments with alarms are supplied with this function disabled and the security code set to
0000.
9.3.13 Adjusting alarm setpoints from the display mode
Access to the alarm setpoints from the indicator display mode is obtained by operating the P and ▲ push buttons simultaneously as shown in Fig 13. If the setpoints are not protected by a security code the alarm setpoint prompt 'SP1' will be displayed. If the setpoints are protected by a security code, 'Code' will be displayed first. Pressing P again will enable the alarm security code to be entered digit by digit using the ▲ and ▼ buttons to change the flashing digit, and the P push button to move control to the next digit. If the correct code is entered pressing E will cause alarm setpoint prompt 'SP1' to be displayed. Pressing the ▲ or ▼ button will toggle the display between the two alarm setpoint prompts 'SP1' and 'SP2'.
If an incorrect security code is entered, or a button is not pressed within twenty seconds, the indicator will automatically return to the display mode.
Page 24
24
9.3.14 Displaying setpoints on BA324NE bargraph
One of the selectable bargraph formats ‘AlrSP’ allows a low or a high setpoint plus the displayed value to be represented, or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14.
Fig 14 Displayed value and setpoints on bargraph
The bargraph area below the low alarm setpoint and the area above the high alarm setpoint are activated. The displayed variable is represented by an activated bar which moves between these low and high alarm setpoints.
Fig 13 Setpoint adjustment from the display mode
To adjust an alarm setpoint select 'SP1' or 'SP2' and press P which will reveal the current setting. Each digit of the setpoint may be adjusted using the ▲ and ▼ push buttons, and the P button to move control to the next digit. When the required setpoint has been entered, pressing E will return the display to the 'SP1' or 'SP2' prompt from which the other setpoint may be selected, or the indicator may be returned to the display mode by pressing E again.
Note: With the indicator in the display mode, direct access to the alarm setpoints is only available when the ACSP menu is enabled - see section
9.3.12
When the activated bar representing the displayed variable is adjacent to the area representing the low or high ararm setpoints, the bar flashes. When a displayed variable equals the low or high alarm the complete bargraph representing the activated alarm flashes irrespective of whether the alarm output has been delayed or cleared.
For this function to operate SP1 must be conditioned as a low alarm and SP2 as a high alarm; SP1 must always be less than SP2. Incorrect configuration is shown by a flashing bargraph scale with no activated bars.
Page 25
25
9.4 Display backlight
The BA304NE and BA324NE loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered.
When loop powered the backlight produces green background illumination enabling the display to be read at night or in poor lighting conditions. No additional power supply or field wiring are required, but the indicator voltage drop is increased. When separately powered the backlight is brighter, but additional field wiring is required.
Fig 15 Terminals for optional backlight
9.4.1 Loop powering the backlight
The backlight is loop powered by connecting it in series with the indicator’s 4/20mA input as shown in Fig 16, which increases the maximum indicator voltage drop from 1.2 to 5V.
9.4.2 Separately powering the backlight
The optional backlight may also be powered from a separate safe area power supply as shown in Fig 17.
Fig 17 Separately powered backlight
The separately powered backlight is a current sink which will draw a constant 34.7mA when the supply voltage is equal to or greater than 11V. At lower supply voltages the backlight will continue to function but with reduced brilliance.
Fig 16 Loop powered backlight
To strictly comply with the requirements of EN 60079:14 Electrical Installation in Hazardous Areas, each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply that can be switched off is often considered adequate.
The ATEX certificate therefore only specifies the maximum safety input voltage Ui for terminals 12 and 14.
Ui = 30V
To strictly comply with the requirements of EN 60079:14 Electrical Installation in Hazardous Areas, each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply that can be switched off is often considered adequate.
Page 26
9.5 Pipe mounting kits
Two pipe mounting kits are available for securing the BA304NE and BA324NE to a horizontal or vertical pipe.
BA392D Stainless steel bracket secured by two
worm drive hose clips. Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm.
BA393 Heavy duty stainless steel bracket
secured by a single 'V' bolt. Will clamp to any vertical or horizontal pipe with an outside diameter between 40 and 80mm.
26
Page 27
27
APPENDIX 1
A1.0 ATEX dust certification
In addition to ATEX certification permitting installation in Zone 2 gas atmospheres which is described in the main section of this instruction manual, the BA304NE and the BA324NE also have ATEX Ex tc certification, allowing installion in Zone 22 combustible dust atmospheres.
A1.1 Zones and Maximum Surface
Temperature
The indicators have been certified as Group II Category 3D Ex tc IIIC T80ºC Dc IP66 apparatus with a Ta of –40ºC to +70C. This is dust ignition protection by enclosure complying with EN 60079-31.
When installed as specified in this instruction manual and complying with the requirements of EN 61241-14 the indicators may be installed in:
Zone 22 explosive atmosphere in the form of
a cloud of combustible dust in air is not likely to occur in normal operation, but if it does occur, will only persist for a short period.
A1.2 Installation
All the circuits shown in the main section of this manual for indicator installations in Zone 2 flammable gas atmosheres, may also be used for Zone 22 combustible dust applications. The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in this instruction manuals and comply with the requirements of EN 60079-14 Electrical
installations design, selection and erection
EN 60079-14, requires that each of the wires entering the hazardous area should be individually fused and contain a means of isolation. However, in practice instrumentation energised by a current limited power supply that can be switched off is often considered adequate.
A1.3 Maintenance
Ex tc protection does not permit live maintenance, but when fitted with an optional intrinsically safe external keypad the BA304NE and BA324NE indicators may be calibrated in Zone 22 providing the terminal cover is not removed
.
Be used with dusts having a Minimum Ignition Temperature of:
Dust cloud 120°C
Dust layer on indicator 155 up to 5mm thick.
*
°
C
Dust layer on indicator Refer to over 5mm thick. * EN 60079-14
At an ambient temperature between -40 and +70°C
* Unlikely occurance in Zone 22
ENSURE PLANT SAFETY BEFORE
STARTING MAINTENANCE
The indicator terminal and control covers should only be removed and live maintenance performed when there is little risk of a combustible dust being present. During maintenance ensure that dust or water do not enter the enclosure. Before replacing the control and terminal covers ensure that the sealing gaskets are undamaged and free from dirt and foreign bodies.
Inspection of the indicator’s mechanical condition and removal of accumulated dust from the outside of the enclosure should be regularly performed. The interval between inspections depends upon environmental conditions. Removal of flammable dust should be performed with care to avoid creating a dust cloud.
Page 28
APPENDIX 2 IECEx certification
A2.0 The IECEx Certification Scheme
IECEx is a global certification scheme for explosion protected products which aims to harmonise international certification standards. For additional information about the IECEx certification scheme and to view the BEKA associate certificates, please visit www.iecex.com
A2.1 IECEx Certificate of Conformity
The BA304NE and the BA324NE loop powered indicators and the optional accessories have been issued with an IECEx Certificate of Conformity number IECEx ITS 11.0016 that specifies the following certification codes:
Ex nA ic IIC T5 Gc Ex tc IIIC T80ºC Dc IP66 Ta = -40ºC to 70ºC
28
The specified gas and dust safety parameters are identical to the ATEX safety parameters described in the main section and Appendix 1 of this manual.
The IECEx certificate may be downloaded from www.beka.co.uk, www.iecex.com or requested from the BEKA sales office.
A2.2 Installation
The IECEx and ATEX certificates specify identical safety parameters and installation requirements for both approvals as defined by IEC 60079-14. The ATEX installation requirements specified in the main section and Appendix 1 of this manual should therefore be used for installations which are made using the IEC Code of Practice IEC 60079-14. However the local code of practice should always be consulted.
Loading...