Installation and Operating Instruction for B.E.G. - Occupancy detector PD4-M-DALI/DSI-SM/FC
1. Product information
• Occupancy detector for daylight-dependent lighting
control
• DALI / DSI interface for controlling digitally dimmable
electronic ballasts as a group
• Switching between DSI and DALI program by remote
control or DIP switch
• Extension of the detection area by slave devices is
possible
• Other functions adjustable by remote control (optional)
• Manual switching and dimming via pushbutton possible
• Orientation light function
2. Operation
The presence detector controls the light automatically according
to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light
and compares it with the set value brightness on the detector.
If the ambient light is sufficient, lighting will not be switched.
If the ambient light level is below the set value brightness, a
movement activates the lighting in the room.
The detector switches the light off despite of a person being present if there is enough natural light for 5 min or if no movement is
detected for one follow-up time.
5a. Position DIP switches, LEDs and
Potentiometer SM
5b. Position DIP switches, LEDs and
Potentiometer FC
PD4-M-DALI/DSI
Light measurement
I II III
CBA
PD4-Surface
mounting
C
B
A
DIP
1
2
3
I II III
DIP switch functions
DIP 1 Full automatic mode
(VA)
DIP 2 LED ON
DIP 3 Operation mode DALI Operation mode DSI
Potentiometer A Brightness (constant light control)
Potentiometer B Follow-up time light
Potentiometer C Follow-up time (orientation light)
LED I green
LED II red
LED III white
®
Semi-automatic mode
(HA)
LED OFF
3. Safety information
Work on the 110-240V mains supply may only
be carried out by qualified professionals or by
!
instructed persons under the direction and supervision of qualified skilled electrical personnel in
accordance with electrotechnical regulations.
!
Disconnect supply before installing!
This device is not suitable for disconnection.
!
Mounting the cover ring after introduction of the
!
power cable (FC version).
4. Mounting
In master/slave mode, the master device must always
!
be installed at the location with least daylight.
The light sensor must be positioned facing away from
!
the window.
4a. Mounting
open
close
4b. Mounting
68 mm
Figure 2
SM
The detector has to be mounted
on a plane and solid surface.
Before mounting, the lense has to be
removed. To do so, twist the lense
anticlockwise through approx. 5°
and lift off.
Having connected up the cables in
accordance with regulations, put on
the lense by turning in a clockwise
direction (see fig. 1). Apply mains
voltage.
Figure 1
FC
A circular opening of diameter
68mm must be produced in the
ceiling. Having connected up the
cables in accordance with regulations, the detector is inserted into
the opening and fixed into
position with the assistance of the
spring clips (see figure 2).
Light
PD4-
False ceiling
mounting
3
1
2
measurement
DIP
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the
supply is first connected. During this time the device does not
respond to movement and stays on.
7. Putting into operation/Settings
Brightness value for constant light control
(Potentiometer A)
The brightness set value can be defined between
10 and 2000Lux. The potentiometer enables a free
selection of the brightness value.
Symbol
:
Symbol :
Follow-up time “Light” (Potentiometer B)
The follow-up time can be set to 1 to 30 minutes.
Symbol TEST: test mode
Irrespective of the brightness, every movement switches the light on for 1sec., then off again for 2 sec.
Follow-up time orientation light (Potentiometer C)
Manually switching the orientation light on/off.
“ON” for permanent orientation light
“OFF” for switching off the orientation light
Night-time operation
Daytime operation
(light evaluation inactive)
8. Wiring diagram
Standard mode with Master/Slave device(s)
L
L
L
N
N
T1
M1
S
N
LN RS + -
Master-Gerät
Connected Slave devices must have the same phase as the
!
Master device.
DA1
L
N
N
E1 DALI/DSI
E1 DALI /DSI
DA
DA
DA
DA
T2
+L‘
RL
-
DA1
N LR
Slave-Gerät
LR
N
9. Manual switching and dimming (see section 23)
By pressing the push button, the phase can be given to the S
terminal.
To turn on or off the light, press the push button briefly. The light
will remain on or off, as long as people are detected plus the
follow-up time.
With a long press of the push button the light will be dimmed
manually. When releasing the button, the current brightness value
is retained.
With renewed long press of the push button, the dimming
direction is reversed.

10. Range
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
2.50 m
24 m
360°
1
Walking across
Walking towards
2
Seated activity
1
6.40 m
8 m
24 m
11. Exclude sources of interference
SM
14. LED function indicators
LED function indicators
Process Standard mode Double-locked
Initialisation time
unprogrammed
Initialisation time
programmed
Motion detection
2
Too bright detected
Too bright / too dark /
undefined in opened state
Switching DALI/DSI
DSI active
Switching DALI/DSI
DALI active
Switching HA/VA
Semi-automatic mode (HA)
active
Switching Preset/User
Preset active
Switching Preset/User
User active
IR signal valid received
IR signal invalid received
100 h function active
Light measurement in
progress
Red flashes
Red flashes
quickly
Red flashes on
each detected
movement
Red flashes 2x
per second
Green flashes
very quickly
Red shines
3 sec.
Green shines
3 sec.
White shines
permanently
Red shines
3 sec.
Green shines
3 sec.
Red and white
shine 3 s
Red shines
0,5 sec.
Red / Green
flash
alternately
Green flashes
1x in 10 sec.
Green
flashes
Green flashes
quickly
Green flashes
on each
detected
movement
Green flashes
2x per
second
Green flashes
very quickly
Red / Green
flash
alternately
Green flashes
1x in 10 sec.
FC
If the detection zone is too large, or areas are covered that should
not be monitored, use the blinds to reduce or limit those areas.
12. Technical data
Power supply: 110-240VAC, 50/60Hz
Power consumption: approx. 1W
Ambient temperature:
Degree of protection/class: IP20 / II
Max. no. of series-connected
electronic ballasts: up to 50 (Broadcast)
Range of coverage Ø
H 2,5 m /T =18°C:
Area of coverage:
Recommended height
for mounting:
Dimensions H x Ø [mm]
63 x 98 103 x 97mm
Declaration of Conformity:
2 - 3 m
This product respects the directives concerning
-25°C to +50°C
seated 6.4m / tangential 24m /
frontal 8m
circular 360°
SM FC
1. electromagnetic compatibility (2004/108/EU)
2. low voltage (2006/95/EU)
3. restriction of the use of certain hazardous substances in electrical
and electronic equipment (2011/65/EU)
13. Article / Part nr. / Accessory
Type SM FC
PD4-M-DALI/DSI 92279 922 75
®
LUXOMAT
Remote control:
IR-PD-DALI-E (incl. wall bracket) -
General remote control 92122
IR-PD-DALI (incl. wall bracket) 92094
IR-PD-DALI-Mini 92112
IR-PD-DALI-LD (incl. wall bracket) 92652
IR-Adapter with Smartphone-App 92726
Accessory:
BSK Wire basket 9219 9
Wall bracket for remote control as replacement 92100
SM-Socket IP54 92161