Installation and Operating Instruction for B.E.G. - Occupancy detector
1. Product information
Occupancy sensor for daylight-dependent lighting control
DALI / DSI interface for controlling digitally dimmable electronic ballasts as a group
Switching between DSI and DALI program by remote control or DIP switches
Version as Master
Extension of the coverage area by slave devices are possible
Other functions can be adjustable by remote control.
Manual switching and dimming via pushbutton possible
Orientation light function
2. Operation
The presence detector controls the light automatically according to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light and compares it with the brightness level on the detector. If the ambient light is sufficient, lighting will not be switched.. If the ambient light level is below the brightness level, a move­ment activated the lighting in the room.
The detector switch the light off instead of a person, if there is enough natural light for 5 min. or until the follow-up time do not recognized any movement in the room.
3. Safety information
instructed persons under the direction and super­vision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not suitable for disconnection.
Mounting the cover ring, after introduction of the power cable (FC version)
4a.
Mounting SM
close
open
The detector must be mounted on a flatsolid ground. Before mounting the detector, the lens must be removed. lar cover ring must be removed prior to assembly. To do this, twist the circular cover ring of the PD2 anticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance with regulations, put on the cover ring by turning in a clockwise direction. Apply mains voltage.
4b. Mounting
A circular opening of diameter 68mm must be produced in the ceiling. Having connected up the cables in accor dance with regulations, the detector is inserted into the opening as shown in the drawing opposite and fixed into position with the assistance of the spring clips.
FC
68 mm
In Master-/Slave-operation the master device must always be installed at the site with less daylight.
The light sensor should be mounted on the opposite side of the window.
The circu-
®
PD4-M-DALI/DSI/PD4-S
PD4-M-DALI/DSI-SM/FC
5a. Position DIP-Switches, LEDs and
Potentiometer SM
Light measurement
CBA
Light measu­rement
I II III
C B
1
A
2
PD4-
Surface
mounting
5b. Position DIP-Switches, LEDs and
Potentiometer FC
3
1
2
DIP
3
PD4-
False ceiling
mounting
I II III
DIP
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the supply is first connected. During this time the device does not respond to movement and stays on.
The initialization mode can be changed by using the remote control
7. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably between 1 and 30 minutes.
Symbol TEST: Test mode Every movement switches on the light for a period of 1 second, switching it off for a period of 2 seconds.
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10 and 2000 Lux. Using the rotary control, the luminan ce set points can be set as desired.
Symbol Symbol : Daytime operation
Orientation lighting
The orientation lighting can be set infinitely variably at between 5 and 60 minutes resp. "ON" for permanent orientation lighting or "OFF" for no orientation lighting. "ON" for permanent orientation lighting "OFF" deactiviation of orientation lighting.
Pulse spacing PD-Slave
9s 2s
2 or 9 seconds can be set for the pause between 2 pulses sent to the master. The setting can be made with activated (
LED ON
For devices with a separate Slave input, 2 sec. can be set.
(INI-ON or INI-OFF)
: Night-time operation
) or deactivated ( ) LED indicator.
DIP-switch function
DIP 1 Fully automatic mode
(VA)
Semi automatic mode (HA)
DIP 2 LED ON LED OFF
DIP 3 operation mode DALI operation mode DSI
Potentiometer A Brightness constant light control Potentiometer B Off delay for light Potentiometer C Orientation lighting
LED I green LED II red LED III white
8.
Wiring diagram
Standard mode with Master/Slave
L
N
LN RS + -
DALI
-
Connected Slaves must have the same phase as the Master.
N DA DA
L
E1 DALI/DSI
9. Manual switching and dimming
By pressing the push button, the phase can be given to the S terminal.
To turn on or off, press the push button briefly. The light will remain on or off, as people are detected plus the follow-up time.
With a long key press the light will dimmed manually. When you release the button, the current brightness value is retained. With renewed dimming, the dimming direction is reversed.
NLR
10. Range
quer zum Melder gehen frontal zum Melder gehen Unterkriechschutz
PD4
1
360°
6,40 m
8 m
2
24 m
1
Walking across Walking towards
2
Seated
2,50 m
24 m
11. Exclude sources of interference
If the detection zone is too large, or areas covered that should not be monitored, use the blinds to reduced or limited those areas.
12. Technical data
Power supply: 110-240V~, 50/60 Hz Power consumption: < 1W Ambient temperature: -25°C to +50°C Degree of protection/class: Max. no. of series-connected electronic ballasts: up to 50 (Broadcast) Recommended height for mounting: Range of coverage Ø H 2,5 m / T = 18°C: seated 4 m / tangential 10 m /
Area of coverage: Dimensions H x Ø [mm]
50x97 84,5x74mm
2 - 3m
IP20 / II
radial 6m
circular 360°
SM FC
Technical data PD4 S lave
Power supply: 110-240V~, 50-60 Hz Impulse output: Optocoupler max. 2W Impulse duration: 2 sec. or 9 sec. Dimensions: see above
Declaration of Conformity:
voltage recommendation 2006/95/EC and the EMV recommen­dation 2004/108/EC.
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED LIGHTS A 100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES) FUNCTION TAKES PLACE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN DOES NOT TAKE PLACE.
The product complies with the low
14. LED-functional indicators
LED-functional indicators
Process Standard mode Double-locked
Initialisation time unprogrammed
Initialisation time programmed
Motion detection
Too bright detected
Too bright / too dark / undefined in opened state
Switching DALI/DSI DSI active
Switching DALI/DSI DALI active
Switching HA/VA VA active
Switching HA/VA VA active
Switching Preset/User Preset active
Switching Preset/User User active
IR signal valid received
IR signal invalid received
100h Function active
Light measurement in progress
Red flashes Green flashes
Red flashes quickly
Red flashes on each detected movement
Red flashes 2x each second
Red flashes very quickly
Red shines 3 sec.
Green shines 3 sec.
Red shines 3 sec.
Green shines 3 sec.
Red shines 3 sec.
Green shines 3 sec.
Red and white shines 3 s
Red shines 0,5 sec.
Red / Green flashes variable
Green shines 1x in 10 sec.
Green flashes quickly
Green flashes on each detec ted movement
Green flashes 2x each second
Green flashes very quickly
Red / Green flashes variable
Green shines 1x in 10 sec.
-
13. Article / Part nr. / Accessory
Typ SM FC FM
PD4-Master-DALI/DSI 92279 92 275 -
PD4-Slave 9214 2 92254 9 2163
®
Remote control:
LUXOMAT
IR-PD-DALI (incl. wall bracket) 92094
Accessory:
BSK Ball basket guard 9219 9 SM-Socket IP54 92161
13. S ettings by remote control when open
!
max
50
Lux
1500
Lux
ON
max
50
Lux
1500
Lux
1500
Lux
!
!
1500
Lux
Settings with remote control override the potentiometer and DIP settings.
The DIP settings are reactivated by
• Reset with Test-Sun setting at the potentiometers
• „RESET“ in the opened state
Remote control LUXOMAT
®
IR-PD-DALI
1. Check Battery:
Open battery compartment by pressing the plastic springs together and remo­ving the battery-holder.
2. Note:
The operable distance of the remote control depends on the brightness. The brighter the less distance the remote could reach the occupancy detector. The setting for "SUN" could only be set with the potentiometer.
By using the remote control IR-PD-DALI, we recommend to set potentiometer 2 on "SUN". Pushing the RESET button (remote control) would reset the brightness independence of the occu­pancy detector (SUN).
IR-PD-DALI
Wall bracket for remote control IR-PD-DALI
14. Settings by remote control when open
Unlocking device – Activation of the programming mode
Resetting when open:
Deletes all values set with the remote control, light OFF.
+
DSI/
DALI
or
or
Switching between DSI and DALI program The Factory setting is DALI
Dimming of the lighting on the desired luminance value
Automatic reading in the current light value as new lumi­nance set point
Adjusting of the luminance set point
from 50 to 1500 Lux
+ / – small steps
/ – big steps
+
Follow-up time
30
min
light
OFF
Orientation lighting on/off
Orientation lighting
10
and its
min
follow-up time
Preset/user mode
Fully automatic / semi automatic mode
Start Light mesaruement by holding down the push button
1
at
min
optionaloptionaloptionaloptional
ON
1
at
min
Exit programming mode
If there is no entry for about 3 min. the programming mode is ended automatically.
optional
t < 5 s
LED ashes
Permanent protection against sabotage
With this function, the detector is per­manently locked. This mode can only be activated for 5 s after closing the detector. In this mode, only the function
„Light on /
Light off“ activated.
18. Light regulation
The detector has two integrated light control algorithms. The set
value for the rst algorithm is adjusted by potentiometer (LUX)
on the device. Very small light amounts, which shine directly to the detector, have the result of a trigger under control of the set value.
The second algorithm has an integrated daylight compensation. Therefore it is necessary, that the detector analyzes the switched light quantity. This algorithm can only be used by remote control. The programming of the setpoint value and the measurement of the light quantity in two steps:
In the open state
The set value will be without daylight (no light in room) adjusted by using the remote control.
Measuring the light quantity, will be initiated by a long press (> 3 sec) at the test button. The detector turns the light on for 5 min. up to 100%. Then the light will be on and off for a short time and stays on after that. This
measuring process is shown by a ashing green LED (10
sec on / 1 sec on). This measuring process is required for each change of the set value.
If the measuring process is not performed, the detector performs this automatically, when the ambient light is for
1 h less than 50 LUX.
19. Fully / Semi automatic mode
The system switches over when the “Light” push-button is open.Each time a push button is pressed, the current operating mode is indicated by the red LED: Red lights for 3 sec. = Fully automatic mode Green lights for 3 sec. = Semiautomatic mode
Fully automatic operation
In this operating mode, the lighting switches automatically on and off for increased comfort, depending on presence and brightness.
Semi automatic operation
In this operating mode the light turns on only after a manual switching, for a increased savings success. Switching off is automatically or manually.
19. Settings during the Self-test cycle
In the rst 60 seconds after connecting the AC voltage, the
following functions can be set:
INI-OFF/ON-Mode:
Turn off or turn on the detector during the self-test cycle of 60 sec. The final state is active. Factory settings of the light is on during initialization.
Initialization mode INI-OFF the detector does not turn on after the power supply voltage. A movement switch on the detector after 60 seconds.
Startup behavior:
The setpoint value can be started after switching on in two ways. The detector switches the lights on to 10% and then adjusts upward (min button) or it switches the light on 100% and regulates down (max button). This is confirmed by a short flashing of red and white LED lighting. By factory default setting, detector switches the light to 100% and regulates toward the set point.
20. Self-test cycle/Reset
Testmode
Disable the test mode
Resetting when closed
The lighting relay is switched off, i.e. opened and the follow-up times reset.
21. 100h Function
(long press when closed)
T5 and T8 are recommended to burn-in for 100h at maximum brightness before dimming. This would prolong the life of the lamp.
At the 100h-Function the detector only switch on and off. A regulation to a set value will be suppressed. The light has to be on for 100h, until the set value get regulated.
The 100h will be activated by pressing a long button press (>3 sec.). An activated time can be stopped by pressing a long button press again. The red/green LED shows if the function gets activated.
Before you can dimmed analog or digital, is a suppres­sion of the dimming function for 100h at T5-or 80h at T8
uorescent lamps and 100% of nominal light necessary.
Failure to comply to the 100h burn-in would lead to the shorten of the life of the lamp. Conditional random variations in light intensity can be the result.
22. Manual Switching
(short press when closed)
You can switch the lighting on and off manually by pressing the pushbutton for a short time. It will stay on or off as long
as people are detected plus the congued follow up time.
23. Manual Dimming – Preset/User
You can dim manually by pressing the push button for a long time (> 2sec.). When the button is released, the current dim­ming value is retained. Upon renewed dimming, the dimming direction is reversed.
Two different operating modes are selected in the opened state.
The system switches over when the "Doublelock" push-button is open (see remote control functions, page 1). Each time a push­button is pressed, the current operating mode is indicated:
Red lights for 3sec. = Preset Green lights for 3sec. = User
PRESET – the luminance set point is set during start-up operation by the installer and remains unchanged. The luminance set-point
congured through manual dimming is only applied for the time
being.
The constant light regulation is now deactivated! The current set
articial light is retained independent of the ambient/daylight
brightness! After switching off and then back on, the original set luminance set-point is reset = constant light regulation is activated.
USER – can only be activated via the remote control!
The luminance set-point is changed upon each manual dimming and re-adjusted by the user. The constant light regulation remains activated!
24. Reset the detector
If the permanent sabotage protection is activated, the detector can be released again as follows:
Switch off the power supply and switch it back on
Let the sensor to initialize for 31 to 59 secs.
Switch off the power supply again
Apply power again and wait for for the self testing
Press the unlock With this procedure, the remote control programmed values are
not deleted (before activation of the sabotage protection). Alternatively, the detector can be reset in this way:
Switch off the power supply
Set potentiometer 1 to "test" and potentiometer 2 to "SUN"
Apply operating voltage
Except of the INI ON/OFF setting, the detector will be reset to factory setting or the setting of the potentionmeter.
Pushing the "RESET" button on the remote control, in opened mode, will delete all of the values which was set by the remote control (beside of INI ON/OFF) and set the detector back to it‘s factory reset.
_PD4-M-DALI/DSI_EN_270314_1