B.E.G. Luxomat PD2-M-DALI/DSI-HVAC Operating Instruction

Page 1
Installation and Operating Instruction for B.E.G. - Occupancy detector
PD2-M-DALI/DSI-HVAC-DE
LUXOMAT
®
PD2-M-DALI/DSI-HVAC/PD2-S
EN
1. Product information
Suitable for dimmable digital electronic ballasts and control moduls
One additional switching channel (NO potential-free, dry) for controlling lights and HVAC (heating, ventilation, air conditioning) devices
DALI/DSI interface
Constant light control
Manual switching / dimming
Full or semi-automatic mode
Set value brightness, follow-up time – LIGHT/HVAC and orientation light adjustable
Sensor and power supply in one housing
Infrared remote control
2. Operation
The presence detector controls the light automatically according to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light and compares it with the brightness level on the detector. If the ambient light is sufficient, lighting will not be switched. If the ambient light level is below the brightness level, a move­ment activates the lighting in the room.
The detector switches the light off, if there is enough natural light for 5 min. or if no movement is detected for one follow-up time.
The second channel can be interpreted as HVAC channel (heating, ventilation, air conditioning). This channel switches the connected load independent of the brightness.
3. Safety advice
!
Work on the 110-240V mains supply may only be
carried out by qualified professionals or by instructed persons under the direction and supervision of quali­fied skilled electrical personnel in accordance with electrotechnical regulations
!
Disconnect supply before installing!
!
This device is not suitable for disconnection.
!
After having connected all cables, please mount the
cap onto the detector.
4.
Mounting FC
A circular opening of diameter 68mm must be drilled into the ceil­ing. Having connected the cables in accor dance with regulations, the detector is inserted into the opening as shown in the drawing above and has to be fixed into position by means of the spring clips.
!
In Master/Slave operation, the master device must always
be installed at location with least daylight.
5. Position DIP switches, LEDs
and potentiometers
PD2-
False ceiling
mounting
CBA
Light measurement
DALI_DSI
HVAC_
LIGHT VA_HA
1
2
3
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the supply is first connected. During this time, the device does not respond to movement and stays on.
The initialization mode can be changed by using the remote control.
7. Putting into operation / Settings
Twilight-switch for constant light control
The set value brightness can be adjusted at between 10 and 2000 Lux. Using the potentiometer, the set value brightness can be adjusted as desired.
Symbol
: Night-time operation
Symbol : Day/night time operation
Follow-up time for light control
The time can be set infinitely variably between 1 and 30 minutes.
Symbol TEST: Test mode Every movement switches on the light independent of brightness for a period of 1 second, switching it off for a period of 2 seconds.
Orientation light
The follow-up time can be set infinitely variably at between 5 and 60 minutes. Manually switching ON/OFF the orientation light. „ON“ for permanent orientation light „OFF“ for deactiviation of orientation light
Follow-up time for device control
The follow-up time can be adjusted between 5 min. and 120 min. The delay is active from a set time of >15 minutes. This delay is about 5 min. If no other movements are detec
-
ted during this time, the delay starts again.
Impulse function
The impulse function can be used to control external HVAC systems. All 9 s will be set a 2.5 sec.
Alarm impulse
In order to initiate an alarm impulse, there have to be three detected movements within a period of 9 sec. This function can be used to display a presence in the room on external visualizations. All 9 sec. will be set an impulse of 2.5 sec.
The device does not fulfil the requirements of DIN EN50131­2-2 and therefore cannot be used in professional intrusion detection systems.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses sent to the master. The setting can be made with activated ( ) or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.
DIP switch functions
DIP 1 Fully automatic mode
(VA)
Semi-automatic mode (HA)
DIP 2 HVAC function Light control*
DIP 3 Operation mode DALI Operation mode DSI
* If you select „LIGHT“, the switching relay R2 operates synchro-
nously to the DALI light channel. The potentiometer R2 has no function in this setting.
Potentiometer A Lux Channel 1 Potentiometer B Time Channel 1 Potentiometer C Orientation light Potentiometer D HVAC Channel 2
LED I green LED II red LED III white
8.
Wiring diagram
Standard mode with Master/Slave
L N
L
N DA DA
E1 DALI/DSI
L
N NO
NO
R
S
+ -
Master Slave
L
R N
DA
HVAC H VAC
M1
T1
T2
9.
Manual switching and dimming
By pressing the push button, the phase can be given to the S terminal.
To turn on or off, press the push button briefly. The light will remain on or off, as people are detected plus the follow-up time.
With a long key press the light will be dimmed manually. When you release the button, the current brightness value is retained. Upon renewed dimming, the dimming direction is reversed.
Taking the phase to the R terminal by using a button, the HVAC channel can be switched with a short key press.
10. Range
10 m
6 m
4 m
10 m
360°
2.50 m
2
1
1 2
quer zum Melder gehen frontal zum Melder gehen Unterkriechschutz
Walking across Walking towards Seated
!
Connected slaves must have the same phase
as the Master.
R1
TE
1
3
6
22
18
16
10
30
25
LUX
40
2000
600
1200
200
9s 2s
LED ON LED OFF
LUX
40
2000
600
1200
200
R1
TE
1
3
6
22
18
16
10
30
25
LUX
40
2000
600
1200
200
20%
60
5
10
50
30
OFF
ON
!
R1
TE
1
3
6
22
18
16
10
30
25
LUX
40
2000
600
1200
200
R2
A
120
60
5
15
30
40
50
20%
60
5
10
50
30
OFF
ON
68 mm
A
Page 2
11. Exclude sources of interference
If the detection zone is too large, or areas are covered that should not be monitored, use the blinds to reduce or limit those areas.
12. Technical data
Sensor and power supply in one case
Power supply: 110-240VAC, 50/60 Hz Power consumption: ca. 1W Ambient temperature: -25°C to +50°C Degree of protection/class:
IP20 / II
Recommended height for mounting:
2 - 3m
Range of coverage Ø H 2.5m /T =18°C: seated
6.4m /
tangential
24 m /
radial
8m
Area of coverage:
circular 360°
Dimensions H x Ø [mm]
FC
84,5 x 80 mm
Visible part when built into ceiling:
15 x 80 mm
Lux value: 10 - 2000 Lux
• DALI/DSI
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts:
up to 50
Time settings:
1 - 30 min. / test
• Channel 2 Type of contact: NOC/with pre-travel tungsten Contact load: 2300W, cosϕ =1;
1150 VA, cosϕ = 0.5, µ contact
Technical data PD2 Slave
Power supply: 110-240 VAC, 50/60 Hz Impulse output: Optocoupler max. 2 W Impulse duration: 2 sec. or 9 sec. Dimensions: see above
Declaration of Conformity:
The product complies with the low voltage recommendation 2006/95/EC and the EMV recommen­dation 2004/108/EC.
13. Article / Part nr. / Accessory
Type FC
PD2-Master-DALI/DSI-HVAC 92698
PD2-Slave 9216 6
LUXOMAT
®
Remote control:
IR-PD-DALI-1C (incl. wall bracket) 92116
Accessories:
BSK Wire basket 9219 9
14. LED function indicators
LED function indicators
Process Standard mode Double locked
Initialisation time unprogrammed
red flashes green flashes
Initialisation time programmed
red flashes quickly
green
flashes
quickly
Motion detection
red flashes on each detected movement
green
flashes on each detected movement
Too bright detected
red flashes 2x per second
green
flashes
2x
per second
Too bright / too dark / undefined in opened state
red flashes very quickly
green
flashes very quickly
Toggle DALI/DSI DSI active
red shines 3 sec.
Toggle DALI/DSI DALI active
green shines 3 sec.
Toggle HA/VA VA active
red shines 3 sec.
Toggle HA/VA VA active
green shines 3 sec.
Toggle Preset/User Preset active
red shines 3 sec.
Toggle Preset/User User active
green shines 3 sec.
IR signal valid received
red and white shines 3 s
IR signal invalid received
red shines 0,5 sec.
100 h function active
red / green flashes variable
red / green flashes variable
Exit programming mode
If there is no entry for about 3 min. the programming mode is ended automatically.
Wall bracket for remote control IR-PD-DALI-1C
IR-PD-DALI-1C
15. Putting into operation of the remote control
IR-PD-DALI-1C (optional)
Settings with remote control override the potentiometer and DIP settings.
The DIP settings are reactivated by
• Setting the potentiometers to “TEST“ and ”SUN”, or
• Pressing the “Reset” button on the remote control in open state
Remote control LUXOMAT
®
IR-PD-DALI-1C
1. Check Battery:
Open battery compartment by pressing the plastic springs together and remov­ing the battery-holder.
2. Note:
Using the remote control, the occupancy detector can only be operated in dependence on brightness. The setting "SUN" can only be set with potentiometer A.
By using the remote control IR-PD-DALI-1C, we recommend to set potentiometer A on "SUN". Pushing the RESET button (remote control) would reset the brightness independence of the occupancy detector (SUN).
!
16. Settings by remote control in open state
Unlocking device – Activation of the programming mode
Resetting when open:
Deletes all values set with the remote control, light OFF.
Orientation light on/off
Automatic reading in the current light value as new lumi­nance set value
or
Dimming of the lighting on the desired luminance value
Adjusting of the luminance set value from 50 to 1500 Lux
+ / – small steps
+
/ – big steps
max
50
Lux
1500
Lux
ON
OFF
max
50 Lux
1500
Lux
ON
DSI/ DALI
Toggle between DSI and DALI program The Factory setting is DALI
or
+
Fully automatic / semi-automatic mode
Preset/user mode
Follow-up time orientation light
at
1
min
10 min
1. Start Light measure­ment by holding down the push button
2. Start LED ON/OFF a short press of pushbutton
optionaloptionaloptionaloptional
Follow-up time Channel 1: 1 - 30min.
Follow-up time Channel 2 (HVAC): 5 - 60 min. or impulse
1
min
5
min
30
min
60
min
Permanent double lock
With this function, the detector is perma­nently locked. This mode can only be activated during 5 sec. after closing the detec­tor. In this mode, only the function
„Light ON/
OFF“ can be activated.
Red LED ashes
optional
t < 5 sec.
Page 3
MAN 7860_PD2-M-DALI/DSI-HVAC_EN_160914_2
21. 100 h function
(long press when closed)
T5 and T8 are recommended to burn-in for 100h at maximum brightness before dimming. This would prolong the life of the lamp.
In the 100 h function mode, the detector only switches on and off. A dimming to the set value will be suppressed. The lamp has to burn for 100h, until the set value gets regulated.
The 100h function will be activated by pressing the button longer (>3 sec.). An activated time can be stopped by a long press of the button again. The red / green LED indicates if the function is activated.
Before any dimming is possible, the dimming function is
suppressed for 100h at T5 or 80 h at T8 uorescent lamps .
They have to burn in at 100%.
Failure to comply to the 100h burn-in would lead to reduc­ing the life of the lamp. Unwanted random variations in light intensity can be the result.
24. Reset the detector
The double lock being activated, the detector can be reset (deacti­vation of the double lock) as follows:
Disconnect operating voltage
Connect operating voltage for 31 to 59 secs.
Disconnect operating voltage again
Connect operating voltage again and wait for the self testing
Open detector
With this procedure, the remote control programmed values are not deleted (before activation of the double lock).
Alternatively, the detector can be reset in this way:
Disconnect operating voltage
Set potentiometer B to "TEST" and potentiometer A to "SUN"
Connect operating voltage
Except of the INI ON/OFF setting, the detector will be reset to factory settings or the settings of the potentiometers.
Pushing the "RESET" button on the remote control in open state will delete all of the values which were set by means of the remote control (except of INI ON/OFF) and set the detector back to factory settings.
17. Light regulation
The detector integrated two different light control algorithms. The
set value for the rst algorithm is adjusted by potentiometer (LUX)
on the device. Very small light amounts, which shine directly to the detector, have the result of a trigger under control of the set value.
The second algorithm has an integrated daylight compensation. Therefore, it is necessary that the detector analyses the switched light quantity. This algorithm can only be used by remote control. The programming of the set value and the measurement of the light quantity is carried out in two steps:
In the open state
The set value will be adjusted without daylight (please darken the room) by using the remote control.
Measuring the light quantity will be initiated by a long press (> 3 sec) of the test button. The detector turns the light on for 5 min. at 100%. Then the light will turn off and on for a short time and stays on after that. This
measuring process is shown by a ashing green LED (10
sec off / 1 sec on). This measuring process is required for every change of the set value.
If the measuring process is not performed, the detector performs it
automatically when the ambient light is less than 50 LUX for 1 h.
18. Fully automatic/ Semi-automatic mode
1500
Lux
The mode is changed using the button "Light" in the open state. Each time the button is pressed, the current operating mode is indicated by the LEDs: Red lights for 3 sec. = Fully automatic mode Green lights for 3 sec. = Semi-automatic mode
Fully automatic mode
In this operating mode, the lighting switches on and off automatically for increased comfort depending on presence and brightness.
Semi-automatic mode
In this operating mode, the light turns on only after a manual switching, for an increased savings success. Switching off is automatically or manually.
The semi-automatic mode basically behaves like the fully automatic mode. The only difference is that the switching on has to be done by hand, always!
!
19. Settings during the Self-test cycle
In the rst 60 seconds after connecting the AC voltage, the
following functions can be set:
!
INI-OFF/ON mode:
Turn off or turn on the detector during the self-test cycle of 60 sec. The final state is active. Factory setting is that the light is on during initialization.
In the mode INI-OFF, the detector does not turn on after connection to mains. Even movement switches the detector on only after 60 sec.
Startup behavior:
The set value can be reached in two ways after switching on. The detector switches the lights on at 10% and then adjusts upwards (min button) or it switches the light on at 100% and regulates down (max button). This is confirmed by a short flashing of red and white LEDs as well as the lighting. By factory default setting, the detector switches the light on at 100%.
20. Self-test cycle/Reset
Test mode
“TEST” button for activating the test mode, “Reset” button for deactivating it.
Resetting when closed
The lighting is switched off, and the follow-up times are reset.
22. Manual Switching
(short press when closed)
1500
Lux
You can switch the lighting on and off manually by pressing the button for a short time. It will stay on or off as long as
people are detected plus the congured follow-up time.
23. Manual Dimming – Preset/User
Manually dimming with external pushbutton - You can dim manually by pressing the push button for a long time (> 2sec.). When the button is released, the current dimming value is retained. Upon renewed dimming, the dimming direction is reversed.
Two different operating modes can be selected in the open state.
The button "Doublelock" is for toggling between the modes. Each time the button is pressed, the current operating mode is indicated:
Red lights for 3sec. = Preset Green lights for 3sec. = User
PRESET – the set value brightness is adjusted during start-up operation by the installer and remains unchanged. The set value
brightness congured through manual dimming is only applied for
the time being. The constant light regulation is now deactivated!
The current set articial light level is maintained independent of
the ambient/daylight brightness! After switching off and then on again, the originally adjusted set value brightness is reset = constant light regulation is activated.
USER
The set value brightness is changed upon each manual dimming and is re-adjusted by the user. The constant light regulation remains activated!