B.E.G. LUXOMAT PD1-M-2C, LUXOMAT PD1-S Installation And Operating Instruction Manual

3. Putting into operation / Settings
Self test cycle
The product enters an initial 60-second self-test cycle, when the supply is first connected. The occupancy detector is ready for operation.
Follow-up time for light control
The time can be set infinitely variably at between 15 seconds and 16 minutes.
Symbol
: Impulse < 1sec.
Symbol
TEST: Test mode (Every movement switches on the
light for a period of 1 second, switching it off for a period of 2 seconds after that regardless of the level of brightness.)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10 and 2000 Lux. Using the rotary control, the luminance set points can be set as desired.
Symbol
: Night-time operation
Symbol
: Daytime/ Night-time operation
Follow-up time for appliance-control
The time can be set infinitely variably at between 5 minutes and 120 minutes. There is a period of delay prior to switch-on of between 5 - 10 minutes for times set in excess of 15 minutes.
Symbol : Impulse = 1sec. Symbol A: Alarm impulse = 1sec.
Installation and Operating Instruction for B.E.G. - Occupancy detectors PD1-M-2C/-S-SM/-FC/-FM
2a.
Installation of the LUXOMAT® PD1-M-2C/-S-SM
2b. Installation of the LUXOMAT
®
PD1-M-2C/-S-FC
4.
PD1-M-2C: Settings carried out using remote control (optional)
Remote control LUXOMAT® IR-PD
1. Check Battery:
open battery compartment by pressing the plastic springs together and removing the battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio­meter 1 at “TEST” and Potentiometer 2 not at “SUN”. All values which have been programmed using the remote control will be deleted in the event of power failure in the position “TEST/ SUN”. Please switch Potentiometer 2 over to “MOON” or any other value.
Caution: Settings with remote control supersede the settings by courtesy of potentiometers.
1. Mounting preparations
Work on the 230V mains supply may only be carried out by quali­fied professionals or by instructed persons under the direction and supervision of qualified skilled elec­trical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
When in Master/ Slave mode of operation, the Master-appliance must always be installed at the location where there is least daylight.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e. opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated). This operating mode can only be activated during the period of 5 seconds after pressing the “lock“ button. This status will only permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/ off
The light will remain switched on/ off for as long as move­ments are detected in the areas of coverage. Once the last movement has been detected, the light will remain on for the duration of the follow-up time as per setting. The appliance will then return independently to the mode selected (Fully or Semi-automatic).
Option:
Wall bracket for remote control IR-PD
2c.
Installation of the LUXOMAT® PD1-M-2C/-S-FM
IR-PD
IR-PD-Mini
B.E.G.
LUXOMAT® PD1-M-2C/PD1-S
The detector can be installed in conventional inlet­sockets mounted on the ceiling.
The assembly plate enclosed must be stripped off prior to instal­lation and secured to the ceiling using 4 screws and ensuring that it is not laterally transposed.
For surface-mounting, an inwall sensor unit is combined with a surface-mounted receptacle as a housing base.
Before mounting the base, the enclosed mounting plate must be mounted true to side, i.e. the writing must be legible.
Now fix the base on ceiling or wall, but first put the cable through one of the cable openings provided. The detector must be mounted on a flat, solid surface.
Next prepare the sensor part by screwing in both fixing screws, then connect the cable as per the wiring diagram.
Now insert the sensor part and check for matching positioning of the two markings. Press beyond the spring housing pressure so that the sensor part firmly locks in place. Now turn the sensor part counter-clockwise for about 10° to the stop.
The detector has been designed and developed specifically for installation in sus­pended ceilings.
A circular opening of diameter 68 – 70mm must be produced in the ceiling.
Having connected up the cables in accor dance with regulations, the detector is inserted into the opening as shown in the drawing opposite and fixed into position with the assistance of the spring clips.
120
60
50
40 30
15
10
A
16
10
5
2
1
30
15
2000
1200
600
200
40
5
1
1 2
2
120
60
50
40 30
15
10
A
16
10
5
2 1
30
15
TEST
2000
1200
600
200
40
5
2000
1200
600
200
40
120
60
50
40 30
15
10
A
16
10
5
2
1
30
15
TEST
5
120
60
50
40 30
15
10
A
5
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
TEST
5
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
TEST
5
B.I.T.
Q.C.
PASSED
1
GB
6 mm
Having connected up the cables in ac­cordance with regulations, the detector can be placed in position as shown in the drawing opposite and, applying a little pressure, can then be locked into position with the assistance of the spring clips.
Unlocking device
Lock device
Luminance set point
Automatic reading in the current light value as new luminance set point
Individual light value 2 - 2500Lux
Follow-up time (relay and channel 1)
15sec. up to 30 min.
Impulse function (relay and channel 1)
1sec. ON, 9 sec. OFF
Time setting (relay and channel 2)
5 min. up to 120 min.
Impulse function (relay and channel 2)
The voltage-free contact is closed for a period of 2 seconds. This is followed by a period of idle time of 8 seconds’ duration.
Alarm impulse program for appliance control (relay 2)
The relay will not close until at least three movements have been registered over a period of 10 seconds (impulse = 1 second).
Preset/ user mode
Fully automatic/semi automatic mode => (see page 2, point 5)
Semi automatic: red LED (ashing), Fully automatic: red LED on for approx. 3sec.
Resetting when open
All values which have been programmed using the remote control IR-PD are deleted, and those values which have been set by potentiometer are activated.
 
A
3
1500
Lux


 


R1



R2
Sensor and power supply in one case for onwall-, ceiling­and flushmounting
Power supply: 230V~ +6 %/-10% Power consumption: < 1W Ambient temperature: -25°C to +50°C Degree of protection/class: SM IP54, FC and FM IP20, FC
with accessory IP23 / II
Settings: manually and by remote control Light values: 20 - 1000Lux (Remote control) Extension of the detection area: with Slaves Area of coverage: square 4 x 90° Range of coverage Ø H 2,50m / T= 18°C:
seated 4.20m / tangential 7.50m / radial 4.50 m
Recommended height for mounting: 2 - 3 m Light measurement: mixed light, daylight + artificial light Lux values: 10 - 2000Lux (Potentiometer)
• Relay/Channel 1 for light-connection
Type of contact: dry contact type NO Contact load: 2300W cos (ϕ)=1 / 1150VA cos(ϕ) = 0.5 Time-settings: 15sec. - 16min. (30min. with remote
control) / Test
• Relay/Channel 2 for HVAC
Contact load: 230V~, 3 A cos(ϕ) =1 Time-settings: 5 min. - 120min. with time delay of 5 min.
for follow-up time > 15min.
Dimensions
H x Ø [mm]
SM FC FM
PD1-M-2C 80 x 98 84 x98 65 x 98 Visible portion when built into ceiling: 30 x 98mm
Technical data PD1-Slave
Electrical data same as above, but just one channel for signaling motion detection
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the EMV recommendation 2004/108/EC
11.
Technical data PD1-Master-2C
10. PD1-M-2C - Connections
Type SM FC FM
PD1-M-2C (Master) 92177 92174 92170
PD1-S (Slave) 92178 92175 92172
LUXOMAT
®
Remote control:
IR-PD (incl. wall bracket) 92160 IR-PD-Mini 92159
Accessory:
BSK Ball basket guard 92199 Wall bracket for remote control as replacement
92100 Blinds 92260 Occupancy detectors - Covering IP23 92206 SM-Socket for PD1-FM 92171
8. Article / Part nr. / Accessory
MAN 6316 – 211209–1
7. Range of Coverage
5. Fully / Semi automatic mode
(for IR-PD functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati­cally on and off for increased comfort, depending on presence and brightness.
Semiautomatic operation (Semiautomatic can only be activated via the remote control!)
In this operating condition, in order to gain increased savings, the lighting is energized only after being manu­ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully automatic one. However, the difference is that switching­on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired in parallel on the “R” button input (ON/ OFF).
6. Manual Switching
You can switch the lighting on and off manually by pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
12. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT® PD1-M-2C (red and green LED‘s)
Red LED indicating self-checking mode (over a period of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second EEPROM/ memory empty
Flashing rapidly
EEPROM/ memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked Flashing extremely rapidly
Not-accepted command, occurs, for example, when an attempt is made to input twilight-value are too bright or too dark
Lights up for 3 seconds
Fully automatic mode
Flashing for 3 seconds
Semi automatic mode
Green LED as an indicator of status (only for status “Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off (dependent upon operating mode)
Not illuminated
Detector identifies dark, light on (dependent upon operating mode)
lluminated for 2 seconds
Signal validly received (dependent upon operating mode)
7.50 m
4.20 m
7.50 m
4 x 90°
2.50 m
1 2
1
quer zum Melder gehen frontal zum Melder gehen Unterkriechschutz
Walking across Walking towards Seated
1500
Lux
1500
Lux
Connection PD1-M-2C
NONO
NR L L
SLAVE
L'
3A
2
9. Wiring diagrams
Standard operation, manual switching possible (NO-contact to be pressed for approx. 1sec.). The potentiometers not to be set on “Test“ or “Sun“ otherwise the preadjusted values will get lost during this manual operation.
Master-/Slave-operation, i.e. Masters opera­te as Slaves but with additional push button function to switch the light manually. The preset
values will not get lost. The Master is the only unit to read in the levels and to switch the connected loads. The Slave units will react on motion only, independ­ently of the Lux levels, by sending an impulse via the dry contact, to the Master.
Terminal connection for Master-/Slave-operation
R 2
MASTER MASTER/SLAVE
modus
Master-/Slave-operation with one Master and several Slaves. The Master is the only unit
to read in the Lux levels and to switch the connected loads. The Slave units will react on motion only, in­dependently of the Lux levels, by sending an impulse via the dry contact, to the Master.
Terminal connection for standard operation
HVAC
MASTER
HVAC
SLAVE
MASTER
Terminal connection for Master-/Slave-operation
Standard operation with external push button
HVAC
MASTER
Standard operation
3
3