Thank you for purchasing the motion detector. You have opted for a quality product from the B.E.G. range and for one which has been manufactured, tested, packaged and despatched with the utmost care. Please read the information contained in these directions before commencing assembly. We reserve the right to make any technical adjustments which are in the interests of product ­improvement.
CAUTION: have all work involving the 230 V mains
supply carried out by a qualied electrician! Before starting disconnect the mains!
Type Part-No.
Indoor 180-SC, fully tted, pure white
Sensorinsert for Indoor 180-SC 92668 Covering IP20, pure white 92630 Covering IP20, trafc white 92631 Covering IP20, cream 92632
Covering IP20, silver 92633
Covering IP20, anthracite 92634 Covering IP54, pure white 92139
Accessory
Stair light switch SCT1 92655
92650
1. Function
With the LUXOMAT® Indoor 180 you acquired a
B.E.G. -motion detector for ush mounting in indoor
and outdoor applications.
LUXOMAT®
conceived for use with automatic stairway lighting devices. The
LUXOMAT®
standard light-contact push buttons. You can do this in both 3-wire as well as with 4-wire circuits. It is not necessary to rewire.
LUXOMAT® Indoor 180 -SC needs only two wires and
takes the power it needs to operate from the stairwell lighting-timer switch-off-device (ca. 4mA/230 VAC) .
Detecting movement
The LUXOMAT corresponds to the functioning of typical motion sensors, i.e., thermal radiation of persons and other heat sources (e.g. animals) moving within the sensing area are measured and the ambient lumi­nosity is compared with a twilight threshold value.
Ambient luminosity
Set the twilight threshold value on the “LUX” rotary
control. The LED (behind the Fresnel lens) ashes
Indoor 180 -SC was specically
Indoor 180 -SC is used to replace
®
Indoor 180 -SC’s motion detection
quickly if the ambient luminosity is set higher than the adjusted twilight threshold. The LED is extin­guished as soon as the ambient luminosity is less than the adjusted twilight threshold.
Triggering the stairwell lighting-timer
If the ambient luminosity sinks below the twilight threshold value and a movement is detected, the
LUXOMAT
through a high-performance FET for ca. 100 msec.
(this corresponds to briey pushing the button).
This short impulse actuates the stairwell lighting­timer and the connected lighting is switched on for the switch-off delay time set on the stairwell lighting-timer.
Post-triggering the stairwell lighting-timer
A new impulse can be triggered only after ca. 10 seconds. This delay is necessary to ensure the
LUXOMAT
As it is possible to connect several detectors (up to ten detectors) in parallel to one stairwell lighting­timer, each detector is capable of detecting the impulse from one connected detector and, if applicable, to generate a new impulse delayed correspondingly.
Suppressing the twilight threshold-value query
Each impulse leads to the stairwell lighting-timer being switched on or post-triggered. That means all the detectors in the stairwell area “see” the switched-on connected lighting so that the evalua-
tion of the twilight threshold value becomes difcult
or even impossible. Therefore, upon detection of an impulse, all detectors suppress the twilight threshold-value query for the time set on the “MIN” rotary control. Every detected motion leads to a post-triggering impulse, independent of the ambient luminosity. We recommend setting the time set on the “MIN” rotary control either the same or a bit higher than the switch-off delay time set on the stairway lighting-timer. The LED displays as follows during the suppression phase of the current ambient luminosity:
--> bright: the LED ashes very quickly
--> dark: LED off
Detection area
The LUXOMAT® Indoor 180 -SC is equipped with a hemispherical Fresnel lens, which produces a semicircular sensing area (horizontal 180°, vertical ca. 60°) in wall installations. The size of the moni­tored area is 10m from the front and side for the recommended installation height of during movements that are crossways to the line of the lens segments.
The number of parallel connected LUXOMAT® Indoor 180-SC’s
Do not connect more than ten LUXOMAT® Indoor 180 -SC’s in parallel in order to prevent possible spurious triggering. The max. possible quantity is also restricted through the type of stairway lighting-timer used: Caution – if not enough power can be drawn from the stairway lighting-timer, the supply voltage for the motion sensors sinks and malfunctions occur in the motion sensor. Furthermore, the stairway lighting-timer switch might be permanently switched on.
®
Indoor 180 -SC closes the supply feed
®
Indoor 180 -SC has sufcient power.
1.10 - 2.20 m
Wiring/connection
It is necessary to pay attention to the polarity of the two wires.
Make sure you observe the following points prior to installation:
The LUXOMAT® Indoor 180 -SC is intended for installation in standard size-I inlet-sockets. We recommend installing at a height of 1.10 to 2.20 m.
• Ensure the view is clear as the infrared rays
cannot penetrate through solid objects.
• If you do not want movement underneath the
sensor to be detected, you can clip the enclosed covering cap (A) onto the mask cover (B) *If the sensor covers zones that should not be monitored, the corresponding lens segments must be masked off, for instance with transparent tape, which can be determined by testing.
Frontal approach
Motion sensors are most sensitive if the move­ment
is crossways to the line of the lens seg­ments. When being approached from the front the sensitivity and thus the effective range is significantly reduced.
3. Installation
The detector can be installed in conventional instal­lation sockets. Installation should be made to a wall with a height of
For the combination with switches of leading manufacturers the enclosed additional blinds can be used.
1.10 to 2.20 m
.
Mounting diagram
A
B
F
E
• Clear mains’ voltage!
Connect sensor part (A) according to the regula-
tions and as shown in the wiring diagrams (pt. 5).
• Depending upon the concealed housing, fasten
at the top and the bottom or left and right using the enclosed screws (B).
• Additionally to the horizontal detection plane the
Indoor 180 has a vertical detection plane which detects also movements underneath the motion­detector. In order to prevent detection within the vertical range of coverage, apply cover (C).
• Next introduce and fasten the blinds (D) and the covering-cap (E).
• Switch on mains‘ voltage. The LUXOMAT®
Indoor 180 is ready for use after having com­pleted a self-checking cycle of about 60 seconds.
D
C
Page 2
• Settings of the operating time and twilight value.


• Mount covering-cap (F).
• The covering-cap (F) can be removed as shown
in the drawing.
D
D
F
F
For outdoor installations additionally the IP54-acces-
sory-xing-set has to be mounted (Part nr. 9 213 9).
4. Adjustment – Rotary control
4.1 Twilight threshold value:
The lighting actuator value can be preset between 5 and 2000 Lux
Night setting
Day/night operation
LED
4.1
4.2
C
4.2 Suppressing the twilight threshold-value query
The suppression time can be set from ca. 1min. to 10min.
5. Wiring diagrams:
Standard mode with 1-channel motion detector
(e.g. stairs) Indoor 180-SC (max. 10)
6. Technical data
• Operating voltage via the stairway lighting- timer 230 VAC
• Power consumption ca. 4mA /230 VAC
• Impulse duration 0.1sec.
• Impulse switching capacity
max. 200 mA /230 VAC
• Detection area 180 ° horizontal ca. 60° vertical
• Detection range at
height:
10m
max.
during sideways passing
ca. 3m during direct approach
• Twilight threshold value ca. 2 - 2000 Lux
• Twilight threshold-value suppression ca. 1min. - 10min.
• Dimensions L x W 87 x 87mm Installation depth 36mm
• Protection IP20, II
• Housing UV- and shock-resistant
Notice:
The impeccable function can only be guaranteed by using the SCT1 staircase lighting time switch (92655) of B.E.G. Commercially available stairway-lighting timer­switches differentiate according to the type and manner in which the neon glow-lamp push button is energized. There are models available with integrated half-
wave or full-wave rectication.
As the
LUXOMAT® Indoor 180 -SC uses the result-
ing neon glow-lamp supply to power itself, this determines the current consumption and thus the max. possible number of the 180 -SC’s.
Caution:
Full-wave rectication leads to greater dissipation
power-loss and thus to the LUXOMAT® Indoor 180-SC becoming heated-up.
1.10 - 2.20 m
installation
(with accessory IP54)
Polycarbonate
LUXOMAT® Indoor
9. Trouble shooting – Practical hints
1. Lamp does not light up
- Tungsten halogen lamp defective
Replace tungsten halogen lamp
- No mains connection
Check connection by qualified electrician
- Incorrect setting of lux level
Correct setting of lux level
- Unit mounted too high
Mount at recommended height
- PIR detector lens obstructed by dirt or other objects
Clean lens or remove objects
- Main fuse defective
Check or replace by qualified electrician
2. Delayed lamp activation
- Mounted too high
Mount at height stated in specification
(
1.10 - 2.20m
- Direct line of approach
Re-direct walking so that the approach is not
frontally
3. Lamp stays on continuously
- Continual thermal activity detected ie. extractor fan, central heating ducts
Check for any activity which could cause unit
detection to be maintained
- Delay time set too high
Reduce time delay Check ambient noise-level, if necessary switch off
noise-sources
4. Limitation of range
(not up to the minimum specication)
- Mounted too high
Correct mounting height
- Temperature difference between ambient tem­perature and source of heat too small
No improvement possible
- Direction of movement aimed directly at lens of motion detector
Move laterally to detector
)
L
N
LN
30 sec. 
10min.
E1
34
7. Electromagnetic compatibility
It cannot be excluded that spurious triggering can be caused when placed directly in the area of strong radio transmitters (e.g. radio operators, taxi control centres, cell phones etc.).
However, these phenomena do not cause any
defects in the sensor technology. If such spurious triggering does occur, the LUXOMAT® Indoor
L΄΄΄΄L
C1
L΄΄΄΄L
C1
180 -SC automatically switches off after the source
of HF interference has disappeared.
8. Detection area
1.10 - 2.20 m
1
3 m
10 m
1 Walking towards 2 Walking across
2
180°
12 m