B.E.G. 91022, 91021, LC-Click-N 140, LC-Click-N 200 Installation Instructions

GB
1:4
1.
0.5
0.25 Futura Book 24Pt
40
LUXOMAT® LC-Click-N 140 / 200
Installation and Operation Instruction motion detector B.E.G.LUXOMAT® LC-Click-N 140 and LC-Click-N 200
1. Mounting preparations
1
2
1) Caution: have all work involving the
110-240V mains supply carried out by
a qualified electrician! Before starting disconnect the mains! Please be aware, that the LUXOMAT® LC-Click-N 140/200 is not suitable as an intrusion detector, since it is not equipped with a tamper contact.
2) Socket base corner mounting
The device is not suited for safe disconnection of the mains supply.
Important: The LUXOMAT® LC-Click-N 140/200 has to be mounted in such a way, that the adjusting elements / rotary regulators are always pointed downward.
Caution: Do not connect more than2 LUXOMAT® LC-Click-N in one circuit, to avoid any erroneous switching.
2. Wall mounting
Mount the plug-in socket with two screws and the enclosed seal rings on a firm base. (Pay attention to inserting of the connection cable, see point 3)
3.
Inserting of the connection cable
2
1
1) Cable entry points
2) Terminal markings
4. Sensor head optics
By swinging the sensor head horizontally (ca. 90°) and vertically (ca. 85°) detection area can be changed.
5.
Exclude sources of interference
If necessary, the lens segment(s) corresponds to unwanted detection zones may be masked
with the enclosed covers to reduce the eld
of vision.
6. Mounting types
1
1) Wall mounting
7. Putting into operation / Settings
Self test cycle
After mounting and connecting the 230 VAC supply volta­ge, the LC-Click-N 140/200 runs a self testing unit. Then the unit is ready for operation and the settings can be made manually or with remote control.
1.2
50
6
20
4
20
sec
min
2) Influence of weather reduces the lifetime of
10
130
1000
2 Lux
1) If possible mount unit on a safe place (wall or ceiling mount)
1.2
50
20
130
1000
4 sec
6
20 min
40
10
2 Lux
the unit. Please take care to mount correctly.
Follow-up time
4 sec. ... 20 min.
Lux value
Night operation...Dusk...Day operation (Day operation: light sensor inactive, switching at any brightness value)
> 1m
3) Minimum distance to switched lighting, frontally or laterally to device: 1m
4) Never mount the connected lights below the motion detector!
8. Range of Coverage
2,50 m
3
4 m
2 m
12 m
Walking Towards
1
2
Walking across
Anti-creep
3
2,50 m
2
140°
3
4 m
2 m
12 m
2
1
Walking Towards
Walking across
2
Anti-creep
3
1
10 m
1
10 m
9. Wiring diagrams
Standard mode with 1-channel motion detector
L
N
Standard mode with 1-channel motion detector with permanent light function
L
N
Standard mode with 1-channel motion detector with NC pushbutton
L
N
E1
N L L‘
C1
Parallel connection with 1-channel motion detectors max. 2 parallel
L
N
E1
N
10. Dimensions (mm)
L‘
L L
N
C1
L‘
C1
11.
1. Lamp does not light up Cause - Action
Lamp is defective
No mains connection
80
Switching threshold of the twilight switch is not correct
67
36
Detection area not set correctly Set detection area correctly. Unit mounted too high
78
2. Delayed lamp activation
Mounted too high
Only direct in-line approach of detector is
60
possible
78
3. Lamp stays on continuously
Continuous thermal movement within detec­tion area
Check the correct functioning of the detector in fully covering the lens (lights should go out after a certain time-delay). Motion detector is switched parallel to a switch that enables direct manual switching on
E1 S1
N L L‘
C1
Standard mode with 1-channel motion detector (e.g. stairs)
L
N
E1
L
N
L‘
Trouble Shooting-Practical hints
- Replace light bulb.
- Check mains fuse.
- Accordingly adjust sensitivity of twilight switch via the setting dial.
- Mount at recommended height (2.50m)
PIR detector lens obstructed by dirt or other objects
- Clean lens or remove objects
- Mount at height stated in specication (2.5 m)
- Mount detector in such a way that a sideways approach is also detected.
- Remove the heat source out of the detec­tion area.
- Mind the correct connection of the switch.
optional:
RC
S1 = switch for permanent light RC = RC-suppression kit if required
L
N
T2
T1
30 s -
10min.
4
3
4. Light source remains on for long periods when no persons are present
Permanent inuence from heat sources within
detection area (trees, shrubs when blown by the wind, presence of animals like cats and dogs in the detection area)
- Reduce detection area of the detector in turning the detector head downward or cover parts using the enclosed covers.
Direct sunlight radiation into detector lens
- Shelter lens from direct sunlight.
Detector mounted above extractor fan
- Change mounting place of the detector.
5. Limitation of range (not up to the minimum
specication)
Mounting height is not optimal
- Accordingly change mounting height (2.50 m).Persons only move directly towards
the detector
- Mount detector in such a way that a sideways
approach is also detected.
Steep terrains
- Adjust spherical head accordingly.
6. No reaction to vehicles
Vehicle not warmed up Vehicle is well insulated (by silencing equipment)
E1T7
L
N
L‘
C1
T 1 = NC button
Manual switching additionally possible (press opener approx. 2 sec.).
12. Technical data
Power supply
Detection area
140° LC-Click-N 200 200° and 360° anti-creep protection
Range of coverage in m: max. 12 m when walking across (tangential
Degree of protection/class: IP 54 / Class II /
Dimension: Ambiente temperature: -25°C to +50°C
Package:
: 110 - 240VAC,
50/60Hz
: LC-Click-N 140
L 103 x B78 x H 80 mm
Housing UV- and shock-resistant Polycar­bonate
)
Chanel 1 for light control Contact load: 1000W, cosφ=1 ,
µ-Contact
Time-settings: Brightness value: 2 - 2000 Lux
Declaration of Conformity:
The product complies with the low voltage recommendation 2006/95/EC/ and the EMV recommendation 2004/108/EC.
13.
Article / Part nr. / Accessory
4 s - 20min.
Article Colour Part.-nr.
LC-Click-N 140 white 91001
LC-Click-N 140 black 91021
LC-Click-N 140 brown 91011
LC-Click-N 200 white 9100 2
LC-Click-N 200 black 91022
LC-Click-N 200 brown 91012
Accessory: RC-Suppressor 10880
MAN 7023 – 240714-8