BECKWITH ELECTRIC M-2001D Quick Start Manual

Page 1
M-2001D Tapchanger Control Quick Start Guide
Death or severe electrical shock can occur.
WARNING: In no case should the line current circuit be interrupted with the regulator
or transformer energized. Do not remove auxiliary current transformers without shorting the current inputs.
Exercise care during installation, operation and maintenance procedures
The equipment described in this manual contains voltages high enough to cause serious
injury or death. Only qualied personnel should install, operate, test, and maintain this
WARNING:
Remove Fuses Before Service.
WARNING: When an adapter panel is not used, automatic shorting of
CT inputs is not provided by the M2001D/M-2050; the customer must provide a method for shorting the CT's before the control is disconnected.
24-Pin Connector (P2)
Voltage Input (Polarity)
Neutral
Load Current (Return)
Load Current (Polarity)
Circulating Current (Polarity)
Circulating Current (Return)
Tapchanger Raise Output
Motor Power Input
Voltage Reduction Step #2 or
Contact KeepTrack 1R1L/1N Input
Contact "Wetting"
Supply + 12 Vdc
Operations Counter/
Switch Status Input #1
Operations Counter/
Switch Status Input #2
Input 1 Motor Seal-in/
Switch Status
Neutral Position Detector #1
Neutral Position Detector #2
Tapchanger Lower Output
Non-Sequential Operation/Auto Tap Inhibit Input/SCADA Cutout
Voltage Reduction Step #1 or
Contact KeepTrack 1R1L/1N Input
Motor Seal-in Disconnect Output
User-Programmable Alarm
Self-Test Alarm
User-Programmable Alarm
Non-Interruptable Pwr Supply Input
Self-Test Alarm
P3
Source Voltage Input
Aux Output
Aux Input A1
Or DVAr2 Disable Input
Aux Input A2
Aux Input A3
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Fuse ¼ Amp
Voltage Input (Polarity)
Load Current (Return) See Note 2
Voltage Input (Return) See Note 2
Load Current (Polarity) 0.2 A
Circulating Current (Polarity) 0.2A
Circulating Current (Return)
Self-Test Alarm (Return) See Note 4
User-Programmable Alarm (Return)
Self-Test Alarm (Input) See Note 4
User-Programmable Alarm (Input)
Motor Seal-in
Note 3
AUTO
OFF
OFF
RAISE
LOWER
RAISE
LS
LOWER
LS
AL INTERLOCK
AR INTERLOCK
AUX LOWER (AL)
AUX RAISE (AR)
AL AR
MOTOR
FUSE 6 A
MOTOR POWER 120/240 V
See Note 1
R L
NOTES:
1. Motor voltage may be 120 or 240 V to neutral, or 240 V phase-to-phase.
2. The customer is to provide an earth ground connection to the CT/VT’s
neutral connection, external to the control.
3. To Motor Power Seal-In board.
4. If the M-2001D is configured for the SCAMP pushbutton Auto/Manual
Switch type, then the Self-Test Alarm relay is NOT available.
TX
Bottom View
Top View
Front
Fiber Optic V-Pin
Connector (optional)
Fiber Optic ST
Connector
RJ-45 Ethernet over
Copper (optional)
Control Power
Backup Input
BlueTooth
Ethernet over Fiber
Optic (optional)
RS-485
RS-232 DE9S
In-Line, 6-Pin Connector
for the M-2025B, C or D
Current Loop Module
24-Pin Blue Connector for
M-2000 Series Adapter
Panels or Direct Connection
Source Voltage Input
One Aux Output
Three Aux Inputs
LCD SCREEN Pressing any pushbutton will wake up the LCD and display the heading corresponding to the “Hot Button”
label inside the pushbutton - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR.
EXIT/WAKE Pushbutton The EXIT WAKE Pushbutton wakes the LCD from sleep mode and begins scrolling through a list of user programmed metered/calculated values.
While navigating through the di󰀨erent HMI
menus the EXIT pushbutton is used to:
- Exit a level to the next higher level
- Cancel data entry
- Clear the screen when at the header level
VR Pushbutton Activates the user dened
Voltage Reduction Steps.
Shortcuts/Arrows
SETP Access to the Setpoints Screens.
MNTR Access to the Monitoring Screens.
ENT/UTL Pushbutton Access to the
Utilities screens and ENTER button.
While navigating through the di󰀨erent HMI
menus the ENT pushbutton is used to:
- Enter the edit mode of a screen
- Store a setpoint or condition in memory
- Enter the sub heading data level
- Reset certain monitoring screens
CNFG Access to the Conguration
Screens.
COMM Access to the Communication Screens.
RAISE LED Out of Band Low Voltage.
LOWER LED Out of Band High Voltage.
REV PWR LED Indicates reverse power
ow.
OK LED Illuminates to indicate the micro controller is functioning properly and is extinguished when a Motor Seal-in Failure
Block is in e󰀨ect.
COM1 TX/RX LEDS Indicates when control is transmitting and/or receiving data.
ALARM LED Indicates any of the programmable alarms are activated.
V/RED LED Indicates voltage reduction has been invoked.
- Continuous illumination and one periodic
ash indicates Level 1 Voltage Reduction.
- Continuous illumination and two periodic
ashes indicates Level 2 Voltage Reduction.
- Continuous illumination and three periodic
ashes indicates Level 3 Voltage Reduction.
MANUAL LED Indicates automatic control is disabled and in manual mode.
LOCAL LED Indicates control is switched into Local mode. Cannot command control to raise or lower via SCADA.
USB Port Used for Direct TapTalk® Communications Connection.
Smart FlashCard Slot Used for loading
and saving setpoints, saving Datalog les, SOE les, OSC les, Clone save and load, load and save DNP les, Firmware Update, save Wake-up Screens, save ALL
Metering Parameters and can be utilized as an Access Code Key.
Scan this QR Code for direct access to product software and support documents.
Page 2
Press ENT to view Tapchanger Status
Press ENT to view Alarm Status
Press ENT to view Input Status
Press ENT to view Output Status
Peak RMS Curr x.x mA (x.x) T
Avg RMS Curr x.x mA (x.x) T
Profile Duration XXXX.Xms(xxxx.x)T
Peak Motor Current E x.x mA
Voltage % THD x.x %
Current % THD xx.x %
Press ENT to view Voltage Harmonics
Press ENT to view Current Harmonic
Status
Motor Current
Harmonics
MONITOR
UTIL SETP
Tap Information
Present Demand
Demand History
Energy Metering
Tap Position/Cal DISABLE
Drag Hands E L= 0 N R= 0 N
Definite Timer Raise xxs Lower xxs
Intertap Timer xxx %
Operation Counter x
Resettable Counter E x
Neutral Sw Counter x
Lower Counter x
Raise Counter x
Press ENT to view specific Tap Stats
Press ENT to clear Tap Statistics
RTN Success Counter xxxxx
RTN Status DISABLED
Count to RTN Active xxxxx
Demand Interval xx Min
Demand Load Voltage xxx.x Volts
Demand Pri. Current
xxx.x Amps
Demand Pri. Watts
x.xx MW
Demand Pri. VArs
x.xx MVArs
Demand Pri. VA x.xx MVA
Demand Interval xx Min
Min Load Voltage E x.x Volts
Max Load Voltage E xxx.x Volts
Max Pri.Current E xxx.x Amps
Max Primary Watts E x.xx MW
Max Primary VArs E x.xx MVAr
Max Primary VA E x.xx MVA
PF @ Max VA E
x.xxx PF
Press ENT to reset Demand History
Press ENT to perform Master Reset
Watt Hours Fwd
E
x kWh
Lagging VAr Hours E x kVArh
Watt Hours Rev E xx kWh
Leading VAr Hours E x kVArh
Press ENT to reset Energy Metering
Press ENT to perform Master Reset
If DVAr enabled
Metering
Load Voltage xxx.x Volts
Meter Out Voltage xxx.x Volts
Source Voltage
disabled
Load Current x.x mA Lead/Lag
Circulating Current x.x mA LEAD/LAG
DVar Current x.x mA LEAD/LAG
Compensated Voltage xxx.x Volts
Primary Voltage x.xx kV
Primary Src Voltage
disabled
Primary Current xxx.x Amps
Primary Watts
x.xx MW
Primary VArs
x.xx MVArs
Primary VA
x.xx MVA
Power Factor
x.xxx LEAD/LAG
Frequency xx.x Hz
Load Voltage xxx.x Volts
Watt Hours Fwd E x.xxx MWh
Press ENT to view Tapchanger Status
Press ENT to view Alarm Status
Press ENT to view Input Status
Press ENT to view Output Status
Peak RMS Curr x.x mA (x.x) T
Avg RMS Curr x.x mA (x.x) T
Profile Duration XXXX.Xms(xxxx.x)T
Peak Motor Current E x.x mA
Voltage % THD x.x %
Current % THD xx.x %
Press ENT to view Voltage Harmonics
Press ENT to view Current Harmonic
Status
Motor Current
Harmonics
* Power Flow Reverse setting screens are only available when the "Reverse Power Operation" selection under "Common Settings" is selected to either: REGULATE REVERSE, REG. R MEASURED SRC, DISTRIBUTED GENERATION, AUTO DETERMINE or AUTO DETERMINE MEASURED. If Distributed Generation is selected, then only LDC values can be set.
Selecting BLOCK, IGNORE or RETURN TO NEUTRAL disables the Power Flow Reverse setting screens.
Active Setpoint Profile or Setpoint Profile
Selected for Editing
Limits 1
Profile Settings
Common Settings 1
Block Raise Voltage
xxx.x Volts
Block Lower Voltage
xxx.x Volts
Runup Deadband
x.x Volts
Current Block Limit xxx mA
Runback Deadband
x.x Volts
Runup Enable/Disable disable
Active Profile 1
Edit Profile 1 Name
"Empty"
Profile to Edit 1
Repeats for
Profiles 2-4
LDC Selection RX
Timer Reset INTEGRATING
Timer Characteristic DEFINITE
Power Direction Bias NONE
Rev Power Operation BLOCK *
Bandcenter Fwd
xxx.x Volts
LDC X Fwd x Volts
Bandwidth Fwd
x.x Volts
LDC Z Fwd
x Volts
With LDC R,X
With LDC Z
Bandcenter Rev
xxx.x Volts
Bandwidth Rev
x.x Volts
LDC X Fwd x Volts
LDC Z Fwd
x Volts
With LDC R,X
With LDC Z
VAr Bias 1
Disable on Rev Pwr disable
Set VAr Bias Method Step
Set VAr Bias Method disable (Step, Linear)
Fwd Max Cap Bnk Size 12000 KVAr
Rev Max Cap Bnk Size 12000 KVAr
Lead % Pickup 75
Lag % Pickup 75
VAr Bias Volt Step
1.0 Volts
Max VAR Bias Time 300 mins
Curr Mult Base Value x
Disable on Rev Pwr disable
Set VAr Bias Method Linear
Linear V Bias -X x Volts
Normlzd Lin V Bias -X x.x Volts
Linear V Bias -X Lmt
x.x Volts
Linear V Bias +X x Volts
Normlzd Lin V Bias +X x.x Volts
Linear V Bias +X Lmt x.x Volts
To Profile Settings
To VAr Bias
Voltage Reduction 1
VRed Turnoff Time x Min
Smart VR disable
Save VR at Power Off DON"T SAVE
Standard VR disable
Reduction Step 1 %
2.5
Reduction Step 3 %
7.5
Reduction Step 2 %
5.0
LDC R Fwd x Volts
Definite(Inverse) Delay Fwd xx Sec
Power Flow Rev 1
Power Flow Fwd 1
LDC R Fwd x Volts
Definite (Inverse) Delay Fwd xx Sec
SETPOINTS
MNTR CNFG
Sheet 2 of 4
800-M-2001D-QSG-08 (03-17)
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.
COMMUNICATION
CNFG UTIL
CONFIGURATION
SETP COMM
UTILITIES
COMM MNTR
To
Harmonics
To Tap
Information
Page 3
CONFIGURATION
SETP COMM
Tap Settings
Tapchanger Type
Remote Voltage Bias
Enable/Disable disable
RVB HB Timer
x Secs
RVB Scale Factor
x.x
Rev RVB Scale Factor
x.x
Run Through Neutral
Enable/Disable disable
Reset RTN Succ Ctr Press ENT to begin
Max Allowed Taps
x
Max RTN Standby Ops xx
Taps Between Runs
xxxx
Max Load Current xx mA
Nameplate
Auto/Man Sw Type SCAMP SWITCH
Scamp Init Pwrup AUTO MODE
Auto/Man Sw Type NONE/TOGGLE
Comm Block Auto DON'T SAVE
CT Multiplier xxxx X
Load VT Config LINE_TO_GROUND
Aux Curr Transformer xxx mA
CT/Load VT Phasing
x Deg
Load VT Multiplier
xx.x X
Load VT Correction x.x Volts
CT/Source VT Phasing x Deg
Source VT Multiplier
xx.x X
Source VT Correction
x.x Volts
Norm. VT. Multiplier
x.xx
Power Display Option SINGLE_PHASE
Fast Volt Recovery disable
Fast Volt R Setting
x.x V
Auto/Man Switch Type set to SCAMP
in Nameplate
Programmable Alarm
Prog Alarm Function –<0000000000000000
Prog Alarm Function NORMAL/AS DEADMAN OUT
Op Count Signal Alrm
x
Clear Sealin Alarm Ready Press ENTER
Clr Low Current Blk Ready Press ENTER
Clr RTN Fail To Opr Ready Press ENTER
System Clock
Set Date and Time xx/xx/xx xx:xx:xx
Daylight Savings disable
Input Selection
Input Selection 1 SWITCH STATUS
Input Selection 2 NONSEQ INPUT
Input Selection 3 VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Change
xxx
Average RMS % Change
xxx
Duration % Change
xxx
Init. Motor Current Press ENT to reset
Regulator Type TYPE A
Output Selection CONTINUOUS
Output Pulse
x.x Sec
Low Current Block disable
Paralleling
Tap Limits ENABLED
Not settable unless an external source of Tap
Position is selected
Tap Position/Cal DISABLE
Tap Information disable
Tap Block Raise xx
Tap Block Lower –xx
Highest Tap xx
Lowest Tap
–xx
Intertap Delay
x Sec
Seal-in Fail Block ENABLE
Op Counter Config
1 X / 2 X/
COUNT WINDOW/
CAM FOLLOWER
Cam Follower disable
X Mode Delay xx ms
Op Counter Preset xxxxxx
Ntrl Counter Preset xxxxxx
Lower Counter Preset xxxxxx
Tapchanger Type LTC
Regulator Vendor Default
Counter Time Window x.x Sec
Raise Counter Preset xxxxxx
Maximum Tap Wear
xxxxx
IndTapWear Alrm Set
100 %
Cooper Quick Drive disable
Op Ctr = Count Window
Op Ctr = 1X/2X
Paralleling Type DISABLE
Paralleling Type DELTA VAR #1
Paralleling Type CIRCULATING I
Paralleling Type DISABLE
Paralleling Type DELTA VAR #2 or DELTA VAR #2 (KT)
DVAR2 Sensitivity
x.x
DVAR2 Reac I Lmt
xxx mA
DVAR2 I Ratio
x.xx
Paralleling Type MASTER/FOLLOWER
MASTER/FOLLOWER NONE
Paralleling Address
xx
Num. Devices
x
T.P.R. Timeout
xxxxx
Breaker Option
xxxxxx
Tap Difference
x
Clear Lockout Alarm Ready Press ENTER
Paralleling Type PEER2PEER DELTAVAR
P2P DVar Sensitivity
x.x
DVAR2 Reac I Lmt
xxx mA
Topology Single Bus
Paralleling Address
xx
Num. Devices
x
P2P Update Speed
xxxxx
Clear Lockout Alarm Ready Press ENTER
Load Side Brk Config Not Used
Right Tie Brk Config Not Used
Left Tie Brk Config Not Used
MVA Rating
x.x
I Multi Correction
xxx %
Tap Limits disable/ENABLE
Tap Info ENABLED
To Data Logging
Auto/Man Switch Type set to SCAMP
in Nameplate
Programmable Alarm
Prog Alarm Function –<0000000000000000
Prog Alarm Function NORMAL/AS DEADMAN OUT
Op Count Signal Alrm x
Clear Sealin Alarm Ready Press ENTER
Clr Low Current Blk Ready Press ENTER
Clr RTN Fail To Opr Ready Press ENTER
System Clock
Set Date and Time xx/xx/xx xx:xx:xx
Daylight Savings disable
Input Selection
Input Selection 1 SWITCH STATUS
Input Selection 2 NONSEQ INPUT
Input Selection 3 VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Change
xxx
Average RMS % Change
xxx
Duration % Change
xxx
Init. Motor Current Press ENT to reset
CBEMA Setup
Harmonics Setup
Data Logging
Data Log Select
111111111111111
Data Log Interval
x mins
Press ENT to clear Data Log Records
Paralleling
Paralleling Type DISABLE
Paralleling Type DELTA VAR #1
Paralleling Type CIRCULATING I
Paralleling Type DISABLE
Paralleling Type DELTA VAR #2 or DELTA VAR #2 (KT)
DVAR2 Sensitivity
x.x
DVAR2 Reac I Lmt
xxx mA
DVAR2 I Ratio
x.xx
Paralleling Type MASTER/FOLLOWER
MASTER/FOLLOWER NONE
Paralleling Address xx
Num. Devices
x
T.P.R. Timeout xxxxx
Breaker Option
xxxxxx
Tap Difference x
Clear Lockout Alarm Ready Press ENTER
Paralleling Type PEER2PEER DELTAVAR
P2P DVar Sensitivity x.x
DVAR2 Reac I Lmt xxx mA
Topology Single Bus
Paralleling Address
xx
Num. Devices x
P2P Update Speed
xxxxx
Clear Lockout Alarm Ready Press ENTER
Load Side Brk Config Not Used
Right Tie Brk Config Not Used
Left Tie Brk Config Not Used
MVA Rating x.x
I Multi Correction xxx %
Min I Thresh. ENABLED
Use TapTalk For CBEMA in SOE or OSC
Event 1 ENABLE
Event1 Sag Pickup
xx %
Event1 Sag Dropout
xx %
Event1 Sag Min Dur
1 cycles (xx ms)
Repeats for
Events 2 thru 4
Clear All Counters Ready Press ENTER
V 2-16 Har. Alarm
011101111111111
V 17-31 Har. Alarm
000000000000001
V Alarm Threshold
x.x %
I 2-16 Har. Alarm
011101011111111
I 17-31 Har. Alarm
000000000000001
I Alarm Threshold
xx %
Min I Thresh. Enable ENABLE
Min Fund I Threshold
xx mA
Harmonic Alarm Delay
xx s
Normal Voltage
xxx.x Volts
Input Selection
Input Selection 1 SWITCH STATUS
Input Selection 2 NONSEQ INPUT
Input Selection 3 VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Change xxx
Average RMS % Change
xxx
Duration % Change xxx
Init. Motor Current Press ENT to reset
CBEMA Setup Harmonics Setup
Data Logging
Data Log Select
111111111111111
Data Log Interval
x mins
Press ENT to clear Data Log Records
Min I Thresh. ENABLED
Use TapTalk For CBEMA in SOE or OSC
Event 1 ENABLE
Event1 Sag Pickup xx %
Event1 Sag Dropout xx %
Event1 Sag Min Dur 1 cycles (xx ms)
Repeats for
Events 2 thru 4
Clear All Counters Ready Press ENTER
V 2-16 Har. Alarm 011101111111111
V 17-31 Har. Alarm 000000000000001
V Alarm Threshold
x.x %
I 2-16 Har. Alarm 011101011111111
I 17-31 Har. Alarm 000000000000001
I Alarm Threshold xx %
Min I Thresh. Enable ENABLE
Min Fund I Threshold xx mA
Harmonic Alarm Delay
xx s
Normal Voltage
xxx.x Volts
To
Nameplate
Sheet 3 of 4
800-M-2001D-QSG-08 (03-17)
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.
COMMUNICATION
CNFG UTIL
MONITOR
UTIL SETP
SETPOINTS
MNTR CNFG
UTILITIES
COMM MNTR
Page 4
If Memory Card is present, the first menu
displayed under Communication is the
Memo
ry Card menu, otherwise the
Memory Card menu is not displayed.
If IEC 61850 is purchased
COMMUNICATION
CNFG UTIL
Memory Card
Load Setpoints Press ENT to begin
Save Setpoints Press ENT to begin
Save Datalog Press ENT to begin
Save seq. of events Press ENT to begin
Save oscillograph Press ENT to begin
Clone save Press ENT to begin
Clone load Press ENT to begin
Load DNP Config Press ENT to begin
Save DNP Config Press ENT to begin
Save Metering Data Press ENT to begin
Firmware Update Press ENT to begin
Load IEC config Press ENT to begin
Save IEC Config Press ENT to begin
SD Quick Capture Press ENT to begin
Comm Settings
Comm1 Port Type RS485
Comm2 Port Type RS232
Comm Protocol DNP3.0
DNP Configuration M2001D DNP DEFAULT
CID File ID M2001D DEFAULT
Src Addr Validation disable
Substation Address DNP x
Feeder Address DNP x
Comm Address DNP x Mdbus x
Baud Rate 9600
Parity NONE
Stop Bits ONE STOPBIT
Sync Time x mS
Output Pulse
x.x Sec
Comm Access Security disable
Comm Access timeout
xx sec
TX Delay
xx ms
Heartbeat Option Disabled
Protocol MODBUS
Baud Rate 115200
Parity NONE
Stop Bits TWO STOPBITS
Sync Time xx mS
RS232
Bluetooth Enable ENABLE
Bluetooth Reset Ready Press ENTER
Bluetooth Protocol MODBUS
Authentication disable
Friendly Name M2001D-1
Bluetooth Pass Reset Ready Press ENTER
Control BT Device XX:XX:XX:XX:XX:XX
Bluetooth Mode MODE0
Bluetooth
Set LCD Contrast: E ************
User Line 1 E
Beckwith Electric
User Line 2 E
M-2001D
Level 1 Access Code Press ENT to change
Level 2 Access Code Press ENT to change
Clear Osc Records Ready Press ENTER
Oscillograph Message ENABLE
HMI
DHCP Enable ENABLE
IP Address
0.0.0.0
Net Mask
0.0.0.0
Gateway
0.0.0.0
Enter Modbus Port 502
Enter DNP Port 20000
Auto Negotiation ENABLE
Keepalive time
7200 sec
Ethernet
Radius Server 1 IP x. x. x. x
Radius Server 2 IP x. x. x. x
Radius 1 Auth. Port 1812
Radius 2 Auth. Port
1814
Radius Secret Code Press ENT to change
IEEE 1686 Standard not used/ Authen with Encryp*
Radius 1 Acc. Port 1813
Radius 2 Acc. Port 1815
Radius En./Dis. disable
IPSEC En./Dis. disable
Load User config Press ENT to begin
Load IPsec config Press ENT to begin
SNTP Enable disable
SNTP Server Address
0.0.0.0
Time Zone GMT
–5 Hr
UTILITIES
COMM MNTR
Bias Voltage Status/Test Mode
Load Voltage XXX.X Volts
Voltage Offset
X
Volt Cal Coefficient
32767 X
Volt RMS Coefficient 32762 X
Control Load I x.x mA Lag/Lead
Curr Cal Coefficient 32767 X
Power Factor
x.xxx Lag/Lead
I Sin Coefficient
0 X
I Cos Coefficient
8192 X
Motor Current x.xx mA
Mtr Cal. Coefficient 8192 X
Mtr Sin Coefficient 0 X
Mtr Cos Coefficient 8192 X
Calibration/Test
Mtr RMS Coefficient 8192 X
Circ Cal. Coefficien 32767 X
Circ Sin Coefficient
0 X
Circ Cos Coefficient 8192 X
LED Scroll Test Press ENT to begin
Input Test Press ENT to Begin
Output Test Press ENT to test
Button Input Test Press ENT to Begin
Change Src Input press ENTER.
Watchdog resets: x Total resets: xx
Clear reset counters Press ENT to begin
X1 Duration 0 ms, Avg: 0 ms
Alarm Activity Press ENT to Begin
About
Serial Number xxxxx
Firmware Version D-0214VXX.XX.XX
EE Checksum
XxXXXx
Last Loaded File CRC
x.x
Hardware Number x
Comm Options En/Dis 11101111111111
Sheet 4 of 4
800-M-2001D-QSG-08 (03-17)
CONFIGURATION
SETP COMM
SETPOINTS
MNTR CNFG
MONITOR
UTIL SETP
© 2011 Beckwith Electric Co. All Rights Reserved
Technical Support
www.beckwithelectric.com / 727 544-2326
Email Support: [email protected]
*NOTE: Once IEEE 1686 Standard cyber security is enabled, the user must enter a valid User Name and Password to access any menus other than the "Utilities/About" menu. This selection cannot be changed to "not used" without entering a valid User Name and Password.
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.
Loading...