Beckett RWF40 Instructions

Page 1
865
7
RWF40... complete with housing
Compact
RWF40...
Universal Controllers
The RWF40... is a universal digital boiler temperature / pressure controller with functions designed specifically for the control of heat generating plant.
The RWF40... and this Data Sheet are intended for use by OEMs which integrate the controller in their products!
Mechanical design
The controller is supplied complete with housing for flush panel mounting. The RWF40... is matched to the controlled variable and the required setpoint range by mak­ing parameter settings. The control parameters can be set and optimized while the burner is running. All settings are made with 4 buttons located on the unit front and are directly displayed.
LEDs on the front indicate the following operating states:
- Control ON / OFF
- Positioning pulses ON or OFF for driving the burner´s air damper when using
modulating burner control, or stage I / stage II when using 2-stage burner control
- «2-stage» operating mode
- Position of the configurable contact «K6»
- Manual control ON / OFF
During operation, the digital display above the LEDs shows the setpoint (green), the actual value (red) and – when making parameter settings – the relevant parameters.
CC1N7865en
01.09.2005
Building Technologies
HVAC Products
Page 2
Warning notes
Mounting notes
Installation notes
To avoid injury to persons, damage to property or the environment, the following warning notes should be observed!
Do not open, interfere with or modify the controller!
All activities (mounting, installation and service work, etc.) must be performed by qualified staff
When selecting the cables, when making the installation and the electrical connec- tions, observe the regulations of VDE 0100 «Erection of power installations with rated voltages below AC 1000 V» and the relevant national regulations
Provide double-pole isolation of the controller from the mains supply if there is a risk of touching live parts while work is carried out
Check to ensure that wiring is in an orderly state
Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage
Ensure that the relevant national safety regulations are complied with
Please observe the notes given in the user documentation B7865
Commissioning notes
Standards and certificates
Service notes
Prior to commissioning the plant, check to ensure that wiring is in an orderly state
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Electromagnetic compatibility EMC NAMUR recommentation
89 / 336 EEC NE21, EN 50 081 part 1 and EN 50 082 part 2
ISO 9001: 2000 Cert. 00739
ISO 14001: 1996 Cert. 38233
For service purposes, the controller can be removed from its housing with no need for tools
The electrical connections ar e made via the screw terminals located at the rear of the housing
Each time a unit has been replaced, check to ensure that wiring is in an orderly state and that the wires are firmly connected
Disposal notes
The unit contains electrical and electronic components and must not be disposed of together with household waste.
2/10 Building Technologies CC1N7865en
HVAC Products 01.09.2005
Local and currently valid legislation must be observed.
Page 3
Type summary
A
ccessories
Controller with RWF40.000A97
- 3-position output
- housing
- fixing material and seal
Controller with RWF40.001A97
- 3-position output
- analog output
- housing
- fixing material and seal
Controller with RWF40.002B97
- 3-position output
- analog output
- RS-485 port
- housing
- fixing material and seal
Packaging variants (20 pieces, without documentation) RWF40.010A97 RWF40.011A97
Adapter frame for replacing the RWF32... ARG40
Bracket ARG41
For mounting the RWF40... on 35 mm DIN rails to DIN 46277
Dummy cover AVA10.200/109 For covering a panel cutout for the RWF40...
Demo case KF8892
For demonstrating the functions of the RWF40... controller
3/10
Building Technologies CC1N7865en HVAC Products 01.09.2005
Page 4
Technical data
General controller data
Environmental conditions
Mains voltage AC 110...240 V +10 % / -10 % Mains frequency 48...63 Hz Safety class II to DIN 0631 Mounting position optional Terminals for 2 x 1.5 mm² or 1 x 2.5 mm² Power consumption max. 10 VA Safety extra low-voltage DC 24 V Contact rating of the control outputs
(relays «K1...K3»)
- Up to 2 x 10
- Up to 10
5
switching cycles
7
switching cycles
2 A / AC 24...240 V
0.1 A / AC 24...240 V Weight complete with housing approx. 760 g Recommended actuator running time 15...60 s Degree of protection of housing
- Front
- Base
IP 65, EN 60529 IP 20, EN 60529
Storage
DIN EN 60 721-3-1 Temperature range -20...+60 °C Humidity < 75 % r.h.
Transport
Temperature range -40...+70 °C Humidity < 75 % r.h.
Operation
Temperature range -20...+50 °C Humidity < 75 % r.h.
Condensation, formation of ice and ingress of water are not permitted!
4/10 Building Technologies CC1N7865en
HVAC Products 01.09.2005
Page 5
Function
Block structure
The RWF40... provides the following functions:
- One digital PID controller with a 3-position or analog output (optional)
- To control 2-stage burners, the RWF40... can be switched over to provide 2-
position control
- Automatic thermostat (or pressurestat) function in low-fire operation
- One shift controller for weather-dependent setpoint shifting
- One minimum limiter and on e maximum limiter for the boiler temperat ure or the
boiler pressure
- One limit thermostat to DIN 3440 (output 1)
- One potential-free configurable contact
- Manual operating mode
- Communication via serial port (option)
- Self-setting function
3 analog inputs
Input 1:
Actual value
for Pt100, Ni100, Pt1000, LG-Ni1000, thermocouples or standard signals
Input 2:
External setpoint, setpoint shifting
for 0...1 k resistor or linearized standard signals
Input 3:
Outside temperature
for Pt1000, LG-Ni1000
Release of burner
Output 1:
- Relay (N.O. contact)
Floating ou tput
Output 2:
-Relay (actuating device open) Output 3:
- Relay (actuating device closed)
Limit comparator
Output 4:
- Relay (N.O. contact)
2 binary inputs
For potential-free contacts
Input 1:
Operating mode changeover
Input 2:
Setpoint shifting / changeover
Power supply
AC 110 ...240 V +10%/-10%,
48...63 Hz, max. 10 VA
7865f01e/0905
RWF40...
Power supply measuring transducer
DC 24 V, 30 mA (short-circu it proof)
Analog output (optional)
Output 5: Analog output DC 0...10 V, DC 0...20 mA, DC 4...20 mA
Serial port (optional)
RS-485 MOD bus protocol
5/10
Building Technologies CC1N7865en HVAC Products 01.09.2005
Page 6
Function of the controller when used for burner control
Low-fire operation
In low-fire operation, the RWF40... operates like a control thermostat or pressurestat. This means that it operates as a 2-position controller maintaining the required setpoint by switching the burner on and off. The switching differential for 2-position operation can be adjusted within a wide range. If the demand for heat increases, the controller switches to high-fire operation only when an adjustable limit is exceeded. This function is aimed at optimizing the burner´s switching ratio.
High-fire operation, 2-stage control
In that case, the RWF40... operates as a 2-position controller with adjustable switching thresholds. Using the relays of the 3-position output, the RWF40... drives the actuator to the 1 switches between the minimum signal for the 1 for the 2
st
and 2nd output stage. In this operating mode, the optional analog output
nd
stage.
High-fire operation, modulating control
In that case, the RWF40... operates as a PID / PI controller with a 3-position output without position feedback signals or, optionally, with a modulating output. By making use of its self-setting facility, the RWF40... is able to determine the PID / PI control parameters, or the parameters can be set manually.
Binary input 1 (change­over of operating mode)
Using a potential-free contact, the RWF40... can be switched from the modulating mode to 2-stage operation.
Binary input 2 (setpoint shifting or setpoint changeover)
In the case «setpoint shifting» is configured, the current setpoint is shifted by an adjust­able amount. Configuration of «setpoint changeover» provides changeover between 2 setpoints adjusted on the RWF40... If analog input 2 is configured for an «external set­point», changeover is provided between the setpoint adjusted on the RWF40... and an external setpoint.
Limit comparator
Potential-free contact «K6» can be assigned a number of functions. Example:
Limit value supervision
Operation
4 buttons on the unit front are used to operate and program the RWF40... During op­eration and programming, the 7-segment displays show the parameter values and pa­rameter names.
Weather-dependent setpoint shifting
The controller´s standard configuration ex works is such that when connecting a QAC22… outside sensor, automatic changeover to weather-dependent setpoint shifting takes place.
The signal delivered by the QAC2... outside sensor must not be fed parallel to sev­eral RWF40...!
st
stage and the maximum output signal
6/10 Building Technologies CC1N7865en
HVAC Products 01.09.2005
Page 7
Function of the controller when used for burner control (cont´d)
A
A
nalog input 1 (actual
value sensor)
To acquire the actual value, a number of sensors can be connected to the RWF40...
Measurement range 2-or 3-wire resistance
sensors
Thermocouples NiCr-Ni / type «K» -200...+1372 °C (-328...+2502 °F) Cu-Cu-Ni / type «T» -200...+400 °C (-328...+752 °F) NiCroSil-NiSil / type «N» -100...+1300 °C (-148...+2372 °F) FeCuNi / type «J» -200...+1000 °C (-328...+1832 °F) Pt-RhPt / type «S» 0...1768 °C (-32...3214 °F) ¹) Pt-RhPt / type «R» 0...1768 °C (-32...3214 °F) ¹) Pt-RhPt / type «B» 0...1820 °C (32...3308 °F) ¹)
Linearized standard signals
Pt100 / IEC 751 -200...+850 °C (-328...+1562 °F) Pt1000 / IEC 751 -200...+850 °C (-328...+1562 °F) Ni100 / DIN 43760 -60...+230 °C (-76...+482 °F) Ni1000 / DIN 43760 -60...+230 °C (-76...+482 °F) LG-Ni1000 -50...+160 °C (-58...+320 °F)
0...20 mA scalable -1999...+9999
4...20 mA scalable -1999...+9999 DC 0...10 V scalable -1999...+9999 DC 0...1 V scalable -1999...+9999
¹) Only RWF40.0X2B97
The power provided for the measuring transducers is DC 24 V / 30 mA.
nalog input 2 (external setpoint shift or external setpoint)
Feeding a signal to analog input 2, the controller´s setpoint can be influenced. The influence can be scaled.
The following signals can be used:
- Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA
- 1 k potentiometer in a 2-wire circuit
7/10
Building Technologies CC1N7865en HVAC Products 01.09.2005
Page 8
Connection diagram (basic diagram)
Temperature and pressure control on a dual-fuel burner. Burner control and supervision are provided by burner control type LAL... or LFL...
Note
DC 24 V at terminals «G+» and «G-» is used for powering the QBE... pressure sensor!
LN
G1+ M1B9
RWF40...
M9
XB6 M6
Q13
Q14
Y1
Y2D1Q
GND
D2
Legend
LAL..., LFL...
19
45
ST
B
MB M
QAE...
QAC...
MR
BSG...
0
I
L N
GAS
18
BS
2
1
0
BV1
LK
N
RV
BV1
BV2
v
7865a01/1004
a
OIL
9
20
1110
z
M
~
m
MIN.
int. ext.
S1
SQ...
RWF40...
SQ...
GND
D2
int. ext.
S1
G+ M1 XU 6 M6
LN
U1-
G-
Q13
Q14
Y1
Y2D1Q
LAL..., LFL...
19
45
ST
B
G
M
18
BS
2
1
0
9
20
1110
QBE...
0...10 V
BSG...
0
I
L N
GAS
BV1
LK
N
RV
BV1
v
BV2
a
OIL
7865a02/0905
z
M
~
m
MIN.
a Limit switch for air damper position OPEN QAE... Immersion temperature sensor BS Operation selector QBE... Pressure sensor 1 = firing on gas RV Gas control damper (modulating burner control) S1 Internal / external setpoint switch (E) 2 = firing on oil SQ... Actuator of burner´s air damper and gas (2-stage burner control) control damper BV... Fuel valve ST Connections for burner control´s start BSG... Remote setpoint adjuster (active when control loop «S1» is closed) v Auxiliary switch for the release of the L... Burner control 2nd fuel valve depending on the air damper LK Burner´s air damper position m (MIN) Auxiliary switch for controlling low-fire z End switch for the fully CLOSED operation positi on of the air damper QAC... Outside sensor for weather-dependent setpoint shifting
8/10 Building Technologies CC1N7865en
HVAC Products 01.09.2005
Page 9
Dimensions
A
Dimensions in mm
48
RG40 adapter frame
RWF40
PGM EXIT
43,5
K6
96
15,5
91,5
127,5
112
Panel cutout to DIN 43 700
+0,6
45
+0,8 92
7865m01e/0300
7865m02/0799
Building Technologies CC1N7865en HVAC Products 01.09.2005
9/10
Page 10
Dimensions (cont´d)
A
RG41
94
8
3
35,5
Dimensions in mm
61,4
45
13
60
153
68
83
45
7,5
12,5
7865m04/1004
© 2005 Siemens Building Technologies Production GmbH
10/10 Building Technologies CC1N7865en
HVAC Products 01.09.2005
Subject to change!
Loading...