BeaconMedaes TotalAlert 2 Installation, Operation And Maintenance Instructions

Page 1
Installation, Operation, and Maintenance Instructions
6-847718-00 Rev. B00
Page 2
Page 3
1
6-847718-00 Rev. B00
Introduction
Product Identification......................................................................................................4
Alarm Modular Components...........................................................................................5
Annunciator Module .................................................................................................5
LED Module..............................................................................................................5
Breakout Board ........................................................................................................5
Relay Board..............................................................................................................6
Digital Display Module..............................................................................................6
Multi-Signal Module..................................................................................................6
Blank Module............................................................................................................6
Definition of Statements .................................................................................................7
Definitions.......................................................................................................................7
Alarm Configurations....................................................................................................10
Master Alarms.........................................................................................................11
Area Alarms............................................................................................................12
Combo Alarms........................................................................................................14
Electromagnetic Compatibility ......................................................................................16
FCC ........................................................................................................................16
ICES-003................................................................................................................16
EN 60601-1-2 .........................................................................................................16
Installation Overview
Master Alarms ........................................................................................................21
Area Alarms............................................................................................................21
Combo Alarms........................................................................................................22
Installation Procedures
Rough-In.......................................................................................................................23
Alarm Panel Back Box ...........................................................................................23
Remote Sensor Back Box ......................................................................................24
Pipeline Connection ...............................................................................................25
Pull Wire .......................................................................................................................27
General Requirements ...........................................................................................27
Wire Type And Size ................................................................................................27
Wire Routing...........................................................................................................28
Determining Number Of Conductors......................................................................29
Wiring ...........................................................................................................................30
Power Supply .........................................................................................................30
Remote Sensor ......................................................................................................31
Breakout Board Inputs............................................................................................32
Relay Board Outputs..............................................................................................33
Multi-Signal Module Inputs.....................................................................................34
Digital Display Module Master/Slave......................................................................35
Multi-Signal Module Relays....................................................................................35
General Fault / Aux Relays ....................................................................................36
Digital Display Module High / LowRelays ..............................................................36
Ethernet..................................................................................................................37
Building Automation System ..................................................................................37
Contents
Page 4
2
6-847718-00 Rev. B00
Contents
Field Wiring Cable Shield Grounding .....................................................................39
Finish............................................................................................................................40
Front Panel Mounting.............................................................................................40
Local Sensor ..........................................................................................................41
Remote Sensor ......................................................................................................42
Labeling..................................................................................................................43
Wiring Schematics
Wiring Schematic 1: Power Supply.............................................................................46
Wiring Schematic 2: Sensor Module to Digital Display Module..................................47
Wiring Schematic 3: Multiplexer / Breakout Boards....................................................48
Wiring Schematic 4: Relay Board ...............................................................................49
Wiring Schematic 5: Multi-Signal Module Inputs.........................................................50
Wiring Schematic 6: Digital Display Module Master/Slave .........................................51
Wiring Schematic 7: Multi-Signal Module Relay Outputs ...........................................52
Wiring Schematic 9: Digital Display Module High / Low Relays ..................................53
Wiring Schematic 8: General Fault / Auxiliary Relays ................................................53
Wiring Schematic 10: Remote Pressure / Vacuum Switches .....................................54
Wiring Schematic 11: Johnson Controls Metasys® N2 Connection ...........................55
Operation
Start-Up and Checking .................................................................................................56
Master Alarm Panel................................................................................................56
Area Alarm Panel ...................................................................................................57
Combo Alarm Panel ...............................................................................................58
Set-Up Procedures.......................................................................................................59
Annunciator Module ...............................................................................................59
Multiplexer Module .................................................................................................62
Digital Display Module............................................................................................64
Digital Display Module-Advanced...........................................................................66
Multi-Signal Module................................................................................................69
Multi-Signal Module-Advanced...............................................................................70
Set-Up Network Interface.............................................................................................72
Set-Up Using Web Pages ............................................................................................76
Accessing the Web Page .......................................................................................76
Login in to Setup Pages .........................................................................................77
Enroll Devices ........................................................................................................78
Setup Alarm Messages ..........................................................................................80
Setup Area Alarms .................................................................................................84
Setup Device ..........................................................................................................86
Electronic Notification.............................................................................................88
Electronic Notification - Server Setup ....................................................................89
Set Clock ................................................................................................................90
Administer Users ....................................................................................................91
Setup Network........................................................................................................92
Clear Network.........................................................................................................94
Clear Event Log .....................................................................................................96
Transfer Setup........................................................................................................98
Monitoring Mode.........................................................................................................100
Page 5
3
6-847718-00 Rev. B00
Annunciator Module .............................................................................................100
Multiplexer / LED Module .....................................................................................101
Digital Display Module..........................................................................................101
Multi-Signal Module..............................................................................................102
Browsing Alarm Web Pages.......................................................................................103
Accessing the Web Page .....................................................................................103
Current Alarms .....................................................................................................104
Signals..................................................................................................................105
Network Devices ..................................................................................................106
View Device..........................................................................................................107
Device Information ...............................................................................................108
Event Log .............................................................................................................109
Diagnostics ...........................................................................................................110
Download Configuration .......................................................................................111
Network Statistics .................................................................................................112
Testing
Alarm System .............................................................................................................114
Annunciator Module....................................................................................................114
Multiplexer Module .....................................................................................................116
Digital Display Module ................................................................................................117
Multi-Signal Module ....................................................................................................118
Power Supply .............................................................................................................119
Troubleshooting
Troubleshooting Guide ...............................................................................................120
Replacement Parts
Front Panel Components - Area Alarm ......................................................................129
Front Panel Components - Master Alarm...................................................................130
Front Panel Components - Combo Alarm ..................................................................131
Back Box Components - Area Alarm..........................................................................132
Back Box Components - Master / Combo Alarm .......................................................133
Breakout and Relay Board Components - Master / Combo Alarm ............................134
Sensor Components...................................................................................................135
Labeling......................................................................................................................136
Field Installation Kits ..................................................................................................136
Notes ...............................................................................................................................137
Master Alarm Signal Input Data ....................................................................................138
Warranty..........................................................................................................................140
Contents
Page 6
4
6-847718-00 Rev. B00
Product Identification
Introduction
Each alarm is identified by a model num­ber, lot code and serial number.
Installation procedures vary depending on the alarm configuration.
The model number/lot code label is located on the inside of the alarm back box (Figure 1).
The serial number is located on the annun­ciator module board (Figure 2).
Figure 2: Product Serial Number
Serial number label
Model number/lot code label
Figure 1: Product Identification Labels
Page 7
5
6-847718-00 Rev. B00
Features:
• User interface pushbuttons for alarm panel TEST function, audible alarm MUTE
and set-up increase ! and decrease ".
• Green alarm panel POWER ON indicator.
• Red flashing alarm system fault indicator.
• Red audible alarm mute indicator.
• Audible alarm
• General fault relay that activates on any alarm panel fault condition.
• Auxiliary relay that activates when the audible alarm is sounding.
• Alphanumeric two line by 20 character display (Master/Combo Alarms only).
• Embedded web server with web pages to view and set up alarm.
• 10Base-T Ethernet Jack.
• Ethernet LINK, TX and RX indicators.
• Heartbeat indicator.
• Event log.
(Master/Combo Alarms only)
Features:
• Monitors up to 64 normally closed dry-contact switch signals.
• Five gas service indicators for normal (green) or abnormal (red) conditions.
• Signal inputs can be programmed to any of the gas service indicators.
• Adjustable brightness of LED indicators.
• Heartbeat indicator.
(Master/Combo Alarms only)
Features:
• Adds an additional five gas service indicators to a Multiplexer Module.
(Master/Combo Alarms only)
Features:
• Screw terminals for 32 dry-contact switch signals.
• Terminals accept 14 to 22 AWG wires.
• Connector for optional relay board.
Introduction
Breakout Board
LED Module
Multiplexer Module
Annunciator Module
Alarm Modular Components
Page 8
6
6-847718-00 Rev. B00
Introduction
(Area/Combo Alarms only)
Features:
• Digital LED readout of system pressure signal transmitted from sensor module.
• Adjustable brightness of digital LED readout.
• Individual LED’s indicate when system pressure/vacuum is HIGH (red), LOW (red), or NORMAL (green).
• Programmable high and low alarm thresholds.
• Adjustable audible alarm mute duration.
• Individual high and low alarm dry-contact relay outputs.
• Can transmit pressure or vacuum signal to another digital display module for remote applications.
(Area Alarms only)
Features:
• Monitors up to five normally closed dry­contact switch signals.
• Separate indicators for each of five signals for normal (green) or abnormal (red) conditions.
• Available (optional) with separate dry­contact relay outputs for each of five signals.
• Adjustable brightness of LED indicators.
Features:
• Reserves a space in alarm panel for future expansion.
• Used to fill unused alarm panel module locations.
Alarm Modular Components (Cont.)
Blank Module
Multi-Signal Module
Digital Display Module
(Master/Combo Alarms only)
Features:
• Screw terminals for 32 dry-contact relay outputs. Dry contacts are normally-closed when alarm panel is powered.
• Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC
.
• Terminals accept 14 to 22 AWG wires.
Relay Board
Page 9
7
6-847718-00 Rev. B00
Address Resolution Protocol (ARP)
Protocol used by a device to learn the MAC address of another device so it can send it an Ethernet packet.
Area Alarm Panel
Alarm panel that monitors medical gas and vacuum systems serving a specific area.
Auxiliary Fault Relay
Single-pole double-throw dry-contact relay output located on annunciator module. Used to activate a remote alarm or building management system. The relay will activate whenever ANY audible alarm on panel is in
progress. Pressing MUTE button on annunciator module deactivates relay until audible alarm is again reactivated.
Combo Alarm Panel
Alarm panel that combines features of a master alarm panel and an area alarm panel.
Crossover Cable
Network cable that swaps transmit and receive pairs so cable can be used to connect two computers or devices without the use of a hub or switch.
Domain Name Server (DNS)
A device that has a list of device names matched to IP addresses. Browsers use this resource to locate the IP address of a named device. NetBIOS name service provides this function on a local network.
Dry-Contact
Electrical contact isolated or unconnected from any electrical source.
Dynamic Host Configuration Protocol (DHCP)
A protocol used by a server to assign IP addresses to devices and computers.
Definitions
Definition of Statements
Statements in this manual preceded by following words are of special significance.
WARNING: Means there is a possibility
of injury or death to yourself or others.
CAUTION: Means there is a possibility
of damage to unit or other property.
SHOCK HAZARD: Means there is a
possibility of electric shock.
NOTE:
Indicates points of particular interest
for more efficient and convenient operation.
ATTENTION: Means precautions for
handling electrostatic sensitive devices are to be observed.
Introduction
Page 10
8
6-847718-00 Rev. B00
Introduction
Electromagnetic Compatibility (EMC)
Verification that a product meets required standards for emmisions of and immunity from electromagnetic energy in its intended environment.
Ethernet
A standard high-speed network medium specified by IEEE standard 802.3.
Ethernet Hub
A device that connects many Ethernet devices together. All devices on the hub receive messages sent from all of the other connected devices.
Ethernet Switch
A device that connects many Ethernet devices together with optimization. Message destinations are examined and passed only to the correct device.
Firewall
A computer or computer software that prevents unauthorized access to private data from outside computer users.
Gateway
A computer or device that connects two computer networks together (such as a private network and the Internet).
General Fault Relay
Single-pole double-throw dry-contact relay output located on annunciator module. Used to activate remote alarm or building management system. Relay will activate whenever ANY audible alarm on panel is in progress. Unlike
Auxiliary Fault Relay, pressing MUTE button on annunciator module WILL NOT deactivate relay. General Fault Relay will deactivate only after alarm condition is corrected and alarm panel resumes normal status.
HyperText Transfer Protocol (HTTP)
Protocol used to manage the request and transfer of web pages to a computer.
Internet Protocol (IP) Address
Unique number that identifies a device on a network.
LED
Light Emitting Diode
Local Sensors
Pressure / vacuum sensors mounted inside alarm panel back box. Sensor rough-in must be piped to medical gas / vacuum pipelines.
Media Access Control (MAC) Address
A unique hardware address of a device on an Ethernet.
Master Alarm Panel
Monitors medical gas and vacuum source equipment and main pipelines.
NetBIOS Name Service
Local method of addressing a device by name. This allows a web browser to reference a device by name, such as TA2_12345, instead of an IP address, such as 192.168.2.3.
Remote Sensors
Pressure / vacuum sensors mounted outside of alarm panel back box. Sensor rough-ins may be mounted separately or ganged together near pressure / vacuum pipelines. Sensors must then be wired to alarm panel.
Simple Mail Transfer Protocol (SMTP)
Protocol for sending email on a network.
Subnet Mask
A binary number used to separate the network portion from the host portion of a network address.
SMTP Client
Computer or device that uses SMTP to send email by communicating with an SMTP server. The TotalAlert 2 acts as an SMTP client.
SMTP Server
Computer or device that uses SMTP to receive email from an SMTP client and then transfer it across the internet.
Definitions (Cont.)
Page 11
9
6-847718-00 Rev. B00
Transmission Control Protocol (TCP)
Protocol used to send data streams between two devices. TCP guarantees reliable and in order data from sender to receiver.
User Datagram Protocol (UDP)
Protocol used to send short messages between computers. UDP does not guarantee reliable transmission (packets may be lost, duplicated or out of order), but is faster and more efficient than TCP.
VFD
Vacuum Fluorescent Display
Definitions (Cont.)
Introduction
Page 12
10
6-847718-00 Rev. B00
Alarm Configurations
Introduction
All TotalAlert 2 alarm panels are factory pre­configured. Configuration of alarm panel varies dependent upon customer’s requirements.
Three types of alarm panels are available.
• Master alarms (6-TA2M series) (Page 11)
• Area alarms (6-TA2A series) (Page 12)
• Combo alarms (6-TA2C series) (Page 14)
Page 13
11
6-847718-00 Rev. B00
Model Number Scheme:
6-TA2M _ _ _
32 or 64 Designates number of signals
R or blank R = With Relays
Master alarm panels include the following modular components:
• Annunciator module with VFD
• One multiplexer module
• One LED module
• One or two breakout boards
• One or two relay boards (Optional)
Master alarm panels can monitor 32 or 64 switched inputs.
Inputs can be assigned to any one of 10 gas service indicators.
2 line by 20 character vacuum fluorescent display shows signal names.
Optional dry contact relays are available for all signals.
Master Alarms
Alarm Configurations (Cont.)
Example: P/N 6-TA2M32R
Introduction
Figure 4: Master Alarm
Figure 3: Master Alarm Panel
Page 14
12
6-847718-00 Rev. B00
Introduction
Sensor modules are mounted inside alarm panel box
Copper tubes connect to pressure/vacuum pipelines
Area alarm panels include the following modular components:
• Annunciator module
• 4 or 8 digital display, multi-signal or blank modules
• Sensors for all digital display modules (except 6-TA2AN series)
Area alarm panels may consist of any combination of digital display modules, multi­signal modules or blank modules.
If alarm panel is configured with digital display modules, pressure/vacuum sensors will be included for connection to pressure / vacuum pipeline (except 6-TA2AN series).
Sensors may be located inside alarm panel back box (local sensors) or outside alarm panel back box (remote sensors).
Local sensors must be connected to pressure / vacuum pipelines via copper tubing (Figure 5). Remote sensor may be mounted near pressure / vacuum pipeline and then wired to alarm panel (Figure 6).
Two alarm panel sizes support either 4 or 8 alarm modules.
Area Alarms
O
OXYGEN
D
OXYGEN - 100 PSI
X
NITROUS OXIDE
A
MEDICAL AIR
F
MEDICAL AIR - 100 PSI
5
AIR (ISO)
7
LABORATORY AIR
2
O2-CO2
4
O2-He
C
CARBON DIOXIDE
G
CARBON DIOXIDE - 100 PSI
1
CO2-O2
3
He-O2
H
HELIUM
V
VACUUM
6
VACUUM (ISO)
8
LABORATORY VAC
W
WAGD
N
NITROGEN
9
INSTRUMENT AIR
J
ARGON
DIGITAL DISPLAY MODULES
M
MULTI-SIGNAL MODULE
R
MULTI-SIGNAL MODULE W/ RELAYS
B
BLANK
Alarm Configurations (Cont.)
Model Number Scheme:
12345678
6-TA2A _ - _ _ _ _ _ _ _ _
L = Local Sensors R = Remote Sensors N = No Sensors
Position within alarm panel (Figures 7 and 8)
Designates type of alarm panel component from table
Figure 5: Local Sensors
Figure 6: Remote Sensors
Sensors have separate mounting boxes for mounting near pressure/vacuum pipeline and then must be wired to alarm panel
Copper tubes connect to pressure/vacuum pipelines
Page 15
13
6-847718-00 Rev. B00
NOTE:
When an alarm panel is ordered with either local or remote sensors, ALL sensors will either be local or remote. Alarm panels with combination of local and remote sensors are not available.
NOTE:
Alarm panel components in table on previous page are listed in order of criticality. Unless other­wise specified, most critical component will fill position one, next less critical component will fill position two, etc. etc.
234
1
123
45678
Area Alarms (Cont.)
Alarm Configurations (Cont.)
Introduction
Example: Model Number 6-TA2AR-OXAVWNBB
Example: Model Number 6-TA2AL-BOAV
Figure 10: Large Area Alarm
Figure 9: Small Area Alarm Panel
Figure 8: Large Area Alarm Front Panel
Figure 7: Small Area Alarm Front Panel
Page 16
14
6-847718-00 Rev. B00
123
Figure 12: Large Combo Alarm Front Panel
123 456
Model Number Scheme:
123456
6-TA2C _ _ _ - _ _ _ _ _ _
Position within alarm panel (Figures 11 and 12)
Designates type of alarm panel component from table
Alarm Configurations (Cont.)
Combo Alarms
Combo alarms include the following modular components:
• Annunciator module with VFD
• One multiplexer module
• One LED module (Large Combo Only).
• One or two breakout boards
• One or two relay boards (Optional)
• 3 or 6 digital display or blank modules
Combo alarms can monitor 32 or 64 switched inputs.
Inputs can be assigned to any one of 5 (small combo) or 10 (large combo) gas service indicators.
Optional dry contact relays are available for all signals.
Combo alarms can also monitor up to 3 (small combo) or 6 (large combo) digital display modules.
NOTE:
Sensors on combo alarms are always remotely mounted.
32 or 64 Designates number of signals
R or blank R = With Relays
O
OXYGEN
D
OXYGEN - 100 PSI
X
NITROUS OXIDE
A
MEDICAL AIR
F
MEDICAL AIR - 100 PSI
5
AIR (ISO)
7
LABORATORY AIR
2
O2-CO2
4
O2-He
C
CARBON DIOXIDE
G
CARBON DIOXIDE - 100 PSI
1
CO2-O2
3
He-O2
H
HELIUM
V
VACUUM
6
VACUUM (ISO)
8
LABORATORY VAC
W
WAGD
N
NITROGEN
9
INSTRUMENT AIR
J
ARGON
DIGITAL DISPLAY MODULES
B
BLANK
NOTE:
Multi-signal modules are not allowed in combination alarms.
Introduction
Figure 11: Small Combo Alarm Front Panel
Page 17
15
6-847718-00 Rev. B00
Example: Model Number 6-TA2C64-OXAVWN
Example: Model Number 6-TA2C32R-OAV
Combo Alarms (Cont.)
Introduction
Figure 14: Large Combo Alarm Panel
Figure 13: Small Combo Alarm Panel
Page 18
16
6-847718-00 Rev. B00
This device complies with part 15 of the FCC Rules. Operation is subject to the fol­lowing two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Medical Electrical Equipment needs spe­cial precautions regarding EMC and needs to be installed and put into service accord­ing to the EMC information provided in this manual.
Portable and mobile RF communications equipment can affect Medical Electrical Equipment.
The use of accessories, transducers, and cables other than those specified by the manufacturer, may result in increased emissions or decreased immunity of the TotalAlert 2.
The TotalAlert 2 should not be used adja­cent to, or stacked with, other equipment. If adjacent or stacked use is necessary, the TotalAlert 2 should be observed to verify normal operation in the configuration in which it will be used.
EN 60601-1-2
ICES-003
FCC
Electromagnetic Compatibility
Introduction
Page 19
17
6-847718-00 Rev. B00
Electromagnetic Compatibility (Cont.)
Introduction
EN 60601-1-2 (Cont.)
Guidance and manufacturer's declaration - electromagnetic emissions
The TotalAlert 2 is intended for use in the electromagnetic environment specified below. The customer or the user of the TotalAlert 2 should assure that it is used in such an environment.
Emissions test Compliance Electromagnetic environment - guidance
RF emissions CISPR 11
Group 1
The TotalAlert 2 uses RF energy only for its internal function. Therefore, its RF emissions are very low and are not likely to cause any interference in nearby electronic equipment.
RF emissions CISPR 11
Class A
The TotalAlert 2 is suitable for use in all establishments other than domestic and those directly connected to the public low-voltage power supply network that supplies buildings used for domestic purposes.
Harmonic emissions IEC 61000-3-2
Class A
Voltage fluctuations/ Flicker emissions IEC 61000-3-3
Complies
Guidance and manufacturer's declaration - electromagnetic immunity
The TotalAlert 2 is intended for use in the electromagnetic environment specified below. The customer or the user of the TotalAlert 2 should assure that it is used in such an environment.
Immunity test
IEC 60601
test level
Compliance level Electromagnetic environment - guidance
Electrostatic Discharge (ESD) IEC 61000-4-2
±6 kV contact ±8 kV air
±6 kV contact ±8 kV air
Floors should be wood, concrete or ceramic tile. If floors are covered with synthetic material, the relative humidity should be at least 30 %.
Electrical fast transient/burst IEC 61000-4-4
±2 kV for power supply lines ±1 kV for input/output lines
±2 kV for power supply lines ±1 kV for input/output lines
Mains power quality should be that of a typical commercial or hospital environment.
Surge IEC 61000-4-5
±1 kV differential mode ±2 kV common mode
±1 kV differential mode ±2 kV common mode
Mains power quality should be that of a typical commercial or hospital environment.
Voltage dips, short Interruptions and voltage variations on power supply input lines IEC 61000-4-11
<5 % U
T
(>95 % dip in UT)
for 0,5 cycle <40 %
U
T
(>60 % dip in UT)
for 5 cycles <70 %
U
T
(>30 % dip in UT)
for 25 cycles <5 %
U
T
(>95 % dip in UT)
for 5 sec
<5 % U
T
(>95 % dip in UT)
for 0,5 cycle <40 %
U
T
(>60 % dip in UT)
for 5 cycles <70 %
U
T
(>30 % dip in UT)
for 25 cycles <5 %
U
T
(>95 % dip in UT)
for 5 sec
Mains power quality should be that of a typical commercial or hospital environment. If the user of the TotalAlert 2 requires continued operation during power mains interruptions, it is recommended that the TotalAlert 2 be powered from an uninterruptible power supply or battery.
Power frequency (50/60 Hz) magnet­ic field IEC 61000-4-8
3 A/m 3 A/m Power frequency magnetic fields should be at levels
characteristic of a typical location in a typical commercial or hospital environment.
NOTE UTis the a.c. mains voltage prior to application of the test level.
Page 20
18
6-847718-00 Rev. B00
Introduction
Electromagnetic Compatibility (Cont.)
EN 60601-1-2 (Cont.)
Guidance and manufacturer's declaration - electromagnetic immunity
The TotalAlert 2 is intended for use in the electromagnetic environment specified below. The customer or the user of the TotalAlert 2 should assure that it is used in such an environment.
Immunity test
IEC 60601
test level
Compliance level Electromagnetic environment - guidance
Conducted RF IEC 61000-4-6
Radiated RF IEC 61000-4-3
3 Vrms 150 kHz to 80 MHz
3 V/m 80 MHz to 2,5 GHz
3 Vrms
3 V/m
Portable and mobile RF communications equipment should be used no closer to any part of the TotalAlert 2, including cables, than the recommended separation distance calculated from the equation applicable to the frequency of the transmitter.
Recommended separation distance
d = 1,2√P
d = 1,2√P
80 MHz to 800 MHz
d = 2,3√P 800 MHz to 2,5 GHz
where P is the maximum output power rating of the transmitter in watts (W) according to the transmitter manufacturer and d is the recommended separation distance in metres (m).
Field strengths from fixed RF transmitters, as determined by an
electromagnetic site survey,
a
should be less than the compliance
level in each frequency range.
b
Interference may occur in the vicinity of equipment marked with the following symbol:
NOTE 1 At 80 MHz and 800 MHz, the higher frequency range applies. NOTE 2 These guidelines may not apply in all situations. Electromagnetic propagation is affected by absorption and reflection from
structures, objects and people.
a
Field strengths from fixed transmitters, such as base stations for radio (cellular/cordless) telephones and land mobile radios, amateur radio, AM and FM radio broadcast and TV broadcast cannot be predicted theoretically with accuracy. To assess the
electromagnetic environment due to fixed RF transmitters, and electromagnetic site survey should be considered. If the measured field strength in the location in which the TotalAlert 2 is used exceeds the applicable RF compliance level above, the TotalAlert 2 should be observed to verify normal operation. If abnormal performance is observed, additional measures may be necessary, such as reorienting or relocating the TotalAlert 2.
b
Over the frequency range 150 kHz to 80 MHz, field strengths should be less than 3 V/m.
Page 21
19
6-847718-00 Rev. B00
Electromagnetic Compatibility (Cont.)
EN 60601-1-2 (Cont.)
Introduction
Recommended separation distances between
portable and mobile RF communications equipment and the TotalAlert 2
The TotalAlert 2 is intended for use in the electromagnetic environment in which radiated RF disturbances are controlled. The customer or the user of the TotalAlert 2 can help prevent electromagnetic interference by maintaining a minimum distance between portable and mobile RF communications equipment (transmitters) and the TotalAlert 2 as recommended below, according to the maximum output power of the communications equipment.
Rated maximum output
power of transmitter
W
Separation distance according to frequency of transmitter
m
150 kHz to 80 MHz
d = 1,2√P
80 MHz to 800 MHz
d = 1,2√P
800 MHz to 2,5 GHz
d = 2,3√P
0,01 0,12 0,12 0,23
0,1 0,38 0,38 0,73
1 1,2 1,2 2,3
10 3,8 3,8 7,3
100 12 12 23
For transmitters rated at a maximum output power not listed above, the recommended separation distance d in metres (m) can be estimated using the equation applicable to the frequency of the transmitter, where P is the maximum output power rating of the transmitter in watts (W) according to the transmitter manufacturer.
NOTE 1 At 80 MHz and 800 MHz, the separation distance for the higher frequency range applies.
NOTE 2 These guidelines may not apply in all situations. Electromagnetic propagation is affected by absorption and reflection from
structures, objects and people.
Page 22
20
6-847718-00 Rev. B00
Page 23
21
6-847718-00 Rev. B00
1. Install alarm panel back box (Page 23).
2. Pull wire (Page 27).
3. Power supply wiring (Page 30).
4. Breakout board input wiring (Page 32).
5. Relay board wiring (Page 33).
6. Front panel installation (Page 40).
7. Ethernet wiring (Page 37).
8. General fault/Aux Relay wiring (if required) (Page 36).
9. Building automation system wiring (if required) (Page 37).
10.Labeling (Page 43).
1. Install alarm panel back box (Page 23).
2. Install remote sensor back box (if required) (Page 24).
3. Pipeline connections (Page 25).
4. Pull wire (Page 27).
5. Power supply wiring (Page 30).
6. Front panel installation (Page 40).
7. Remote sensor wiring (if required) (Page 31).
8. Sensor installation (Local: Page 41, Remote: Page 42).
9. Ethernet wiring (Page 37).
10.Digital display module master/slave wiring (if required) (Page 35).
11. Digital display module high/low relay wiring (if required) (Page 36).
12.Multi-signal module input wiring (if required) (Page 34).
13. Multi-signal module relay output wiring (if required) (Page 35).
14.General fault/Aux Relay wiring (if required) (Page 36).
15.Labeling (Page 43).
Area Alarms
Master Alarms
Installation Overview
Page 24
22
6-847718-00 Rev. B00
Combo Alarms
Installation Overview
1. Install alarm panel back box (Page 23).
2. Install remote sensor back box (Page 24).
3. Pipeline connections (Page 25).
4. Pull wire (Page 27).
5. Power supply wiring (Page 30).
6. Breakout board input wiring (Page 32).
7. Relay board wiring (Page 33).
8. Front panel installation (Page 40).
9. Remote sensor wiring (if required) (Page 31).
10.Remote sensor installation (Page 42).
11. Ethernet wiring (Page 37).
12.Digital display module master/slave wiring (if required) (Page 35).
13.Digital display module high/low relay wiring (if required) (Page 36).
14.General fault/Aux Relay wiring (if required) (Page 36).
15.Building automation system wiring (if required). (Page 37)
16.Labeling (Page 43).
Page 25
23
6-847718-00 Rev. B00
Alarm panel back box will be one of two sizes. Height and depth of both size boxes are identical. Refer to Figure 15 for dimensions of both boxes.
If alarm panel is configured with digital display modules, sensor assemblies will be included for connection to pressure / vacuum pipeline.
Sensors may be located inside alarm panel back box (local sensors) or outside alarm panel back box (remote sensors).
If equipped with local sensors, copper tubes will extend from top of back box to be connected to pressure / vacuum pipeline.
Alarm Panel Back Box
1. Prepare rough wall opening large enough to accommodate alarm panel back box. Alarm panel back box must have rigid vertical members for support on both left and right sides. Power to alarm panel shall enter through lower left or top left conduit hole in back box.
2. Remove cardboard dust cover and insert alarm panel back box into wall opening. Secure with fasteners suitable for vertical supports (Figure 16).
3. Mounting brackets on each side of back box are adjustable and factory preset for 5/8” thick drywall. After drywall installation, front edge of back box should be flush with finished surface of wall. If needed, make any necessary bracket adjustments at this time (Figure 17).
4. Reinstall cardboard dust cover.
Figure 16: Back Box Mounting
Small box
Large box
Back Box details
simplified for clarity
Rough-In
Installation Procedures
Figure 15: Alarm Panel Back Box Dimensions
Page 26
Alarm panels ordered with remote sensors are provided with separate metal boxes for each sensor. Mount each sensor box as follows:
1. Remove sensor rough-in from mounting box (Figure 18).
2. Using four mounting holes provided, attach box to a wall or other structural support (fasteners by others).
3. Reinstall sensor rough-in.
24
6-847718-00 Rev. B00
Rough-In
Figure 18: Remote Sensor Back Box
Loosen screws to adjust back box depth (same each side)
Four holes in back of box are provided for surface mounting
Rear conduit knockouts (either side) are recommended for sensor wiring
Remote Sensor Back Box
Alarm Panel Back Box (Cont.)
Installation Procedures
Figure 17: Mounting Bracket Adjustment
Page 27
25
6-847718-00 Rev. B00
Pipeline Connection
Sensor Module
1. Braze copper extension tubes from sensor rough-in to appropriate pressure/vacuum piping system drops (Figure 19). Braze connections per procedures required by NFPA 99 or CAN/CSA-Z305.1. Use appropriate measures to prevent overheating and damage to internal components of sensor rough-in assemblies.
2. Perform standing pressure tests and cross connection tests as required by NFPA and CSA.
Installation Procedures
Rough-In
Figure 19: Sensor Pipeline Connection
Connection should be made on top of pipe
Horizontal run of pipeline
Horizontal run of pipeline
Connection should be made on top of pipe
REMOTE SENSOR
LOCAL SENSOR
Page 28
26
6-847718-00 Rev. B00
Pressure Switch
DISS (Diameter Index Safety System) connection kits are recommended for use when attaching pressure switches to pressure/vacuum pipeline. To utilize these kits, a 1/4-18 NPT female thread must be provided in piping system. All necessary components are included in each gas specific kit (Figure 20).
Rough-In
Pipeline Connection
Figure 20: Pressure Switch Pipeline Connection
DISS Kit Gas Service Model No:
6-120004-10 Oxygen 6-120004-11 Nitrous Oxide 6-120004-12 Medical Air 6-120004-13 Vacuum 6-120004-14 Nitrogen 6-120004-18 Instrument Air 6-120004-19 Evac. (WAGD) 6-120004-20 Carbon Dioxide 6-120004-21 CO2/O2 6-120004-22 O2/CO2 6-120004-23 He/O2 6-120004-24 O2/He 6-120004-25 Helium
To pipeline
To pressure switch
DISS male
body
with check
DISS nut
and nipple
Installation Procedures
Page 29
27
6-847718-00 Rev. B00
• Power all alarms from life safety branch of emergency power system as required by applicable standards.
• Protect all wiring from physical damage by raceways or conduit as required by applicable standards.
• Wire master panels directly to switches or sensors as required by applicable standards.
• Wiring runs should be made with color coded wire. Record color, signal, and source of signal for each wiring lead to aid in connection of alarm finish components.
• Avoid installing alarm panels near radio transmitters, electrical motors, or switchgear.
All low voltage wiring must meet the fol­lowing criteria:
• Copper wire no smaller than 22 AWG.
• Circuit length not to exceed 5000 feet.
• Cable must be twisted-pair shielded type. Multi-pair cables within one common shield are acceptable.
Wire Type And SizeGeneral Requirements
Pull Wire
Installation Procedures
Page 30
28
6-847718-00 Rev. B00
Holes for entrance of low voltage field wiring
Two choices of conduit holes for entrance of AC mains power
to
p
e
n
try
side entry
For top entry, remove shield for access. Reinstall shield after connection is made
Figure 22: Wire Routing for Area Alarms
Figure 21: Wire Routing for Master / Combo Alarms
Two holes or knockouts are provided for entrance of AC mains power. One hole on left side and one hole on top left of alarm panel back box.
NO OTHER HOLES SHOULD BE PUNCHED OR USED.
Several additional holes or knockouts are provided on right side of top panel and bottom for entrance of low voltage field wiring(Figures 21 and 22).
Two choices of conduit knockouts for entrance of AC mains power
top entry
side entry
Knockouts for entrance of low voltage field wiring
Knockouts for entrance of low voltage field wiring
Wire Routing
Pull Wire (Cont.)
Installation Procedures
Page 31
29
6-847718-00 Rev. B00
Determining Number Of Conductors
• Relay outputs
Two conductors are required for each signal between relay output terminals and remote device (such as a building automation system).
Refer to Wiring Schematic 4 (Page 49) for multiplexer/relay board.
Refer to Wiring Schematic 7 (Page 52) for multi-signal module.
Refer to Wiring Schematic 8 (Page 53) for annunciator module.
Refer to Wiring Schematic 9 (Page 53) for digital display module.
• Digital display module master/slave
Two panels may be connected together so digital display module pressure reading(s) of first panel will be duplicated at second panel.
Two conductors for each digital display module must be routed from first alarm panel to second alarm panel.
Refer to Wiring Schematic 6 (Page 51).
• Ethernet
An eight conductor category 5 network cable is required between each alarm panel to be networked and a facility’s Ethernet hub or switch.
The following rules along with references to this manual’s schematics clarify wiring requirements.
• Digital display modules to sensors
Two conductors are required between each digital display module and sensor module (twisted pair).
Refer to Wiring Schematic 2 (Page 47).
• Switched signal inputs
Two conductors are required for each signal between the signal input terminals and the source signal switch.
These signals can originate at source equipment or from pressure switches mounted on main pressure / vacuum pipelines.
When two master alarms are required, the same switch / relay contacts can be wired to both alarm panels. (See CAUTION below).
Both pairs of wires should originate from switch/relay contacts.
Refer to Wiring Schematic 3 (Page 48) for multiplexer/breakout board.
Refer to Wiring Schematic 5 (Page 50) for multi-signal module.
Refer to Wiring Schematic 10 (Page 54) for pressure switches.
Pull Wire (Cont.)
Installation Procedures
CAUTION:
Do not connect TotalAlert 2 master/combo alarm to switch/relay contacts connected to any alarm panels other than those listed below:
• TotalAlert 2
• MEGA2
• MEGA
Page 32
30
6-847718-00 Rev. B00
Alarm panels require 100 to 250 VAC 50/60 Hz. power. Refer to Wiring Schematic 1 (Page. 46).
For NFPA 99 compliance, alarm panel must be connected to life safety branch of the emergency electrical system.
1. Remove four nuts (area alarms) or screws (master or combo alarms) from plastic power supply shield.
2. Remove plastic shield from power supply.
3. Connect incoming line, neutral and ground wires to the terminal block.
5. Reinstall plastic power supply shield while making sure all high voltage wires are contained within plastic shield.
6. Secure plastic shield with four nuts (area alarms) or screws (master or combo alarms).
Installation Procedures
Power Supply
Wiring
WARNING:
RISK OF ELECTRIC SHOCK
Disconnect power at the circuit breaker before removing power supply shield.
Page 33
31
6-847718-00 Rev. B00
1. Identify each pair of field installed sensor wires inside alarm panel back box assembly.
2. Route each pair of sensor wires as shown in Figure 23 to appropriate digital display module. Each digital display module is labeled with the gas type. Verify the appropriate remote sensor wires are connected to correct digital display module.
3. Connect positive sensor wires to terminals 5 and 6 for each remote sensor and digital display module. Refer to Wiring Schematic 2 (Page 47).
Figure 23: Remote Sensor Wire Routing
Holes provided for entrance of remote wiring
Route wires behind metal brace
Remote Sensor
Wiring (Cont.)
Installation Procedures
Page 34
32
6-847718-00 Rev. B00
Breakout Board Inputs
A master or combo alarm with 32 signals has only one breakout board. Signals are numbered A1 through A32.
A master or combo alarm with 64 signals has two breakout boards. Signals are labeled A1 through A32 on breakout board A and B1 through B32 on breakout board B.
1. Identify each pair of field installed source equipment signal wires inside alarm panel back box assembly.
2. Route each pair of signal wires as shown in Figure 24 to appropriate terminals on breakout board(s).
3. Connect each pair of signal wires to desired breakout board terminals. The terminals are labeled “Signal 1” through “Signal 32”. Refer to Wiring
Schematic 3 (Page 48).
NOTE:
Each pair of terminals labeled on the multi-signal module connector is labeled “+” and “COM”. Ensure that when a source equipment dry contact is wired to two master panels, the same side of the dry contact is connected to the same terminal at both panels. For example, if the source equip­ment’s normally closed contact is wired to the “+” of the first master panel, ensure it is also connect­ed to the “+” terminal of the second master panel.
CAUTION:
Source equipment signal wires must be connect­ed to normally-closed, dry contacts. No electrical voltage can be present and contacts must be closed during normal equipment operation. When contacts open, an alarm condition will be activat­ed.
Wiring (Cont.)
Figure 24: Breakout Board Wire Routing
Installation Procedures
CAUTION:
Do not connect TotalAlert 2 master/combo alarm to switch/relay contacts connected to any alarm panels other than those listed below:
• TotalAlert 2
• MEGA2
• MEGA
Page 35
33
6-847718-00 Rev. B00
Wiring (Cont.)
Relay Board Outputs
Installation Procedures
A master or combo alarm with 32 signals has only one relay board. Signals are numbered A1 through A32.
A master or combo alarm with 64 signals has two relay boards. Signals are labeled A1 through A32 on relay board A and B1 through B32 on relay board B.
1. Identify each pair of field installed relay
output signal wires inside alarm panel back box assembly.
2. Route each pair of relay output signal
wires as shown in Figure 25 to appropriate terminals on relay board(s).
3. Connect each pair of signal wires to
desired relay board terminals. The terminals are labeled “1” through “32”. Refer to Wiring Schematic 4 (Page 49).
Figure 25: Relay Board Wire Routing
Page 36
34
6-847718-00 Rev. B00
Wiring (Cont.)
Multi-Signal Module Inputs
Installation Procedures
1. Identify each pair of field installed source equipment signal wires inside alarm panel back box assembly.
2. Route each pair of signal wires as shown in Figure 26 to appropriate multi-signal module.
3. Connect each pair of signal wires to desired multi-signal module terminals. The terminals are labeled “Signal 1” through “Signal 5”. Refer to Wiring Schematic 5 (Page 50).
Signal 1 corresponds to top row of indicators on front panel of multi-signal module. Signal 5 corresponds to bottom row (Figure 27).
NOTE:
Each pair of terminals labeled on the multi-signal module connector is labeled “+” and “COM”. Ensure that when a source equipment dry contact is wired to two master panels, the same side of the dry contact is connected to the same terminal at both panels. For example, if the source equip­ment’s normally closed contact is wired to the “+” of the first master panel, ensure it is also connect­ed to the “+” terminal of the second master panel.
Holes provided for entrance of remote wiring
Route wires behind metal brace
Figure 27: Multi-Signal Module Signal Numbering
Signal 1
Signal 2
Signal 3
Signal 4
Signal 5
CAUTION:
Source equipment signal wires must be connect­ed to normally-closed, dry contacts. No electrical voltage can be present and contacts must be closed during normal equipment operation. When contacts open, an alarm condition will be activat­ed.
Figure 26: Source Equipment Wire Routing
CAUTION:
Do not connect TotalAlert 2 master/combo alarm to switch/relay contacts connected to any alarm panels other than those listed below:
• TotalAlert 2
• MEGA2
• MEGA
Page 37
35
6-847718-00 Rev. B00
Wiring (Cont.)
Multi-Signal Module Relays
Installation Procedures
Digital Display Module Master/Slave
Digital display modules of two alarm panels may be wired together in such a way that pressure readings of first panel can be duplicated at second panel.
Each digital display module has RS-422 digital outputs and inputs. By connecting digital output (master output) of first panel to digital inputs (slave input) of the second panel, second panel will duplicate pressure readings.
Connect the master output terminals of the sending digital display module to the slave input terminals of the receiving digi­tal display module.
Refer to Wiring Schematic 6 (Page 51).
As an option, mutli-signal modules may be ordered with five output relays, one for each of five signals that multi-signal is capable of monitoring.
Each relay has a set of dry, normally­closed contacts that will open when an alarm is activated on corresponding front panel signal. For example, when an alarm condition activates on top multi-signal front panel alarm location (Signal 1), relay labeled “Signal 1” will activate opening its contacts. Relay contacts will remain open as long as alarm condition is active, even if
audible alarm is silenced by MUTE button.
When alarm condition is corrected, relay contacts will close.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC.
Refer to Wiring Schematic 7 (Page 52).
Page 38
36
6-847718-00 Rev. B00
Wiring (Cont.)
Digital Display Module High / Low Relays
Installation Procedures
Each digital display module is supplied with two separate output relays. One relay for high line pressure alarm and another for low line pressure alarm.
Each relay has a set of dry, normally­closed contacts that will open when an alarm is activated on corresponding front panel signal.
For example, when a low pressure alarm condition activates on digital display module front panel, relay labeled “Low Relay” will activate, opening its contacts.
Relay contacts will remain open as long as alarm condition is active, even if audible
alarm is silenced by MUTE button.
When alarm condition is corrected, relay contacts will close.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC.
Refer to Wiring Schematic 9 (Page 53).
General Fault / Aux Relays
Annunciator Module General Fault Relay:
The annunciator module is supplied with an alarm panel general fault output relay.
This relay has a set of dry contacts that may be wired either normally open or normally closed.
The relay will activate when ANY alarm on ENTIRE alarm panel is activated. Relay will remain activated as long as alarm condition is active, even if audible alarm is
silenced by MUTE button.
When alarm condition is corrected, relay will deactivate. Relay contact ratings are
2
A @ 30 VDC/0.5 A @ 125 VAC
. Refer to
Wiring Schematic 8
(Page 53).
Annunciator Module Auxiliary Relay:
The annunciator module is supplied with an additional auxiliary relay.
Auxiliary relay has a set of dry contacts that may be wired either normally open or normally closed.
Auxiliary relay will activate when ANY alarm on ENTIRE alarm panel is initiated. Auxiliary relay will deactivate when audible
alarm is silenced by MUTE button.
If alarm condition is still active when mute function cancels, auxiliary relay will reactivate.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC. Refer to Wiring Schematic 8 (Page 53).
Page 39
37
6-847718-00 Rev. B00
Installation Procedures
Wiring (Cont.)
TotalAlert 2 master and combo alarm panels are compatible with Johnson Controls Metasys® N2 building automation system.
Each alarm panel is field programmed with a unique N2 address.
Using this address, Johnson Controls system can monitor alarm panel status including digital pressure readings and programmed alarm set points.
Each alarm panel is connected to a common two-wire RS-485 serial computer interface bus. Two wires are connected to connector TB1 of annunciator module and then connected to common data bus.
Refer to Wiring Schematic 11 (Page 55).
Building Automation System Mapping
The state of each of the 64 switched inputs of a master or combo alarm is available using BI1 through BI64.
BI65 is true if there are any active alarms. For efficient single point monitoring, enroll BI65 in the BAS polling table.
BI66 indicates the state of the audible alarm.
Additional information is available using integer data points ADI1 through ADI5.
ADI1 = device serial number, low 2 bytes.
ADI2 = device serial number, high 2 bytes.
NOTE:
The following information is intended to be used by Information Sytems or Building Automation personnel.
Building Automation SystemEthernet
Alarms can be connected together in a TotalAlert alarm network.
Connect the network cable modular plug to annunciator module modular jack J9.
Page 40
38
6-847718-00 Rev. B00
Wiring (Cont.)
Installation Procedures
Building Automation System (Cont.)
ADI3 = device firmware version.
ADI4 = number of switched inputs indicating an alarm condition.
ADI5 = number of remote alarm modules indicating an alarm condition.
If you are planning to use the Metasys® building automation system with the TotalAlert 2, request the following file from BeaconMedaes technical support:
Filename: TotalAlert2v1.ddl
************************************************ ********************** * BeaconMedæs TotalAlert2® Medical Gas Alarm version 1.00 * Point Type Max Allowed * ---------------------- ----------­* AD - Analog Data 32 (ADI & ADF read-only) * BI - Binary Input * Never map output points in a CS model and as discrete objects. * The N, N or Y, Y after the point label means: * 1st one - Can be overridden * 2nd one - Can be adjusted ************************************************ ********************** @MODEL+ CSMODEL "TotalAlert2", "VND" BITITLE "Inputs" ADTITLE "Alarm Summary" CSBI "BI1" ,Y,N,"INPUT_A1","Normal","Alarm" CSBI "BI2" ,Y,N,"INPUT_A2","Normal","Alarm" CSBI "BI3" ,Y,N,"INPUT_A3","Normal","Alarm" CSBI "BI4" ,Y,N,"INPUT_A4","Normal","Alarm" CSBI "BI5" ,Y,N,"INPUT_A5","Normal","Alarm" CSBI "BI6" ,Y,N,"INPUT_A6","Normal","Alarm" CSBI "BI7" ,Y,N,"INPUT_A7","Normal","Alarm" CSBI "BI8" ,Y,N,"INPUT_A8","Normal","Alarm" CSBI "BI9" ,Y,N,"INPUT_A9","Normal","Alarm" CSBI "BI10" ,Y,N,"INPUT_A10","Normal","Alarm" CSBI "BI11" ,Y,N,"INPUT_A11","Normal","Alarm" CSBI "BI12" ,Y,N,"INPUT_A12","Normal","Alarm" CSBI "BI13" ,Y,N,"INPUT_A13","Normal","Alarm" CSBI "BI14" ,Y,N,"INPUT_A14","Normal","Alarm" CSBI "BI15" ,Y,N,"INPUT_A15","Normal","Alarm" CSBI "BI16" ,Y,N,"INPUT_A16","Normal","Alarm" CSBI "BI17" ,Y,N,"INPUT_A17","Normal","Alarm" CSBI "BI18" ,Y,N,"INPUT_A18","Normal","Alarm" CSBI "BI19" ,Y,N,"INPUT_A19","Normal","Alarm" CSBI "BI20" ,Y,N,"INPUT_A20","Normal","Alarm" CSBI "BI21" ,Y,N,"INPUT_A21","Normal","Alarm" CSBI "BI22" ,Y,N,"INPUT_A22","Normal","Alarm" CSBI "BI23" ,Y,N,"INPUT_A23","Normal","Alarm" CSBI "BI24" ,Y,N,"INPUT_A24","Normal","Alarm" CSBI "BI25" ,Y,N,"INPUT_A25","Normal","Alarm"
CSBI "BI26" ,Y,N,"INPUT_A26","Normal","Alarm" CSBI "BI27" ,Y,N,"INPUT_A27","Normal","Alarm" CSBI "BI28" ,Y,N,"INPUT_A28","Normal","Alarm" CSBI "BI29" ,Y,N,"INPUT_A29","Normal","Alarm" CSBI "BI30" ,Y,N,"INPUT_A30","Normal","Alarm" CSBI "BI31" ,Y,N,"INPUT_A31","Normal","Alarm" CSBI "BI32" ,Y,N,"INPUT_A32","Normal","Alarm" CSBI "BI33" ,Y,N,"INPUT_B1","Normal","Alarm" CSBI "BI34" ,Y,N,"INPUT_B2","Normal","Alarm" CSBI "BI35" ,Y,N,"INPUT_B3","Normal","Alarm" CSBI "BI36" ,Y,N,"INPUT_B4","Normal","Alarm" CSBI "BI37" ,Y,N,"INPUT_B5","Normal","Alarm" CSBI "BI38" ,Y,N,"INPUT_B6","Normal","Alarm" CSBI "BI39" ,Y,N,"INPUT_B7","Normal","Alarm" CSBI "BI40" ,Y,N,"INPUT_B8","Normal","Alarm" CSBI "BI41" ,Y,N,"INPUT_B9","Normal","Alarm" CSBI "BI42" ,Y,N,"INPUT_B10","Normal","Alarm" CSBI "BI43" ,Y,N,"INPUT_B11","Normal","Alarm" CSBI "BI44" ,Y,N,"INPUT_B12","Normal","Alarm" CSBI "BI45" ,Y,N,"INPUT_B13","Normal","Alarm" CSBI "BI46" ,Y,N,"INPUT_B14","Normal","Alarm" CSBI "BI47" ,Y,N,"INPUT_B15","Normal","Alarm" CSBI "BI48" ,Y,N,"INPUT_B16","Normal","Alarm" CSBI "BI49" ,Y,N,"INPUT_B17","Normal","Alarm" CSBI "BI50" ,Y,N,"INPUT_B18","Normal","Alarm" CSBI "BI51" ,Y,N,"INPUT_B19","Normal","Alarm" CSBI "BI52" ,Y,N,"INPUT_B20","Normal","Alarm" CSBI "BI53" ,Y,N,"INPUT_B21","Normal","Alarm" CSBI "BI54" ,Y,N,"INPUT_B22","Normal","Alarm" CSBI "BI55" ,Y,N,"INPUT_B23","Normal","Alarm" CSBI "BI56" ,Y,N,"INPUT_B24","Normal","Alarm" CSBI "BI57" ,Y,N,"INPUT_B25","Normal","Alarm" CSBI "BI58" ,Y,N,"INPUT_B26","Normal","Alarm" CSBI "BI59" ,Y,N,"INPUT_B27","Normal","Alarm" CSBI "BI60" ,Y,N,"INPUT_B28","Normal","Alarm" CSBI "BI61" ,Y,N,"INPUT_B29","Normal","Alarm" CSBI "BI62" ,Y,N,"INPUT_B30","Normal","Alarm" CSBI "BI63" ,Y,N,"INPUT_B31","Normal","Alarm" CSBI "BI64" ,Y,N,"INPUT_B32","Normal","Alarm" CSBI "BI65" ,Y,N,"ANY_ALARM","No_Alarms","Alarm" CSBI "BI66" ,Y,N,"AUD_ALM","Off","On" CSAD "ADI1" ,N,Y,"Serial_1","" CSAD "ADI2" ,N,Y,"Serial_2","" CSAD "ADI3" ,N,Y,"VERSION","" CSAD "ADI4" ,N,Y,"NUMBER_LOCAL_ALARMS","" CSAD "ADI5" ,N,Y,"NUMBER_REMOTE_ALARMS","" CSAI "AI1",Y,N,"DDM1","" CSAI "AI2",Y,N,"DDM2","" CSAI "AI3",Y,N,"DDM3","" CSAI "AI4",Y,N,"DDM4","" CSAI "AI5",Y,N,"DDM5","" CSAI "AI6",Y,N,"DDM6","" CSAI "AI7",Y,N,"DDM7","" CSAI "AI8",Y,N,"DDM8",""
Page 41
39
6-847718-00 Rev. B00
Installation Procedures
Field Wiring Cable Shield Grounding
All field wiring cable shields must be grounded inside alarm panel back box.
A grounding screw is provided in upper right corner of area alarm back box (Figure 28).
Grounding screws are provided in top and bottom of master and combo alarm back boxes (Figure 29).
Shields from several cables may be wrapped together and crimped into one ring lug (by others) .
Cable shield
grounding screw
(crimp lug not provided)
CAUTION:
Keep shield wires to ground screw as short as possible so they can not touch front panel circuit boards when front panel is closed.
Figure 29: Cable Shield Grounding-Master/Combo
Cable shield grounding screws located at top and
bottom of back box
(crimp lugs not provided)
Figure 28: Cable Shield Grounding-Area
Wiring (Cont.)
Page 42
40
6-847718-00 Rev. B00
Installation Procedures
Front Panel Mounting
Finish
1. Remove front panel assembly from static shielding shipping bag.
2. Remove front panel mounting screws from alarm panel back box assembly (Figures 30 and 31).
3. Remove lanyard mounting screws from alarm panel back box assembly (Figure 30 and 31).
4. Attach front panel to alarm panel back box using screws removed in step 2 (Figure 32).
5. Attach lanyards to alarm panel back box using screws removed in step 3.
6. Remove nut from front panel grounding lug.
7. Install front panel grounding wire using nut removed in step 6
8. Connect power supply DC wire harness to J6 on annunciator module. Refer to Wiring Schematic 1 (Page 46).
NOTE:
Harness connector is keyed to prevent incor­rect orientation, however, use care to ensure correct pin alignment.
Figure 32: Attach Front Panel and Lanyards
Figure 31: Area Alarm Panel Screws
Figure 30: Master / Combo Panel Screws
Lanyard screws
Lanyard screws
Front panel mounting screws
Front panel mounting screws
Front panel mounting screws
Front panel mounting screws
ATTENTION:
Observe Precautions for Handling
ELECTROSTATIC SENSITIVE
DEVICES
Page 43
41
6-847718-00 Rev. B00
1. Remove sensor module from shipping
carton.
2. Insert sensor into valve opening in
pressure/vacuum service rough-in (Figure 33). An indexing pin provides for proper orientation and prevents gas service cross-connection. Push sensor all the way in and secure with (2) #6-32 x 1-1/4” screws. Repeat this process for all sensors within alarm panel.
3. The digital display module(s) located
on front panel assembly are factory wired with a harness and polarized two-pin connector for each sensor module. Each digital display module is labeled with the gas type. Match gas type of each sensor to gas type of each digital display module and join polarized connectors of sensor and digital display module harnesses.
NOTE:
Remove blue protective netting from sensor connector.
Local Sensor
Figure 33: Local Sensor Mounting
Finish
Installation Procedures
Indexing Pin
Indexing Hole
Screws
NOTE:
Pressure/vacuum service rough-ins have been installed in a specific order to optimize sensor module wire routing.
Page 44
42
6-847718-00 Rev. B00
Installation Procedures
1. Remove sensor module from shipping carton. Each sensor module is shipped with a wiring pigtail that has a two-pin polarized connector.
2. Wire nut pigtail to field installed wiring inside sensor mounting box. Note polarity of wiring and corresponding field wiring color or number for later.
3. Join polarized connector in sensor mounting box to mating connector on sensor module (Figure 34).
4. Insert sensor into valve opening in sensor rough-in. An indexing pin provides for proper orientation and prevents gas service cross­connection. Push sensor all the way in and secure with (2) #6-32 x 1-1/4” screws.
5. Tuck excess wiring into open space behind sensor.
NOTE:
Remove blue protective netting from sensor connector.
Figure 34: Remote Sensor Module Connection
Remote Sensor
Valve opening
Sensor
Polarized connector
Finish
NOTE:
Do not ground shield drain wire at sensor.
Page 45
43
6-847718-00 Rev. B00
Labeling
Finish
Installation Procedures
Annunciator Module (Area Alarms)
Label annunciator module using provided panel location label.
1. Mark location on panel location label.
2. Slide location label into pocket in front of annunciator module (Figure 36).
Figure 36: Annunciator Module Location Label
Multiplexer Module/LED Module
Label each LED using the provided gas service identification labels.
Multiplexer module LEDs are numbered 1 through 5 from top to bottom.
LED module LEDs are numbered 6 through 10 from top to bottom.
1. Apply gas identification label to insert.
2. Slide insert with label into pocket in front of multiplexer or led module (Figure 35).
Align gas ID label with line on insert
Figure 35: Multiplexer Module Labeling
Page 46
44
6-847718-00 Rev. B00
Label
(provided)
Slide label into slit in front panel overlay
Digital Display Module
Label each digital display module using provided location labels.
1. Mark location on location label.
2. Slide location label into pocket in front of digital display module (Figure 37).
Multi-Signal Module
Label each multi-signal module using provided system status labels.
Blank system status labels are provided for custom signal names.
1. Slide system status labels into pockets in front of multi-signal module (Figure 38).
Installation Procedures
Labeling (Cont.)
Finish
Label
(provided)
Slide label(s) into slits in front panel overlay
Location label
Sensor Module
1. Mark location monitored by sensor in space provided on sensor label (Figure 39).
Figure 39: Sensor Module Location Label
Figure 38: Multi-Signal Front Panel Labeling
Figure 37: Digital Display Module
Page 47
45
6-847718-00 Rev. B00
The wiring schematics listed below are provided.
Call BeaconMedæs at 1-888-4MEDGAS (1-888-463-3427) for technical support.
1. Power Supply (Page 46)
2. Sensor Module to Digital Display
Module (Page 47)
3. Multiplexer/Breakout Boards (Page 48)
4. Relay Board (Page 49)
5. Multi-Signal Module Inputs (Page 50)
6. Digital Display Module Master/Slave
(Page 51)
7. Multi-Signal Module Relay Outputs
(Page 52)
8. General Fault/Auxiliary Relays
(Page 53)
9. Digital Display Module High/Low Relays
(Page 53)
10 Remote Pressure/Vacuum Switches
(Page 54)
11 Johnson Controls Metasys® N2
Connection (Page 55)
Wiring Schematics
Page 48
46
6-847718-00 Rev. B00
Wiring Schematic 1: Power Supply
Annunciator module
20-wire ribbon
cable to modules
Power supply
Fuse holder
Ground (green)
Line (black)
Neutral (white)
3-wire power supply harness
120 VAC mains power connections from life safety branch of the emergency electrical system
Ground screw
Red
Orange
Black
20-wire ribbon
cable to modules
Terminal block
Ground wire To front panel
Wiring Schematics
Page 49
47
6-847718-00 Rev. B00
Wiring Schematic 2: Sensor Module to Digital Display Module
Digital Display Module
Digital Display Module
Remote sensor mounting box
(remote from alarm panel)
Local Sensor
(inside alarm panel back box)
2-pin polarized connector
2-pin polarized connector
20 wire ribbon cable to adjacent module
LOCAL SENSOR
REMOTE SENSOR
20 wire ribbon cable to adjacent module
* Sensor pigtail
Sensor pigtail
(provided)
Wire nuts
Field wiring
(by others)
* NOTE:
Sensor pigtails for local sensors are factory con­nected to digital display module.
Pin 5 - red (+)
Pin 6 - black (-)
Pin 5 (+)
Pin 6 (-)
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
GAS ID
Wiring Schematics
Page 50
48
6-847718-00 Rev. B00
Wiring Schematic 3: Multiplexer / Breakout Boards
Wiring Schematics
20-wire ribbon cable to modules
10-wire ribbon cable to LED module
40-wire ribbon cable to multiplexer module connector A
40-wire ribbon cable to multiplexer module connector B
Multiplexer module
SIGNAL B32
SIGNAL B1
SIGNAL A32
SIGNAL A2
SIGNAL A1
Dry normally-closed contacts at source equipment or line pressure switches
COM
+
COM
+
COM
+
COM
+
COM
+
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
To additional master alarm panel(s)
Breakout board A
Breakout board B
CAUTION:
Do not connect TotalAlert 2 master/combo alarm to switch/relay contacts connected to any alarm panels other than those listed below:
• TotalAlert 2
• MEGA2
• MEGA
Page 51
49
6-847718-00 Rev. B00
Wiring Schematic 4: Relay Board
Wiring Schematics
Breakout board B
Breakout board A
Relay board A
Relay board B
Dry normally-closed output relay contacts
NOTE:
Output relay contacts are dry normal­ly closed type. Contacts open upon designated alarm activation.
Pressing MUTE on Annunciator Module DOES NOT reset relay. Relay deactivates when alarm condi­tion is corrected.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC
.
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
SIGNAL A1
SIGNAL A2
SIGNAL A32
SIGNAL B1
SIGNAL B32
Page 52
50
6-847718-00 Rev. B00
Wiring Schematic 5: Multi-Signal Module Inputs
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Dry normally-closed contacts at source equipment or line pressure switches
COM
+
COM
+
COM
+
COM
+
COM
+
20 wire ribbon cable to adjacent module
20 wire ribbon cable to adjacent module
Pin 1
Pin 10
Pin 1
Pin 10
Multi-Signal Module
at FIRST master alarm panel
Multi-Signal Module
at SECOND master alarm panel
SIGNAL 1 - pin 1 (+), pin 2 (COM)
SIGNAL 2 - pin 3 (+), pin 4 (COM)
SIGNAL 3 - pin 5 (+), pin 6 (COM)
SIGNAL 4 - pin 7 (+), pin 8 (COM)
SIGNAL 5 - pin 9 (+), pin 10 (COM)
Multi-Signal Module front panel
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
“M” OR “R” Module
Wiring Schematics
CAUTION:
Do not connect TotalAlert 2 master/combo alarm to switch/relay contacts connected to any alarm panels other than those listed below:
• TotalAlert 2
• MEGA2
• MEGA
Page 53
51
6-847718-00 Rev. B00
Wiring Schematic 6: Digital Display Module Master/Slave
Digital Display Module
at master alarm panel
Digital Display Module at slave alarm panel
Signal from
sensor module
Pin 5 (+)
Pin 6 (-)
Master output to slave
Pin 4 (-) / Pin 3 (+)
Slave input from master
Pin 1 (+)
Pin 2 (-)
20 wire ribbon cable to adjacent module
20 wire ribbon cable to adjacent module
NOTE:
The above master to slave wiring configuration DOES NOT comply with NFPA 99 wiring guide­lines for two required master panels.
If digital display modules are used for a master alarm, EACH master panel must be directly con­nected to a sensor module for each pressure/vac­uum service.
Additional panels, if desired, may be connected as indicated above.
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
Wiring Schematics
Page 54
52
6-847718-00 Rev. B00
Wiring Schematic 7: Multi-Signal Module Relay Outputs
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Dry normally-closed contacts at source equipment or line pressure switches
COM
+
COM
+
COM
+
COM
+
COM
+
Multi-Signal Module
with relays
20 wire ribbon cable to adjacent module
SIGNAL 1 - pins 1 & 2
SIGNAL 2 - pins 3 & 4
SIGNAL 3 - pins 5 & 6
SIGNAL 4 - pins 7 & 8
SIGNAL 5 - pins 9 & 10
Dry normally-closed output relay contacts
NOTE:
Output relay contacts are dry normally closed type.
Contacts open upon designated alarm activation. Contacts remain open until alarm condition is cor­rected.
Pressing MUTE on Annunciator Module WILL deactivate relay until audible alarm is again reacti­vated.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC
.
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 39 for details.
Wiring Schematics
Page 55
53
6-847718-00 Rev. B00
Wiring Schematic 8: General Fault / Auxiliary Relays
Wiring Schematic 9: Digital Display Module High / Low Relays
Annunciator Module
Digital Display Module
20 wire ribbon cable to adjacent module
General Fault Relay
N/C (pin 5)
N/O (pin 3)
Common (pin 4)
N/O (pin 6)
Common (pin 7)
N/C (pin 8)
Auxiliary Relay
NOTE:
General Fault Relay
activates when ANY alarm
on panel is in progress.
Pressing MUTE on Annunciator Module DOES NOT reset relay. Relay deactivates when alarm condition is corrected.
Auxiliary Relay (optional)
activates when ANY
audible alarm on panel is in progress.
Pressing MUTE on Annunciator Module WILL deactivate relay until audible alarm is again reacti­vated.
Relay contact ratings are 2A @ 30 VDC/0.5 A @ 125 VAC.
20 wire ribbon cable to adjacent module
Low Alarm Relay
N/C (pin 8)
Common (pin 7)
N/C (pin 10)
Common (pin 9)
High Alarm Relay
NOTE:
High
Alarm Relay activates when high line pres­sure alarm on digital display module is in progress. When relay activates normally closed contacts open.
Pressing MUTE on Annunciator Module DOES NOT deactivate relay. Relay deactivates when high line pressure alarm condition is corrected.
Low
Alarm Relay activates when low line pressure alarm on digital display module is in progress. When relay activates normally closed contacts open.
Pressing MUTE on Annunciator Module DOES NOT deactivate relay. Relay deactivates when low line pressure alarm condition is corrected.
Relay contact ratings are 2A @ 30 VDC/0.5 A @ 125 VAC.
Wiring Schematics
Page 56
54
6-847718-00 Rev. B00
Wiring Schematic 10: Remote Pressure / Vacuum Switches
P/N 6-129030-XX thru 6-129032-XX Series
Pressure Switches
P/N 6-129033-XX Series
Vacuum Switches
* Terminals to be
used for TotalAlert 2 and other systems sensing fault on electrical contacts opening.
Typical Wiring Schematic for above
Pressure Switches
Typical Wiring Schematic for above
Vacuum Switches
1/4” NPT Female
3/4” Female Conduit
Connection
1/4” NPT Female
1/4” NPT Male x DISS Valve
(Vacuum or WAGD)
1/4” NPT Male x DISS Valve
(Gas Specific)
HIGH
LOW LOW
N/C
N/O
C C
N/O
N/C
C
N/O
N/C
Wiring Schematics
Page 57
55
6-847718-00 Rev. B00
Wiring Schematic 11: Johnson Controls Metasys® N2 Connection
Wiring Schematics
To Johnson Controls Metasys® N2 Building Automation
Annunciator Module
GND - +
RS-485
Page 58
56
6-847718-00 Rev. B00
NOTE:
If any module appears to be malfunctioning, refer to Troubleshooting Guide.
Status LEDs
1. Turn on electrical power to alarm panel.
2. Make following observations:
• POWER ON light illuminates on
front of alarm panel.
• Boot message is shown on
vacuum fluorescent display.
• Alarm modules warm-up for ten
seconds. During warm-up, no audible or visual alarms activated. After warm-up, audible and visual alarms are initiated for any active alarm.
3. Press MUTE button to silence audible alarm.
4. Make following observations:
• If all signals are unprogrammed
(factory default) LEDs will illuminate green for 10 seconds, then turn off.
• If signals are assigned to LEDs,
multiplexer and LED modules indicate current status for the signals and vacuum fluorescent display displays signal information.
• Connected, but unprogrammed
signals are shown on the vacuum fluorescent display.
Unassigned Input [INPUT NUMBER]
Browse at: http:// TA2_12345
Version: [VERSION] SN 12345
BeaconMedaes
TotalAlert 2 System
Booting...
Master Alarm Panel
Start-Up and Checking
Operation
Figure 40: Multiplexer/LED Module
Page 59
57
6-847718-00 Rev. B00
Status LEDs
LED Display
SIGNAL #1
SIGNAL #2
SIGNAL #3
SIGNAL #4
SIGNAL #5
Status LEDs
Operation
Start-Up and Checking (Cont.)
1. Turn on electrical power to alarm
panel.
2. Make following observations:
• Green POWER ON LED illuminates on front of alarm panel.
• Alarm modules warm-up for ten seconds. During warm-up, no audible or visual alarms activated. After warm-up, audible and visual alarms are initiated for any active alarm.
3. Press MUTE button to silence audible alarm.
4. Pressurize piping system (medical gas and vacuum).
5. Make following observations:
• Digital display modules display
actual pipeline pressures or vacuum levels.
• If digital display module pipeline
pressures and vacuum levels are within pre-set limits, NORMAL LED is illuminated.
• If digital display module pipeline
pressures and vacuum levels are outside pre-set limits, status LEDs show HIGH or LOW.
• If a fault code is displayed (
-- FF 11 --
,
-- FF 22 --, -- FF 33 --
or
-- FF 44 --
) refer to
Troubleshooting Guide.
• Multi-signal modules indicate
current status from dry-contact switches. Unused signals can be disabled. Refer to Set-Up
Procedure.
Area Alarm Panel
Figure 42: Multi-signal Module
Figure 41: Digital Display Module
Page 60
58
6-847718-00 Rev. B00
Operation
Combo Alarm Panel
Start-Up and Checking (Cont.)
1. Turn on electrical power to alarm panel.
2. Make following observations:
• POWER ON light illuminates on
front of alarm panel.
• Boot message is shown on
vacuum fluorescent display.
• Alarm modules warm-up for ten
seconds. During warm-up, no audible or visual alarms activated. After warm-up, audible and visual alarms are initiated for any active alarm.
3. Press MUTE button to silence audible alarm.
4. Pressurize piping system (medical gas and vacuum).
5. Make following observations:
• Digital display modules display
actual pipeline pressures or vacuum levels.
• If digital display module pipeline
pressures and vacuum levels are within pre-set limits, NORMAL indicator is illuminated.
• If digital display module pipeline
pressures and vacuum levels are outside pre-set limits, status indicators show HIGH or LOW.
• If a fault code is displayed (
-- FF 11 --
,
-- FF 22 --, -- FF 33 --
or
-- FF 44 --
) refer to
Troubleshooting Guide.
Browse at: http:// TA2_12345
Version: [VERSION] SN 12345
BeaconMedaes
TotalAlert 2 System
Booting...
• Multiplexer modules indicate current status from dry-contact switches.
• Connected, but unprogrammed signals are shown on the vacuum fluorescent display.
Unassigned Input [INPUT NUMBER]
Page 61
59
6-847718-00 Rev. B00
Operation
Annunciator Module
Set-Up Procedures
Setup Using Front Panel Controls (Master and combo alarm panels)
Many parameters may be set using front panel controls, but some parameters must be set up using web pages.
1. Press SETUP button on back of annunciator module to enter setup mode.
2. N2 Address
This parameter is the Johnson Controls Metasys® N2 Address.
Possible values are: 1- 255 (Factory default: 1)
3. Clear Network
Answering ‘Yes’ will clear and rebuild the medical gas network.
4. Reset Users
Answering Yes will clear all user ids and reset User 1 name and password to factory defaults: Username: new Password: new
Reset users
[YES/NO]
Clear network
[YES/NO]
N2 Address
[VALUE]
Press or to change the value
Press ‘TEST’ for the next item
**** Device **** **** Setup ****
NOTE:
Before setting up signals, fill out Master Alarm Signal Input Data table on page 138.
5. Input gas type
Sets the gas type for signal XXX.
Possible GAS TYPES are:
Oxygen Nitrous Oxide Medical Air Vacuum Nitrogen Lab Air Lab Vacuum Argon Instrument Air WAGD Carbon Dioxide CO2-O2 O2-CO2 He-O2 O2-He Helium Custom Unused Dental Air
If gas type is set to ‘Unused’, step 5 is repeated for the next input number.
6. Input Message
Sets the alarm message for signal XXX.
There are several pre-programmed messages or a custom message can be selected. A custom message must be entered using web page setup.
Possible values depend on gas type selected in previous step (See Table 1).
7. Input lights LED
Assigns LED to signal XXX. Possible values are 1 - 10 for master and large combo alarms, and 1 - 5 for small combo alarms.
Input XXX lights LED [LED Number]
Input XXX message
[Message]
Input XXX gas type
[GAS TYPE]
Page 62
60
6-847718-00 Rev. B00
Operation
Set-Up Procedures
Annunciator Module (Cont.)
Signal
Oxygen
Nitrous Oxide
Medical Air
Vacuum
Nitrogen
Laboratory Air
Laboratory Vacuum
Argon
Instrument Air
WAGD
Carbon Dioxide
CO2-O2
O2-CO2
He-O2
O2-He
Helium
Custom Gas Type
Dental Air
Liquid Level Low
X X X X X
High Line Pressure
X X X X X X X X X X X X X X
X
Low Line Pressure
X X X X X X X X X X X X X X
X
Reserve Pressure Low
X X X X X X X X X X X X X X
X
Main Supply Lvl. Low
X X X X X X X X X X X
2nd Supply in Use
X X X X X X X X X X X X X X
X
Resrv. Supply in Use
X X X X X X X X X X X X X X
X
Reserve Supply Low
X X X X X X X X X X X X X X
X
System Malfunction
X X X X X X X
X
Thermal Shutdown
X X X X X X X
X
Service Required
X X X X X X X
X
Backup Vac Pump On
X X X X
Low Vacuum
X X X X
Low Water
X X X X
Dryer Malfunction
X X X X
X
Dew Point High
X X X X
X
Carbon Monoxide High
X X X X
X
Change Filter
X X X X
X
Receiver Water High
X X X X
X
Separator Water High
X X X X
X
Air Disch. Temp High
X X X X
X
Backup Compressor On
X X X X
X
Compressor Malfunc.
X X X X
X
Cylinder Rsrv.in Use
X X X X
X
Cylinder Reserve Low
X X X X
X
Secondary Supply Low
X X X X X X X X X X X X X X
X
Custom Message
X X X X X X X X X X X X X X X X X
X
Table 1. Predefined Messages
Page 63
61
6-847718-00 Rev. B00
Set-Up Procedures
Operation
Only unused LEDs and LEDs with the same gas type are available.
8. Return to step 5 for remaining inputs.
9. After setting up Input B32 the alarm panel will return to monitoring mode.
10.To return to monitoring mode without setting up every signal, press SETUP button again.
Reset Users and IP Configuration
1. While holding the SETUP button, press and release the RESET button.
2. Continue to hold the SETUP button for 5 seconds.
3. The parameters listed in Table 2 will be set to factory defaults.
Reset Factory Defaults
1. While holding the SETUP button, press and release the RESET button.
2. Continue to hold the SETUP button for 10 seconds.
3. The parameters listed in Tables 2 and 3 will be set to factory defaults.
Annunciator Module (Cont.)
Setting Factory default
User 1 Name new User 2 Name [Blank] User 3 Name [Blank] User 1 Password new User 2 Password [Blank] User 3 Password [Blank]
IP address mode
Try DHCP, then try
fixed IP address Subnet mask 255.255.255.0 Default fixed IP address
192.168.1.100
Default fixed subnet mask
255.255.255.0
Default fixed gateway192.168.1.1 Automatic discovery Enabled Date/Time format 24 hours SMTP server address
0.0.0.0 (unused)
CAUTION:
This procedure will revert annunciator module set­tings to factory defaults. There is no way to recover previously programmed settings after resetting factory defaults.
Table 2. Reset Users and IP Config.
Setting Factory default
Facility [Blank]
Contact [Blank]
Location [Blank]
SMTP server name [Blank]
Email address 1 [Blank]
Email address 2 [Blank]
Email address 3 [Blank]
Email address 4 [Blank]
Email address 5 [Blank]
All area locations [Blank]
Peer network device list
Cleared (including manually entered devices)
Event log Cleared
All signal gas types Unused
All signal LEDs 0 (unassigned)
All signal locations [Blank]
All signal messages Input XXX
All custom gas types "Custom"
Table 3. Reset Factory Defaults
Page 64
62
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
Multiplexer Module
6. Select desired display brightness by pressing either ! or " buttons. Each push will increase or decrease brightness of display. Audible alarm will chirp one time with each button press and two times when limit is reached.
7. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence.
8. Multiplexer module will return to monitoring mode.
Setting Audible Alarm Repeat Time and Display Intensity:
Used to set time interval for reactivation of audible alarm after alarm MUTE
button has been pressed.
1. Loosen two screws on front of alarm panel. Hinge open front cover.
2. Locate SETUP button on multiplexer module circuit board (Figure 43).
3. Press and release SETUP button. Audible alarm will chirp and multiplexer module front panel LED indicators will show current audible alarm repeat time as shown below:
Indicator Illuminated Repeat Time
None OFF LED 1 - red 1 Min. LED 2 - red 5 Min. LED 3 - red 15 Min. LED 4 - red 30 Min. LED 1 - green 1 Hr. LED 2 - green 2 Hr. LED 3 - green 8 Hr. LED 4 - green 12 Hr. LED 5 - green 24 Hr.
4. Using either ! or " buttons, select desired audible alarm repeat time.
5 Press and release TEST button on
front of alarm panel. All LEDs will illuminate.
NOTE:
To comply with the requirements of the City of New York Department of Buildings; Materials and Equipment Acceptance Division (M.E.A.), set audible alarm repeat time to 30 minutes.
NOTE:
Normally, no setup is required for the multiplex­er module. The following advanced setup pro­cedures are available.
Multiplexer Module Board
SETUP
button
TEST
button
Up and down
buttons
LED 1
LED 2
LED 3
LED 4
LED 5
Status LEDs
Figure 44: Multiplexer Module LEDs
Figure 43: Multiplexer Programming Buttons
Page 65
63
6-847718-00 Rev. B00
Operation
LED 1
LED 2
LED 3
LED 4
LED 5
Bit 4 (16)
Bit 0 (1)
Bit 1 (2)
Bit 2 (4)
Bit 3 (8)
Bit 5 (32)
Bit 6 (64)
Bit 7 (128)
Figure 45: Binary data represented by LEDs
Red LEDs
Green LEDs
Set-Up Procedures (Cont.)
Multiplexer Module (Cont.)
Setting Communication Parameters:
Address range is 0 to 255. Factory default setting is 8.
Network address is shown as a binary number on specific red and green front panel LEDs. A numeric value is assigned to each LED (Figure 45).
For example, if LEDs for bits 0 and 2 were illuminated, network address would be 5 (1 + 4 = 5).
1. Press and HOLD set-up button. Audible alarm will chirp when set-up button is first pushed and again two seconds later. Release button after second audible alarm chirp.
2. Multiplexer module front panel LEDs will show network address. If no LEDs are illuminated, address is 0.
3. Using either ! or " buttons, select desired network address between 0 and 255.
4. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence.
5. Multiplexer module will return to monitoring mode.
CAUTION:
Communication parameters are factory set and should not be changed. These instructions are provided for programming replacement modules.
Page 66
64
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
Digital display modules are shipped from the factory with the following settings:
Gas/Vacuum Alarm Set Point Service Low High Pressure (50 psig) 40 psig 60 psig Pressure (100 psig) 80 psig 120 psig Nitrogen, Instr. Air 140 psig 190 psig Vacuum/WAGD 12 in Hg. none
Changing units and alarm set points:
1. Loosen two screws on front of alarm panel. Hinge open alarm panel’s front cover.
2. Locate SETUP button on circuit board of digital display module to be adjust­ed (Figure 46).
3. Press and release SETUP button. Audible alarm will chirp and
SS EE TT 11
will
be displayed.
4. Press and release TEST button on front of alarm panel. Current unit of measure will be displayed. Select desired unit of measure by pressing either ! or " buttons. Available units of measure are:
KK PP AA
(kPa)
PP SS II
(psig)
II NN KK 99
(in Hg)
NN NN KK 99
(mm Hg)
5. Press and release TEST button. The LOW indicator will illuminate and
LL OO
will be displayed. After two seconds current low alarm setting will be displayed. Select desired low alarm setting by pressing either ! or " buttons. Low alarm setting ranges are:
Digital Display Module Board
SETUP
button
TEST
button
Up and down
buttons
Low alarm
LED
High alarm
LED
Display
Digital Display Module
Figure 47: Digital Display Module
NOTE:
Audible alarm will chirp with each button push.
Figure 46: Digital Display Programming Buttons
Page 67
65
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
00
to
11 33 88 00(11 77 22 55
*) (kPa)
00
to
22 00 00(22 55 00
*) (psig)
00
to
33 22
(in Hg)
00
to
88 00 00
(mm Hg)
*N2 and instrument air only
6. Press and release TEST button.
HIGH indicator will illuminate and
KK ,,
will be displayed. After two seconds current high alarm setting will be displayed. Select desired high alarm setting by pressing either ! or " buttons. High alarm setting ranges are:
00
to
11 33 88 00(11 77 22 55
*) (kPa)
00
to
22 00 00(22 55 00
*) (psig)
00
to
33 22
or
NN OO NN EE
(in Hg)
00
to
88 00 00
or
NN OO NN EE
(mm Hg)
*N2 and instrument air only
7. Press and release TEST button to
save changes.
DD OO NN EE
will be
displayed for two seconds.
8. Digital display module will return to
monitoring mode.
NOTE:
If module is idle for more than one minute dur­ing set-up procedure, module will chirp three times, return to monitoring mode and will default to previous settings. No changes to settings will be saved.
The set-up must be completed and the module
must display
DD OO NN EE
in order for changes to be
saved.
Digital Display Module (Cont.)
Page 68
66
6-847718-00 Rev. B00
Operation
Digital Display Module-Advanced
Two additional levels of “advanced” set-up features are available.
The first advanced level,
SS EE TT 22
, is used to
adjust communication related parameters.
Changing Communication Parameters
AA DD DD RR
(network address)
A network address uniquely identifies each digital display module in the alarm panel.
Address range is 00to
22 55 55
.
For TotalAlert 2 alarm panels, this setting is programmed at the factory when the alarm panel is assembled and should not be changed.
BB AA UU DD
(baud rate) Used to set communication speed. User choices are
44 88 00 00
or
99 66 00 00
.
Baud rate must be set to
99 66 00 00
. for
TotalAlert 2 alarm panels.
NN DD FF
(network data format)
Defines data word length. Choices are
88
(bits) or
11 66
(bits). NDF must be set to
11 66
for TotalAlert 2 alarm panels.
PP DD FF
(pressure data format) Defines data word length transmitted to a slave alarm panel. User choices are
88
(bits) or
11 66
(bits). Factory setting is
11 66
.
Set-Up Procedures (Cont.)
1. Press and HOLD SETUP button for TWO seconds until
SS EE TT 22
is displayed.
2. Press and release TEST button on front of alarm panel.
AA DD DD RR
will be displayed for one second and then current network address. Select
desired address by pressing ! or " buttons. Each module must have a unique address.
3. Press and release TEST button.
BB AA UU DD
will be displayed for one second
and then current baud rate. Select desired baud rate by pressing ! or " buttons.
4. Press and release TEST button.
NN DD FF
will be displayed for one second and then current network data format. Select desired data format by pressing ! or " buttons.
5. Press and release TEST button.
PP DD FF
will be displayed for one second and then current pressure data format. Select desired data format by pressing ! or " buttons.
6. Press and release TEST button to save changes.
DD OO NN EE
will be
displayed for two seconds.
7. Digital display module will return to monitoring mode.
NOTE:
If module is idle for more than one minute dur­ing set-up procedure, module will chirp three times, return to monitoring mode and will default to previous settings. No changes to settings will be saved.
Set-up must be completed and module must
display
DD OO NN EE
in order for changes to be
saved.
CAUTION:
Communication parameters are factory set and should not be changed. These instructions are provided for programming replacement modules.
Page 69
67
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
Digital Display Module-Advanced
(Cont.)
The second advanced level,
SS EE TT 33
, is used to adjust other miscellaneous parameters as listed below:
Changing Miscellaneous Parameters
SS EE RR UU
(gas service identification)
Used to set digital display module’s gas service identification for communication with a digital sensor.
User choices are:
00 22
(oxygen)
NN 22 00
(nitrous oxide)
AA ,, RR
(medical air)
UU AA ((
(vacuum)
NN 22
(nitrogen)
LL AA ,, RR
(lab air)
LL UU AA ((
(lab vacuum)
AA RR 99 NN
(argon)
II AA ,, RR
(instrument air)
UU AA 99 DD
(WAGD)
(( 00 22
(carbon dioxide)
(( -- 00 22
(CO2/O2)
00 22 -- ((
(O2/CO2)
KK EE 00 22
(He/O2)
00 22 KK EE
(O2/He)
KK EE
(Helium)
NN OO NN EE
(none)
OO FF FF SS
(display offset) Used to adjust digital module’s display. User choices are 00,11,22,
-- 11
, or
-- 22
.
Factory setting is 00.
RR EE PP TT
(audible alarm repeat) Used to set time interval for reactivation of audible alarm after alarm MUTE button
has been pressed.
User choices are:
OO FF FF
11,55, 11 55,33 00
(minutes),
11 HH RR, 88 HH RR, 11 22 HH RR
or
22 44 HH RR
(hour).
Factory setting is
OO FF FF
.
When set to
OO FF FF
, audible alarm will not reactivate after an active alarm has been silenced. Any new alarm will reactivate audible alarm.
II NN TT SS
(display intensity)
Used to adjust digital module’s display brightness.
Factory setting is maximum intensity.
1. Press and HOLD SETUP button for
FOUR seconds until
SS EE TT 33
is displayed.
2. Press and release TEST button on front
of alarm panel.
SS EE RR UU
will be displayed for one second and then current gas service identification. Select desired
gas service by pressing ! or " buttons.
3. Press and release TEST button.
OO FF F
F SS
will be displayed for one second and then current display offset. Select offset by pressing ! or " buttons.
4. Press and release TEST button.
RR EE PP TT
will be displayed for one second and then current audible alarm repeat time. Select desired repeat time by pressing ! or " buttons.
5. Press and release TEST button.
II NN TT SS
will be displayed. Select desired display brightness by pressing ! or " buttons. Each push will change brightness of display. Audible alarm will chirp one time with each push and two times when limit reached.
6. Press and release TEST button to save changes.
DD OO NN EE
will be displayed for
two seconds.
Page 70
68
6-847718-00 Rev. B00
Set-Up Procedures (Cont.)
Digital Display Module-Advanced
(Cont.)
7. Digital display module will return to monitoring mode.
NOTE:
If module is idle for more than one minute dur­ing set-up procedure, module will chirp three times, return to monitoring mode and will default to previous settings. No changes to settings will be saved.
Set-up must be completed and module must
display
DD OO NN EE
in order for changes to be saved.
Operation
Page 71
69
6-847718-00 Rev. B00
Set-Up Procedures (Cont.)
Multi-Signal Module
Changing signal options:
1. Loosen two screws on front of alarm panel. Hinge open front cover.
2. Locate SETUP button on circuit board of multi-signal module to be adjusted (Figure 48).
3. Press and release SETUP button. Audible alarm will chirp and both green and red indicators for top location (Signal 1) will illuminate.
4. Using either ! or " buttons, enable or disable Signal 1 location. When red indicator is illuminated, location is ENABLED. Turning off red indicator disables location. Signal locations can not be disabled if wired to a closed­contact circuit.
5. Press and release TEST button on front of alarm panel. Both green and red indicators for second location (Signal 2) will be illuminated.
6. Using either ! or " buttons, enable or disable Signal 2 location. When red LED is illuminated, location is enabled. Turning off red LED disables location.
7. Repeat steps 5 and 6 above for remaining signal locations (Signal 3, 4, and 5).
8. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence has been reached.
9. Multi-signal module will return to monitoring mode.
NOTE:
If module is idle for more than one minute during set-up procedure, module will chirp three times, return to monitor mode and will default to previ­ous settings. No changes to settings will be saved.
Set-up must be completed in order for changes to be saved.
Multi-Signal Module Board
SETUP
button
NOTE:
Audible alarm will chirp with each button push.
TEST
button
Up and down
buttons
Signal 1
Signal 2
Signal 3
Signal 4
Signal 5
Status LEDs
Figure 49: Multi-Signal Module LEDs
Figure 48: Digital Display Programming Buttons
Page 72
Two additional levels of “advanced” set-up features are available. The first level is used to adjust basic communication related parameters. The second level is used to adjust alarm repeat time and display intensity.
Setting Communication Parameters:
A network address uniquely identifies each alarm module in the alarm panel. Address range is 0 to 255.
Network address is shown as a binary number on specific red and green front panel LEDs. A numeric value is assigned to each LED (Figure 50)
For example, if LEDs for bits 1 and 2 were illuminated, network address would be 6 (2 + 4 = 6).
1. Press and HOLD set-up button. Audible alarm will chirp when set-up button is first pushed and again two seconds later. Release button after second audible alarm chirp.
2. Multi-signal alarm module front panel LEDs will show current network address. If no LEDs are illuminated, address is 0.
2. Using either ! or " buttons, select desired network address between 0 and 255.
3. Press and release TEST button on front of alarm panel. Front panel LEDs (Bit 0 and Bit 4) will show current communication baud rate. If only Bit 4 LED is illuminated, baud rate is 4800. If BOTH Bit 0 and Bit 4 LEDs are illuminated, baud rate is 9600.
Baud rate must be set to 9600 for TotalAlert 2 alarm panels.
4. Using either ! or " buttons, select desired baud rate (4800 or 9600).
5 Press and release TEST button on front
of alarm panel. Front panel LEDs (Bit 1 and Bit 5) will show current communication data format. If only Bit 5 LED is illuminated, data format is 8­bit word length (factory setting). If BOTH Bit 1 and Bit 5 LEDs are illuminated, data format is 16-bit word length.
6. Using either ! or " buttons, select desired data format (8-bit or 16-bit).
7. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence has been reached.
8. Multi-signal module will return to monitoring mode.
NOTE:
If module is idle for more than one minute during set-up procedure, module will chirp three times, return to monitoring mode and will default to pre­vious settings. No changes to settings will be saved.
Set-up must be completed in order for changes to be saved.
70
6-847718-00 Rev. B00
Multi-Signal Module-Advanced
Set-Up Procedures (Cont.)
Operation
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Bit 4 (16)
Bit 0 (1)
Bit 1 (2)
Bit 2 (4)
Bit 3 (8)
Bit 5 (32)
Bit 6 (64)
Bit 7 (128)
Figure 50: Binary data represented by LEDs
Red LEDs
Green LEDs
CAUTION:
Communication parameters are factory set and should not be changed.
Page 73
71
6-847718-00 Rev. B00
Operation
Set-Up Procedures (Cont.)
Multi-Signal Module-Advanced (Cont.)
Setting Audible Alarm Repeat Time and Display Intensity:
Used to set time interval for reactivation of audible alarm after alarm MUTE button
has been pressed.
1. Press and HOLD SETUP button. Audible alarm will chirp when SETUP button is first pushed, again after two seconds and a third time after four seconds. Release button after third audible alarm chirp. Multi-signal module front panel LED indicators will show current audible alarm repeat time as shown below:
Indicator Illuminated Repeat Time
None OFF Signal 1 - red 1 Min. Signal 2 - red 5 Min. Signal 3 - red 15 Min. Signal 4 - red 30 Min. Signal 1 - green 1 Hr. Signal 2 - green 2 Hr. Signal 3 - green 8 Hr. Signal 4 - green 12 Hr. Signal 5 - green 24 Hr.
2. Using either ! or " buttons, select desired audible alarm repeat time.
3 Press and release TEST button on front
of alarm panel. All LED indicators will illuminate.
4. Select desired display brightness by pressing either ! or " buttons. Each push will increase or decrease brightness of display. Audible alarm will chirp one time with each button push and two times when limit is reached.
NOTE:
To comply with the requirements of the City of New York Department of Buildings; Materials and Equipment Acceptance Division (M.E.A.), set audible alarm repeat time to 30 minutes.
5. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence.
6. Multi-signal module will return to monitoring mode.
NOTE:
If module is idle for more than one minute dur­ing set-up procedure, module will chirp three times, return to monitoring mode and will default to previous settings. No changes to settings will be saved.
Set-up must be completed in order for changes to be saved.
Page 74
72
6-847718-00 Rev. B00
Equipment Required
• PC with an Ethernet connection
• PC with a web browser, such as Microsoft Internet Explorer
• Category 5 Ethernet cable (10BaseT) (if connecting through a switch or hub)
• Category 5 Ethernet crossover cable (if connecting PC directly to alarm)
Physical Connection
1a.Connect each device to an Ethernet
switch or hub using a Cat-5 Ethernet cable (Figures 53-55).
1b.For direct connection to a PC without
using a hub or switch, connect the device to the PC using a Cat-5 Ethernet crossover cable (Figure 52).
2. Verify the green LINK LED on the annunciator module illuminates (Figure 51).
NOTE:
It is best to use a switch instead of a hub because the devices communicate at 10 Mbits/s. A switch also improves network performance and keeps unnecessary traffic from being routed to the alarm.
CAUTION:
Have the facility’s Information Systems personnel set up the network interface. If the set up is done improperly, equipment may not perform properly.
CAUTION:
The information systems personnel should be notified before changing any of the network settings. Changing the settings could keep the equipment from working properly.
Link LED Indicates physical connection
10BaseT Ethernet Connector
Receive LED Indicates device is receiving packets
Transmit LED Indicates device is transmitting packets
Figure 51 Ethernet status LEDs
Set-Up Network Interface
Operation
Page 75
73
6-847718-00 Rev. B00
Operation
Addressing using DHCP (factory
default)
1. Upon power-up, the device will search
for a DHCP server. If a DHCP server is found, IP Address, subnet mask and gateway are automatically obtained.
2. If a DHCP server is not found, the fixed
IP configuration will be used:
3. The device will check for a DHCP
server every 3 minutes. If a DHCP server is found, fixed IP configuration will be discarded and the DHCP provided IP configuration will be used.
Addressing using fixed IP address
1. Upon power-up, the device will
immediately begin using the fixed IP configuration.
Connecting to the alarm
1. Start a web browser such as Microsoft
Internet Explorer.
2a.Enter the Device Name in the browser’s
address bar.
Device Name: TA2_XXXXX where XXXXX is the device serial number.
2b.Enter the Device’s IP address in the
browser’s address bar:
Example: http://192.168.1.100
NOTE:
To learn the IP address of a master or combo alarm, press and hold the TEST button on the front panel for 5 seconds. The IP address will be shown on the VFD.
Factory default fixed IP Configuration
IP Address: 192.168.1.100
Gateway: 192.168.1.1
Subnet Mask: 255.255.255.0
Set-Up Network Interface (Cont.)
NOTE:
Browsers can locate devices in the following three ways:
1. IP Address Example: http://192.168.1.100
2. Local name lookup using NetBIOS name service Example: http://TA2_12345
This method works on a LAN if NetBIOS name lookup is enabled.
3. DNS name lookup Example: http://www.yourfacility.com/TA2_12345
This method requires the device to be enrolled in the facility’s DNS server.
Page 76
74
6-847718-00 Rev. B00
Figure 53 Simple Unmanaged Network
Figure 52 Direct Connection
Set-Up Network Interface (Cont.)
Operation
Hub or Switch
Computer
Computer
Page 77
75
6-847718-00 Rev. B00
Operation
Figure 55 Complex Managed Network
Hub or Switch
Computer
Hub or Switch
Network Server
Hub or Switch
Hub or Switch
Computer
Network Server
Network Router
Figure 54 Simple Managed Network
Page 78
76
6-847718-00 Rev. B00
Operation
1. Start a web browser such as Microsoft Internet Explorer.
2a.Enter the Device Name in the browser’s
address bar.
Device Name: TA2_XXXXX where XXXXX is the device serial number.
2b.Enter the Device’s IP address in the
browser’s address bar:
Example: http://10.10.5.10
3. After you enter the device name or IP address, the alarm’s home page will be displayed (Figure 56).
Accessing the Web Page
Set-Up Using Web Pages
NOTE:
To learn the IP address of a master or combo alarm, press and hold the TEST button on the front panel for 5 seconds. The IP address will be shown on the VFD.
NOTE:
To learn the serial number of the alarm, cycle the power on the alarm panel. The serial number will be shown on the VFD during the bootup sequence:
The serial number can also be found on a label inside the alarm panel. Open the front panel and locate the bar code label on the annunciator module.
Version: 1.0.0 SN 12345
NOTE:
To learn the name of a master or combo alarm, cycle the power on the alarm panel. The name will be shown on the VFD during the bootup
sequence:
Browse at: http:// TA2_12345
Figure 56: Typical alarm panel home page
NOTE:
If you rename the alarm panel, you can still use the factory programmed device name to access the alarm home page.
Page 79
77
6-847718-00 Rev. B00
Operation
1. Click Log in and Setup or Login on the
left pane.
2. The web browser will request a
username and password (Figure 57).
3. The factory defaults are:
Username: new
Password: new
4. The left sidebar will now contain the
setup links (Figure 58)
NOTE:
Logging in applies only to the computer on which the login occurs. If more than one PC is being used to access the alarm web pages, each one must be logged in individually. The computer stays logged in until the user closes the browser.
Login in to Setup Pages
Set-Up Using Web Pages (Cont.)
Figure 58: Logged in
WARNING:
Change the factory programmed password after the first time you log in. Otherwise, inappropriate personnel may change settings which could endanger patient welfare. Refer to Administer Users on page 91.
Figure 57: Login Dialog
Page 80
78
6-847718-00 Rev. B00
Operation
Each TotalAlert 2 alarm panel keeps a list of up to 75 other devices on the medical gas network.
1. Click on Enroll Devices
to access the
Enroll Devices Setup page (Figure 59).
2. Click on an unused Device # link to enroll a new device.
3. Enter the device IP address and Device Serial Number then click Submit (Figure 60).
4. The Enroll/Delete Device Complete page will be displayed (Figure 61).
5. Click Return to Enroll Devices
to return
the the Enroll Device Setup page.
Enroll Devices
Set-Up Using Web Pages (Cont.)
Figure 59: Enroll Device Setup
NOTE:
The factory default settings will cause all devices on the same subnet to be automatically discovered. Enroll Devices is only necessary if the alarm network is spread across multiple subnets.
NOTE:
Device # links are disabled for automatically enrolled devices.
NOTE:
Fixed IP addresses should be used for manually enrolled devices. If a manually enrolled device’s IP address changed, the entry in the device list is NOT automatically updated.
Page 81
79
6-847718-00 Rev. B00
Operation
Enroll Devices (Cont.)
Set-Up Using Web Pages (Cont.)
Figure 61: Enroll/Delete Device Complete
Figure 60: Enroll/Delete Device
Page 82
80
6-847718-00 Rev. B00
Setup Alarm Messages
Set-Up Using Web Pages (Cont.)
This setup page is used to configure switched alarm signals.
1. Click Setup Alarm Messages to access the Alarm Message Setup page (Figure 62).
2. Click on the Alarm Input link for the signal to set up.
3. The Signal Setup - Step 1 page will be displayed (Figure 63).
4. Select the gas type from the drop-down menu then click Next.
NOTE:
If a custom gas type is required, select Custom from the Gas Type drop-down menu.
NOTE:
Before setting up signals, fill out Master Alarm Signal Input Data table on page 138.
Figure 62: Alarm Message Setup
NOTE:
These settings can be transferred from one TotalAlert 2 master or combo alarms to another master or combo alarm. Refer to Transfer Setup on page 98.
Operation
Page 83
81
6-847718-00 Rev. B00
Setup Alarm Messages (Cont.)
Set-Up Using Web Pages (Cont.)
Operation
Figure 65: Signal Setup - Step 2
Figure 64: Signal Setup - Custom Gas Type
Figure 63: Signal Setup - Step 1
Page 84
82
6-847718-00 Rev. B00
Draft 29 June 2007
5. If Custom gas type was selected, enter the custom gas type and click next (Figure 64).
6. The Signal Setup - Step 2 page will be displayed (Figure 65).
7. Select the Message for the alarm input from the drop-down menu.
8. Select the LED number for the alarm input (Refer to Figure 66).
9. Enter the Location then click Next.
10.If Custom Message was selected, enter the custom message and click Next (Figure 67).
11. The Signal setup Summary page will be displayed (Figure 68).
12.To return to the Alarm Message Setup page click on the Return to
Alarm
Message Setup link.
NOTE:
Only one type of gas can be assigned to each LED. After an LED has been assigned to a type of gas, that LED number is available only for that particular type of gas.
NOTE:
If a custom message is required, select Custom Message from the Message drop-down menu.
Setup Alarm Messages (Cont.)
Set-Up Using Web Pages (Cont.)
Figure 66: LED Numbering
1 2 3 4 5
6 7 8 9
10
1 2 3 4 5
1 2 3 4 5
6 7 8 9
10
Master Alarm
Small Combo Alarm
Large Combo Alarm
Operation
Page 85
83
6-847718-00 Rev. B00
Setup Alarm Messages (Cont.)
Set-Up Using Web Pages (Cont.)
Figure 68: Signal Setup - Summary
Operation
Figure 67: Signal Setup - Custom Message
Page 86
84
6-847718-00 Rev. B00
Setup Area Alarms
Set-Up Using Web Pages (Cont.)
Operation
This setup page is used to configure area alarm locations.
1. Click Setup Area Alarms to access the Area Alarm Setup page (Figure 69).
2. Click on the Module # link for the digital display module to set up.
3. The Area Alarm Setup - Step 1 page will be displayed (Figure 70).
4. Enter the location then click Next.
5. The Area Alarm Setup - Summary page will be displayed (Figure 71).
6. To return to the Area Alarm Setup page click on the Return to
Area Alarm Setup
link.
Figure 69: Area Alarm Setup
Page 87
85
6-847718-00 Rev. B00
Setup Area Alarms (Cont.)
Set-Up Using Web Pages (Cont.)
Figure 71: Area Alarm Setup - Summary
Operation
Figure 70: Area Alarm Setup - Step 1
Page 88
86
6-847718-00 Rev. B00
Operation
Setup Device
Set-Up Using Web Pages (Cont.)
This setup page is used to configure alarm panel name, location, N2 address, facility description and contact information.
1. Click Setup Device
to access the Setup
Device page (Figure 72).
2. Enter the new device name.
To access the web pages by using the name you have given it, NetBIOS Name Service over TCP/IP must be enabled on your computer (See Set-Up Network Interface on page 72).
• Without the NetBIOS Name Service
enabled, the device must be accessed by using its IP address.
• To learn a master or combo alarm’s
IP address, press and hold the TEST button for 5s.
3. Enter the Location.
4. If the device will be connected to a Johnson Controls Metasys® building automation system, select the N2 address.
5. Enter the Facility Description.
6. Enter the Contact Information.
7. Click the Submit button.
8. The Device Setup Accepted page will be displayed (Figure 73).
NOTE:
The information in these fields identify the alarm panel that generated an alarm or an event. This information is displayed on the event log and on electronic notification messages.
Page 89
87
6-847718-00 Rev. B00
Operation
Figure 73: Device Setup Accepted
Figure 72: Setup Device
Setup Device (Cont.)
Set-Up Using Web Pages (Cont.)
Page 90
88
6-847718-00 Rev. B00
Electronic Notification
Set-Up Using Web Pages (Cont.)
This setup page is used to configure elec­tronic notification (email, pager, phone text message). The device acts as an SMTP client. An SMTP server is required for electronic notification to function.
1. Click Electronic Notification
to access the Electronic notification page (Figure 74).
2. Enter up to five email addresses then click Submit.
3. The Email Setup Accepted page will be displayed (Figure 75).
NOTE:
Email address 1 is also used as the email sender.
NOTE:
Refer to your mobile device provider for text message email address format.
Figure 75: Email Setup Accepted
Operation
Figure 74: Electronic Notification
Page 91
89
6-847718-00 Rev. B00
Electronic Notification - Server Setup
Set-Up Using Web Pages (Cont.)
1. Click Electronic Notification to access
the Electronic notification page (Figure 74).
2. Click on the link to set up email server
(Figure 76).
3. Enter the SMTP server name or IP
address then click Submit.
4. The Email Server Setup Accepted page
will be displayed (Figure 77).
NOTE:
Obtain the SMTP server name or IP address from the facility’s Information Systems department.
Figure 77: Email Server Setup Accepted
NOTE:
SMTP Server Address has priority over the SMTP Server Name. To use the SMTP Server Name, leave the SMTP Server Address blank.
Operation
Figure 76: Email Server Setup
Page 92
90
6-847718-00 Rev. B00
Set Clock
Set-Up Using Web Pages (Cont.)
1. Click Set Clock to access the Set Clock page (Figure 78).
2. Select the current time and date from the drop-down menus.
3. Click the check box if time information should be displayed in 12 hour format.
4. Click Submit.
5. The Set Clock Accepted page will be displayed (Figure 79).
NOTE:
Clock setup uses 24 hour clock format.
Figure 79: Set Clock Accepted
NOTE:
The clock is used to date/time stamp web pages and event log entries.
Operation
Figure 78: Set Clock
Page 93
91
6-847718-00 Rev. B00
1. Click on Administer Users to access the
User Administration page (Figure 80).
2. Enter user names and passwords then
click Submit.
3. The User Setup Accepted page will be
displayed (Figure 81).
Administer Users
Set-Up Using Web Pages (Cont.)
WARNING:
Change the factory programmed password after the first time you log in. Otherwise, inappropriate personnel may change settings which could endanger patient welfare.
NOTE:
For security reasons, only User 1 has access to change user names and passwords.
NOTE:
User names and passwords are case sensitive.
NOTE:
If you forget your username or password, they can be reset to factory defaults. For master and combo alarms, refer to Reset Users on page 59. For area alarms, refer to Reset Users and IP Configuration on page 61.
Figure 81: User Setup Accepted
Operation
Figure 80: User Administration
Page 94
92
6-847718-00 Rev. B00
Setup Network
Set-Up Using Web Pages (Cont.)
1. Click Setup Network to access the Network Setup page (Figure 82).
The current IP configuration is shown under Current Settings.
2. Select the IP Addressing mode.
3. If Use fixed IP address is selected, enter the Fixed IP address, Fixed subnet mask and Fixed gateway.
4. To disable automatic discovery broadcasts, uncheck the Automatic Discovery check box.
5. Click Apply to save the new settings.
6. The Network Setup Accepted page will be displayed (Figure 83).
Figure 82: Network Setup
Operation
NOTE:
To learn more about the network settings, refer to Set up Network Interface on page 72.
CAUTION:
The Information Systems personnel should be notified before changing any of the network set­tings. Changing the settings could keep the equipment from working properly.
Page 95
93
6-847718-00 Rev. B00
Setup Network (Cont.)
Set-Up Using Web Pages (Cont.)
Operation
Figure 83: Network Setup Accepted
Page 96
Clear Network clears and refreshes the device list memory for all devices on the alarm network.
1. Click Clear Network
to access the Clear
Network page (Figure 84).
2. Click Clear Network.
3. The confirm clear network dialog will be displayed (Figure 85).
4. Click OK to clear the network.
5. The Clear Network Accepted page will display (Figure 86)
94
6-847718-00 Rev. B00
Clear Network
Set-Up Using Web Pages (Cont.)
Operation
NOTE:
Clear network only refreshes devices on the same subnet as the device that issued the clear network command. Manually enrolled devices are not refreshed by clear network.
Figure 85: Confirm Clear Network
Figure 84: Clear Network
Page 97
95
6-847718-00 Rev. B00
Figure 86: Clear Network Accepted
Operation
Page 98
96
6-847718-00 Rev. B00
Clear Event Log
Set-Up Using Web Pages (Cont.)
1. Click Clear Event Log to access the Clear Event Log page (Figure 87).
2. Click Clear Event Log.
3. The confirm clear event log dialog will be displayed (Figure 88).
4. Click OK to clear the event log.
5. The Event Log page will display (Figure 89)
Figure 88: Confirm Clear Event Log
CAUTION:
Be sure to save the event log prior to clearing it. It is impossible to recover the event log after it is cleared.
Operation
Figure 87: Clear Event Log
Page 99
97
6-847718-00 Rev. B00
Operation
Figure 89: Event Log Cleared
Page 100
1. Click Transfer Setup to access the Transfer Setup page (Figure 90).
2. A list of compatible master alarms will be displayed.
3. Click on the link for the alarm that will receive the settings.
4. Click Transfer Setup to transfer the settings (Figure 91).
5. The Transfer Setup Complete page will be displayed (Figure 92)
98
6-847718-00 Rev. B00
Transfer Setup
Set-Up Using Web Pages (Cont.)
Operation
Figure 90: Transfer Setup List
Loading...