BeaconMedaes MEGA3 Installation, Operation And Maintenance Instructions

Page 1
Installation, Operation and Maintenance Instructions
Andersen Medical Gas 12 Place Lafifitte Madisonville, LA 70447 http://www.TheMedicalGas.com 1-866-288-3783
MEGA3 NFPA Medical Gas Notification System
Part number 4107 9016 59
Revision 03 August 27, 2015
Page 2
Page 3
Installation, Operation and Maintenance Manual
MEGA3 NFPA Medical Gas Notification System
This unit is purchased from:
Date purchased:
Model number:
Part number:
Option(s) included:
Any information, service or spare parts requests should be directed to:
BeaconMedæs 1800 Overview Drive Rock Hill, SC 29730
Telephone: (888) 463-3427 Fax: (803) 817-5750
BeaconMedæs reserves the right to make changes and improvements to update products sold previously without notice or obligation.
Part number 4107 9016 59
Revision 03 August 27, 2015
Page 4
Page 5
MEGA3 NFPA Medical Gas Notification System
Table of Contents
1.0 Introduction
1.1 Product Identification
1.2 User Interface Layout
1.2.1 MEGA3 Features
1.2.2 Master Alarm
1.2.3 Area Alarm
1.2.4 Combination Alarm
1.2.5 Boards
1.3 Definition of Statements
1.4 Definitions
1.5 Alarm Configurations
1.5.1 Master Alarms
1.5.2 Area Alarms
1.5.3 Gas Combination Alarms
1.6 MEGA3 Medical Gas Notification System Parent Model Number Chart
2.0 Installation Procedures
2.1 Alarm Panel Rough-In Box
2.2 Gas Sensor Installation
2.2.1 Local Sensors
2.2.2 Remotely Installed Sensors in Pipeline
2.2.3 Remotely Installed Sensors in Zone Valve Box
2.3 Wiring
2.3.1 General Requirements
2.3.2 Wire Type And Size
2.3.3 Determining Number Of Conductors
2.3.4 Power Supply
2.3.5 B60 Gas Input Board
2.3.6 B1X Signal Input Board
2.3.7 B4X Relay Output Board
2.3.8 B50 4-20mA Combination Board
2.3.9 General Fault Relay
2.3.10 Field Wiring Cable Shield Grounding
i
4107 9016 59.03
Page 6
MEGA3 NFPA Medical Gas Notification System
Table of Contents (continued)
2.4 Finish Assembly
2.4.1 Front Panel Mounting
2.4.2 Locally Installed Sensors
2.4.3 Remotely Installed Sensors in Pipeline
3.0 Wiring Schematics
3.1 NFPA Master Wiring Diagram
3.2 NFPA Area Wiring Diagram
3.3 NFPA Combination Wiring Diagram
4.0 Operation
4.1 Overview
4.1.1 Main Screen
4.1.2 Gas Badge
4.1.3 Source Signals
4.1.4 Toolbar
4.1.5 Fault Status
4.1.6 Display Screens
4.2 Alarm Configuration
4.3 Setting Up an Area Alarm
4.3.1 Configuring Gas ID Badges
4.3.2 Initial Setup of an Unconfigured Area Alarm
4.4 Setting Up a Master Alarm
4.4.1 Configuring Source Badges
4.4.2 Initial Setup of an Unconfigured Master Alarm
4.5 Setting Up a Combination Alarm
4.5.1 Configuring Source Badges
4.5.2 Configuring Gas ID Badges
4.5.3 Initial Setup of an Unconfigured Combination Alarm
4.5.4 Miscellaneous Tab 4 .6 Additional Components
4.6.1 4-20 mA Devices
4.6.2 Relay Output Board (B4X Board)
5.0 Retrofit
5.1 Retrofit of TotalAlert2 Area Alarm Panel (4-gas, 8-gas) and MEGA2 Alarms
5.1.1 Remove Components from Existing Alarm
5.1.2 Install New Power Supply
4107 9016 59.03
ii
Page 7
MEGA3 NFPA Medical Gas Notification System
5.1.3 Install New Components
5.1.4 Install Trim Plate
5.2 Retrofit of TotalAlert1 Alarm Panels
5.2.1 Remove Components from Existing Alarm
5.2.2 Install Gas-Specific Sensors (Area or Combination alarms only)
5.2.3 Install New Power Supply
5.2.4 Install New Components
5.2.5 Install Trim Plate
5.3 Retrofit of Other Alarm Panels
5.3.1 Remove Components from Existing Alarm
5.3.2 Determine Proper Placement of New Components
5.3.3 Install Gas-Specific Sensors (Area or Combination alarms only)
5.3.4 Install New Power Supply
5.3.5 Install I/O Modules
5.3.6 Install Trim Components
5.3.7 Install Front Panel
6.0 Maintenance
7.0 Troubleshooting
iii
4107 9016 59.03
Page 8
Page 9
MEGA3 NFPA Medical Gas Notification System
1.0 Introduction
1.1 Product Identification
Each alarm is identified by a Model number, Part number, and Lot Code.
Installation procedures vary depending on the alarm configuration.
The product ID label is located on the inside of the alarm back box (Figure 1).
1.2 User Interface Layout
Home Button
Mute Indicator LED
Power LED
Warning LED
Mute ButtonHorn
Figure 2: User Interface Layout
1.2.1 MEGA3 Features:
• 10.2” Touch Screen LCD display.
• Green alarm panel POWER LED indicator.
• Red alarm system WARNING LED indicator.
• Red alarm MUTE INDICATOR LED.
• Audible alarm horn
• Heartbeat LED to indicate proper operation on internal printed circuit boards and gas sensor assemblies.
Figure 1: Product Identification Labels
1.2.2 Master Alarm
Features:
Monitors up to 40 normally closed dry-con­tact switch signals.
• Forty gas service indicators for normal (green) or abnormal (red) conditions.
1-1
4107 9016 59.03
Page 10
MEGA3 NFPA Medical Gas Notification System
1.2.3 Area Alarm
Monitors up to 8 digital gas sensors.
Features:
• Digital pressure/vacuum read out with Low/Normal/High indicators
• Rough-in box capable of holding 8 locally mounted sensors.
• Customizable Gas ID labels with location
• General fault relay that activates on any pressure/vacuum fault condition
1.2.4 Combination Alarm
Monitors a mix of normally closed dry-con­tact switch signals, 6 digital gas pressure/ vacuum signals, and provides dry-contact relay outputs.
1.2.5 Boards
B06 Digital Gas Sensor Board
Features:
• Monitors the Pressure/Vacuum from the pipeline, and provides a gas-specific digi­tal signal for the alarm.
• Heartbeat indicator to indicate proper operation.
• Embedded in gas sensor assembly.
NOTE:
I = 4-20mA Inputs X = Source Signal Inputs Y = Dry-Contact Relay Outputs D = Digital Gas Sensor Inputs
B05 Power Supply Board
Features:
• Supplies 24VDC to all circuit boards in the alarm
Figure 4: B06 Digital Gas Sensor Board
B10, B11 NFPA Signal Input Board
Features:
• Monitors up to 20 normally closed dry­contact switch signals on each board
• Heartbeat indicator to signal proper op­eration.
Figure 3: B05 Power Board
4107 9016 59.03
Figure 5: B10, B11 Signal Input Board
1-2
Page 11
MEGA3 NFPA Medical Gas Notification System
B40, B41, B42, B43 Relay Output Board
Features:
• Provides 16 normally closed dry-contact relay outputs for external monitoring.
• Heartbeat indicator to indicate proper operation.
Figure 6: B40, B41, B42, B43 Relay Output Board
B50 4-20mA Combination Board
B60 Gas Input Board
Features:
• Monitors up to 8 Digital Gas Sensor Boards. One normally closed dry-contact relay output is available and opens when any fault occurs.
• Heartbeat indicator to signal proper op­eration.
Figure 8: B60 Gas Input Board
B65 Gas Combination 3D, 10X, 6Y Board
Features:
• Monitors up to 4 4-20mA inputs, 7 nor­mally closed dry-contact switch signals, and provides 6 normally closed dry-con­tact relay outputs for external monitoring.
• Heartbeat indicator to indicate proper operation.
Figure 7: B50 4-20 mA Combination Board
Features:
• 3 Gas Sensors, 10 inputs, 6 outputs
Figure 9: B65 Gas Combination 3D, 10X, 6Y Board
1-3
4107 9016 59.03
Page 12
MEGA3 NFPA Medical Gas Notification System
1.3 Definition of Statements
Statements in this manual preceded by the following words are of special significance.
WARNING: Means there is a possibility of injury or death to yourself or others.
CAUTION: Means there is a possibility of damage to unit or other property.
SHOCK HAZARD: Means there is a possibility of electric shock.
ATTENTION: Means precautions for han­dling electrostatic sensitive devices are to be observed.
NOTE: Indicates points of particular interest for more ecient and convenient operation.
1.4 Definitions
Address Resolution Protocol (ARP)
Protocol used by a device to learn the MAC address of another device so it can send an Ethernet packet.
Area Alarm Panel
Alarm panel that monitors medical gas and vacuum systems serving a specific area.
Combination Alarm Panel
Alarm panel that combines features of a mas­ter alarm panel and an area alarm panel.
4-20 mA
Input which monitors a two or three wire 4-20mA transducer.
Crossover Cable
Network cable that swaps transmit and re­ceive pairs so cable can be used to connect two computers or devices without the use of a hub or switch.
Domain Name Server (DNS)
A device that has a list of device names matched to IP addresses. Browsers use this resource to locate the IP address of a named device. NetBIOS name service provides this function on a local network.
Dry-Contact
Electrical contact isolated or unconnected from any electrical source.
Dynamic Host Configuration Protocol (DHCP)
A protocol used by a server to assign IP addresses to devices and computers.
Electromagnetic Compatibility (EMC)
Verification that a product meets required standards for emissions of and immunity from electromagnetic energy in its intended environment.
Ethernet
A standard high-speed network medium specified by IEEE standard 802.3.
4107 9016 59.03
1-4
Page 13
MEGA3 NFPA Medical Gas Notification System
Ethernet Switch
A device that connects many Ethernet devices together with optimization. Message destina­tions are examined and passed only to the correct device.
Firewall
A computer or computer software that pre­vents unauthorized access to private data from outside computer users.
Gateway
A computer or device that connects two com­puter networks together (such as a private network and the Internet).
General Fault Relay
Single-pole single-throw dry-contact relay output. Used to activate remote alarm or building management system. Relay will open whenever ANY audible alarm on panel is in progress. General Fault Relay will deac­tivate only after alarm condition is corrected and alarm panel resumes normal status.
HyperText Transfer Protocol (HTTP)
Protocol used to manage the request and transfer of web pages to a computer.
Internet Protocol (IP) Address
Unique number that identifies a device on a network.
LED
Light Emitting Diode
Local Sensors
Pressure / vacuum sensors mounted inside alarm panel back box. Sensor assembly must be piped to medical gas / vacuum pipelines.
Media Access Control (MAC) Address
A unique hardware address of a device on an Ethernet.
NetBIOS Name Service
Local method of addressing a device by name. This allows a web browser to reference a device by name instead of an IP address, such as 192.168.2.3.
Remote Sensors
Pressure / vacuum sensors mounted outside of alarm panel back box. Sensor assembly may be mounted separately or ganged to­gether near pressure / vacuum pipelines. Sensors must then be wired to alarm panel.
Simple Mail Transfer Protocol (SMTP)
Protocol for sending e-mail on a network.
Subnet Mask
A binary number used to separate the net­work portion from the host portion of a network address.
SMTP Client
Computer or device that uses SMTP to send e-mail by communicating with an SMTP server. The MEGA3 alarm panel acts as an SMTP client.
SMTP Server
Computer or device that uses SMTP to receive email from an SMTP client and then transfer it across the internet.
Transmission Control Protocol (TCP)
Protocol used to send data streams between two devices. TCP guarantees reliable and in order data from sender to receiver.
User Datagram Protocol (UDP)
Protocol used to send short messages be­tween computers. UDP does not guarantee reliable transmission (packets may be lost, duplicated or out of order), but is faster and more ecient than TCP.
Master Alarm Panel
Alarm panel that monitors medical gas and vacuum source equipment and main pipe­lines.
1-5
4107 9016 59.03
Page 14
MEGA3 NFPA Medical Gas Notification System
1.5 Alarm Configurations
All MEGA3 alarm panels are factory pre- con­figured. Configuration of alarm panel varies dependent upon customer’s requirements.
Three types of alarm panels are available.
• Master alarms
• Area alarms
• Combination alarms
1.5.1 Master Alarms
Master alarm panels include the following modular components:
• Signal input boards (B10, B11) that can accept 20 signals per board; maximum of 2 boards.
• Relay boards (B40, B41, B42, B43) that can be used to control 16 dry-contact sig­nals per board; maximum of 4 boards.
Master alarm panels can monitor 20 or 40 switched inputs.
1.5.2 Area Alarms
Area alarm panels include the following mod­ular components:
• Gas Sensor input board (B60) that can be used for up to 8 digital gas sensors.
• Digital gas sensor assembly, can be mounted locally in the rough-in box, re­motely on the gas pipeline, or in a com­patible BeaconMedæs Zone Valve Box. Maximum of 8 digital gas sensor assem­blies per area alarm panel.
Area alarm panels may be configured for 1 to 8 gas inputs. If alarm is configured with gas inputs, the sensors will be included for con­nection to pressure/vacuum pipeline.
Sensors may be located inside the alarm rough-in (local sensors) utilizing the DISS inlet tube assemblies provided for brazing to the hospital pipelines.
Copper tubes
connect to
pressure/vacuum
pipelines
Inputs can be assigned to any gas service indicators.
Model Number Scheme:
____ - ________ - __ -_____
Series - Configuration - Gas - Retrofit
See Model Number Chart in Section 1.6.
Example:
MEGA3 Master 40X 32Y Example Model Number: M3-M22
Figure 10: Master Alarm Front Panel
Sensor modules are
mounted inside alarm
panel box
Figure 11: Local Sensors
Sensors may be located outside the alarm rough-in (remote sensors) utilizing the DISS inlet tube assembly or by an 1/4”NPT port.
4107 9016 59.03
1-6
Page 15
MEGA3 NFPA Medical Gas Notification System
Copper tubes
connect to pressure/
vacuum pipelines
Sensor modules are mounted outside alarm rough-in
Figure 12: Remote Sensors
Model Number Scheme:
____ - ________ - __ -_____
1.5.3 Gas Combination Alarms
Gas Combination alarms include the follow­ing modular components:
• B1X, B60 or B65 boards
• 4-20 mA Combination - Can be added to any alarms (if room)
Combination alarms can monitor 30 switched inputs.
Optional dry contact relays are available for all signals.
Combination alarms can also monitor up to 6 digital gas sensors.
Model Number Scheme:
____ - ________ - __ -_____
Series - Configuration - Gas - Retrofit
See Model Number Chart Section 1.6.
Example:
MEGA3 Area OAV Example Model Number: M3-A10-OAV
Series - Configuration - Gas - Retrofit
See Model Number Chart on Section 1.6.
Example:
MEGA3 Combination 20X 16Y 8D OVOV Example Model Number: M3-C21-OVOV
Figure 13: Area Alarm Front Panel
Figure 14: Combination Alarm Front Panel
1-7
4107 9016 59.03
Page 16
MEGA3 NFPA Medical Gas Notification System
1.6 MEGA3 Medical Gas Notification System Parent Model Number Chart
M3 - ___ - _
B C
Variable B
Alarm Type and Size
Allowable Value Description
M01 Master, 0 Inputs, 16 Relay Outputs M10 Master, 20 Inputs M11 Master, 20 Inputs, 16 Relay Outputs M12 Master, 20 Inputs, 32 Relay Outputs M13 Master, 20 Inputs, 48 Relay Outputs M20 Master, 40 Inputs M21 Master, 40 Inputs, 16 Relay Outputs M22 Master, 40 Inputs, 32 Relay Outputs
A10 Area Alarm, Up to 8 Area Gases
C01
C10*
C11*
C12*
C40
C41*
C44*
Notes:
* Limitations on Combination Panels:
• C10, C11, C12 Combinations x 0-10 source signal Inputs used, Display up to 6 Area gases x 11-20 source signal Inputs used, Display up to 4 Area gases
• C41 x 0-20 source signal Inputs used, Display up to 4 4-20mA
devices
x 21-27 source signal Inputs used, Display up to two 4-20mA
devices
• C44 x Display up to 6 gas badges maximum, combination of
4-20mA and area gases, with maximum 4 4-20mA badges.
Combination, 10 Inputs, 6 Relay Out­puts, Up to 3 Area Gases
Combination, 20 Inputs, Up to 6 Area Gases
Combination, 20 Inputs, 16 Relay Outputs, Up to 6 Area Gases
Combination, 20 Inputs, 32 Relay Outputs, Up to 6 Area Gases
Combination, 7 Inputs, 6 Relay Out­puts, 4 Inputs for 4-20mA devices
Combination, 27 Inputs, 6 Relay Out­puts, 4 Inputs for 4-20mA devices
Combination, 7 Inputs, 6 Relay Out­puts, 4 Inputs for 4-20mA devices, Up to 6 Area Gases
Variable C
Gas Type (Area and Combination Only)
Allowable Value Description
O Oxygen
X Nitrous Oxide A Medical Air V Medical Vacuum
W WAGD
N Nitrogen C Carbon Dioxide (CO2) D Oxygen 100 psig
F Medical Air 100 psig
G Carbon Dioxide 100 psig
9 Instrument Air 1 CO2-O2 (CO2 over 7%) 2 O2-CO2 (CO2 not over 7%) 3 HE-O2 (HE over 80%) 4 O2-HE (HE not over 80%) 7 Laboratory Air 8 Laboratory Vacuum
H Helium
J Argon S Surgical Air B AGSS E N2O-O2
M Mixed Gas
NOTE:
Standard configurations listed above. For special configurations contact BeaconMed­aes Customer Service (888) 463-3427.
4107 9016 59.03
1-8
Page 17
MEGA3 NFPA Medical Gas Notification System
2.0 Installation Procedures
2.1 Alarm Panel Rough-In Box
The rough-in box can be installed between 16” on center standard studs. Mounting ears on either side of the rough-in box are provided for attachment to studs, with depth adjustment to accommodate dierent thick­nesses of wall board.
Knock out plugs are provided in the top and bottom of the box for routing of supply pow­er, Ethernet CAT5 cable, gas sensor tubes, or other necessary wiring.
DO NOT drill rough-in box.
1. Prepare rough wall opening large enough to accommodate alarm rough-in box. Alarm rough-in box must have rigid verti­cal members for support on both left and right sides. Power to alarm panel shall en­ter through bottom left or top left conduit hole in rough-in box.
2. Remove cardboard dust cover and DISS tube assemblies (if included) and insert alarm rough-in box into wall opening. [Secure with fasteners suitable for vertical supports (Figure 16)].
3. Mounting brackets on each side of rough­in box are adjustable and factory preset for 5/8” thick drywall. After drywall installation, front edge of rough-in box should be flush with finished surface of wall. If needed, make any necessary bracket adjustments at this time (Figure
16).
4. Reinstall cardboard dust cover to prevent dust and debris from entering the rough­in box.
13.50”
10”
4”
Figure 15: Alarm Panel Rough-In Box Dimensions
Loosen nuts to adjust rough-in box depth (same each side)
Figure 16: Mounting Bracket Adjustment
2-1
4107 9016 59.03
Page 18
MEGA3 NFPA Medical Gas Notification System
2.2 Gas Sensor Installation
2.2.1 Locally Installed Sensors
1. Locate copper adapter tube(s) packaged inside the alarm rough-in box.
2. Install tube(s) into the top of the rough­in box through the holes provided. Notice the Gas ID labels and position appropriately for connection to the hospital piping. Apply Gas ID label
provided with tube adapter to the inside of the rough-in box to identify the ports after walls are closed in.
3. Braze copper adapter tube(s) to appropriate pressure/vacuum piping system drops (Figure 17). Braze connections per procedures required by NFPA 99 or CAN/CSA-Z7396.1-12. Use appropriate measures to prevent overheating.
4. Install the Gas Specific DISS check valve into the appropriate tube adapter.
2.2.2 Remotely Installed Sensors in Pipeline
1. Sensors can be installed onto the hospital pipeline.
2. Braze copper adapter tube(s) to appropriate pressure/vacuum piping system connections (Figure 18).
3. Braze connections per procedures required by NFPA 99 or CAN/ CSA-Z7396.1-12
4. Use appropriate measures to prevent overheating.
5. Install the Gas Specific DISS check valve into the appropriate tube adapter.
6. Perform standing pressure test and cross connection tests as required by NFPA and CSA.
Connection should be made on top of pipe
REMOTE SENSOR
5. Perform standing pressure test and cross connection tests as required by NFPA and CSA.
Connection should be made on top of pipe
LOCAL SENSOR
Figure 18: Remote Pipeline Installation
2.2.3 Remotely Installed Sensors in Zone Valve Box
1. Remote sensors can be installed in a compatible BeaconMedæs Zone Valve Box. (NOTE: copper adapter tube not needed for Zone Valve box installation (Figure 19).
2. For Zone Valve Box mounting, an additional Installation Kit is required, part
number 4107 4016 25 for each sensor.
Figure 17: Sensor Pipeline Connection
4107 9016 59.03
2-2
Page 19
MEGA3 NFPA Medical Gas Notification System
2.3.2 Wire Type and Size
All low voltage wiring must meet the follow­ing criteria:
• Copper wire no smaller than 22 AWG, conductor insulation at least 0.010in (0.25mm), jacket insulation at least
0.030in (0.76mm), rated for 300V and 60°C (140°F) minimum.
• Circuit length not to exceed 5000 feet.
• Cable must be twisted-pair shielded type. Multi-pair cables within one common
Figure 19: Zone Valve Box Location
shield are acceptable.
2.3 Wiring
2.3.1 General Requirements
1. All alarms are to be powered from life safety branch of emergency power system as required by applicable standards.
2. Protect all wiring from physical damage by raceways or conduit as required by ap­plicable standards.
3. Wire alarm panels directly to switches or sensors as required by applicable stan­dards.
4. Wiring runs should be made with color coded wire. Record color, signal, and source of signal for each wiring lead to aid in connection of alarm finish compo­nents.
5. Avoid installing alarm panels near radio transmitters, electrical motors, or switch gear.
2.3.3 Determining Number of Conductors
The following rules along with references to this manual’s schematics clarify wiring requirements.
• Digital Gas Sensor Modules
Two conductor cables (must be twisted pair type with shield) are required for each Gas Sensor module to the Gas Input board.
Refer to NFPA Area Wiring Diagram (Section
3.2).
• Switched signal inputs
Two conductor cables (must be twisted pair type with shield) are required for each signal between the signal input terminals and the source signal switch.
These signals can originate at source equip­ment or from pressure switches mounted on main pressure / vacuum pipelines.
When two master alarms are required, the same switch / relay contacts can be wired to both alarm panels. (See CAUTION below).
Both pairs of wires should originate from switch/relay contacts.
2-3
4107 9016 59.03
Page 20
MEGA3 NFPA Medical Gas Notification System
Refer to NFPA Master/Combination Wiring Diagram (Section 3.1/3.3) for B1X, B50, B65
signal boards.
• Relay outputs
Two conductors are required for each signal between relay output terminals and remote device (such as a building automation sys­tem). Refer to the wiring requirements of the connecting device when selecting the ap­propriate type of conductors to use (i.e.. wire gauge, twisted or not, shielded or not.)
Refer to NFPA Master/Combination Wiring Diagram (Section 3.1/3.3) for B4X, B50, B65 signal boards.
2.3.4 Power Supply
A power supply assembly is provided with the alarm panel. The installer must use 18AWG copper supply wiring minimum with an insulation of not less than 1/32 inch (0.8mm) thick. Power supply shall be con­nected to a building installed circuit breaker. Circuit breaker shall be a maximum of 15 amps and marked as disconnecting means for the alarm panel. It is recommended that the circuit breaker be in close proximity to the alarm panel and properly selected according to local and national regulations.
CAUTION:
Do not connect MEGA3 master/combina­tion alarm to switch/relay contacts connect­ed to any alarm panels other than those listed below:
• TotalAlert Infinity
• TotalAlert 2
• MEGA3
• MEGA2
• MEGA
™
Holes are provided in the top and bottom of the rough-in box for main power (Figure 20).
If power is entering from the top, it must be routed under the cable raceway.
NO OTHER HOLES SHOULD BE PUNCHED OR USED.
Several additional holes or knockouts are pro­vided on the top panel and bottom for en­trance of low voltage field wiring (Figure 20).
Contractor to install UL rated strain relief or conduit connector
Cable Raceway
Power Supply Wire Entrance for power cable (alternate)
Figure 20: Wire Routing
NOTE:
All wiring shall be protected from physical damage by raceways or conduit in accordance with NFPA 70, National Electric Code.
Alarm panels require 100 to 250 VAC 0/60 Hz 250mA power. NFPA Area Wiring Diagram (Section 3.2).
4107 9016 59.03
2-4
Page 21
MEGA3 NFPA Medical Gas Notification System
For NFPA 99 compliance, alarm panel must be connected to life safety branch of the emergency electrical system.
1. Remove four screws from plastic power supply shield.
2. Remove plastic shield from power supply.
3. Connect incoming line and neutral wires to the terminal block. Ground wire con­nects directly to the rough-in box (chassis) at the green screw below the power sup­ply (Figure 21).
4. DO NOT remove or alter the Green facto­ry installed ground wire from the terminal block to chassis.
5. Reinstall plastic power supply shield while making sure all high voltage wires are contained within plastic shield.
6. Secure plastic shield with four screws.
2.3.5 B60 Gas Input Board
An Area alarm has 8 Gas Inputs. Signals are numbered D01 thru D08. There is a single relay output for general gas fault notification.
1. Identify each pair of twisted gas sensor wires inside the alarm rough-in box.
2. Route each pair of sensor wires as shown (Figure 23) to appropriate terminals.
3. Connect each pair of sensor wires to terminal blocks noting the correct polar­ity Red (+), Black (-). NFPA Area Wiring
Diagram (Section 3.2)
NOTE:
If gas sensor wires are landed on the terminal blocks in the same order as defined by the model number of the alarm panel, then initial setup will be easier and gas sensor channels will not need to be recon­figured.” Example T3-A10-OAV means “O” Oxygen is defaulted to D01, “A” Medical Air is defaulted to D02, etc. See Section 1.6.
Line Voltage Neutral
Ground
Figure 21: Supply Power Wiring
WARNING:
RISK OF ELECTRIC SHOCK
Disconnect power at the circuit breaker before removing power supply shield.
Holes provided for entrance of remote wiring
2-5
Figure 22: Remote Sensor Wire Routing
4107 9016 59.03
Page 22
MEGA3 NFPA Medical Gas Notification System
Figure 23: B60 Board Wire Routing
2.3.6 B1X Signal Board
A Master or Combination alarm panel can contain multiple signal input boards; up to a maximum of 2 boards or 40 signal inputs.
B10 and B11boards are labeled X01 thru X20.
Identify each twisted pair of field installed signal input signal wires inside the alarm rough-in box.
Route each pair of signal input signal wires as shown in Figure 24 to appropriate terminals on input board(s).
Connect each pair of signal wires to terminal blocks noting the correct polarity (+,-). Refer to NFPA Master/Combination Wiring Dia- gram (Section 3.1/3.3).
Figure 24: B1X Signal Board Wire Routing
CAUTION:
Do not connect MEGA3 master/combina­tion alarm to switch/relay contacts connect­ed to any alarm panels other than those listed below:
• TotalAlert Infinity
™
• TotalAlert2
• MEGA3
• MEGA2
• MEGA
CAUTION:
Source equipment signal wires must be connected to normally-closed, dry con­tacts. No electrical voltage can be present and contacts must be closed during normal equipment operation. When contacts open, an alarm condition will be activated.
4107 9016 59.03
2-6
Page 23
MEGA3 NFPA Medical Gas Notification System
NOTE:
Each pair of terminals labeled on the signal board connector is labeled “+” and “-”. Ensure that when a source equipment dry contact is wired to two master panels, the same side of the dry contact is connected to the same termi­nal at both panels. For example, if the source equipment’s normally closed contact is wired to the “+” of the first master panel, ensure it is also connected to the “+” terminal of the second master panel.
2.3.7 B4X Relay Output Board
A Master or Combination alarm can contain multiple relay output boards; up to a maxi­mum of 4 boards with 16 relay outputs each. The B4X boards (B40, B41, B42, B43) utilize normally closed dry contact relay outputs.
Figure 25: B4X Board Wire Routing
The outputs on the B4X boards are labeled Y01 through Y16.
Identify each pair of field installed relay output signal wires inside the alarm rough-in box. Route each pair of relay output wires as shown in Figure 25 to the appropriate termi­nals on the relay board. Connect each pair of signal wires to the terminal blocks, noting the correct polarity (+,-). Refer to NFPA Mas-
ter/Combination Wiring Diagram (Section
3.1/3.3).
2-7
4107 9016 59.03
Page 24
MEGA3 NFPA Medical Gas Notification System
2.3.8 B50 4-20mA Combination Board
A Combination alarm can contain a B50 board that contains four 4-20mA inputs that can be used with a 2 or 3 wire transmitter. The board also contains seven signal inputs, which monitor normally closed signal inputs, and six normally closed dry contact relay out­puts. Each alarm panel can have a maximum of one B50 board.
Identify each set of field installed 4-20mA input signal wires (2 or 3 wires per set) inside the alarm rough-in box. Route each set of in­put wires to the appropriate terminals on the B50 board. Connect each set of signal wires to the terminal blocks, noting the correct polarity (Figure 26).
2.3.9 General Fault Relay
The B60 Gas Input board is supplied with an alarm panel general fault output relay.
This relay has a set of dry contacts that is wired normally closed.
The relay will activate when ANY alarm on the ENTIRE alarm panel is activated. Relay will remain activated as long as alarm condi­tion is active, even if audible alarm is silenced by MUTE button.
When alarm condition is corrected, relay will deactivate. Relay contact ratings are 35A @ 30VDC / 3A @ 250VAC. Refer to NFPA Area
Wiring Diagram (Section 3.2).
2.3.10 Field Wiring Cable Shield Grounding
Figure 26: B50 Board Wire Routing
All field wiring cable shields must be ground­ed inside alarm panel rough-in box.
Holes are provided in the top and bottom of the alarm rough-in box for grounding screws (Figure 27).
Shields from several cables may be wrapped together and crimped into one screw (by oth­ers).
4107 9016 59.03
Grounding Holes Provided
Figure 27: Cable Shield Grounding-Area
2-8
Page 25
MEGA3 NFPA Medical Gas Notification System
CAUTION:
Keep shield wires to ground screw as short as possible so they can not touch front panel circuit boards when front panel is closed.
2.4 Finish Assembly
2.4.1 Front Panel Mounting
ATTENTION:
Observe Precautions for Handling
ELECTROSTATIC SENSITIVE DEVICES
Ground Lug
Figure 28: Front Panel Screws
1. Remove front panel assembly from pack­aging.
2. Remove front panel mounting screws from alarm panel rough-in box assembly (Fig­ures 28).
3. Remove lanyard mounting nut from alarm panel back box assembly (Figure 28).
4. Attach front panel to alarm panel rough­in box using screws removed in step 2 (Figure 29).
5. Attach lanyard to alarm panel back box using screws removed in step 3.
6. Remove nut from front panel grounding lug.
7. Install front panel grounding wire using nut removed in step 6.
8. Connect the grey cable on the front panel to the open power/communication port on the power supply.
Figure 29: Attach Front Panel and Lanyard
NOTE: Harness connector is keyed to prevent incorrect orientation. However, use care to ensure correct pin alignment.
2-9
4107 9016 59.03
Page 26
MEGA3 NFPA Medical Gas Notification System
2.4.2 Locally Installed Sensors
1. Remove sensor module from shipping carton.
2. Connect sensor with DISS fitting to the appropriate DISS check at the top of the rough-in box. Verify Gas ID labels match between the sensor and piping to ensure no cross connections occur. Repeat this process for all sensors within alarm panel.
3. Connect wires into input terminals of B60 board (See section 2.4.2).
2.4.3 Remotely Installed Sensors in Pipeline
1. Remove sensor from shipping carton.
2. Connect sensor with DISS fitting to the appropriate DISS Check on the hospital pipeline or BeaconMedæs Zone Valve box. Verify Gas ID labels match between the sensor and piping to ensure no cross con­nections occur.
3. Wire nut pigtail to field installed wiring. Note polarity of wiring and corresponding field wiring color or number for later (See section 2.3.5).
NOTE: Do not ground shield drain wire at sensor.
Figure 30: Local Sensor Mounting
NOTE:
If gas sensor wires are landed on the terminal blocks in the same order as defined by the model number of the alarm panel, then initial setup will be easier and gas sensor channels will not need to be reconfigured.” Example T3-A10-OAV means “O” Oxygen is defaulted to D01, “A” Medical Air is defaulted to D02, etc. See section 1.6.
4107 9016 59.03
Figure 31: Remote Sensor Module Connection
2-10
Page 27
MEGA3 NFPA Medical Gas Notification System
3.0 Wiring Schematics
3.1 NFPA Master Wiring Diagram
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD
Notes:
1. MAIN DISCONNECT PROVIDED BY OTHERS
2. FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM
3. FIELD SIGNAL WIRING TO BE MINIMUM 22AWG
TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM
RESISTANCE
EQUIPMENT OR LINE PRESSURE SWITCHES.
VERIFY USING TABLE 1.
ONLY.
4. -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX.
5. INPUTS FROM DRY NORMALLY-CLOSED CONTACTS FROM SOURCE
6. RELAY OUTPUT CONTACTS RATED 3A / 30VDC MAX.
7. SEE MODULE LABEL TO SET MODULE ADDRESS (POSITIONS 2,3, & 4).
8. SET ADDRESS SWT POSITION 1 TO “ON” FOR LAST MODULE IN CHAIN
3-1
FACTORY WIRED
CHASSIS GROUND
ENCLOSURE
GROUND SCREW
Figure 32: Wiring Diagram for NFPA MEGA3 Master Alarm
4107 9016 59.02
Page 28
MEGA3 NFPA Medical Gas Notification System
3.2 NFPA Area Wiring Diagram
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD
Notes:
1. MAIN DISCONNECT PROVIDED BY OTHERS
2. FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM
3. FIELD SIGNAL WIRING TO BE MINIMUM 22AWG
TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM RESIS-
TANCE
4. -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX.
5. SIGNAL INPUTS FROM GAS SENSOR MODULES.
6. RELAY OUTPUT CONTACT RATED 3A / 30VDC MAX.
USING TABLE 1.
7. SEE MODULE LABEL TO SET MODULE ADDRESS (POSITIONS 2,3, & 4). VERIFY
8. SET ADDRESS SWT POSITION 1 TO “ON” FOR LAST MODULE IN CHAIN ONLY.
FACTORY WIRED
CHASSIS GROUND
Figure 33: Wiring Diagram for NFPA MEGA3 Area Alarm
4107 9016 59.02
3-2
ENCLOSURE
GROUND SCREW
Page 29
MEGA3 NFPA Medical Gas Notification System
3.3 NFPA Combination Wiring Diagram
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD
TOTAL CIRCUIT LENGTH NOT TO EXCEED 10,000’ & MAX. 1K OHM RESIS-
TANCE
EQUIPMENT OR LINE PRESSURE SWITCHES.
USING TABLE 1.
INPUT OR OUTPUT MODULES, OR BOTH.
Notes:
1. MAIN DISCONNECT PROVIDED BY OTHERS
2. FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM
3. FIELD SIGNAL WIRING TO BE MINIMUM 22AWG
4. -- -- -- -- INDICATES FIELD WIRING OUTSIDE OF BOX.
5. SIGNAL INPUTS (UP TO 8) FROM GAS SENSOR MODULES.
6. SINGAL INPUTS FROM DRY NORMALLY-CLOSED CONTACTS FROM SOURCE
7. RELAY OUTPUT CONTACT RATED 3A / 30VDC MAX.
8. SEE MODULE LABEL TO SET MODULE ADDRESS (POSITIONS 2,3, & 4). VERIFY
9. SET ADDRESS SWT POSITION 1 TO “ON” FOR LAST MODULE IN CHAIN ONLY.
10. ALARMS ARE CONFIGURATION DEPENDENT: AND MAY CONTAIN EITHER
3-3
Figure 34: Wiring Diagram for NFPA MEGA3 Combination Alarm
FACTORY WIRED
CHASSIS GROUND
ENCLOSURE
GROUND SCREW
4107 9016 59.02
Page 30
Page 31
MEGA3 NFPA Medical Gas Notification System
4.0 Operation
4.1 Overview
The MEGA3 Medical Gas Alarm is a touch­screen gas pressure and system monitoring alarm created for ease of use.
For convenience, it is shipped from the fac­tory as a configured unit.
4.1.2 Gas Badge
Every gas monitored by the alarm will have a gas badge which will show the following information:
• Gas being monitored
• Location where gas is being used
• Gas pressure value
• Gas pressure status (Low, Normal, or High)
Figure 36: Gas Badge
Figure 35: MEGA3 Alarm Main Screen
4.1.1 Main Screen
The first screen that users see on a configured unit is the MAIN screen. The MAIN screen is the main view for the alarm and shows the pressure status of all of the gases (area) or source signals (master) the alarm is monitoring.
NOTE:
The main screen will appear dierent de­pending on whether the alarm panel is con­figured as an area, master or combination.
An area alarm main screen will show gas badges, a master alarm main screen will show source signals, and a combination alarm main screen will show both gas badges and source signals.
4.1.3 Source Signals
Every source signal monitored by the alarm will display the following information once configured:
• Equipment being monitored
• Location of the source equipment
• Signal being monitored
• Source signal status Red (open - in alarm) or Green (closed - normal).
The display can show the status of up to 40 signals. The hardware installed limits how many of the 40 signals can be used.
4-1
Figure 37: Source Signals
4107 9016 59.03
Page 32
MEGA3 NFPA Medical Gas Notification System
5. History button. This icon button toggles to the HISTORY screen. This screen is only available after upgrading to a TotalAlert Infinity™ series of alarms.
The button that corresponds to the screen currently in use will be blue.
4.1.5 Fault Status
If a gas sensor is measuring above or below
Figure 38: Combination Alarm Main Screen
4.1.4 Toolbar
Running from left to right across the bottom of the MAIN screen is the toolbar. The Normal toolbar is available when the alarm is operating in normal status and shows:
the alarm level, the high or low pressure in­dicator on the gas badge will flash for the gas pressure out of range.
If a gas sensor becomes disconnected or shorted, both high and low indicators for that gas will flash and an error code and mes­sage will be displayed.
Home
Alarm Status (normal)
Button Location of Panel
Figure 39: Normal Toolbar
To switch to the Icon toolbar, touch the HOME button.
Home Button Information Button
Alarm Button
Configuration Button
History Button
Figure 40: Icon Toolbar
Icons on the toolbar:
1. Home button. This icon button toggles to the MAIN screen.
2. Alarm button. This icon button toggles to the ACTIVE ALARM screen.
If a configured source signal becomes an open circuit and the source badge and the signal status will change from green to blink­ing red.
The Icon toolbar will appear, and the Alarm button will be flashing red. By default the screen will change to the Active Alarm Screen.
Alarm Button (Red)
Figure 41: Fault Status
NOTE:
The Normal toolbar will automatically reappear when all faults are resolved.
Users can touch any flashing red light to go to the ACTIVE ALARM screen.
3. Configuration button. This icon button toggles to the CONFIGURATION screen.
4. Information button. This icon button toggles to the INFORMATION screen.
4107 9016 59.03
4-2
Page 33
MEGA3 NFPA Medical Gas Notification System
4.1.6 Display Screens
Active Alarm Screen
The ACTIVE ALARM screen provides detailed information about pressures or signals that are in alarm condition.
Gas LocationGas Type Gas Pressure
Area Alarm
Master Alarm
Figure 42: Active Alarm Screen
Configuration Screen
The CONFIGURATION screen is used to con­figure the alarm. The configuration screen is only accessible with a password. It is divided into three parts.
The top left section is the Display section. It contains a small representative view of the MAIN screen and buttons for configuring the MAIN screen.
The top right section is the Settings section. Tabs not accessible are grayed out.
Information Screen
The INFORMATION screen provides pertinent information about the alarm — including high and low alarm values and firmware details — in one central place.
Figure 44: Information Screen
Version Tab
Touch the VERSION tab to view details about the:
• Series, code, and style of the alarm
• Firmware version for the main display board and additional boards
The bottom section is the Icon toolbar.
Display
Icon Toolbar
Figure 43: Configuration Screen
Settings
Figure 45: Version Tab
NOTE:
The version screens automatically scroll. Touch the blinking up or down arrow in the lower right to stop the automatic scroll and start the manual scroll.
4-3
4107 9016 59.03
Page 34
MEGA3 NFPA Medical Gas Notification System
Touch the X button in the upper right to close and return to the INFORMATION screen.
Alarm Points Tab
Touch the ALARM POINTS tab for a quick view of the alarm points—the low and high set points—for each gas badge (area alarm) or source signal configuration (master alarm).
Area Alarm
Test Alarm Tab
Touch the TEST ALARM tab to run a quick test of the hardware. The audible alarm will sound for one-to-two seconds to test that the horn is working prop­erly.
The LEDs on the front of the alarm will il­luminate as well to show that they are still functioning.
Warnings Tab
Touch the WARNINGS tab to view any pos­sible active warnings that would include lost network communication with manually en­rolled devices, lost connection to a connect­ed/initialized board, or when a master signal input is wired, but not assigned/programmed to an alarm sign.
Master Alarm
Figure 46: Alarm Points Tab
This screen provides a complete view of the configuration and is a fast way to check items such as:
• Location where the pressure sensors and source signals are physically wired.
• Gases Monitored
• Areas Monitored
• Low and high pressure set points for area signals
• Source Signals Monitored
Touch the X button in the upper right to close and return to the INFORMATION screen.
Figure 47: Warnings Tab
History Screen
NOTE:
This feature is only available in the TotalAlert Infinity™ series of alarms.
4107 9016 59.03
Figure 48: History Screen
4-4
Page 35
MEGA3 NFPA Medical Gas Notification System
4.2 Alarm Configuration
To set up or change the configuration of an alarm, start on the CONFIGURATION screen. Users are always prompted to enter the pass­word when accessing this screen.
Close
Clear all entered text
EnterBackspace
Figure 49: Password entry
Type the default password (121212), and touch the Enter button. You will be prompted to change the password if not done so previ­ously (Figure 49).
Figure 51: Normal Status Message screen
Figure 50: Configuration Screen
The CONFIGURATION screen displays.
Normal Status Message/Panel ID Descrip­tion
The MEGA3 alarm allows for customization of certain labels and messages.
Normal Status Message
To change the message that is communicated when the alarm is operating in normal status:
1. Touch the [A] button that is located to the left of the configuration screen (Figure 50).
2. Touch the Erase button on the keyboard to delete the existing message (Figure 51).
3. Enter the new word or message.
4. Touch the Save button.
4-5
4107 9016 59.03
Page 36
MEGA3 NFPA Medical Gas Notification System
Figure 52: Panel ID Description screen
Panel ID Description
Figure 53: Area Alarm User Interface
To change the description of the location of the alarm panel:
1. Touch the [B] button that is located to the right of the configuration screen (Figure
50).
2. Touch the Erase button on the keyboard to delete the existing description (Figure
52).
3. Enter the new description.
4. Touch the Save button.
4.3 Setting Up an Area Alarm
4.3.1 Configuring Gas Badges
The MEGA3 area alarm is designed to allow configuration of eight gas badges using the B60 board.
To configure the first badge to custom set­tings, touch the [1] button on the configura­tion screen (Figure 50).
4107 9016 59.03
4-6
Page 37
MEGA3 NFPA Medical Gas Notification System
Eight tabs are used for configuration (Figure 54). Tabs are listed in alphabetical order.
A = [GAS INPUT] B = GAS DESC C = [GAS NAME] D = AREA MONITORED E = [UNITS OF MEASURE] F = LOW ALARM SETTINGS G = HIGH ALARM SETTINGS H = ZERO OFFSET
To change which wired input should be shown on the badge To change color codes based on standard and country To label the gas To edit the location label for a specific gas To change the displayed unit of measure for the pressure/vacuum To adjust the value that should indicate that the pressure is low To adjust the value that should indicate that the pressure is high To make small adjustments to the displayed pressure based on user
preference
B = Gas Desc Tab
Figure 54: Configuring Gas Badges
A = [Gas Input] Tab
Figure 55: Gas Input Tab
To change which wired sensor should be dis­played on that badge:
1. Touch the tab for the appropriate wired gas sensor.
Figure 56: Gas Desc Tab
To change color codes based on your stan­dard and country:
1. Scroll through the codes using the right and left arrows at the bottom of the screen.
2. Touch the tab for the appropriate code.
3. Touch the Save button when you see a check beside your selection.
Note: If the alarm default is correct, touch the X button in the upper right to close the screen.
2. Touch the Save button to close the screen.
4-7
4107 9016 59.03
Page 38
MEGA3 NFPA Medical Gas Notification System
C = [Gas Name] Tab
Figure 57: Gas Name Tab
Use the keyboard to change the gas name. Touch the [<ÁÑ] to toggle to symbols and ex­tended Latin Characters. Touch the [1AZ] key to toggle back to letters and numbers.
D = Area Monitored Tab
E = [Units of Measure] Tab
Figure 59: Units of Measure Tab
To change the unit of measure:
1. Touch the tab for the appropriate unit of measure.
2. Touch the Save button to close the screen.
F = Low Alarm Settings Tab
Figure 58: Area Monitored Tab
To add locations to be monitored:
1. Touch an unused location tab.
2. Using the keyboard, enter the name of the location that you would like to monitor (e.g., ROOM 1). Enter multiple locations as needed (e.g., Room 1, Room 2, Room
5).
3. A check appears when the location is se­lected, the save button has to be pressed if the selection is new.
To edit the location information, touch the Pencil button.
4107 9016 59.03
Figure 60: Low Alarm Settings Tab
You can remove the low alarm set point or customize the low alarm set point.
To remove the low alarm set point:
1. Touch the NONE tab.
2. Touch the check on the CONFIRM SET­TINGS CHANGE screen.
To customize the low alarm set point:
1. Touch the ADJUST tab.
2. Enter the new set point.
3. Touch the Save button.
4-8
Page 39
MEGA3 NFPA Medical Gas Notification System
G = High Alarm Settings Tab
Figure 61: High Alarm Settings Tab
You can remove the high alarm set point or customize the high alarm set point.
To remove the high alarm set point:
1. Touch the NONE tab.
2. Touch the check on the CONFIRM SET­TINGS CHANGE screen.
To customize the high alarm set point:
H = Zero Oset Tab
Figure 62: Zero Oset Tab
In some cases, facility dial gauges may show slightly dierent readings than the MEGA3 alarm (e.g., 46 PSI versus 44 PSI). To match the MEGA3 alarm exactly to a facility dial gauge:
1. Select the oset amount.
2. Touch the Save button to close the screen.
1. Touch the ADJUST tab.
2. Enter the new set point.
3. Touch the Save button.
Configuring Additional Gas Badges
Configure additional gas badges by touching the number on the main configuration screen that corresponds with the gas badge and repeating the steps listed above.
4-9
4107 9016 59.03
Page 40
MEGA3 NFPA Medical Gas Notification System
4.3.2 Initial Setup for an Unconfig­ured Area Alarm
The SETUP INFORMATION screen is the first screen that users will see on an unconfigured alarm. (The MAIN screen is the first screen that users will see on a configured alarm.)
Password Setup - Unconfigured Alarm
• Touch the Configuration button.
Configuration Button
Figure 63: Setup Information Screen
Entering the Password
Note:
If you would like to change the password, touch Change Password. Enter a 4-10 digit password, and touch the Enter button. Con­firm the new password. Touch the X button in the upper right to close the SECURITY PASSWORD screen.
Figure 65: Changing the Security Password
• The CONFIGURATION screen will display as unconfigured and ready for setup.
The ENTER SECURITY PASSWORD screen ap­pears.
Figure 64: Entering the Security Password
• Enter the security password. (The default password is 121212.)
• Touch the Enter button.
• Touch Continue to advance to the CONFIGURATION screen.
Figure 66: Unconfigured Configuration Screen
4107 9016 59.03
4-10
Page 41
MEGA3 NFPA Medical Gas Notification System
Primary Settings Tab
The PRIMARY SETTINGS tab allows you to select the alarm type, initialize boards, and select gas inputs.
• Touch the PRIMARY SETTINGS tab
Alarm Type Tab
The ALARM TYPE screen defines which type of alarm will be displayed and drives later setup functions.
Initialize Modules Tab
The PRIMARY SETTINGS screen will now display with ALARM TYPE checked, INITIALIZE MODULES active, and the other tabs grayed out.
Figure 69: Initialize Modules Tab
• Touch the INITIALIZE MODULES tab. The INITIALIZE MODULES screen is used to set up the boards that are installed. The boards function as the input/output hardware of the alarm.
Figure 67: Alarm Type Tab
• Touch the ALARM TYPE tab.
• Choose a code style based on code re­quirements.
Save Erase
Figure 68: Choosing Code and Alarm Styles
• Touch the AREA tab
• Touch the Save button when you see checks beside your selections to save the settings and return to the PRIMARY SET­TINGS screen.
Note: To clear your selections, touch the Erase button.
Figure 70: Initialize Modules Screen
4-11
4107 9016 59.03
Page 42
MEGA3 NFPA Medical Gas Notification System
At this point, you have two options:
1. Either touch the Scan button to prompt the alarm to autofill the screen for you.
OR
2. Complete the screen by selecting the boards installed in the alarm.
Figure 71: B60 board selected
Note:
• Touch the GAS SENSORS tab.
Figure 73: Gas Input Screen
Users may select up to eight dierent gases on the GAS INPUT screen. These gases cor­respond to the digital gas sensors wired into the GAS INPUT / B60 board (see section
2.4.2).
• To select the first gas, touch the D01 = NONE/BLANK tab.
THE GAS INPUT / B60 board must be select­ed during the configuration of an area alarm.
• Touch the Save button when you see checks beside your selections.
Gas Sensors Tab
The PRIMARY SETTINGS screen will now dis­play with ALARM TYPE and INITIALIZE MOD­ULES checked, GAS SENSORS active, and the last tab grayed out.
Figure 74: Gas Sensors Screen
• Touch the right and left arrows at the bottom of the screen to scroll through additional gas choices, including options to create custom mixes. Select the gas that is wired into the D01 input on the GAS INPUT / B60 board.
Figure 72: Gas Sensors Tab
4107 9016 59.03
4-12
Page 43
MEGA3 NFPA Medical Gas Notification System
4.4 Setting Up a Master Alarm
The master alarm monitors whether source equipment is working properly. Two indepen­dent hard wired alarms are required per facil­ity to meet the 24-hour monitoring require­ment in the NFPA 99 standard.
The information for the signals connected in the field needs to be entered into the alarm using the touch screen interface.
Figure 75: Gas Choices
• Touch the Save button when you see a check beside your selection.
• (If an alarm sounds, press the Mute but­ton on the panel under the screen and continue with setup.)
• Repeat to add additional gases.
• Touch the X button in the upper right to close the GAS SENSORS screen and return to the PRIMARY SETTINGS screen. The alarm will retain your information.
• Touch the X button in the upper right to close the PRIMARY SETTINGS screen. The alarm will retain your information.
Figure 76: Master Alarm User Interface
To set up or change the configuration of an alarm, follow the steps outlined in the initial set-up for an unconfigured master alarm in section 4.4.
4-13
4107 9016 59.03
Page 44
MEGA3 NFPA Medical Gas Notification System
4.4.1 Configuring Source Badges
The MEGA3 alarm is designed to allow the setup and monitoring of 4 source badges. Each source badge has room for 10 source signal inputs (A-K) (Figure 78). Four tabs are used for the detailed con­figuration of each source signal input.
Note:
Maximum wired input signals allowed is 40.
1 = ALARM POINT
2 = GAS MONITORED
3 = SIGNAL SETTINGS
4 = LOCATION
To identify the location where the wires are landed
To choose the gas to be monitored
To select source signal description
To add a location for the source signal
The four tabs for each source signal input are grouped together and named alphabetically (e.g., A1, A2, A3, A4 / B1, B2, B3, B4 / C1, C2, C3, C4 / etc.).
Users can scroll to the first tab for each source signal input by using the right and left ar­rows at the bottom of the screen. Or, to jump quickly to the first tab, simply touch the letter button on the grid on the left that corresponds to the source signal input (A-K) (Figure 78).
Figure 77: Configuration Screen
To configure alarm points in the first badge, touch the [1] button in the numeric display.
Tabs used for configuration of source signal input A
Source
signal
inputs
Figure 78: Configuration of alarm points
The first tab for each source signal input is highlighted and the remainder grayed out to ensure that users complete the setup in the correct order. The other three tabs will become available to you as you advance through setup.
4107 9016 59.03
4-14
Page 45
MEGA3 NFPA Medical Gas Notification System
A1 = Alarm Point Tab
Figure 79: Alarm Point Tab
To identify the location where the wires are landed:
1. Touch the tab for the appropriate board and terminal block. Ex: B10 board, X01 Terminal Block
2. Touch the Save button when you see a check beside your selection to go auto­matically to the GAS MONITORED screen.
A2 = Gas Monitored Tab
A3 = Signal Settings Tab
Figure 81: Signal Settings Tab
To select source signal input text:
1. Touch the NONE/BLANK tab.
2. Scroll through the options using the right and left arrows at the bottom of the screen.
3. Touch the tab for the appropriate option
4. Touch the Save button when you see a check beside your selection to save the selection and return to the SIGNAL SET­TINGS screen.
Figure 80: Gas Monitored Tab
To choose the gas to be monitored:
1. Scroll through the codes using the right and left arrows at the bottom of the screen.
2. Touch the tab for the appropriate gas.
3. Touch the Save button when you see a check beside your selection to go auto­matically to the SIGNAL SETTINGS screen.
5. Touch the X button in the upper right to go automatically to the LOCATION screen.
4-15
4107 9016 59.03
Page 46
MEGA3 NFPA Medical Gas Notification System
A4 = Locations Tab
Figure 82: Locations Tab
To add source locations being monitored:
1. Touch a blank location tab.
2. Using the keyboard, enter the name of the location for the source equipment being monitored (e.g., ROOM 1). Enter multiple locations as needed (e.g., Manifold Room, Roof Top, Source Room).
4.4.2 Initial Setup of an Unconfig­ured Master Alarm
The SETUP INFORMATION screen is the first screen that users will see on an unconfigured alarm.
(The MAIN screen is the first screen that users will see on a configured alarm).
Configuration Button
Figure 83: Setup Information Screen
3. Touch the Save button to close the screen and return to the SOURCE LOCATION screen.
4. Make sure the location you selected is highlighted in green, and touch the save button in the upper right to save and re­turn to the CONFIGURE (SOURCE) screen.
Note: To edit the location information, touch the Pencil button.
Configuring Additional Source Badges
Configure alarm points on additional source badges by touching the number on the numeric display that corresponds with the source badge and repeating the steps listed above.
• Touch the Configuration button.
Entering the Password
The ENTER SECURITY PASSWORD screen ap­pears.
Figure 84: Entering the Security Password
• Enter the security password. (The default password is 121212.)
• Touch the Enter button.
• Touch Continue to advance to the CONFIGURATION screen.
4107 9016 59.03
4-16
Page 47
MEGA3 NFPA Medical Gas Notification System
Note:
If you would like to change the password, touch Change Password. Enter a 4-10 digit password, and touch the Enter button. Con­firm the new password. Touch the X button in the upper right to close the SECURITY PASSWORD screen.
Figure 85: Changing the Security Password
• The CONFIGURATION screen will display as unconfigured and ready for setup
Alarm Type Tab
The ALARM TYPE screen defines which type of alarm will be displayed and drives later setup functions.
• Touch the ALARM TYPE tab.
Figure 86: Alarm Type Tab
• Choose a code style based on code re­quirements.
• Touch the MASTER tab.
Primary Settings Tab
The PRIMARY SETTINGS tab allows you to select the alarm type and initialize boards.
• Touch the PRIMARY SETTINGS tab.
Save Erase
Figure 87: Choosing Code and Alarm Styles
• Touch the Save button when you see checks beside your selections to close the screen and return to the PRIMARY SET­TINGS screen.
Note: To clear your selections, touch the Erase button.
4-17
4107 9016 59.03
Page 48
MEGA3 NFPA Medical Gas Notification System
Initialize Modules Tab
The PRIMARY SETTINGS screen will now dis­play with ALARM TYPE checked and INITIAL­IZE MODULES active.
• Touch the INITIALIZE MODULES tab. The INITIALIZE MODULES screen is used to set
up the boards that are installed. The boards function as the input/output hardware of the alarm.
4.5 Setting Up a Combination Alarm
The combination alarm combines the func­tionality of an area alarm and a master alarm. It monitors two things:
• Gases and their pressures.
• Source equipment. Two independent hard wired alarms monitor-
ing source equipment are required per facility to meet the 24-hour monitoring requirement in the NFPA 99 standard.
For convenience to the customer, the MEGA3 Medical Gas Alarm is shipped from the fac­tory as a configured unit. However, the infor­mation for the signals connected in the field need to be entered into the alarm using the touch screen interface.
Figure 88: Initialize Modules Screen
At this point, you have two options:
1. Either touch the Scan button to prompt the alarm to autofill the screen for you.
OR
2. Complete the screen by selecting the boards installed in the alarm.
Touch the Save button when you see checks beside your selections.
The PRIMARY SETTINGS screen will now dis­play with ALARM TYPE and INITIALIZE MOD­ULES highlighted and checked and the other tabs grayed out.
• Touch the X button in the upper right to close and return to the CONFIGURATION screen.
Figure 89: Combination Alarm User Interface
4.5.1 Configuring Source Badges
• Follow the steps for configuring source badges on a master alarm (section 4.4.1).
4.5.2 Configuring Gas Badges
• Follow the steps for configuring gas badg­es on an area alarm (section 4.3.1).
4107 9016 59.03
4-18
Page 49
MEGA3 NFPA Medical Gas Notification System
4.5.3 Initial Setup of an Unconfig­ured Combination Alarm
The SETUP INFORMATION screen is the first screen that users will see on an unconfigured alarm.
(The MAIN screen is the first screen that users will see on a configured alarm).
Configuration Button
Figure 90: Setup Information Screen
• Touch the Configuration button.
Entering the Password
The ENTER SECURITY PASSWORD screen ap­pears.
Enter the security password. (The default password is 121212.)
• Touch the Enter button.
• Touch Continue to advance to the CONFIGURATION screen.
Figure 92: Changing the Security Password
Note:
If you would like to change the password, touch Change Password. Enter a 4-10 digit password, and touch the Enter button. Con­firm the new password. Touch the X button in the upper right to close the SECURITY PASSWORD screen.
• The CONFIGURATION screen will display as unconfigured and ready for setup.
Figure 91: Entering the Security Password
Primary Settings Tab
The PRIMARY SETTINGS tab allows you to select the alarm type and initialize boards.
• Touch the PRIMARY SETTINGS tab.
4-19
4107 9016 59.03
Page 50
MEGA3 NFPA Medical Gas Notification System
Alarm Type Tab
The ALARM TYPE screen defines which type of alarm will be displayed and drives later setup functions.
• Touch the ALARM TYPE tab.
Figure 93: Alarm Type Tab
• Choose a code style based on code re­quirements.
• Touch the COMBO tab.
Initialize Modules Tab
The PRIMARY SETTINGS screen will now dis­play with ALARM TYPE checked and INITIAL­IZE MODULES active.
• Touch the INITIALIZE MODULES tab. The INITIALIZE MODULES screen is used to set
up the boards that are installed. The boards function as the input/output hardware of the alarm.
Save Erase
Figure 94: Choosing Code and Alarm Styles
• Once the desired tabs are selected, touch the Save button to save the selection an go back to the PRIMARY SETTINGS screen.
Note: To clear your selections, touch the Erase button.
Figure 95: Initialize Modules Screen
At this point, you have two options:
1. Either touch the Scan button to prompt the alarm to autofill the screen for you.
OR
2. Complete the screen by selecting the boards installed in the alarm.
Touch the Save button when you see checks beside your selections.
4107 9016 59.03
4-20
Page 51
MEGA3 NFPA Medical Gas Notification System
Gas Sensors Tab
The PRIMARY SETTINGS screen will now dis­play with ALARM TYPE and INITIALIZE MOD­ULES checked, GAS SENSORS active, and the last tab grayed out.
• Touch the GAS SENSORS tab
B60 Board
Users may select up to six dierent gases on the GAS INPUT screen. These gases cor­respond to the digital gas sensors wired into the GAS INPUT / B60 board.
Note: This setup accommodates:
• Three source badges (10 signals each) and two gas badges = five total badges
• Two source badges (10 signals each) and four gas badges = six total badges
• One source badge (10 signals) and six gas badges = seven total badges
• Touch the Save button when you see a check beside your selection. (If an alarm sounds, press the Mute button on the panel under the screen and continue with setup).
• Repeat to add additional gases.
• Touch the X button in the upper right to close the GAS SENSORS screen and return to the PRIMARY SETTINGS screen. The alarm will retain your information.
•
B65 Board
The GAS SENSORS screen defaults to the B60 board, so users will see a MODULE NOT INI­TIALIZED message.
• To select the first gas, touch the D01=NONE/BLANK tab.
• Touch the right and left arrows at the bottom of the screen to scroll through additional gas choices, including options to create custom mixes. Select the gas that is wired into the D01 input on the GAS INPUT / B60 board.
Figure 96: Gas Choices
Figure 97: B60 Module not initialized
• Touch the B65 tab to go to the GAS COM­BO screen.
4-21
4107 9016 59.03
Page 52
MEGA3 NFPA Medical Gas Notification System
Users may select up to three dierent gases on the GAS COMBINATION screen. These gas­es correspond to the digital gas sensors wired into the GAS COMBINATION / B65 board.
Note: This setup accommodates:
• 10 Source Inputs
• 3 Gas Sensors
• 6 Relay Outputs
• To select the first gas, touch the D01=NONE/BLANK tab.
• Use the right and left arrows at the bot­tom of the screen to scroll through ad­ditional gas choices, including options to create custom mixes. Select the gas that is wired into the D01 input on the GAS COMBINATION / B65 board.
• Touch the Save button when you see a check beside your selection. (If an alarm sounds, press the Mute button on the panel under the screen and continue with setup).
• The GAS COMBINATION screen will now display with the D01=[X] checked
4.5.4 Miscellaneous Tab
Users can customize certain aspects of the MEGA3 Alarm’s appearance and functionality. Aspects of functionality that can be adjusted include the date and time settings.
• Touch the MISCELLANEOUS tab.
Figure 99: Miscellaneous Screen
Figure 98: B65 screen
• Repeat the above steps to select up to two additional gases.
4107 9016 59.03
4-22
Page 53
MEGA3 NFPA Medical Gas Notification System
4.6 Additional Components
4.6.1 4-20mA Devices
To configure a 4-20mA device for monitoring, start on the CONFIGURATION screen. Users are always prompted to enter the password when accessing this screen. Type the password, and touch the Enter but­ton.
The CONFIGURATION screen displays.
Figure 100: Configuration screen
The MEGA3 alarm is designed to allow con­figuration of four gas badges using the B50 board to monitor 4-20mA devices. The alarm must be set as an Area panel or Combination panel. See Alarm Type Tab in Section 4.3.2.
Press the “Scan” button to make sure the B50 board is set up, as it should turn green. Once the B50 board is green, press the “Save” icon to exit the screen. Exit the “Primary Settings” screen.
Figure 102: initialize Modules screen
To configure the first badge to custom set­tings, touch the corresponding number but­ton in the numeric display that represents the badge to be configured. If a badge needs to be added, press the “+” for additional badges. Eight tabs are used for configuration. Tabs are listed in alphabetical order (Figure 103).
Figure 101: Primary Settings screen
After configuring the Alarm Type, the B50 board must be initialized. Select “Initialize Modules” on the Primary Settings Screen.
Figure 103: Configure Area screen
A = [Gas Input] Tab The B50 should be green and there should be 4 choices (I01, I02, I03, I04). Select the wired input to be displayed on that badge:
Touch the tab for the appropriate wired gas sensor.
4-23
4107 9016 59.03
Page 54
MEGA3 NFPA Medical Gas Notification System
Figure 104: B50 Tab, 4-20 mA
Touch the Save button to close the screen.
B = Gas Desc Tab
To assign a color code for the device:
1. Scroll through the codes using the right and left arrows at the bottom of the screen. Custom colors are located on pages 7-8.
2. Touch the tab for the appropriate code.
3. Touch the Save button when you see a check beside your selection.
Figure 106: Gas Text Keyboard
D = Area Monitored Tab
To add locations to be monitored:
1. Touch an unused location tab.
2. Using the keyboard, enter the name of the location that you would like to monitor (e.g., ROOM 1). Enter multiple locations as needed (e.g., Room 1, Room 2, Room
5).
3. A check appears when the location is se­lected, the save button has to be pressed if the selection is new.
To edit the location information, touch the Pencil button.
Figure 105: Gas Color Code Tab
C = [Gas Name] Tab
Use the keyboard to assign a device name. Type in the name of the device to be moni­tored. Touch the [<ÁÑ] to toggle to symbols and extended Latin Characters. Touch the [1AZ] key to toggle back to letters and num­bers. Touch the Save button when complete.
4107 9016 59.03
Figure 107: Source Location
E = [Units of Measure] Tab
To set up the 4-20mA device:
1. Touch the tab for “4MA=” to set the low measurement point of the device (zero for example) and press the save button to exit.
4-24
Page 55
MEGA3 NFPA Medical Gas Notification System
1. Touch the tab for “20MA=” to set the high measurement point of the device (100 for example) and press the save button to exit.
2. Touch the tab for “Units=” to set the method of measurement (percent for example), type in the measurement type and press the save button to exit.
3. Touch the X button in the upper right to close the screen.
G = High Alarm Settings Tab
You can remove the high alarm set point or customize the high alarm set point. To remove the high alarm set point:
Figure 109: Low Alarm Settings
Figure 108: Units of Measure Tab
F = Low Alarm Settings Tab
You can remove the low alarm set point or customize the low alarm set point.
To remove the low alarm set point:
1. Touch the NONE tab.
2. Touch the check on the CONFIRM SET­TINGS CHANGE screen.
To customize the low alarm set point:
1. Touch the ADJUST tab.
2. Enter the new set point.
3. Touch the Save button.
1. Touch the NONE tab.
2. Touch the check on the CONFIRM SET­TINGS CHANGE screen.
To customize the high alarm set point:
1. Touch the ADJUST tab.
2. Enter the new set point.
3. Touch the Save button.
Configuring Additional 4-20mA Devices
Configure additional 4-20mA devices by touching the number on the numeric display that corresponds with the gas badge and repeating the steps listed above.
4-25
4107 9016 59.03
Page 56
MEGA3 NFPA Medical Gas Notification System
4.6.2 Relay Output Board (B4X Board)
To configure a Relay Output, start on the CONFIGURATION screen. Users are always prompted to enter the password when ac­cessing this screen.
Type the password, and touch the Enter but­ton.
The CONFIGURATION screen displays.
The next step is to select the “Relay Outputs” from the menu on the Configuration Screen. The B40 board should be highlighted in Green (or other Relay Output board installed in the rough-in box).
Select the signal that corresponds to the output wires on the relay board (Y01 for example).
Figure 112: Relay Outputs Screen
Figure 110: Configuration Screen
The B40 (or B41, B42, B43) board must be initialized. Touch Primary Settings from the right side menu, then select “Initialize Mod­ules”. Press the “Scan” button to make sure the B40 board is set up, as it should turn green. Once the B40 board is green, press the “Save” icon to exit the screen. Exit the “Pri­mary Settings” screen.
After selecting the signal, you will need to assign it to an alarm signal to send. Select “Wired” on the Relay Output screen if the signal to be relayed is wired into the rough-in box.
Figure 113: Relay Output Signal
There are four choices for the relay output signal.
Figure 111: Initialize Modules Screen
4107 9016 59.03
4-26
Page 57
MEGA3 NFPA Medical Gas Notification System
3. “Many Signals” allows the user to group multiple signals on a single relay output. If any of the signals goes into alarm condi­tion, the relay output will report an alarm condition. Press “Many Signals” to move to the Relay Output screen and select from 1 to 10 signals to group together. Select the number 01 to start, then select the first signal to be grouped by pressing the corresponding number on the Relay Output (such as X01 from the B10 board).
Figure 114: Relay Output Signals Screen
1. A single “Any Fault” which will report a general alarm fault if any of the alarm signals on the alarm go into alarm condi­tion. To select “Any Fault”, press the blue “Any Fault” to change it to green with the check mark. Then press Save to return to Relay Outputs and set up additional outputs.
Press Save to return to the Many Signal Re­lay Output screen. Next select 02 to cap­ture the second signal to be monitored. Repeat up to a grouping of 10 signals.
2. “One Signal” reports a single signal through the relay output. When pressing “One Signal,” the next step is to assign the signal to be transmitted. On the Relay Output screen, select the Input Signal to be transmitted (X01 from the B10 board for example). Press Save to return to the Relay Outputs screen.
Figure 115: Relay Output One Signal
Figure 116: Relay Output Many Signals
4. “Gas Sensor Alarm Fault” allows the user to report a fault condition based on a gas sensor through the relay output. When choosing Gas Sensor Alarm Fault, select the gas sensor to be monitored from the list. Press Save to return to the Relay Out­puts screen.
4-27
Figure 117: Gas Sensor Alarm Fault
4107 9016 59.03
Page 58
Page 59
MEGA3 NFPA Medical Gas Notification System
5.0 Retrofit
Retrofit Kits Include:
Figure 118: TA2/MEGA2/Others 8-Gas Trim Kit
4107 2206 15 Contents
Qty Description
1 Trim Plate Retrofit 16x27 1 Adapter Bracket, Power Supply
2-Position
4 Hardware #6-32 x 1/4” long Pan Head Ma-
chine screw
5.1 Retrofit of TotalAlert2 Area Alarm
Panel (4-gas, 8-gas) and MEGA2 Alarms
NOTE: The existing Digital Gas Sensors will
be reused for the new alarm.
5.1.1 Remove Components from
Existing Alarm
1. Open old alarm panel to be retrofitted and ensure that the retrofit kit to be in­stalled is correct according to the number of Signal Inputs, Relay outputs, and/or Gas Sensor signals (See Appendix A).
2. Ensure that you have the additional trim kit if retrofitting a TotalAlert2/MEGA2, 8-Gas alarm (4107220615).
3. Test Master alarm signals to validate wir­ing and document all signal wires coming into the box with alarm type and loca­tions prior to disconnecting the front panel. This information will be required to setup the new alarm.
4. Turn o the supply power to the alarm.
Figure 119: TotalAlert1 Trim Kit
4107 2206 16 Contents
Qty Description
1 Trim Plate Retrofit TotalAlert1 Single
1
1 Trim Plate Retrofit TotalAlert 1 Adapter Bracket, Power Supply 1 Adapter Bracket, I/O Modules 4 Hardware #6-32 x 1/4” long Pan Head Ma-
chine screw
NOTE: Due to the nature of retrofit installations, you will have parts left over when finished.
Double
CAUTION: Verify that power has been turned o prior to working on the alarm.
5. Remove and discard the front panel from the existing alarm.
6. Remove the old power supply
5-1
4107 9016 59.03
Page 60
MEGA3 NFPA Medical Gas Notification System
5.1.2 Install New Power Supply
Mega Master / Area 4 Gas
a. Install the metal stando bracket that
is included with the retrofit kit onto the studs the power supply was removed from.
b. Mount the new Power Supply (B05)
to the bracket using the nuts provided (Figure 120).
Power Supply
Additional I/O Module
Figure 120: Power Supply, Module Mounting
Power Supply
Mounting Bracket
TA2/MEGA2 Area 8 Gas
a. Install the 2 position metal stando
bracket that is included with the addi­tional trim kit onto the studs the power supply was removed from (Figure 121).
b. Mount the new Power Supply (B05)
and the B60 gas input board to the bracket using the nuts provided with the modules.
B60
Module
Figure 121: Power Supply, Module Mounting
Mounting Bracket
1. Locate the Ground cable attached to the power supply and connect the ring ter­minal end to the rough-in box for chassis ground. Use the self-drilling screw pro­vided.
2. Remove the 4 corner screws from the power supply cover and remove the cover.
3. Connect the supply power Line and Neu­tral wires to the terminal block.
4. Connect the supply power Ground wire directly to the rough-in box.
5. Replace the power supply cover and screws.
4107 9016 59.03
5-2
Page 61
MEGA3 NFPA Medical Gas Notification System
5.1.3 Install New Components
1. Determine the best placement of the re­maining I/O modules inside of the rough­in box.
NOTE: I/O Modules and Power Supply will need to be daisy chain connected via the grey cables supplied with each I/O module.
2. Mount the I/O Modules inside the rough-
in box using the supplied hardware.
3. Connect the grey cable(s) provided; from
the power supply to the white sockets on the I/O modules in a daisy chain manner (Figure 122).
Figure 122: Daisy Chain of Power Supply
4. The last module in the chain needs to have the #1 DIP switch set to “ON” (Fig­ure 123). Refer to the module ID label.
5.1.4 Install Trim Plate
MEGA Master / Area 4 Gas
a. Install trim plate assembly to rough-in
box using the provided screws and/or drywall anchors. Slots in the trim plate will align with existing holes in the rough-in box flanges (Figure 124).
NOTE: Trim ring portion can be removed from the trim plate if the surrounding wall area is in good condition. Mounting of the trim ring only to the rough-in box will result in a cleaner retrofit installation.
TA2/MEGA2 Area 8 Gas
a. Remove the trim ring from the standard
trim plate and install the wide 27” wide x 16” tall trim plate from retrofit option kit (4107220615). Screws are provided in the option kit for attaching the trim ring to the trim plate (Figure 124).
b. Install trim plate assembly to rough-in
box using the provided screws and/or drywall anchors. Slots in the trim plate will align with existing holes in the rough-in box flanges.
Trim Plate
Figure 123: DIP Switch Setting
5. Connect all input signal / output signal /
gas sensor wiring to their respective mod­ules. Refer to the wiring diagram on the Quick Setup Guide for instructions.
5-3
Trim Ring
Figure 124: Retrofit Area Trim Panel
4107 9016 59.03
Page 62
MEGA3 NFPA Medical Gas Notification System
1. Mount the Front Panel assembly to the trim ring using the countersink sheet metal screws provided on the trim ring (Figure 125).
2. Connect the lanyard to the threaded ex­tension on the right side of the trim ring.
3. Connect the grey cable from the Front Panel to the other white socket on the Power Supply board.
4. Connect the ground cable from the Front Panel to the rough-in box using the pro­vided self-drilling screw.
5. Turn on the supply power to the alarm and wait for the alarm to boot up.
6. Setup the new alarm by referring to the Quick Setup guide.
5.2 Retrofit of TotalAlert1 Alarm Panels
5.2.1 Remove Components from Ex­isting Alarm
1. Open old alarm panel to be retrofitted and ensure that the retrofit kit to be in­stalled is correct according to the number of Signal Inputs, Relay outputs, and/or Gas Sensor signals (See Appendix A).
2. Ensure that you have the additional trim kit for retrofitting a TotalAlert1 Single or Double alarm panel (4107220616).
3. Test Master alarm signals to validate wir­ing and document all signal wires coming into the box with alarm type and locations prior to disconnecting the front panel. This information will be required to setup the new alarm.
4. Turn o the supply power to the alarm.
Figure 125: Front Panel Assembly Mounting
CAUTION: Verify that power has been turned o prior to working on the alarm.
5. Remove and discard the front panel from the existing alarm. For TotalAlert1 Double, remove the door from the hinges, remove the lock set and set aside, and discard the door.
NOTE: For TotalAlert1 alarms, all internal components will need to be removed and replaced with new components.
6. Remove and discard of all the components from the alarm rough-in box.
7. Ensure that no low voltage signal wiring is pulled through the input power knockouts inside of the rough-in box.
8. Mount new power supply adapter bracket (small bracket included with kit
4107220616) reusing the hardware and location from the old power supply (Fig­ure 126).
4107 9016 59.03
5-4
Page 63
MEGA3 NFPA Medical Gas Notification System
CAUTION: Ensure that the pressure on the pipeline in the alarm area has been released
Power Supply
I/O Modules
Figure 126: MEGA3™ Adapter Bracket Mounting
Single
9. Snap the I/O module adapter brack­et (large bracket included with kit
4107220616) onto the standos at the rear of the rough-in box (Figure 127).
Power Supply
before removing any components from the pipeline connection.
2. Remove any existing fittings or adapters from the gas tube in the rough-in box.
3. Install the gas specific DISS demand check valve from the supplied tubing package into the appropriate gas tube. To prevent gas leaks, wrap Teflon tape a minimum of three times around the fitting pipe threads.
4. Tighten the adapter until you feel resis­tance; then turn the fitting 2 full turns.
NOTE: If the gas transducer needs to be repositioned in the rough-in box or thread size / fitting style is not compatible; use the included fitting kits to adapt or relocate as needed. Fitting/adapter kit needs to be in­stalled upstream from the DISS connection at the gas sensor.
I/O Modules
Figure 127: MEGA3™ Double Adaptor
Bracket Mounting
5.2.2 Install Gas-Specific Sensors (Area or Combination alarms only)
Local Sensors
1. Install the MEGA3™ gas specific transduc­ers following your records from the disas­sembly.
NOTE: If a DISS demand check valve is not in place then one will need to be installed to comply with NFPA 99.
5. Install the gas specific transducer.
6. Tighten the DISS nut until you feel resis­tance.
7. Repeat steps 2-6 until all of the gas spe­cific transducers are installed.
8. Verify that the gas specific transducers are in the appropriate places by referring to your records from the disassembly.
9. Return pressure to each gas sensor, one gas at a time and check for leaks. Make any adjustments or corrections as needed.
Remote Sensors
1. Sensors are packaged loose so they can easily be installed remotely.
2. Remote sensors are installed directly to the pipeline outside of the rough-in box. Pipeline connections are to be made to the top of the pipe.
NOTE: If a DISS demand check valve is not in place then one will need to be installed to comply with NFPA 99.
5-5
4107 9016 59.03
Page 64
MEGA3 NFPA Medical Gas Notification System
CAUTION: Ensure that the pressure on the pipeline in the alarm area has been released before removing any components from the pipeline connection.
3. Remove any existing fittings or adapters from the gas tube.
4. Install the gas specific DISS demand check valve from the supplied tubing package into the appropriate tube. To prevent gas leaks, wrap Teflon tape a minimum of three times around the fitting pipe threads.
5. Tighten the adapter until you feel resis­tance; then turn the fitting 2 full turns.
NOTE: If the DISS demand check thread size is not compatible with the existing tubing connection; use the included fitting kits to adapt as needed. Fitting/adapter kit needs to be installed upstream from the DISS con­nection at the gas sensor.
5.2.3 Install New Power Supply
1. Mount the new Power Supply (B05) to the adapter bracket using the nuts provided (Figures 126 - 129).
2. Locate the Ground cable attached to the power supply and connect the ring ter­minal end to the rough-in box for chassis ground. Use the self-drilling screw pro­vided.
3. Remove the 4 corner screws from the Power Supply cover and remove the cover.
4. Connect the supply power Line and Neu­tral wires to the terminal block.
5. Connect the supply power Ground wire to the rough-in box.
6. Replace the power supply cover and screws.
6. Install the gas specific transducer.
7. Tighten the DISS nut until you feel resis­tance.
8. Repeat steps 3-7 until all of the gas spe­cific transducers are installed.
9. Verify that the gas specific transducers are in the appropriate places by referring to your records from the disassembly.
10. Return pressure to each gas sensor, one gas at a time and check for leaks. Make any adjustments or corrections as needed.
NOTE: Remote sensors can also be in­stalled in compatible BeaconMedæs Zone Valve boxes with additional adapter kit (4107401625). One required for each sensor.
Power Supply
I/O Modules
Figure 128: MEGA3
Single Module Positions
Power Supply
4107 9016 59.03
I/O Modules
Figure 129: Double Module Positions
5-6
Page 65
MEGA3 NFPA Medical Gas Notification System
5.2.4 Install New Components
1. Mount the I/O Modules to the large adapter bracket using the nuts provided.
NOTE: I/O Modules and Power Supply will need to be daisy chain connected via the grey cables supplied with each I/O module (See figure 122).
2. Connect the grey cable(s) provided; from the power supply to the white sockets on the I/O modules in a daisy chain manner.
3. The last module in the chain needs to have the #1 DIP switch set to “ON” (See Figure 123). Refer to the module ID label.
4. If alarm is an Area or Combination with local sensors, consider the position and placement of the pressure transducers before drilling or mounting any compo­nents. Use the sensor adapter kits provid­ed to relocate the sensors if required.
5. Connect all input signal / output signal / gas sensor wiring to their respective mod­ules. Refer to the wiring diagram on the Quick Setup Guide for instructions.
Figure 130: MEGA3™ Single
Trim Plate Installation
5.2.5 Install Trim Plate
1. Remove the trim ring from the standard
trim plate and install the correspond­ing trim plate from retrofit option kit (4107220616) (Figures 130 & 131). Screws are provided in the option kit for attaching the trim ring to the trim plate. TotalAlert1 Double also requires switch­ing over the door lock set to the new trim plate.
2. Install trim plate assembly to the rough­in box using the holes that align to the rough-in box flanges (TotalAlert1 Single), or attach trim plate assembly to the exist­ing hinges (TotalAlert1 Double).
Door Lock
Figure 131: MEGA3™ Double
Trim Plate Installation
3. Mount the Front Panel assembly hinge to the trim ring using the countersink sheet metal screws provided on the trim ring (Figures 132 - 134).
4. Connect the lanyard to the threaded ex­tension on the right side of the trim ring.
5. Connect the grey cable from the Front Panel to the white socket on the Power Supply board.
6. Connect the Ground cable from the Front Panel to the rough-in box.
7. Turn on the supply power to the alarm and wait for the alarm to boot up.
8. Setup the new alarm by referring to the Quick Setup guide.
5-7
4107 9016 59.03
Page 66
MEGA3 NFPA Medical Gas Notification System
5.3 Retrofit of Other Alarm Panels
5.3.1 Remove Components from Ex­isting Alarm
1. Open old alarm panel to be retrofitted and ensure that the retrofit kit to be in­stalled is correct according to the number of Signal Inputs, Relay outputs, and/or gas sensor signals (See Appendix A).
2. If alarm to be retrofit has a rough-in box greater than 20 inches wide, you will need the optional trim kit (4107220615) to cover the existing box.
3. Test Master alarm signals to validate wir­ing and document all signal wires coming
Figure 132: MEGA3™ Single
Mount Front Panel Assembly
into the box with alarm type and loca­tions prior to disconnecting the front panel. This information will be required to setup the new alarm.
4. Turn o the supply power to the alarm.
Figure 133: MEGA3™ Double
Mount Front Panel Assembly
CAUTION: Verify that power has been turned o prior to working on the alarm.
5. Remove and discard the front panel from the existing alarm.
6. Remove and discard of all the compo­nents from the alarm rough-in box.
7. Ensure that no low voltage signal wiring is pulled through the input power knock­outs inside of the rough-in box.
8. Remove any studs and screws flush with the rough-in box.
9. Remove all sharp edges and burrs from open knockouts and from the inside of the rough-in box.
10. Remove all existing regulatory compliance labels from the inside of the rough-in box.
11. Clean the inside of the rough-in box to remove all of the metal shavings and dirt.
Figure 134: MEGA3™ Double
Mount Front Panel Assembly
4107 9016 59.03
5-8
Page 67
MEGA3 NFPA Medical Gas Notification System
5.3.2 Determine Proper Placement of New Components
1. Determine the proper placement of the MEGA3™ Retrofit Alarm components inside of the rough-in box. Refer to Appen­dix A and illustrations for recommended placement.
NOTE: I/O Modules and Power Supply will need to be daisy chain connected via the grey cables supplied with each I/O module (See Figure 122) The last module in the chain needs to have the #1 DIP switch set to “ON” (See Figure 123).
2. If alarm is an Area or Combination with local sensors, consider the position and placement of the pressure transducers before drilling or mounting any compo­nents. Use the sensor adapter kits provid­ed to relocate the sensors if required.
5.3.3 Install Gas-Specific Sensors (Area or Combination alarms only)
Local Sensors
1. Install the MEGA3™ gas specific transduc­ers following your records from the disas­sembly.
NOTE: If a DISS demand check valve is not in place then one will need to be installed to comply with NFPA 99.
CAUTION: Ensure that the pressure on the pipeline in the alarm area has been released before removing any components from the pipeline connection.
2. Remove any existing fittings or adapters from the gas tube in the rough-in box.
3. Install the gas specific DISS demand check valve from the supplied tubing package into the appropriate gas tube. To prevent gas leaks, wrap Teflon tape a minimum of three times around the fitting pipe threads.
4. Tighten the adapter until you feel resis­tance; then turn the fitting 2 full turns.
NOTE: If the gas transducer needs to be repositioned in the rough-in box or thread size / fitting style is not compatible; use the included fitting kits to adapt or relocate as needed. Fitting/adapter kit needs to be in­stalled upstream from the DISS connection at the gas sensor.
5. Install the gas specific transducer.
6. Tighten the DISS nut until you feel resis­tance.
7. Repeat steps 2-6 until all of the gas spe­cific transducers are installed.
8. Verify that the gas specific transducers are in the appropriate places by referring to your records from the disassembly.
9. Return pressure to each gas sensor, one gas at a time and check for leaks. Make any adjustments or corrections as needed.
Remote Sensors
1. Sensors are packaged loose so they can easily be installed remotely.
2. Remote sensors are installed directly to the pipeline outside of the rough-in box. Pipeline connections are to be made to the top of the pipe.
NOTE: If a DISS demand check valve is not in place then one will need to be installed to comply with NFPA 99.
CAUTION: Ensure that the pressure on the pipeline in the alarm area has been released before removing any components from the pipeline connection.
3. Remove any existing fittings or adapters from the gas tube.
4. Install the gas specific DISS demand check valve from the supplied tubing package into the appropriate tube. To prevent gas leaks, wrap Teflon tape a minimum of three times around the fitting pipe threads.
5. Tighten the adapter until you feel resis­tance; then turn the fitting 2 full turns.
5-9
4107 9016 59.03
Page 68
MEGA3 NFPA Medical Gas Notification System
NOTE: If the DISS demand check thread size is not compatible with the existing tubing connection; use the included fitting kits to adapt as needed. Fitting/adapter kit needs to be installed upstream from the DISS con­nection at the gas sensor.
6. Install the gas specific transducer.
7. Tighten the DISS nut until you feel resis­tance.
8. Repeat steps 3-7 until all of the gas spe­cific transducers are installed.
9. Verify that the gas specific transducers are in the appropriate places by referring to your records from the disassembly.
10. Return pressure to each gas sensor, one gas at a time and check for leaks. Make any adjustments or corrections as needed.
NOTE: Remote sensors can also be in­stalled in compatible BeaconMedæs Zone Valve boxes with additional adapter kit (4107401625). One required for each sensor.
5.3.4 Install Power Supply
NOTE: Alarm panels require 100 to 250 VAC
50/60Hz power. Refer to wiring schematics located on the quick setup guide included. For NFPA 99 compliance, alarm panel must be connected to the life safety branch of the emergency electrical system.
1. Position the power supply module in the rough-in box to verify the fit prior to installation.
2. Mount the power supply using the pro­vided nuts or self-drilling screws
3. Locate the Ground cable attached to the power supply and connect the ring ter­minal end to the rough-in box using the provided self-drilling screw.
4. Remove the 4 corner screws from the power supply cover and remove the cover.
5. Connect the supply power Line and Neu­tral wires to the terminal block.
6. Connect the supply power Ground wire to the rough-in box.
7. Replace the power supply cover and screws.
5.3.5 Install I/O Modules
1. Position the Input/Output modules in the rough-in box to verify the fit prior to installation.
2. Mount each I/O module using the pro­vided nuts or self-drilling screws.
3. Connect the grey cable(s) provided; from the Power Supply to the white sockets on the I/O modules in a daisy chain manner (See Figure 122).
4. The last module in the chain needs to have the #1 DIP switch set to “ON” (See Figure 123). Refer to the module ID label.
5. Connect all input signal / output signal / gas sensor wiring to their respective mod­ules. Refer to the wiring diagram on the Quick Setup Guide for instructions.
4107 9016 59.03
5-10
Page 69
MEGA3 NFPA Medical Gas Notification System
5.3.6 Install Trim Components
The standard retrofit alarm kit comes with a 20” x 16” trim plate assembly which will work for most of the typical installations (Fig­ure 135). In some cases the trim plate is not needed and the existing rough-in box / wall opening can be covered by using the trim ring alone; in that case, remove the 20” x 16” trim plate prior to installing the trim ring to the wall/rough-in box.
For retrofitting of larger 8-gas rough-in panels (up to 24” wide), an optional trim plate kit is required (4107220615) to cover the larger wall opening (Figure 136). If this is required, remove the 20” x 16” trim plate from the trim ring and install the 27” x 16” trim plate prior to installing the trim assembly to the wall/ rough-in box. *Note the orientation of the square notches on the trim ring and plate.
1. Position the trim plate over the rough­in box and determine the best mount­ing method for your case. Use a level to check that the trim plate is plumb.
2. Mark the mounting locations on the dry­wall using the trim plate as your guide.
3. Install the drywall anchors provided as needed.
4. Reposition the trim plate and install the screws provided into the anchors and/or directly into the rough-in box.
Figure 136: Optional Retrofit Area Trim Panel
5.3.7 Install Front Panel
1. Mount the Front Panel assembly to the trim ring using the countersink sheet metal screws provided on the trim ring.
2. Connect the lanyard to the threaded extension on the right side of the trim ring (Figure 137).
3. Connect the grey cable from the Front Panel to the white socket on the Power Supply board.
4. Connect the Ground cable on the Front panel to the rough-in box using the pro­vided self-drilling screw.
5. Turn on the supply power to the alarm and wait for the alarm to boot up.
6. Setup the new alarm by referring to the Quick Setup guide.
Trim Plate
Trim Ring
Figure 135: Standard Trim Plate Assembly
5-11
Figure 137: Front Panel Installation
4107 9016 59.03
Page 70
MEGA3 NFPA Medical Gas Notification System
Appendix A:
Variable A
Alarm Type and Size
Allowable Value Description
A10 Area Alarm, Up to 8 Area Gases
M01 Master, 0 Inputs, 16 Relay Outputs
M10 Master, 20 Inputs
M11 Master, 20 Inputs, 16 Relay Outputs
M12 Master, 20 Inputs, 32 Relay Outputs
M13 Master, 20 Inputs, 48 Relay Outputs
M20 Master, 40 Inputs
M21 Master, 40 Inputs, 16 Relay Outputs
M22 Master, 40 Inputs, 32 Relay Outputs
C01 Combination, 10 Inputs, 6 Relay Outputs, Up to 3
C10 Combination, 20 Inputs, Display up to 6 Area Gases
C11 Combination, 20 Inputs, 16 Relay Outputs, Display up
C12 Combination, 20 Inputs, 32 Relay Outputs, Display up
C40 Combination, 7 Inputs, 6 Relay Outputs, 4 Inputs for
C41 Combination, 27 Inputs, 6 Relay Outputs, 4 Inputs for
C44 Combination, 7 Inputs, 6 Relay Outputs, 4 Inputs
Notes: * Limitations on Combination Panels:
• C10, C11, C12 Combinations x 0-10 source signal Inputs used, Display up to 6 Area gases x 11-20 source signal Inputs used, Display up to 4 Area gases
• C41 x 0-20 source signal Inputs used, Display up to 4 4-20mA devices x 21-27 source signal Inputs used, Display up to 2 4-20mA devices
• C44 x Display up to 6 gas badges maximum, combination of 4-20mA and
area gases, with maximum 4 4-20mA badges.
Area Gases
to 6 Area Gases
to 6 Area Gases
4-20mA devices
4-20mA devices
for 4-20mA devices, Up to 6 Area Gases (maximum display of 6 gas badges, in combination of 4-20mA and gas sensors)
Retrofit Alarm Models
M3- ___ - ___ - R
A
NOTE: For Area Alarm panels, sensor assemblies are not specific to
"Remote" or "Local" installations. It is not necessary to designate the installation type in the model numbering.
Gas Type (Area and Combination Only)
Allowable Value Description
O Oxygen
X Nitrous Oxide
A Medical Air
V Medical Vacuum
W WAGD
N Nitrogen
C Carbon Dioxide (CO2)
D Oxygen 100 psig
F Medical Air 100 psig
G Carbon Dioxide 100 psig
9 Instrument Air
1 CO2-O2 (CO2 over 7%)
2 O2-CO2 (CO2 not over 7%)
3 HE-O2 (HE over 80%)
4 O2-HE (HE not over 80%)
7 Laboratory Air
8 Laboratory Vacuum
H Helium
J Argon
S Surgical Air
B AGSS
E N2O-O2
M Mixed Gas
Example: MEGA3™ Master Alarm Retrofit with 40 Inputs and 32
Relay Outputs
Example Model Number: M3-M22-R
B
Variable B
4107 9016 59.03
Example: MEGA3™ Retrofit AREA Alarm with 4 gases - Oxygen, Ni-
trous Oxide, Medical Air, and Vacuum
Example Model Number: M3-A10-OXAV-R
Example: MEGA3™ Combination Retrofit Alarm with 10 Inputs,
6 Relay Outputs, and 3 gases - Oxygen, Medical Air, and Medical Vacuum
Example Model Number: M3-C01-OAV-R
5-12
Page 71
MEGA3 NFPA Medical Gas Notification System
Layout-2
Layout-3
1
2
3
4
5
6
7
Layout-3
1
2
3
4
5
1
2
3
Layout-2
Layout-3
Layout-5A
1
2
3
4
5
Layout-3
1
2
Typical Retrofit Layouts (Recommended Installation)
Module Components
Letter Designator Description
A B05 Power Supply
B B10-B12 Module (Signals, 20 Inputs)
C B20 Module (TotalAlert2 Retrofit only, 64 Inputs)
D B40-B43 Module (16 Relay Out)
E B50 Module (4-20mA, 4 devices, 7 inputs, 6 outputs)
F B60 Module (Gas Input, 8 gases, 1 output)
G B65 Module (Combination, 3 gases, 10 inputs, 6 outputs)
Dimensions
12.00in
(30.5cm)
B
7.50in
A
(19.1cm)
Digital I and II Alarm from Chemetron
Layout-2
8.38in
(21.3cm)
A
B
B
11.13in
(28.3cm)
Multi-Signal Alarm from Me­daes, Ohmeda, or Ohio
Layout-1
B
14.00in
(35.6cm)
B
B
B
B
A
9.00in
B
(22.9cm)
9.00in
(22.9cm)
14.00in
(35.6cm)
A
Layout-5
MedPlus Medical Gas Alarm from Hill-Rom or Medaes or Alert1 and 2 Series Alarm from Amico
GAS SENSOR
F
(22.9cm)
9.00in
MedPlus Medical Gas Alarm from Hill-Rom or Medaes or Alert1 and 2 Series Alarm from Amico
Layout-3
14.00in
(35.6cm)
A
MedPlus Medical Gas Alarm from Hill-Rom or Medaes or Alert1 and 2 Series Alarm from Amico
Layout-5A
B
B
5-13
4107 9016 59.03
Page 72
MEGA3 NFPA Medical Gas Notification System
7.50in
(19.1cm)
8.38in
(21.3cm)
12.00in
(30.5cm)
GAS SENSOR
8.38in
(21.3cm)
A
A
F
11.13in
F
(28.3cm)
Digital I and II Alarm from Chemetron
8.38in
(21.3cm)
A
F
Line Pressure Alarms from Medaes, Ohmeda, or Ohio
8.38in
GAS SENSOR
(21.3cm)
A
15.00in
(38.1cm)
Line Pressure Alarms from Medaes, Ohmeda, or Ohio
12.00in
(30.5cm)
TA1 Master Retrofit
F
B
GAS SENSOR
A
B
F
14.44in
(36.7cm)
GAS SENSOR
Line Pressure Alarms from BeaconMedaes, Medaes, Ohmeda, or Ohio
4107 9016 59.03
5-14
Page 73
MEGA3 NFPA Medical Gas Notification System
18.00in
(45.7cm)
7.50in
(19.1cm)
GAS SENSOR
7.50in
(19.1cm)
A
Digital I and II Alarm from Chemetron
F
21.00in
(53.4cm)
GAS SENSOR
A
Line Pressure Alarms from Medaes, Ohmeda, or Ohio
F
24.00in
(61.0cm)
9.00in
(22.3cm)
A
MedPlus Medical Gas Alarm from Hill-Rom or Medaes or Alert 1 and 2 Series Alarm from Amico
5-15
GAS SENSOR
F
4107 9016 59.03
Page 74
Page 75
MEGA3 NFPA Medical Gas Notification System
6.0 Maintenance
Power/Sensor
Hole Plug
Part # 836836-00
Alarm Panel Box (Part# 4107 6538 30)
Gas Sensor Module**
See Table 1
Front Panel Assembly (Part# 4107 2129 01)
Power Supply (Part# 4107 2130 05)
I/O Board*
See Table 2 for complete list
Figure 138: Maintenance
6-1
4107 9016 59.03
Page 76
MEGA3 NFPA Medical Gas Notification System
*Table 1: Gas Sensor Module Options
(Service replacement only)
Part Number Gas Sensor Assembly
4107 4016 54 O2 Sensor Assembly 4107 4016 55 N2O Sensor Assembly 4107 4016 56 MedAir Sensor Assembly 4107 4016 57 Vac Sensor Assembly 4107 4016 58 N2 Sensor Assembly 4107 4016 59 IAIR Sensor Assembly 4107 4016 60 WAGD Sensor Assembly 4107 4016 61 CO2 Sensor Assembly 4107 4016 62 CO2-O2 Sensor Assembly 4107 4016 63 O2-CO2 Sensor Assembly 4107 4016 64 HE-O2 Sensor Assembly 4107 4016 65 O2-HE Sensor Assembly 4107 4016 66 HE Sensor Assembly 4107 4016 67 LAB-AIR Sensor Assembly 4107 4016 68 LAB-VAC Sensor Assembly 4107 4016 69 O2-100 Sensor Assembly 4107 4016 70 MedAir-100 Sensor Assembly 4107 4016 71 CO2-100 Sensor Assembly 4107 4016 72 AR Sensor Assembly 4107 4016 73 AGSS Sensor Assembly 4107 4016 74 O2-N2O Sensor Assembly
**Table 2: I/O Boards
Part Number I/O Boards Description
4107 4016 37 B05 Power Module Power supply 4107 4016 38 B1X (Signal Input
Board)
4107 4016 41 B4X (Relay Board) 16 Relay
4107 4016 42 B50 (4-20mA Com-
bination Board)
4107 4016 43 B60 (Gas Input
Board)
4107 4016 44 B65
(Gas Combination Board)
20 Inputs
Outputs 4 Inputs
for 4-20mA Signals
8 Gases
3 Gases, 7 In­puts, 6 Relay Outputs
Cleaning:
Use clean dry microfiber cloth or soft lint­free cloth to remove any smudges located on the touchscreen. Make sure not to apply too much pressure on the screen when cleaning it. Never use paper towels or tissue paper which contain wood fibers that will scratch any plastic surface.
4107 9016 59.03
Periodic Maintenance:
Inspect the alarm periodically and perform a self test (see Section 4.1.6 - Information Screen). This ensures proper operation of the alarm. Any damaged components inside the alarm should be replaced by a authorized BeaconMedæs service technician.
6-2
Page 77
MEGA3 NFPA Medical Gas Notification System
7.0 Troubleshooting
Symptom Possible Cause Corrective Action
No LED power indicator illuminated on alarm front panel
No green “heartbeat” power indicator is il­luminated on connected boards
No green “heartbeat” power indicator is illumi­nated on gas sensor
Fast green "heartbeat" power indicator is illu­minated on gas sensor (2 beats per second)
Red LED illuminated above warning indicator ( ! ).
Lost Connection Warning
Input active and Unassigned Warning
Sensor active and Unassigned Warning
F1 displayed on Area badge
F2 displayed on Area badge
F3 displayed on Area Badge
F4 displayed on Area Badge
AC power is not turned on Check AC power source. Blown power supply fuse Replace fuse. AC power wiring is not connected Check AC entrance wiring at power supply
terminals.
Power supply DC wire harness is not connected properly between the power supply and the main board
Faulty power supply assembly Replace power supply Board has not been initialized Initialize board per instructions in manual. Board dip switches are not set cor-
rectly. Cable not connected correctly Check cable connections between boards. Sensor not connected to the Gas
Input Board. Gas Input Board does not have power
(no “heartbeat”)
Sensor is reading out of range Verify gas pressure in pipeline. If normal,
Active warning Navigate to the warning screen by press-
Alarm has lost network communica­tion with manually enrolled device
The alarm has lost connection to a connected/ initialized board.
Master signal input is wired, but not assigned/programmed to an alarm signal
Sensor is wired to the sensor input board, but not assigned/programmed
Gas sensor is not connected or has shorted.
Gas sensor is reading below range (fault low).
Gas sensor is reading above range (fault high).
Gas sensor connected is wrong type of gas.
Check connections on each end including orientation of cable connectors. Reconnect if necessary.
Set dip switches per diagram on board label.
Verify correct sensor connection to Gas Input Board.
Verify that Gas Input Board has been initial­ized and that dip switches are set correctly. See item 2 above.
replace sensor.
ing the Information button, then selecting Warnings.
Correct communication problem with networked device or remove the enrolled device from the Enrolled Devices list.
Check connections and cable to board.
Assign the wired input to a valid alarm signal.
Assign the wired gas sensor to a valid gas input.
Check gas sensor connection. If connection is good, replace sensor.
Verify gas sensor connections and pipeline pressure. If connection and pressure are good, replace sensor.
Verify gas sensor connections and pipeline pressure. If connection and pressure are good, replace sensor.
Connect the correct type gas sensor.
7-1
4107 9016 59.03
Page 78
MEGA3 NFPA Medical Gas Notification System
Troubleshooting (continued)
Symptom Possible Cause Corrective Action
Area Display pressure/ vacuum reading not matching pipeline.
High or Low alarm, with normal pressure display­ing on Area display
Screen is blank, power on LED is illuminated
Audible alarm reactivates a short period of time after Silence button has been pressed
Bad gauge on pipeline Verify gauge used on pipeline Incorrect unit of measure Check unit of measure, if incorrect, repro-
gram unit of measure.
Gas sensor out of calibration Adjust Zero Oset to correct reading.
(Note: there is a max of 3 psi / 3 “hg oset adjustment). If sensor cannot be adjusted enough, replace sensor.
Alarm set points have been changed. Verify / correct alarm set points.
Screen backlight will time out and shut o. Motion sensor will awaken screen when motion is sensed within 5 ft of screen.
A new alarm condition has occurred. If alarm condition previously silenced,
If screen does not awaken when approach­ing alarm, touch screen to awaken. Possible bad motion sensor.
self corrects and then reactivates again, the alarm panel treats this as a new alarm condition.
4107 9016 59.03
7-2
Page 79
Blank Page
Page 80
1800 Overview Drive Rock Hill, SC 29730
Andersen Medical Gas 12 Place Lafifitte Madisonville, LA 70447 http://www.TheMedicalGas.com 1-866-288-3783
(888) 4-MEDGAS (888) 463-3427
Fax (803) 817-5750
www.beaconmedaes.com
Loading...