BeaconMedaes MEGA 2 Installation, Operation And Maintenance Instructions

Page 1
Part No. 6-847684-00 Rev. D01 Pg. 1
MEGA
2
®
Medical Electronic Gas Alarm
Installation, Operation, and Maintenance Instructions
MAN 01-027
Page 2
Part No. 6-847684-00 Rev. D01
Table of Contents
Introduction
Alarm Modular Components...............................................................................4
Definitions...........................................................................................................5
Alarm Configuration............................................................................................6
Unpacking ..............................................................................................................7
Rough-In Installation
Alarm Panel Back Box Mounting........................................................................8
Remote Sensor Back Box Mounting ..................................................................9
Pipeline Connection
Sensor Module .............................................................................................9
Pressure Switch..........................................................................................10
Wiring Installation
General Requirements......................................................................................11
Wire Type and Size ..........................................................................................11
Wire Routing Inside The Alarm Panel ..............................................................11
Determining Number Of Conductors ................................................................12
Wiring Schematics............................................................................................13
Alarm Wiring Examples ....................................................................................13
Finish Installation
Line Voltage Electrical Connection...................................................................27
Front Panel Installation.....................................................................................27
Sensor Installation
Remote Sensors.........................................................................................28
Local Sensors.............................................................................................29
Remote Sensor Wiring .....................................................................................29
Source Equipment Wiring.................................................................................30
Field Wiring Cable Shield Grounding ...............................................................31
Building Automation System Wiring
Multi-Signal Module Relays........................................................................32
Digital Display Module High/Low Relays....................................................32
Annunciator Module General Fault Relay ..................................................32
Annunciator Module Auxiliary Relay (optional)...........................................32
Johnson Controls METASYS® System......................................................33
Slave Panel Wiring ...........................................................................................33
Page 3
Part No. 6-847684-00 Rev. D01
Table of Contents
Operation
Start-Up and Checking .....................................................................................34
Set-Up Procedure
Digital Display Module ................................................................................35
Multi-Signal Module ....................................................................................38
Monitoring Mode
Digital Display Module ................................................................................40
Multi-Signal Module ....................................................................................41
Testing
Digital Display Module ......................................................................................41
Multi-Signal Module ..........................................................................................42
Power Supply Module ......................................................................................43
Troubleshooting Guide ........................................................................................45
Replacement Parts
Front Panel Components .................................................................................50
Back Box Components.....................................................................................51
Sensor Components.........................................................................................52
Field Installation Kits.........................................................................................53
Page 4
Part No. 6-847684-00 Rev. D01
Annunciator Module
Features:
User interface pushbuttons for alarm panel TEST function, audible alarm MUTE
and set-up increase
! and decrease ".
Green alarm panel POWER ON and red audible alarm mute indicators.
Audible alarm with volume control.
Network wiring terminals and test connector.
General fault relay that activates on any alarm panel fault condition.
Alarm Modular Components
Introduction
Digital Display Module
Features:
Digital LED readout of system pressure signal transmitted from sensor module.
Adjustable brightness of digital LED readout.
Individual LED’s indicate when system pressure/vacuum is HIGH (red), LOW (red), or NORMAL (green).
Programmable high and low alarm thresholds.
Adjustable audible alarm mute duration.
Individual high and low alarm dry-contact relay outputs.
Can transmit pressure or vacuum signal to another digital display module for remote applications.
Can be networked to communicate with a personal computer or Johnson Controls Metasys® building automation system(using Metasys Integrator).
Multi-Signal Module
Features:
Monitors up to five normally closed dry­contact switch signals.
Separate indicators for each of five signals for normal (green) or abnormal (red) conditions.
Available (optional) with separate dry­contact relay outputs for each of five signals.
Can be networked to communicate with a personal computer or Johnson Controls Metasys® building automation system (using Metasys Integrator).
Blank Module
Features:
Reserves a space in alarm panel for future expansion.
Used to fill unused alarm panel module locations.
Page 5
Part No. 6-847684-00 Rev. D01
Definitions
Area Alarm Panel
Alarm panel that monitors medical gas and vacuum systems serving a specific area.
Auxiliary Fault Relay (optional)
A single-pole double-throw dry-contact relay output located on annunciator module. Used to activate a remote alarm or building management system. The relay will activate whenever ANY audible alarm on panel is in
progress. Pressing MUTE button on annunciator module deactivates relay until audible alarm is again reactivated. Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC.
Dry-Contact
An electrical contact that is isolated or unconnected from any electrical source.
General Fault Relay
A single-pole double-throw dry-contact relay output located on annunciator module. Used to activate a remote alarm or building management system. The relay will activate whenever ANY audible alarm on panel is in progress. Unlike Auxiliary Fault Relay,
pressing MUTE button on annunciator module WILL NOT deactivate relay. The General Fault Relay will deactivate only after alarm condition is corrected and alarm panel resumes normal status. Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC.
LED
Light Emitting Diode
Local Sensors
Pressure/vacuum sensors that are mounted inside alarm panel box. The sensor rough-in must be piped to medical gas/vacuum pipelines.
Master Alarm Panel
Alarm panel that monitors medical gas and vacuum source equipment and main pipelines.
Remote Sensors
Pressure/vacuum sensors that are mounted outside of alarm panel box. Sensor rough-ins may be mounted separately or ganged together near pressure/vacuum pipelines. Sensors must then be wired to alarm panel.
All MEGA2 alarm panels are factory pre­configured. The configuration of alarm panel varies dependent upon customer’s requirements. Two sizes of alarm panels are available. The small alarm panel (Figure 1) will accommodate an annunciator module with four alarm modules. The large alarm panel (Figure 2) will accommodate an annunciator module with eight alarm modules.
Figure 1: Four Module Panel
Figure 2: Eight Module Panel
Alarm Configuration
Introduction
Page 6
Part No. 6-847684-00 Rev. D01
Alarm Configuration
Introduction
An alarm panel may consist of any combination of digital display modules, multi­signal modules, or blank modules.
If alarm panel is configured with digital display modules, pressure/vacuum sensors will be included for connection to pressure/vacuum pipeline (except for 6-M2N).
Sensors may be located inside alarm panel rough-in box (local sensors) or outside alarm panel rough-in box (remote sensors).
Local sensors must be connected to pressure/vacuum pipelines via copper tubing (Figure 3). Remote sensor may be mounted near pressure/vacuum pipeline and then wired to alarm panel (Figure 4).
The required alarm panel configuration may be specified within the part number scheme as described below:
Part Number Scheme:
6-M2 ?
- ? ? ? ?
? ? ?
?
Figure 3: Local Sensors
Figure 4: Remote Sensors
1 2 3 4 5 6 7 8
Position within alarm panel (Figures 1 and 2)
L = Local Sensors R = Remote Sensors N = No Sensors
(Slave Applications)
Designates type of alarm panel component from chart below
O
OXYGEN
D
OXYGEN - 100 PSI
X
NITROUS OXIDE
A
MEDICAL AIR
F
MEDICAL AIR - 100 PSI
5
AIR (ISO)
7
LABORATORY AIR
2
O2-CO2
4
O2-He
C
CARBON DIOXIDE
G
CARBON DIOXIDE - 100 PSI
1
CO2-O2
3
He-O2
H
HELIUM
V
VACUUM
6
VACUUM (ISO)
8
LABORATORY VAC
W
WAGD
N
NITROGEN
9
INSTRUMENT AIR
DIGITAL DISPLAY MODULES
M
MULTI-SIGNAL MODULE
R
MULTI-SIGNAL MODULE W/ RELAYS
B
BLANK
Sensor modules are mounted inside the alarm panel box
Copper tubes connect to pressure/vacuum pipelines
Sensors have separate mounting boxes for mounting near pressure/vacuum pipeline and then must be wired to alarm panel
Copper tubes connect to pressure/vacuum pipelines
NOTE:
When an alarm panel is ordered with either local or remote sensors, ALL sensors will either be local or remote. Alarm panels with a combination of local and remote sensors are not available.
NOTE:
Alarm panel components in table above are listed in order of criticality. Unless otherwise specified, the most critical component will fill position one, the next less critical component will fill position two, etc. etc.
Page 7
Part No. 6-847684-00 Rev. D01
Introduction
Alarm Configuration
Example: P/N 6-M2R-OAVB
Example: P/N 6-M2R-OXAVNWMM
Unpacking
1. Remove alarm panel back box from shipping carton. Do not remove alarm front panel (wrapped in anti-static shipping bag).
2. If alarm panel is configured with remote sensors, remove sensor rough-in and mounting box from small individual boxes shipped within main alarm panel shipping carton.
3. Store all other components not removed in steps 1 and 2 inside shipping carton in a safe place for installation later.
4. Install back box and sensor rough-in as described in this manual.
Page 8
Part No. 6-847684-00 Rev. D01
Rough-In Installation
The alarm panel back box will be one of two sizes. The height and depth of both size boxes are the same. Refer to Figure 5 below for dimensions of both boxes.
If alarm panel is configured with digital display modules, sensor assemblies will be included for connection to pressure/vacuum pipeline.
Sensors may be located inside alarm panel rough-in box (local sensors) or outside alarm panel rough-in box (remote sensors).
If equipped with local sensors, copper tubes will extend from top of back box to be connected to pressure/vacuum pipeline.
Figure 5: Alarm Panel Back Box Dimensions
Alarm Panel Back Box Mounting
1. Prepare a rough wall opening large enough to accommodate alarm panel back box. Alarm panel back box must have rigid vertical members for support on both left and right sides. Power to alarm panel shall enter through lower left or top left conduit hole in back box.
2. Remove cardboard dust cover and insert alarm panel back box into wall opening. Secure with fasteners suitable for vertical supports as shown in Figure 6.
3. Mounting brackets on each side of back box are adjustable and factory preset for 5/8” thick drywall. After drywall installation, front edge of back box should be flush with finished surface of wall. If needed, make any necessary bracket adjustments at this time. Refer to Figure 7.
4. Reinstall cardboard dust cover.
Figure 6: Back Box Mounting
Two choices of conduit holes for entrance of AC mains power
Small box - (four modules)
Large box - (eight modules)
top entry
side entry
For top entry, remove shield for access. Reinstall shield after connection is made
Page 9
Part No. 6-847684-00 Rev. D01
Figure 7: Mounting Bracket Adjustment
Rough-In Installation
Pipeline Connection
Figure 8: Remote Sensor Back Box
Sensor Module
1. Braze copper extension tubes from sensor rough-in to appropriate pressure/vacuum piping system drops as shown in Figure 9. Braze connections per procedures required by NFPA 99 or CAN/CSA-Z305.1. Use appropriate measures to prevent overheating and damage to internal components of sensor rough-in assemblies.
2. Perform standing pressure tests and cross connection tests as required by NFPA and CSA.
Loosen screws to adjust back box depth (same each side)
Four holes in back of box are provided for surface mounting
Alarm panels ordered with remote sensors are provided with separate metal boxes for each sensor. Mount each sensor box as follows:
1. Remove sensor rough-in from mounting box (Figure 8).
2. Using four mounting holes provided, attach box to a wall or other structural support. (fasteners by others).
3. Reinstall sensor rough-in.
Rear conduit knockouts (either side) are recommend­ed for sensor wiring
Alarm Panel Back Box Mounting
Remote Sensor Back Box Mounting
Page 10
10
Part No. 6-847684-00 Rev. D01
Rough-In Installation
Pipeline Connection
Pressure Switch
DISS (Diameter Index Safety System) connection kits are recommended for use when attaching pressure switches to pressure/vacuum pipeline. To utilize these kits, a 1/4-18 NPT female thread must be provided in piping system. All necessary components are included in each gas specific kit as shown in Figure
10.
Figure 10: Pressure Switch Pipeline Connection
DISS Kit P/N Gas Service
6-120004-10 Oxygen 6-120004-11 Nitrous Oxide 6-120004-12 Medical Air 6-120004-13 Vacuum 6-120004-14 Nitrogen 6-120004-18 Instrument Air 6-120004-19 Evac. (WAGD) 6-120004-20 Carbon Dioxide 6-120004-21 CO2/O2 6-120004-22 O2/CO2 6-120004-23 He/O2 6-120004-24 O2/He 6-120004-25 Helium
To pipeline
To pressure switch
DISS male
body
with check
DISS nut
and nipple
Figure 9: Sensor Pipeline Connection
Connection should be made on top of pipe
Horiz. run of pipeline
Horiz. run of pipeline
Connection should be made on top of pipe
REMOTE SENSOR
LOCAL SENSOR
Page 11
11
Part No. 6-847684-00 Rev. D01
Wiring Installation
Power all alarms from life safety branch of emergency power system as required by applicable standards.
Protect all wiring from physical damage by raceways or conduit as required by applicable standards.
Wire master panels directly to switches or sensors as required by applicable standards.
Wiring runs should be made with color coded wire. Record color, signal, and source of signal for each wiring lead to aid in connection of alarm finish components.
Avoid installing alarm panels near radio transmitters, electrical motors, or switchgear.
Figure 11: Wire Routing
General Requirements
Wire Type And Size
Wire Routing
Holes for entrance of low voltage field wiring
All low voltage MEGA2 wiring must meet the following criteria:
Copper wire no smaller than 22 AWG.
Circuit length not to exceed 5000 feet.
Cable must be twisted pair shielded type. Multi-pair cables within one common shield are acceptable.
Two 7/8” holes are provided for entrance of AC mains power. One hole on lower left side and one hole on top left of alarm panel back box. NO OTHER HOLES SHOULD BE PUNCHED OR USED. If hole on top left is used, remove shield for access. Reinstall shield after connection is made.
Several additional 7/8” holes are provided on right side of top panel for entrance of low voltage field wiring. Refer to Figure
11.
Two choices of conduit holes for entrance of AC mains power
top entry
side entry
For top entry, remove shield for access. Reinstall shield after connection is made
Page 12
12
Part No. 6-847684-00 Rev. D01
Wiring Installation
MEGA2 alarm panels can be ordered in numerous configurations. The following rules along with references to this manual’s schematics clarify wiring requirements.
All alarm panels require 100 to 250 VAC 50/60 Hz. power. Refer to Wiring Schematic 1 (Pg. 14).
Sensor modules send pressure/vacuum signals to digital display modules. If the alarm panel configuration contains digital display modules and sensor modules that are remotely mounted, two conductors are required between EACH sensor module and digital display module. A sensor module can not be wired to more than one digital display module. Refer to Wiring Schematic 2 (Pg. 15).
Multi-signal modules monitor signals from dry normally closed switch/relay contacts. These signals can originate at source equipment or from pressure switches mounted on main pressure/vacuum pipelines. When two master alarms are required, the same switch/relay contacts can be wired to both alarm panels. Two conductors are required for each alarm panel for each signal. That is, for any given signal, two wires will route to first alarm panel and another two wires will route to second panel. Both pairs of wires will originate from switch/relay contacts. This wiring is duplicated for each source equipment/pressure switch signal. Refer to Wiring Schematics 3 and 8 (Pgs. 16 and
20).
Determining Number Of Conductors
Two panels may be connected together so digital display module pressure reading(s) of first panel will be duplicated at second panel. Two conductors for EACH digital display module must be routed from first alarm panel to second alarm panel. Refer to Wiring Schematic 4 (Pg. 17).
If an alarm panel is to be connected to a Johnson Controls METASYS® system, two conductors must be connected between alarm panel’s annunciator module and monitoring system’s two-wire data bus. Refer to Wiring Schematic 9 (Pg. 21).
Most building automation systems are capable of monitoring dry normally closed relay contacts. If alarm panel is to be connected to this type of building automation system, two conductors must be routed from alarm panel to building automation system for each signal monitored. Refer to Wiring Schematics 5,6, and 7 (Pgs. 18 and 19).
Page 13
13
Part No. 6-847684-00 Rev. D01
Wiring Schematics Alarm Wiring Examples
Wiring Installation
The wiring schematics listed below are provided. Call BeaconMedæs at 1-888­4MEDGAS (1-888-463-3427), for technical support .
1. Power Supply Module
2. Sensor Module to Digital Display Module
3. Multi-Signal Module
4. Remote Pressure/Vacuum Transmission
5. Multi-Signal Module Relays
6. General Fault/Auxiliary Relays
7. Digital Display Module High/Low Relays
8. Remote Pressure/Vacuum Switches
9. Johnson Controls METASYS®
Wiring examples of master/area alarms for the following systems are provided:
1. Two master alarm panels with digital displays - high-pressure manifold/no reserve (oxygen shown) - Pg. 22.
2. Two master alarm panels with digital displays - liquid manifold/high-pressure reserve (oxygen shown) - Pg. 23.
3. Two master alarm panels with digital displays - liquid bulk/liquid reserve (oxygen shown) - Pg. 24.
4. Two multi-signal master alarm panels ­duplex air compressor and vacuum pump systems - Pg. 25.
5. Area alarm panel - gas services for oxygen, medical air, and vacuum - Pg.
26.
Page 14
14
Part No. 6-847684-00 Rev. D01
Wiring Schematic 1: Power Supply Module
Annunciator Module
20-wire ribbon cable to adjacent module
20-wire ribbon cable to adjacent module
Power Supply
Fuse Holder
Ground (green)
Line (black)
Neutral (white)
3-wire power supply harness
120V AC Mains Power Connections
Ground
Screw
Red
Orange
Black
Red
Orange
Black
Page 15
15
Part No. 6-847684-00 Rev. D01
Wiring Schematic 2: Sensor Module to Digital Display Module
Digital Display Module
Digital Display Module
Remote sensor mounting box
(remote from alarm panel)
Local sensor
(inside alarm panel back box)
2-pin polarized connector
2-pin polarized connector
ribbon to adjacent module
LOCAL SENSOR
REMOTE SENSOR
ribbon to adjacent module
* Sensor pigtail
Sensor pigtail
(provided)
Wire nuts
Field wiring
(by others)
* NOTE:
Sensor pigtails for local sensors are factory connected to digital dis­play module.
Pin 5 - red (+)
Pin 6 - black (-)
Pin 5 (+)
Pin 6 (-)
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 31 for details.
Page 16
16
Part No. 6-847684-00 Rev. D01
Wiring Schematic 3: Multi-Signal Module
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Dry normally-closed contacts at source equipment or line pressure switches
COM
+
COM
+
COM
+
COM
+
COM
+
ribbon to adjacent module
ribbon to adjacent module
Pin 1
Pin 10
Pin 1
Pin 10
Multi-Signal Module
at FIRST master alarm
panel
Multi-Signal Module
at SECOND master alarm panel
SIGNAL 1 - pin 1 (+), pin 2 (COM)
SIGNAL 2 - pin 3 (+), pin 4 (COM)
SIGNAL 3 - pin 5 (+), pin 6 (COM)
SIGNAL 4 - pin 7 (+), pin 8 (COM)
SIGNAL 5 - pin 9 (+), pin 10 (COM)
NOTE:
Installer assigns source signals to desired front panel locations and installs provided labels (Refer to Figure 23, page 31).
Multi-Signal Module front panel
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 31 for details.
Page 17
17
Part No. 6-847684-00 Rev. D01
Wiring Schematic 4: Remote Pressure / Vacuum Transmission
Digital Display Module
at master alarm panel
Digital Display Module
at slave alarm panel
Signal from
sensor module
Pin 5 (+)
Pin 6 (-)
Master output to slave
Pin 4 (-) / Pin 3 (+)
Slave input from master
Pin 1 (+)
Pin 2 (-)
ribbon to adjacent module
ribbon to adjacent module
NOTE:
The above master to slave wiring configuration DOES NOT comply with NFPA 99 wiring guidelines for two required master panels. In order to comply, EACH mas­ter panel must be directly connected to a Sensor Module for each pressure/vacu­um service. Additional panels, if desired, may be connected as indicated above.
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 31 for details.
Page 18
18
Part No. 6-847684-00 Rev. D01
Wiring Schematic 5: Multi-Signal Module Relays (Optional)
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Dry normally-closed contacts at source equipment or line pressure switches
COM
+
COM
+
COM
+
COM
+
COM
+
Multi-Signal Module
ribbon to adjacent module
SIGNAL 1 - pins 1 & 2
SIGNAL 2 - pins 3 & 4
SIGNAL 3 - pins 5 & 6
SIGNAL 4 - pins 7 & 8
SIGNAL 5 - pins 9 & 10
Dry normally-closed output
relay contacts
NOTE:
Output relay contacts are dry normally closed type. Contacts open upon designated alarm activation. Contacts remain open until alarm condition is corrected. Alarm mute DOES NOT affect relay condition.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC
.
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 31 for details.
Page 19
19
Part No. 6-847684-00 Rev. D01
Wiring Schematic 6: General Fault / Auxiliary Relays
Wiring Schematic 7: Digital Display Module High / Low Relays
Annunciator Module
Digital Display Module
ribbon to adjacent module
General Fault Relay
N/C (pin 5)
N/O (pin 3)
Common (pin 4)
N/O (pin 6)
Common (pin 7)
N/C (pin 8)
Auxiliary Relay
NOTE:
General Fault Relay
activates when ANY
alarm on panel is in progress. Pressing
MUTE on Annunciator Module DOES NOT reset relay. Relay deactivates when alarm condition is corrected.
Auxiliary Relay (optional)
activates when
ANY audible alarm on panel is in progress.
Pressing MUTE on Annunciator Module WILL deactivate relay until audible alarm is again reactivated.
Relay contact ratings are 2A @ 30 VDC/0.5 A @ 125 VAC.
ribbon to adjacent module
Low
Alarm Relay
N/C (pin 8)
Common (pin 7)
N/C (pin 10)
Common (pin 9)
High Alarm Relay
NOTE:
High Alarm Relay activates when high line pressure alarm on digital display module is in progress. When relay activates normally
closed contacts open. Pressing MUTE on Annunciator Module DOES NOT deacti­vate relay. Relay deactivates when high line pressure alarm condition is corrected.
Low
Alarm Relay activates when low line pressure alarm on digital display module is in progress. When relay activates normally
closed contacts open. Pressing MUTE on Annunciator Module DOES NOT deacti­vate relay. Relay deactivates when low line pressure alarm condition is corrected.
Relay contact ratings are 2A @ 30 VDC/0.5 A @ 125 VAC.
Page 20
20
Part No. 6-847684-00 Rev. D01
Wiring Schematic 8: Remote Pressure / Vacuum Switches
P/N 6-129020-01 (Dual switch for medical gases with 50 PSI nominal pressure)
P/N 6-129021-01
(Dual switch for medical gases with 175 PSI nominal pressure)
P/N 6-129022-01 (Single switch for vacuum)
1/4 NPT female port
1/4 NPT female port
seven - approx. 18” free leads through 3/4” conduit connection
terminal strip
1/2” conduit connection
ground screw
low
high
adjustment dials
high
low
high
yellow
brown*
orange*
purple*
red*
blue
(N/C)
(N/C)
(N/O)
(N/O)
(C)
(C)
NOTE:
Switch contacts shown with 50 PSI pressure applied.
Low switch is preset at 40 PSI.
High switch is preset at 60 PSI.
*Wires/contacts to be used with MEGA2 alarm system
adjustment screws
NOTE:
Switch contacts shown with 20 inHg vacuum applied.
Low switch is preset at 12 inHg.
green
ground
low
low
high
yellow
brown*
orange*
purple*
red*
blue
(N/C)
(N/C)
(N/O)
(N/O)
(C)
(C)
NOTE:
Switch contacts shown with 175 PSI pressure applied.
Low switch is preset at 140 PSI.
High switch is preset at 190 PSI.
*Wires/contacts to be used with MEGA2 alarm system
1/4 NPT female port
four - approx. 18” free leads through 3/4” conduit connection
low
adjustment dial
*Wires/contacts to be used with MEGA2 alarm system
low
purple*
red*
blue
(N/C)
(N/O)
(C)
green
ground
P/N 0208-5096-300 (Single switch for medical gases with 175 PSI nominal pressure)
1/4 NPT male port
three - approx. 12” free leads through 1/2” NPT conduit connection
adjustment sleeve
NOTE: 2 Switches Required.
Switch contacts shown with 175 PSI pressure applied.
Switch is preset at 195 PSI increasing.
Installer must set low switch to 140 PSI decreasing.
*Wires/contacts to be used with MEGA2 alarm system
low
purple*
red*
blue
(N/C)
(N/O)
(C)
high
purple*
red
blue*
(N/C)
(N/O)
(C)
Page 21
21
Part No. 6-847684-00 Rev. D01
Wiring Schematic 9: Johnson Controls METASYS®
Johnson Controls METASYS® or compatible building automation system (Metasys Integrator)
Serial +
Serial -
Annunciator Module of each alarm panel connected to the network shown above
Serial
+ (pin 1)
Serial - (pin 2)
NOTE:
Maintain correct network wiring polarity.
Page 22
22
Part No. 6-847684-00 Rev. D01
Typical Master/Area Alarm Wiring Examples
MAIN LINE
MAIN LINE
O2 Secondary
Supply
O2 Secondary
Supply
MASTER ALARM PANEL #1
MASTER ALARM PANEL #2
Oxygen
Sensor Module
Oxygen
Sensor
Module
Digital Display Module
Digital Display Module
Multi-Signal Module
Multi-Signal Module
pin 1 (+)
pin 2 (com)
pin 1 (+)
pin 5 (+)pin 6 (-)
pin 5 (+)
pin 6 (-)
pin 2 (com)
Connected to main
oxygen pipeline
Connected to main
oxygen pipeline
Normally-closed contacts at
high-pressure oxygen manifold
Example 1: Two master alarm panels with digital displays -
high-pressure manifold/no reserve (oxygen shown).
NOTE:
Switch contacts must be dry, normally-closed type. Alarm activates when contacts open.
Com
Page 23
23
Part No. 6-847684-00 Rev. D01
MASTER ALARM PANEL #1
MASTER ALARM PANEL #2
MAIN LINE
MAIN LINE
O2 Secondary
Supply
O2 Reserve
In Use
O2 Reserve
Low
O2 Secondary
Supply
O2 Reserve
In Use
O2 Reserve
Low
Oxygen
Sensor Module
Digital Display Module
pin 5 (+)pin 6 (-)
Connected to main
oxygen pipeline
Oxygen
Sensor Module
Digital Display Module
Multi-Signal Module
Multi-Signal Module
pin 6 (com)
pin 5 (+)
pin 6 (-)
pin 1 (+)
Connected to main
oxygen pipeline
Secondary Supply -
from liquid O2 manifold
Com
Com
Com
pin 6 (com)
pin 1 (+)
Reserve In Use -
from liquid O2 system
Reserve Low -
from liquid O2 HP back-up
NOTE:
Switch contacts must be dry, normally-closed type. Alarm activates when contacts open.
Example 2: Two master alarm panels with digital displays -
liquid manifold/high-pressure reserve (oxygen shown).
Typical Master/Area Alarm Wiring Examples
Page 24
24
Part No. 6-847684-00 Rev. D01
MASTER ALARM PANEL #1
MASTER ALARM PANEL #2
MAIN LINE
Oxygen
Sensor Module
Oxygen
Sensor
Module
Digital Display Module
Digital Display Module
Multi-Signal Module
Multi-Signal Module
pin 1
pin 5 (+)pin 6 (-)
pin 5 (+)
pin 6 (-)
pin 1
Connected to main
oxygen pipeline
Connected to main
oxygen pipeline
Example 3: Two master alarm panels with digital displays -
liquid bulk/liquid reserve (oxygen shown).
NOTE:
Switch contacts must be dry, normally-closed type. Alarm activates when contacts open.
MAIN LINE
O2 Reserve
In Use
O2 Main Tank
Liquid Low
O2 Reserve
Liquid Low
O2 Reserve Tank
Pressure Low
O2 Reserve
In Use
O2 Main Tank
Liquid Level Low
O2 Reserve
Liquid Level Low
O2 Reserve Tank
Pressure Low
Main Tank Liquid Low -
from main bulk tank
Com
Com
Com
Reserve In Use -
from bulk O2 system
Com
Res. Tank Pressure Low -
from reserve bulk tank
Res. Tank Liquid Low -
from main bulk tank
Typical Master/Area Alarm Wiring Examples
Page 25
25
Part No. 6-847684-00 Rev. D01
B
A
C
D
E
F
G
H
I
J
K
L
M
N
A B C D E F G H
I J
K
L M N
Example 4: Two multi-signal master alarm panels -
duplex air compressor and vacuum pump systems.
O
P
Q
R
O
P Q
R
Typical Master/Area Alarm Wiring Examples
Med. Air Line
Pressure Low
Med. Air Line
Pressure High
Med. Air
CO High
Med. Air
Dew Point High
Med. Air
Lag Compressor
Air Comp.
High Temp.
Low Line
Vacuum
Lag Vacuum
Pump
Vacuum Pump
High Temp.
Med. Air Line
Pressure Low
Med. Air Line
Pressure High
Med. Air
CO High
Med. Air
Dew Point High
Med. Air
Lag Compressor
Air Comp.
High Temp.
Low Line
Vacuum
Lag Vacuum
Pump
Vacuum Pump
High Temp.
LOW
HIGH
com
com
n/c - not used
n/c
n/o
n/o - not used
Multi-Signal Module
Multi-Signal Module
Multi-Signal Module
Multi-Signal Module
Med. Air Line Pressure Switch -
connected to main med. air pipeline
High Dew Point -
from air comp. panel
High Carbon Monoxide -
from air comp. panel
Air Compressor Lag -
from air comp. panel
High Temp. # 2 -
from air comp. panel
High Temp. # 1 -
from air comp. panel
LOW
com
n/c - not used
n/o
High Temp. # 2 -
from vac pump panel
High Temp. # 1 -
from vac pump panel
Vacuum Pump Lag -
from vac pump panel
MASTER ALARM PANEL #1
MASTER ALARM PANEL #2
Vacuum Line Pressure Switch -
connected to main vacuum pipeline
Page 26
26
Part No. 6-847684-00 Rev. D01
Example 5: Area alarm panel - gas services for
oxygen, medical air, and vacuum.
I. C. U.
I. C. U.
I. C. U.
Oxygen
Sensor Module
Connected to main
oxygen pipeline
Med. Air
Sensor Module
Connected to main
med. air pipeline
Vacuum
Sensor
Module
Connected to main
vacuum pipeline
Oxygen Digital Display Module
Med. Air Digital Display Module
Vacuum Digital Display Module
pin 5 (+)
pin 6 (-)
pin 5 (+)
pin 6 (-)
pin 5 (+)
pin 6 (-)
Typical Master/Area Alarm Wiring Examples
NOTE:
Field wiring cable shields must be grounded at only one end, inside alarm panel back box. Refer to page 31 for details.
Page 27
27
Part No. 6-847684-00 Rev. D01
Front Panel Installation
Finish Installation
1. Remove front panel assembly from anti-static shipping bag.
2. Remove two front panel hinge mounting screws and lanyard mounting screw from alarm panel back box assembly (Figure 13).
3. Attach front panel hinge and lanyard to alarm panel back box using screws removed in step 2 as shown in Figure
14. Large (8-module) back boxes use two lanyards, one on each side.
Figure 13: Front Panel Hinge and Lanyard Screws
Figure 14: Attach Front Panel and Lanyard
Line Voltage Electrical Connection
1. Remove four nuts from plastic power supply shield.
2. Remove plastic shield from power supply. The plastic shield contains an in-line fuse holder that is wired to a two-pin plug on left side of power supply assembly. Remove two-pin plug from power supply.
3. The incoming line voltage hot and neutral wires should be connected via wire nuts to black (hot) and white (neutral) wires of power supply two-pin harness. Connect incoming ground wire to alarm box green ground wire. Refer to Figure 12.
4. Carefully position wires in bottom left corner of alarm panel box. Reconnect two-pin harness to power supply male connector. Harness connector is keyed to prevent incorrect orientation, however, use care to ensure correct pin alignment.
5. Reinstall plastic power supply shield while making sure all high voltage wires are contained within plastic shield.
6. Secure plastic shield with four nuts.
Figure 12: Line Voltage Connection
Hinge screws
Lanyard screw
Power Supply
Fuse Holder
Neutral (white)
Line (black)
Ground (green)
Page 28
28
Part No. 6-847684-00 Rev. D01
Finish Installation
4. The alarm panel’s power supply is factory installed with a three-wire harness attached to its right side. Connect loose end of three wire harness to male connector on annunciator module circuit board as shown in Figure 15. The harness connector is keyed to prevent incorrect orientation, however, use care to ensure correct pin alignment.
Figure 15: Power Supply Wire Harness
Remote Sensors:
1. Remove sensor module from shipping carton. Each sensor module is shipped with a wiring pigtail that has a two-pin polarized connector.
2. Wire nut pigtail to field installed wiring inside sensor mounting box. Note polarity of wiring and corresponding field wiring color or number for later.
3. Join polarized connector in sensor mounting box to mating connector on sensor module. Refer to Figure 16.
4. Insert sensor into valve opening in sensor rough-in. An indexing pin provides for proper orientation and prevents gas service cross­connection. Push sensor all the way in and secure with (2) #6-32 x 1-1/4” screws.
Figure 16: Sensor Module Connection
NOTE:
Remove the blue protective netting from the sen­sor connector.
Sensor Installation
Annunciator Module
Power Supply
Three-wire harness
Front Panel Installation
Valve opening
Sensor
Polarized connector
Male connector
NOTE:
Field wiring cable shields must be grounded at only on one end, inside alarm panel back box. Refer to page 31 for details.
black
red
Page 29
29
Part No. 6-847684-00 Rev. D01
1. Identify each pair of field installed sensor wires inside alarm panel back box assembly. Note polarity of each wire from previously installed remote sensor module.
2. Route each pair of sensor wires as shown in Figure 18 to appropriate digital display module. Each digital display module is labeled with the gas type. Verify the appropriate remote sensor wires are connected to correct digital display module.
Finish Installation
5. Tuck excess wiring into open space behind sensor.
6. Mark location monitored by sensor in space provided on sensor label. Refer to Figure 17.
Local Sensors:
1. Remove sensor module from shipping carton.
2. Insert sensor into valve opening in pressure/vacuum service rough-in. An indexing pin provides for proper orientation and prevents gas service cross-connection. Push sensor all the way in and secure with (2) #6-32 x 1­1/4” screws. Repeat this process for all sensors within alarm panel.
3. The digital display module(s) located on front panel assembly are factory wired with a harness and polarized two-pin connector for each sensor module. Each digital display module is labeled with the gas type. Match gas type of each sensor to gas type of each digital display module and join polarized connectors of sensor and digital display module harnesses.
4. Mark location monitored by sensor in space provided on sensor label. Refer to Figure 17.
Figure 17: Sensor Module Location Label
Remote Sensor Wiring
Figure 18: Remote Sensor Wire Routing
NOTE:
Remove the blue protective netting from the sen­sor connector.
Location label
Holes provided for entrance of remote wiring
Route wires behind metal brace
Sensor Installation
Page 30
30
Part No. 6-847684-00 Rev. D01
1. Identify each pair of field installed source equipment signal wires inside alarm panel back box assembly.
2. Route each pair of signal wires as shown in Figure 21 to appropriate multi-signal module.
3. Connect each pair of signal wires to desired multi-signal module terminals. The terminals are labeled “Signal 1” through “Signal 5”. Signal 1 corresponds to top row of indicators on front panel of multi-signal module. Signal 5 corresponds to bottom row. Refer to Figure 22.
4. Insert appropriate source equipment label into multi-signal module front panel as shown in Figure 23. A sheet of common source equipment signals has been provided for convenience. Blank labels are also provided.
Finish Installation
Source Equipment Wiring
CAUTION:
Source equipment signal wires must be connect­ed to normally-closed, dry contacts. No electrical voltage can be present and contacts must be closed during normal equipment operation. When contacts open, an alarm condition will be activat­ed.
NOTE:
Each pair of terminals labeled on the multi-signal module connector is labeled “+” and “COM”. Ensure that when a source equipment dry contact is wired to two master panels, the same side of the dry contact is connected to the same terminal at both panels. For example, if the source equip­ment’s normally closed contact is wired to the “+” of the first master panel, ensure it is also connect­ed to the “+” terminal of the second master panel.
3. Connect positive sensor wire to terminal 5 and negative sensor wire to terminal 6 for each remote sensor and digital display module. Refer to Figure
19.
4. Blank digital display module location labels are provided so each digital display module may be identified with area/zone that it is monitoring. Insert location labels (if desired) as shown in Figure 20.
Figure 19: Remote Sensor Wire Termination
Digital Display Module
From remote sensor
Pin 5 (+)
Pin 6 (-)
Figure 20: Digital Display Module
Remote Sensor Wiring
Label
(provided)
Slide label into slit in front panel overlay
Page 31
31
Part No. 6-847684-00 Rev. D01
Figure 23: Multi-Signal Front Panel Labeling
Finish Installation
Source Equipment Wiring
Figure 21: Source Equipment Wire Routing
Holes provided for entrance of remote wiring
Route wires behind metal brace
Figure 22: Source Signal Wiring Termination
Multi-Signal Module
Signal 1
Signal 2
Signal 3
Signal 4
Signal 5
Sample label
(provided)
Slide label(s) into slits in front panel overlay
Field Wiring Cable Shield Grounding
All field wiring cable shields must be grounded inside alarm panel back box. A grounding screw is provided in upper right corner of alarm back box as shown in Figure 24. Shields from several cables may be wrapped together and crimped into one ring lug (by others) .
Figure 24: Field Wiring Cable Shield Grounding
Cable shield
grounding screw
(crimp lug not provided)
CAUTION:
Keep shield wires to ground screw as short as possible so they can not touch front panel circuit boards when front panel is closed
Page 32
32
Part No. 6-847684-00 Rev. D01
There are several methods of connecting MEGA2 alarm panels to a building automation system depending upon what type of information is required and what type of building automation system is being used.
Multi-Signal Module Relays:
As an option, mutli-signal modules may be ordered with five output relays, one for each of five signals that multi-signal is capable of monitoring. Each relay has a set of dry, normally-closed contacts that will open when an alarm is activated on corresponding front panel signal. For example, when an alarm condition activates on top multi-signal front panel alarm location (Signal 1), relay labeled “Signal 1” will activate opening its contacts. Relay contacts will remain open as long as alarm condition is active, even
if audible alarm is silenced by MUTE button. When alarm condition is corrected, relay contacts will close.
Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC. Refer to Schematic 5 (Pg. 18).
Digital Display Module High/Low Relays:
Each digital display module is supplied with two separate output relays. One relay for high line pressure alarm and another for low line pressure alarm. Each relay has a set of dry, normally­closed contacts that will open when an alarm is activated on corresponding front panel signal. For example, when a low pressure alarm condition activates on digital display module front panel, relay labeled “Low Relay” will activate, opening its contacts. Relay contacts will remain open as long as alarm condition is active, even if audible alarm is silenced by MUTE
button.
Finish Installation
Building Automation System Wiring
When alarm condition is corrected, relay contacts will close. Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC. Refer to Figure Schematic 7 (Pg. 19).
Annunciator Module General Fault Relay:
The annunciator module is supplied with an alarm panel general fault output relay. This relay has a set of dry contacts that may be wired either normally open or normally closed. The relay will activate when ANY alarm on ENTIRE alarm panel is activated. Relay will remain activated as long as alarm condition is active, even
if audible alarm is silenced by MUTE button. When alarm condition is corrected, relay will deactivate. Relay contact ratings are
2 A @ 30 VDC/0.5 A @
125 VAC
. Refer to Schematic 6
(Pg. 19).
Annunciator Module Auxiliary Relay:
As an option, annunciator module may be supplied with an additional auxiliary relay. This auxiliary relay does not replace general fault relay described above. Auxiliary relay has a set of dry contacts that may be wired either normally open or normally closed. Like general fault relay, auxiliary relay will activate when ANY alarm on ENTIRE alarm panel is initiated. Unlike general fault relay, auxiliary relay will deactivate when audible alarm is
silenced by MUTE button. If alarm condition is still active when mute function cancels, auxiliary relay will reactivate. Relay contact ratings are 2 A @ 30 VDC/0.5 A @ 125 VAC. Refer to Schematic 6 (Pg. 19).
Page 33
33
Part No. 6-847684-00 Rev. D01
Finish Installation
Johnson Controls METASYS® System:
The MEGA2 alarm panel is compatible with Johnson Controls METASYS® building automation system (Using METASYS® Integrator). Each MEGA2 alarm panel is connected to a common two-wire RS-485 serial computer interface bus. Two wires are connected to pins 1 and 2 of annunciator module and then connected to common data bus. Refer to Schematic 9 (Pg. 21) for details. Each digital display module and multi-signal module within alarm panel is field programmed with a unique network address. Using this address, Johnson Controls system can monitor alarm panel status including digital pressure readings and programmed alarm set points.
Building Automation System Wiring
Digital display modules of two alarm panels may be wired together in such a way that pressure readings of first panel can be duplicated at second panel. Each digital display module has RS-422 digital outputs and inputs. By connecting digital output (master output) of first panel to digital inputs (slave input) of the second panel, second panel will duplicate pressure readings. Refer to Schematic 4 (Pg. 17) for details.
Slave Panel Wiring
Page 34
34
Part No. 6-847684-00 Rev. D01
Operation
Start-Up and Checking
Digital Display Module
Multi-Signal Module
Status LED
Indicators
LED Display
SIGNAL #1
SIGNAL #2
SIGNAL #3
SIGNAL #4
SIGNAL #5
Status LED
Indicators
NOTE:
If any module appears to be malfunctioning, refer to Troubleshooting Guide.
1. Turn on electrical power to alarm
panel.
2. Make following observations:
POWER ON light illuminates on front of alarm panel.
Digital display and multi-signal modules warm-up for ten seconds. During warm-up, no audible or visual alarms activated. After warm-up, audible and visual alarms are initiated for any active alarm.
3. Press MUTE button to silence audible alarm.
4. Pressurize piping system (medical gas and vacuum).
5. Make following observations:
Digital display modules display
actual pipeline pressures or vacuum levels.
If digital display module pipeline
pressures and vacuum levels are within pre-set limits, NORMAL indicator is illuminated.
If digital display module pipeline
pressures and vacuum levels are outside pre-set limits, status indicators show HIGH or LOW.
If a fault code is displayed (
-- FF 11 --
,
-- FF 22 --, -- FF 33 --
or
-- FF 44 --
) refer to
Troubleshooting Guide.
Multi-signal modules indicate
current status from dry-contact switches. Unused signals can be disabled. Refer to Set-Up Procedure.
Page 35
35
Part No. 6-847684-00 Rev. D01
Operation
Set-Up Procedure
Digital display modules are shipped from the factory with the following settings:
Gas/Vacuum Alarm Set Point Service Low High Pressure (50 psig) 40 psig 60 psig Pressure (100 psig) 80 psig 120 psig Nitrogen, Instr. Air 140 psig 190 psig Vacuum/WAGD 12 in Hg. none
Changing units and alarm set points:
1. Loosen two screws on front of alarm panel. Hinge open alarm panel’s front cover.
2. Locate SETUP button on circuit board of digital display module to be adjust­ed.
3. Press and release SETUP button. Audible alarm will chirp and
SS EE TT 11
will
be displayed.
4. Press and release TEST button on front of alarm panel. Current unit of measure will be displayed. Select desired unit of measure by pressing either ! or " buttons. Available units of measure are:
KK PP AA
(kPa)
PP SS II
(psig)
II NN KK 99
(in Hg)
NN NN KK 99
(mm Hg)
5. Press and release TEST button. The LOW indicator will illuminate and
LL OO
will be displayed. After two seconds current low alarm setting will be dis­played. Select desired low alarm set­ting by pressing either ! or " but­tons. Low alarm setting ranges are:
00
to
11 33 88 00(11 77 22 55
*) (kPa)
00
to
22 00 00(22 55 00
*) (psig)
00
to
33 22
(in Hg)
00
to
88 00 00
(mm Hg)
*N2 and instrument air only, DDM firmware 1.0.6 or later
Digital Display Module
SETUP
button
TEST
button
Up and down
buttons
NOTE:
Audible alarm will chirp with each button push.
If module is idle for more than one minute during set-up procedure, module will chirp three times, return to monitor mode and will default to previ­ous settings. No changes to settings will be saved.
The set-up must be completed and the module
must display
DD OO NN EE
in order for changes to be
saved.
Low alarm
indicator
High alarm
indicator
Display
Digital Display Module
Page 36
36
Part No. 6-847684-00 Rev. D01
Operation
Set-Up Procedure
6. Press and release TEST button. HIGH indicator will illuminate and
KK ,,
will be displayed. After two seconds current high alarm setting will be dis­played. Select desired high alarm set­ting by pressing either ! or " but­tons. High alarm setting ranges are:
00
to
11 33 88 00(11 77 22 55
*) (kPa)
00
to
22 00 00(22 55 00
*) (psig)
00
to
33 22
or
NN OO NN EE
(in Hg)
00
to
88 00 00
or
NN OO NN EE
(mm Hg)
*N2 and instrument air only, DDM firmware 1.0.6 or later
7. Press and release TEST button to save changes.
DD OO NN EE
will be dis­played for two seconds. Digital dis­play module will return to monitoring mode.
NN DD FF
(network data format)
Defines data word length transmitted to building automation system. User
choices are
88
(bits) or
11 66
(bits). Factory
setting is 88.
PP DD FF
(pressure data format) Defines data word length transmitted to a slave alarm panel. User choices are
88
(bits) or
11 66
(bits). Factory setting is 88.
The second advanced level,
SS EE TT 33
, is used to adjust other miscellaneous parameters as listed below:
SS EE RR UU
(gas service identification)
Used to set digital display module’s gas service identification for communication with a digital sensor.
User choices are:
00 22
(oxygen)
NN 22 00
(nitrous oxide)
AA ,, RR
(medical air)
UU AA ((
(vacuum)
NN 22
(nitrogen)
LL AA ,, RR
(lab air)
LL UU AA ((
(lab vacuum)
AA RR 99 NN
(argon)
(DDM firmware 1.0.6 or later)
II AA ,, RR
(instrument air)
UU AA 99 DD
(WAGD)
(( 00 22
(carbon dioxide)
(( -- 00 22
(CO2/O2)
00 22 -- ((
(O2/CO2)
KK EE 00 22
(He/O2)
00 22 KK EE
(O2/He)
KK EE
(Helium)
NN OO NN EE
(none)
OO FF FF SS
(display offset) Used to adjust digital module’s display. User choices are 00,11,22,
-- 11
, or
-- 22
.
Factory setting is 00.
Digital Display Module
(Advanced)
Digital Display Module
Two additional levels of “advanced” set-up features are available.
The first advanced level,
SS EE TT 22
, is used to adjust basic communication related parameters. The parameters adjustable
within
SS EE TT 22
are listed below:
AA DD DD RR
(network address)
A network address uniquely identifies each digital display module to a personal computer or Johnson Controls
Metasys
®
system. Address range is
00
to
22 55 55
. Factory setting is 00.
BB AA UU DD
(baud rate) Used to set communication speed. User choices are
44 88 00 00
or
99 66 00 00
.
Factory setting is
44 88 00 00
.
NOTE:
Set to
NN OO NN EE
if using analog sensors.
Page 37
37
Part No. 6-847684-00 Rev. D01
RR EE PP TT
(audible alarm repeat)
Used to set time interval for reactivation of audible alarm after
alarm MUTE button has been pressed. User choices are
OO FF FF,11,55
,
11 55,33 00
(minutes),
11 HH RR, 88 HH RR, 11 22 HH RR
or
22 44 HH RR
(hour). Factory setting is
OO FF FF
.
When set to
OO FF FF
, audible alarm will not reactivate after an active alarm has been silenced. Any new alarm will reactivate audible alarm.
II NN TT SS
(display intensity) Used to adjust digital module’s display brightness. Factory setting is
maximum intensity.
Changing Communication Parameters -
(
SS EE TT 22
):
1. Press and HOLD SETUP button for TWO seconds until
SS EE TT 22
is displayed.
2. Press and release TEST button on front of alarm panel.
AA DD DD RR
will be displayed for one second and then current network address. Select
desired address by pressing ! or " buttons. Each module must have a unique address.
3. Press and release TEST button.
BB AA UU DD
will be displayed for one second
and then current baud rate. Select desired baud rate by pressing ! or " buttons.
4. Press and release TEST button.
NN DD FF
will be displayed for one second and
Operation
Set-Up Procedure
NOTE:
If module is idle for more than one minute during set-up procedure, module will chirp three times, return to monitor mode and will default to previous settings. No changes to settings will be saved.
Set-up must be completed and module must dis-
play
DD OO NN EE
in order for changes to be saved.
then current network data format. Select desired data format by pressing ! or " buttons.
5. Press and release TEST button.
PP DD FF
will be displayed for one second and then current pressure data format. Select desired data format by pressing ! or " buttons.
6. Press and release TEST button to save changes.
DD OO NN EE
will be displayed for two seconds. Digital display module will return to monitoring mode.
Changing Miscellaneous Parameters -
(
SS EE TT 33
):
1. Press and HOLD SETUP button for FOUR seconds until
SS EE TT 33
is
displayed.
2. Press and release TEST button on front of alarm panel.
SS EE RR UU
will be displayed for one second and then current gas service identification. Select desired gas service by
pressing ! or " buttons.
3. Press and release TEST button.
OO FF FF SS
will be displayed for one second
and then current display offset. Select offset by pressing ! or " buttons.
4. Press and release TEST button.
RR EE PP TT
will be displayed for one second and then current audible alarm repeat time. Select desired repeat time by
pressing ! or " buttons.
5. Press and release TEST button.
II NN TT SS
will be displayed. Select desired display brightness by pressing !
or " buttons. Each push will change brightness of display. Audible alarm will chirp one time with each push and two times when limit reached.
6. Press and release TEST button to save changes.
DD OO NN EE
will be displayed for two seconds. Digital display module will return to monitoring mode.
Digital Display Module (Advanced)
Page 38
38
Part No. 6-847684-00 Rev. D01
Operation
Set-Up Procedure
Multi-Signal Module
Changing signal options:
1. Loosen two screws on front of alarm panel. Hinge open front cover.
2. Locate SETUP button on circuit board of multi-signal module to be adjusted.
3. Press and release SETUP button. Audible alarm will chirp and both green and red indicators for top location (Signal 1) will illuminate.
4. Using either ! or " buttons, enable or disable Signal 1 location. When red indicator is illuminated, location is ENABLED. Turning off red indicator disables location. Signal locations can not be disabled if wired to a closed­contact circuit.
5. Press and release TEST button on front of alarm panel. Both green and red indicators for second location (Signal 2) will be illuminated.
6. Using either ! or " buttons, enable or disable Signal 2 location. When red LED is illuminated, location is enabled. Turning off red LED disables location.
7. Repeat steps 5 and 6 above for remaining signal locations (Signal 3, 4, and 5).
8. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence has been reached. Multi­signal module will return to monitoring mode.
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
TEST
button
Up and down
buttons
NOTE:
Audible alarm will chirp with each button push.
If module is idle for more than one minute during set-up procedure, module will chirp three times, return to monitor mode and will default to previ­ous settings. No changes to settings will be saved.
The set-up must be completed in order for changes to be saved.
Multi-Signal Alarm Module Circuit Board
SETUP
button
Green LED
Red LED
SIGNAL 1
Page 39
39
Part No. 6-847684-00 Rev. D01
Operation
Multi-Signal Module (Advanced)
Set-Up Procedure
Two additional levels of “advanced” set-up features are available. The first level is used to adjust basic communication related parameters. The second level is used to adjust alarm repeat time and display intensity.
Setting Communication Parameters:
A network address uniquely identifies each multi-signal alarm module to a personal computer or Johnson Controls Metasys
®
system. Address range is 0 to
255. Factory default setting is 0. Since a multi-signal alarm module does not have a digital display, network address is shown as a binary number on specific red and green front panel LED indicators. Table below assigns a numeric value to each specific LED indicators. For example, if LED indicators for bits 0, 1, 2, and 3 were all illuminated, network address would be 15 (1+2+4+8=15).
Binary data represented by LED indicators
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
128 64 32 16 8 4 2 1
Numeric value of each bit
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Bit 4 (green)
Bit 0 (red)
Bit 1 (red)
Bit 2 (red)
Bit 3 (red)
Bit 5 (green)
Bit 6 (green)
Bit 7 (green)
1. Press and HOLD set-up button. Audible alarm will chirp when set-up button is first pushed and again two seconds later. Release button after second audible alarm chirp. Multi­signal alarm module front panel LED indicators (Bit 0 through Bit 7) will show current network address. If no indicators are illuminated, address is 0 (factory setting).
2. Using either ! or " buttons, select desired network address between 0 and 255.
3. Press and release TEST button on front of alarm panel. Front panel LED indicators (Bit 0 and Bit 4) will show current communication baud rate. If only Bit 4 LED is illuminated, baud rate is 4800 (factory setting). If BOTH Bit 0 and Bit 4 LEDs are illuminated, baud rate is 9600.
4. Using either ! or " buttons, select desired baud rate (4800 or 9600).
5 Press and release TEST button on
front of alarm panel. Front panel LED indicators (Bit 1 and Bit 5) will show current communication data format. If only Bit 5 LED is illuminated, data format is 8-bit word length (factory setting). If BOTH Bit 1 and Bit 5 LEDs are illuminated, data format is 16-bit word length.
6. Using either ! or " buttons, select desired data format (8-bit or 16-bit).
7. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence has been reached. Multi­signal module will return to monitoring mode.
Page 40
40
Part No. 6-847684-00 Rev. D01
Setting Audible Alarm Repeat Time and Display Intensity:
Used to set time interval for reactivation
of audible alarm after alarm MUTE button has been pressed.
1. Press and HOLD SETUP button. Audible alarm will chirp when SETUP button is first pushed, again after two seconds and a third time after four seconds. Release button after third audible alarm chirp. Multi-signal module front panel LED indicators will show current audible alarm repeat time as shown below:
Indicator Illuminated Repeat Time
None OFF Signal 1 - red 1 Min. Signal 2 - red 5 Min. Signal 3 - red 15 Min. Signal 4 - red 30 Min. Signal 1 - green 1 Hr. Signal 2 - green 2 Hr. Signal 3 - green 8 Hr. Signal 4 - green 12 Hr. Signal 5 - green 24 Hr.
2. Using either ! or " buttons, select desired audible alarm repeat time.
3 Press and release TEST button on
front of alarm panel. All LED indicators will illuminate.
4. Select desired display brightness by pressing either ! or " buttons. Each push will increase or decrease brightness of display. Audible alarm will chirp one time with each button push and two times when limit is reached.
5. Press and release TEST button to save changes. LEDs will sweep from top to bottom to indicate end of set-up sequence. Multi-signal module will return to monitoring mode.
Operation
Set-Up Procedure
Monitoring Mode
Monitoring mode is the normal operating mode of the MEGA2system.
Digital Display Module:
Digital display modules monitor pipeline pressure or vacuum.
• The LED display indicates pipeline pressure or vacuum.
• If piping pressure or vacuum level is within high and low alarm limits, green NORMAL indicator is illuminated.
• If pressure or vacuum level drops to, or below, low alarm set-point, audible alarm activates and red LOW indicator flashes.
• If pressure or vacuum level rises to, or above, high alarm set-point, audible alarm activates and red HIGH indicator flashes.
• When front panel alarm MUTE button is pressed, audible alarm is silenced. Alarm indicator remains illuminated, but does not flash.
• Visual indicator will remain illuminated as long as alarm condition remains.
• If audible alarm repeat time has been set, audible alarm will reactivate, and visual indicator will again flash after specified time.
NOTE:
Sensor faults will be displayed as
-- FF 11 --, -- FF 22 --
,
-- FF 33 --
or
-- FF 44 --
error codes. Refer to trou-
bleshooting section for details.
Multi-Signal Module (Advanced)
Page 41
41
Part No. 6-847684-00 Rev. D01
Operation
Multi-Signal Module:
Multi-Signal modules monitor up to five dry-contact switches.
• If the signal is normal (switch contacts closed), green indicator for signal is illuminated.
• If an alarm occurs (switch contacts open), audible alarm activates and red indicator for signal flashes.
• When front panel alarm MUTE button is pressed, audible alarm is silenced. Alarm indicator remains illuminated, but does not flash.
• Visual indicator will remain illuminated as long as alarm condition remains.
• If audible alarm repeat time has been set, audible alarm will reactivate, and visual indicator will again flash after specified time.
Monitoring Mode
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Testing
Digital Display Module:
Press and hold the front panel TEST but­ton for five seconds to initiate the following sequence:
Audible alarm sounds briefly as
TT EE SS TT
is
displayed.
All LED display segments and LOW, NORMAL, and HIGH indicators flash for five seconds (firmware up to revision
1.0.3).
LED display segments and LOW,
NORMAL, and HIGH indicators illuminate in sequence (firmware revision 1.0.4 and later).
Firmware revision (e.g.
11.. 00.. 66
) is displayed
for two seconds.
AA DD DD RR
is briefly displayed and then current MEGA network module address is displayed for two seconds. (Factory default
address is 00).
Current units of measure setting (e.g.
PP SS II
)
is displayed for two seconds.
LL OO
is briefly displayed, LOW alarm indicator is illuminated, and current low alarm set point is displayed for two seconds.
KK ,,
is briefly displayed, HIGH alarm indicator is illuminated, and current high alarm set point is displayed for two seconds.
Module returns to monitoring mode.
Front panel
TEST button
Periodic testing of alarm system is recommended. Digital display modules and multi-signal alarm modules have built­in self-test modes. Front panel TEST button will initiate self-test mode on all alarm panel modules at same time.
Page 42
42
Part No. 6-847684-00 Rev. D01
Testing
Multi-Signal Module:
Press and hold front panel TEST button for five seconds to initiate following sequence:.
• Audible alarm sounds briefly.
• All red and green indictors flash for five seconds.
• Software revision is displayed as follows:
- Expressed as a three digit number
(e.g. 1.0.2).
- Each digit of number is displayed
separately for two seconds and separated from the next digit by a brief flashing of all indicators.
- Each number is displayed in a
binary code where each multi-signal module indicator has a binary value.
- Example: Software revision 1.0.2
would be displayed as follows:
First digit is determined by two second illumination of top left indicator (bit 0 = number 1).
All indicators quickly flash.
Second digit is determined to be 0 because no indicators are illuminated for two seconds.
All indicators quickly flash.
Third digit of is determined by two second illumination of second left indicator (bit 1 = number 2).
• After all three digits of software revision have been displayed, all indicators illuminate for one second before displaying current MEGA network address.
• Current network address is displayed for two seconds in a binary code where each multi-signal module indicator has a binary value.
• All indicators illuminate for one second and module returns to monitoring mode.
SIGNAL 1
SIGNAL 2
SIGNAL 3
SIGNAL 4
SIGNAL 5
Bit 4 (green)
Bit 0 (red)
Bit 1 (red)
Bit 2 (red)
Bit 3 (red)
Bit 5 (green)
Bit 6 (green)
Bit 7 (green)
Binary data represented by LED indicators
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
128 64 32 16 8 4 2 1
Numeric value of each bit
Page 43
43
Part No. 6-847684-00 Rev. D01
Testing
Power Supply Assembly:
The power supply assembly converts AC mains power to +5 and +24 volts DC. AC mains power can be any value between 100 and 250 volts AC. In order to verify power supply assembly is functioning correctly, perform following procedure.
1. Loosen two front panel screws and open alarm panel.
2. If no indicator lights or LED displays are illuminated on front of alarm panel, first verify internal fuse is good (Figure 25). If fuse is good, continue this procedure.
3. Using a digital volt meter, measure DC voltage between black (-) and orange (+) wires where power supply harness plugs into annunciator module (Figure 26).
When making measurements, do not disconnect cable from annunciator board. Insert meter
probes into back of white plastic connector.
4. Verify DC voltage is 4.5 to 5.5 volts.
5. Measure voltage between black (-) and red (+) wires.
6. Verify DC voltage is 22.0 to 26.0 volts.
7. If voltages above are not within specification, verify correct AC input power as follows:
8. Remove four keps nuts and plastic shield from power supply. Do not disconnect wires from fuse holder or harness from power supply.
9. Position plastic shield (wires attached) so that power supply’s AC input connector is accessible.
WARNING:
RISK OF ELECTRIC SHOCK ! USE EXTREME CAUTION -
The remainder of this procedure requires removal of the clear plastic power supply shield. Even if fuse is removed, the high voltage input wiring remains energized.
10.Using a digital volt meter, measure AC voltage between white (neutral) and black (line) wires on back of power supply connector (Figure 27). Verify AC input voltage is 100 to 250 volts.
11. If AC input voltage is within specification, replace power supply assembly.
Figure 25: Alarm Panel Internal Fuse
Internal fuse holder
Page 44
44
Part No. 6-847684-00 Rev. D01
Testing
Figure 26: Power Supply Output Testing
Figure 27: Power Supply AC Input Testing
Three-wire harness
from power supply
Black (gnd)
Orange (+5)
Red (+24)
Annunciator Module
Line (black)
Neutral (white)
Power Supply Assembly
Fuse
Holder
Page 45
45
Part No. 6-847684-00 Rev. D01
Troubleshooting Guide
Symptom Possible Cause Corrective Action
a. AC power is not turned on. b. Blown internal fuse. c. AC power wiring is not
connected.
d. Three-wire power supply
harness is not connected between power supply and annunciator board
e. Faulty power supply
assembly.
a. Check AC power source. b. Replace fuse. c. Check AC entrance wiring at power
supply terminals. Verify two-pin plastic connector is plugged into power supply circuit board.
d. Check connections on each end
including orientation of cable connectors. Reconnect if necessary.
e. Replace power supply assembly.
1) No visual indicators illuminated on entire alarm panel
a. 20-wire ribbon cable(s)
between annunciator module and digital display or multi­signal modules not
connected. b. Faulty 20-wire ribbon cable. c. Faulty digital display or multi-
signal module. d. Faulty annunciator module.
2) No visual indicators illuminated on isolated module(s). Green annunciator module POWER indicator is illuminated.
a. Reconnect ribbon cable(s). b. All alarm panels have two 20-wire
ribbon cables (attached to annunciator connectors “J1” and “J2”). Remove suspect cable (both ends) and replace with other cable. If problem is corrected, replace faulty cable.
c. If alarm panel contains another
working digital display or multi-signal module, unplug ribbon cable from working module and connect to non­working module. If module does not illuminate, replace faulty digital display or multi-signal module.
d. Replace faulty annunciator module.
3) Constant audible alarm that can not be silenced by pressing front panel MUTE
button. No visual alarm on any digital display or multi-signal module.
a. Faulty digital display or multi-
signal module. b. Faulty 20-wire ribbon cable. c. Faulty annunciator module.
a. Disconnect digital display and/or
multi-signal modules one at a time from 20-wire ribbon cables. If disconnecting a module cancels audible alarm, replace that faulty module.
b. After all modules have been
disconnected from 20-wire ribbon cables, disconnect each cable, one at a time from annunciator module. If disconnecting ribbon cable cancels alarm, replace that faulty cable.
c. If both 20-wire ribbon cables have
been removed from annunciator module, and audible alarm has not cancelled, replace faulty annunciator module.
Page 46
46
Part No. 6-847684-00 Rev. D01
6) Audible alarm does not sound when visual indicator is illuminated. Pressing front
panel MUTE button causes visual indicator to stop flashing but remain illuminated.
a. 20-wire ribbon cable not
connected well to annunciator module or digital display/multi-signal module
with visual alarm. b. Faulty 20-wire ribbon cable. c. Faulty annunciator module. d. Faulty digital display or multi-
signal module.
a. Reconnect ribbon cable(s). b. All alarm panels will incorporate two
20-wire ribbon cables. Exchange cable connected to affected module with other one (assuming all modules connected to that cable are working correctly). If problem follows cable, replace cable.
c. Cause an alarm condition (by
unplugging field wiring connector) on another module that is connected to same 20-wire ribbon cable. Verify audible alarm on this test module activates. If audible alarm does not activate, replace faulty annunciator module.
d. If audible alarm on test module (step c)
activates, replace faulty digital display or multi-signal module.
Troubleshooting Guide
Symptom Possible Cause Corrective Action
5) Flashing visual indicator and audible alarm on digital display or multi-signal module that can not be silenced by pressing front
panel MUTE button. When MUTE button is pressed, visual indicator continues to flash.
a. 20-wire ribbon cable not
connected well to annunciator module or digital display/multi-signal module
with visual alarm. b. Faulty 20-wire ribbon cable. c. Faulty annunciator module. d. Faulty digital display or multi-
signal module.
a. Reconnect ribbon cable(s). b. All alarm panels will incorporate two 20-
wire ribbon cables. Exchange cable connected to affected module with other one (assuming all modules connected to that cable are working correctly). If problem follows cable, replace cable.
c. Cause an alarm condition (by
unplugging field wiring connector) on another module that is connected to same 20-wire ribbon cable. Verify visual indicators on this test module
stop flashing when MUTE button is pressed. If visual indicators continue to flash, replace faulty annunciator module.
d. If visual indicators on test module (step
c) stop flashing when MUTE button is pressed, replace faulty digital display or multi-signal module.
4) Visual indicators are dimly illuminated or vary in brightness between one or more digital display or multi­signal modules. Front panel green POWER indicator is illuminated brightly.
a. Programmable display
intensity levels have been set too low or at different values between modules.
b. Faulty digital display or multi-
signal module.
a. Reset display intensity values for
each module. Refer to Set-Up instructions pages 35 - 40.
b. Replace faulty module.
Page 47
47
Part No. 6-847684-00 Rev. D01
Troubleshooting Guide
Symptom Possible Cause Corrective Action
7) Audible alarm reactivates a short period of time after
MUTE button has been pressed.
a. A new alarm condition has
occurred.
b. Programmable alarm repeat
function has reactivated audible alarm.
a. If alarm condition previously silenced
self-corrects and then reactivates again, alarm panel treats as a new alarm condition. Flashing visual indicators represent new alarm conditions. After being silenced, visual indicators will stop flashing, but remain illuminated.
b. Set alarm repeat value at desired
time interval. Refer to Set-Up instructions pages 35 - 40.
8) Audible alarm activates when it should, but sound level is too low.
a. Audible alarm volume is set
too low.
b. Faulty annunciator module.
a. Adjust alarm volume potentiometer
located on annunciator module clockwise to increase. Factory default setting is max. clockwise position (max. volume).
b. Replace faulty annunciator module.
10)Multi-signal alarm will not activate on either master alarm when source contacts open.
a. Correct field wiring. Verify common
wire of both master panels are connected to same side of source equipment switch.
9) Multi-signal alarm will not activate on one master alarm when source contacts open. Second master works correctly.
a. Field wiring misconnection. b. Faulty multi-signal module.
a. Correct field wiring. Verify multi-
signal module is connected to correct source equipment switch.
b. Replace multi-signal module.
11) One or more multi-signal alarms are in alarm condition even though they are not wired to source equipment.
a. Field wiring misconnection.
a. Unused signals have not
been turned off.
a. Perform programming procedure in
order to turn off unused signals. Refer to Set-Up instructions pages 35 through 40.
12)High or low pressure alarm activated when digital dis­play indicates pressure or vacuum is within normal lim­its.
a. Alarm set-points have been
changed.
b. Faulty digital display module.
a. Use digital display module test mode
as described on page 41 to check current set-points. If incorrect, reprogram low and/or high alarm set­pints. Refer to Set-Up instructions pages 35 through 40.
b. Replace faulty digital display module.
Page 48
48
Part No. 6-847684-00 Rev. D01
14)Low alarm with
-- FF II --
display
on digital display module.
No pressure or vacuum signal to digital display module as a result of: a. Sensor wiring disconnected
or wiring polarity reversed. b. Faulty digital display module. c. Faulty sensor module.
a. Correct sensor wiring. If sensor is
mounted remotely, verify field wiring continuity and polarity from sensor to digital display module connector pins 5 (+) and 6 (-).
b. If alarm panel contains another
working digital display module, remove field wiring connector from suspect module and connect to working (test) module. If test module
provides any reading other than
-- FF II --
, replace faulty digital display module.
c. If test module in step b above also
gives
-- FF II --
, replace faulty sensor
module.
15)Low alarm with
-- FF 22 --
display on digital display module.
Pressure or vacuum signal to digital display module out of measurement range (too low) as a result of: a. No pressure or vacuum in
pipeline. b. Faulty digital display module. c. Faulty sensor module.
a. Apply appropriate pressure or
vacuum to pipeline.
b. If alarm panel contains another
working digital display module, remove field wiring connector from suspect module and connect to working (test) module. If test module provides any reading other than
-- FF 22 --
, replace faulty digital display
module.
c. If test module in step b above also
gives
-- FF 22 --
, replace faulty sensor
module.
13)Pressure or vacuum digital display does not match pressure or vacuum levels in pipeline.
a. Incorrect digital display “unit
of measure”. b. Faulty digital display module. c. Faulty sensor module.
a. Use digital display module test mode
as described on page 41 to check current unit of measure (PSI, in Hg, kPa, mm Hg). If incorrect, reprogram unit of measure. Refer to Set-Up instructions pages 35 through 40.
b. If alarm panel contains another
working digital display module, remove field wiring connector from suspect module and connect to working (test) module. If test module provides correct reading, replace faulty digital display module.
c. If test module in step b above also
gives incorrect display, replace faulty sensor module.
Troubleshooting Guide
Symptom Possible Cause Corrective Action
Page 49
49
Part No. 6-847684-00 Rev. D01
Symptom Possible Cause Corrective Action
Troubleshooting Guide
16)High alarm with
-- FF 33 --
display on digital display module.
Pressure or vacuum signal to digital display module out of measurement range (too high) as a result of: a. Shorted sensor wiring. b. Faulty digital display module. c. Faulty sensor module.
a. Correct sensor wiring. b. If alarm panel contains another
working digital display module, remove field wiring connector from suspect module and connect to working (test) module. If test module provides any reading other than
-- FF 33 --
, replace faulty digital display
module.
c. If test module in step b above also
gives
-- FF 33 --
, replace faulty sensor
module.
17)High and low alarm with
-- FF 44 --
display on digital
display module.
Gas/vacuum service mismatch between digital display module and digital sensor module as a result of: a. Sensor wired to wrong digital
display module.
b. Digital display module
programmed with the wrong service.
a. Correct sensor wiring. b. Program digital display module for
the correct gas/vacuum service. Refer to Set-Up instructions page 36.
18)No blinking LED on digital sensor module.
No power to digital sensor due to: a. Faulty wiring. b. Faulty digital sensor module.
a. Correct sensor wiring. b. Replace digital sensor module.
19)Fast blinking LED on digital sensor module.
Sensor out of range: a. Vacuum digital sensor
module connected to pressure service.
b. Pressure digital sensor
module connected to vacuum service.
c. Faulty digital sensor module.
a. Verify piping connections. Vacuum
sensor maximum overpressure: 30
psi. b. Verify piping connections. c. Replace digital sensor module.
Page 50
50
Part No. 6-847684-00 Rev. D01
1
2
3
12
11
9
10
8
7
Replacement Parts
ITEM
PART
NUMBER DESCRIPTION
1 6-868163-00 20-wire Ribbon Cable (4-module alarm box)
- 6-868164-00 20-wire Ribbon Cable (8-module alarm box)
2 6-865315-00 Field Wiring Connector - Annunciator Module 3 6-231982-00 Circuit Board - Annunciator Module (includes item 2)
- 6-231982-RL Circuit Board - Annunciator Module with Auxiliary Relay (includes item 2)
4 6-811611-00 Screw - #6-32 x 7/16”, Pan Head 5 6-838104-00 Lanyard 6 6-814669-00 Screw - #6-20 x 1/4”, Pan Head, Self-Tapping 7 6-811752-00 Screw - #6-32 x 1-1/4”, Pan Head 8 6-811058-00 Screw - #4-40 x 1/4”, Flat Head 9 6-838982-00 Hinge 10 6-231980-00 Circuit Board - Digital Display Module (includes item 12)
- 6-231981-00 Circuit Board - Multi-Signal Module (includes item 12)
- 6-231981-RL Circuit Board - Multi-Signal Module with Relays (includes item 12)
11 6-811608-00 Screw - #6-32 x 1/4”, Pan Head 12 6-865316-00 Field Wiring Connector - Digital Display/Multi-Signal Module
4
6
5
Front Panel Components
Page 51
51
Part No. 6-847684-00 Rev. D01
Replacement Parts
Back Box Components
4
5
6
7
8
9
10
11
12
13
14
15
16
18
17
1
ITEM PART NUMBER DESCRIPTION
1 6-814669-00 Screw - #6-20 x 1/4”, Pan Head, Self-Tapping 2 6-425458-00 Shield 3 6-814669-00 Screw - #6-20 x 1/4”, Pan Head, Self-Tapping 4 6-231938-00 Wire Harness - Power Supply Ground 5 6-231941-00 Wire Harness - Ground 6 6-814008-00 Screw - Grounding 7 6-231937-00 Wire Harness - AC Input 8 6-231939-00 Wire Harness - Fuse 9 Included In Item 11 Nut - Fuse Holder 10 6-616506-00 Shield - Power Supply 11 6-865500-00 Fuse Holder 12 6-865546-00 Fuse - 1.0 Amp, 250VAC, Time Delay 13 Included In Item 11 Fuse Holder Cap 14 6-827530-00 Nut - #6-32, Keps 15 6-231936-00 Wire Harness - Power Supply DC Output 16 6-829628-00 Standoff 17 6-867540-00 Power Supply Assembly 18 6-831904-00 Spacer
3
2
Page 52
52
Part No. 6-847684-00 Rev. D01
Replacement Parts
Sensor Components
Applicable to both local and
remote sensor mounting
Remote sensor mounting only
1
2
9
6
7
4
5
ITEM PART NUMBER DESCRIPTION
1 6-814669-00 Screw - #6-20 x 1/4”,
Pan Head, Self-Tap 2 6-425428-00 End Cap 3 Sensor Mounting Assy.
(incl. items 1,2,6,7& 9)
- 6-129340-10 Oxygen
- 6-129340-11 Nitrous Oxide
- 6-129340-12 Medical Air
- 6-129340-13 Vacuum
- 6-129340-14 Nitrogen
- 6-129340-16 Air (ISO)
- 6-129340-17 Vacuum (ISO)
- 6-129340-18 Instrument Air
- 6-129340-19 WAGD
- 6-129340-20 Carbon Dioxide
- 6-129340-21 CO2/O2
- 6-129340-22 O2/CO2
- 6-129340-23 He/O2
- 6-129340-24 O2/He
- 6-129340-25 Helium
- 6-129340-26 Lab Air
- 6-129340-27 Lab Vacuum
- 6-129340-28 O2 (100 PSI)
- 6-129340-29 Air (100 PSI)
- 6-129340-30 CO2 (100 PSI)
ITEM
PART NUMBER
DESCRIPTION
4 6-231935-00 Sensor Pigtail 5 Analog Sensor
- 6-231760-00 Oxygen
- 6-231761-00 Nitrous Oxide
- 6-231762-00 Medical Air
- 6-231763-00 Vacuum
- 6-231764-00 Nitrogen
- 6-231765-00 Helium
- 6-231766-00 Lab Air
- 6-231767-00 Lab Vacuum
- 6-231768-00 Instrument Air
- 6-231769-00 WAGD
- 6-231770-00 Carbon Dioxide
- 6-231771-00 CO2/O2
- 6-231772-00 O2/CO2
- 6-231773-00 He/O2
- 6-231774-00 O2/He
- 6-231776-00 Air (ISO)
- 6-231777-00 Vacuum (ISO)
- 6-231778-00 Oxygen (100PSI)
- 6-231779-00 Air (100 PSI)
- 6-231780-00 CO2 (100 PSI) 6 6-814669-00 Screw - #6-20 x 1/4”,
Pan Head, Self-Tap
7 6-425555-00 Mounting Box
3
8
Page 53
53
Part No. 6-847684-00 Rev. D01
ITEM PART NUMBER DESCRIPTION
8 Digital Sensor
- 6-232460-00 Oxygen
- 6-232461-00 Nitrous Oxide
- 6-232462-00 Medical Air
- 6-232463-00 Vacuum
- 6-232464-00 Nitrogen
- 6-232465-00 Helium
- 6-232466-00 Lab Air
- 6-232467-00 Lab Vacuum
- 6-232468-00 Instrument Air
- 6-232469-00 WAGD
- 6-232470-00 Carbon Dioxide
- 6-232471-00 CO2/O2
- 6-232472-00 O2/CO2
- 6-232473-00 He/O2
- 6-232474-00 O2/He
- 6-232476-00 Air (ISO)
- 6-232477-00 Vacuum (ISO)
- 6-232478-00 O2 (100 PSI)
- 6-232479-00 Air (100 PSI)
- 6-232480-00 CO2 (100 PSI)
9 Console Rough-In
- 6-233010-00 Oxygen O2 (100 PSI)
- 6-233011-00 Nitrous Oxide
- 6-233012-00 Medical Air Air (100 PSI) Lab Air
- 6-233013-00 Vacuum Lab Vacuum
- 6-233014-00 Nitrogen
- 6-233016-00 Air (ISO)
- 6-233017-00 Vacuum (ISO)
- 6-233018-00 Instrument Air
- 6-233019-00 WAGD
- 6-233020-00 Carbon Dioxide CO2 (100 PSI)
- 6-233021-00 CO2/O2
- 6-233022-00 O2/CO2
- 6-233023-00 He/O2
- 6-233024-00 O2/He
Field Installation Kits
ITEM P
ART NUMBER DESCRIPTION
1 Digital Display Module
- 6-290980-10 Oxygen
- 6-290980-11 Nitrous Oxide
- 6-290980-12 Medical Air
- 6-290980-13 Vacuum
- 6-290980-14 Nitrogen
- 6-290980-16 Air (ISO)
- 6-290980-17 Vacuum (ISO)
- 6-290980-18 Instrument Air
- 6-290980-19 WAGD
- 6-290980-20 Carbon Dioxide
- 6-290980-21 CO2/O2
- 6-290980-22 O2/CO2
- 6-290980-23 He/O2
- 6-290980-24 O2/He
- 6-290980-25 Helium
- 6-290980-26 Lab Air
- 6-290980-27 Lab Vacuum
- 6-290980-28 O2 (100 PSI)
- 6-290980-29 Air (100 PSI)
- 6-290980-30 CO2 (100 PSI)
2 Multi-Signal Module
- 6-290981-00 W/O Relays
- 6-290981-RL W/ Relays
Field installation kits include everything required to replace a blank module with a digital display mod­ule or a multi-signal module. Digital display module kits include sensors.
NOTE:
Before ordering replacement sensor, determine whether faulty sensor is analog or digital type by part number listed on sensor label.
Faulty sensors must be replaced with same type.
Page 54
54
Part No. 6-847684-00 Rev. D01
Notes
Page 55
55
Part No. 6-847684-00 Rev. D01
Notes
Page 56
BeaconMedæs warrants the MEGA2Medical
Electronic Gas Alarm to be free of defects in materials or workmanship when installed and operated in accordance with instructions. The warranty period is 30 months from shipment date or 24 months from startup, whichever period ter- minates earlier.
This warranty covers all necessary parts and labor required for correction of the defect whether by any or all of repair, replacement, or credit, which election shall be made by Beacon at it’s sole discretion.
This warranty requires the owner to ensure that the equipment is 1) started up or placed in service by an authorized representative of BeaconMedæs, 2) certified in accordance with NFPA 99, most recent edition, by a properly quali- fied certification agency, and 3) maintained in strict accordance with Operation and Maintenance Instructions provided with the product.
Warranty claims will be honored only after examination by BeaconMedæs and only when such examination shall disclose to BeaconMedæs’ reasonable satisfaction that such equipment has not been damaged in shipment or installation, improperly installed, operated outside of any published operating limits (including but not limited to temperature, pressure, humidity, or ven- tilation), improperly or inadequately maintained, field modified in any way, improperly repaired, or in any other way improperly applied or used.
All claims against this warranty require prompt notification, within the warranty period, of any seeming defect. Failure to promptly notify BeaconMedæs of the seeming defect will invali- date all warranties.
This warranty excludes damage or defect caused by shipping, acts of God, fire, war, labor difficulties, action of government, or other cause beyond the reasonable control of BeaconMedæs.
This warranty is given in lieu of all other war- ranties, expressed or implied, including implied warranties of fitness for a particular purpose and merchantability. In no event shall BeaconMedæs be liable for damages in excess of the value of the defective product, nor shall BeaconMedæs be liable for any direct, special or consequential damages, loss of profit of any kind, or for loss of use of the products.
Warranty
Loading...