BEA 10PS12, 10PS24 Instruction Manual

Page 1
12 and 24VDC POWER SUPPLY
INSTRUCTION MANUAL
These power supplies are UL-Listed control units for use with electromagnetic locking devices and systems. They may be ordered with optional battery backup systems to power devices in the case of power loss.
GENERAL DESCRIPTION:
POWER SUPPLY POWER SUPPLY WITH BATTERY BACKUP DESCRIPTION ENCLOSURE DIMENSIONS INPUT POWER OUTPUT POWER RATING MAXIMUM # OF MAGLOCKS
OUTPUTS
12 VOLT 24 VOLT
12 VDC 24 VDC 2 Amps 2 Amps
UP TO 3 MAGLOCKS UP TO 6 MAGLOCKS Fire alarm release
Auto/ Manual reset after fire alarm release Auxiliary power for keypads/ external controls
Fire alarm release Auto/ Manual reset after fire alarm release Auxiliary power for keypads/ external controls
POWER SUPPLY BOARD DESCRIPTION:
TB1
TB2
TERMINAL DESCRIPTION
1 N/C 2 N/O 3 COMMON
Field selection for automatic or manual system reset. For system to automatically reset
4 & 5
6 & 7
8 & 9
10 & 11
1 & 2
when the fire alarm contact is reset, put jumper wire across these terminals. If manual reset is required, a normally open (momentary switch) is used across these terminals. Momentary activation of switch will reset the system. To be tied to (normally closed) fire alarm contacts. The fire alarm contacts will open and release all magnetic locks immediately. If fire alarm system supervision is not required, a jumper across the terminals is required to derive 24 VDC from output terminals. Auxiliary 12 VDC output (0.1 Amp max, not fused) for other system components, requiring 12 VDC power. (For 10PS24/PB only) Auxiliary 24 VDC output (0.25 Amp max, not fused) for other system components, requiring 24 VDC power.
Optional battery backup unit terminals. Jump these two wires if battery backup is not supplied.
Auxiliary form ‘C’ dry contact. Fire alarm supervised.
If after troubleshooting a problem, a satisfactory solution cannot be achieved, please call B.E.A., Inc.
for further assistance during Eastern Sta ndard Time at
1-800-523-2462 from 7am - 5pm or 1-800-407-4545 from 5pm - midnight & weekends.
DO NOT leave any problem unresolved. If you must wait for the following workday to call B.E.A., leave the door inoperable until satisfactory repairs can be made. NEVER sacrifice the safe operation of the automatic door or gate for an incomplete solution.
75.0148 V1 July 2000