B&D Mfg QT-MAXX User Manual

QT®-MAXX FLOW CENTER
INSTALLATION INSTRUCTIONS
GeoMagnaCurves
80
70
60
50
40
FTHEAD
30
20
10
0
0 5 10 15 20 25 30 35
FLOW(GPM)
Fig. 1.
QT®-MAXX Flow
Center Flow Chart
1Pump
2Pump
NOTE: Read the entire instruction manual before starting the installation.
WARRANTY
This flow center is warranted for two years from date of sale. Alleged defective product must be returned to B&D Mfg., Inc., 901 9th Street, Scranton, Iowa 51462, for inspection via prepaid freight. Defective parts will be repaired or replaced at the manufacturer’s discretion. No allowance for labor or property damage is implied. Warranty of performance is limited to the table provided with the unit and only when being used in a closed-loop, heat pump system. No warranty of performance is provided when pump(s) are provided by others.
INTRODUCTION
These instructions cover the installation of the QT 1-230MAXX-NC, 2-230MAXX-NC. The QT closed-loop, ground source heat pumps. The package contains a water vessel, an air-eliminating dip tube, a pump protecting check valve, pump(s), ball valves that allow the pump(s) to be removed for service without loss of fluid to the system, sensors and UPC controller.
Installing and servicing of air conditioning and heating equipment can be hazardous due to system pressures and electrical components. Only trained, qualified personnel should install, start-up and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils or cleaning and replacing filters. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature, tags, stickers and labels attached to the equipment and to any other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
B&D Mfg, Inc 901 9th Street Scranton, IA 51462 Phone (712) 652-3424 Fax (712) 652-3388 www.bdmfginc.com
–MAXX Flow Center is a prepackaged pumping station to be used with
®
-MAXX Flow Center Part No. 1-230MAXX, 2-230MAXX,
®
SAFETY CONSIDERATIONS
1
Patent No. 5,244,037
INSTALLATION
Before installing the QT
–MAXX Flow Center, check the flow charts and loop table against system flow and pressure drop
®
characteristics to be sure the correct flow center is selected for the system. A one-pump flow center can accommodate flow for 3 1/2-ton units and smaller. A two-pump flow center can accommodate flow for 3 1/2- through 6-ton units. (See Fig. 1) To ensure adequate flow, the selection must be made based on your specific system design.
The flow center must be located between the heat pump and the ground source system heat exchanger. Location should be selected on the basis of ease of installation and future service. The flow center is used for filling, flushing, air elimination, adding anti-freeze and operating the system. This flow center should never be pressurized.
GRUNDFOS
SENSOR
Heat Pump
WATER OUT
WATER IN
Connect to Heat Pump
GRUNDFOS
SENSOR
P/T Plug
By-Pass Valve
"T" With threaded plug used for bleeding air
Fig. 2. Recommended Piping Schematic For
Maximum Flexibility (Required With Internal Headers)
GRUNDFOS
SENSOR
2
By-Pass Valve
Heat Pump
GRUNDFOS
WATER OUT
WATER IN
Connect to Heat Pump
SENSOR
1
P/T Plug
3
4
Flush Tee's
for
Outside Header
Fig. 3. Recommended Schematic (For Use with
Underground Headers; Flush Cart Required)
The recommended piping schematic is usable with all types of closed-loop, ground source heat pump systems, vertical bore holes, horizontal loops, slinky, outside headers or inside headers. This recommended method allows for isolating the heat pump or the loop field for separate flushing and purging. Additionally, the flow through the loops can be reversed, which may be required when using external headers. Make sure to install the Grundfos Sensors. (One on
the supply and one the return side of the heat pump) Refer to Fig. 2 or 3 for the location of sensors.
NOTE: The QT
one QT
–MAXX Flow Centers are designed to work with only one heat pump per loop field. More than
®
–MAXX Flow Center on a common loop field will not work properly. Call B&D Mfg., Inc. for
®
information on equipment designed for multiple heat pumps. Swivel nuts should be hand tight only and a quarter of a turn with a wrench if needed.
Fig. 2 Illustrates a recommended piping schematic that can be utilized when an internal header is used and separate
purging of the heat pump and the ground loop is not required.
It is recommended that a tee with a threaded plug is located between the heat pump and the ground loop. This plug allows the air to be vented from the system piping and will help remove air from the system during start up.
NOTE: Loops should not contain any dirt or debris prior to connecting to the flow center.
Fig. 3 Illustrates a recommended piping schematic for a system with underground headers.
Piping is similar for either schematic with the exception of Fig. 2 showing all earth loops penetrating the mechanical area of the interior wall. Provide ball valves and P/T ports where indicated. Ball valves shall be the same as pipe size or greater. The flow center should be fastened to the wall with the bracket provided and all piping should be adequately supported. All piping shall be properly sized for the flow rate (GPM) required by the system. Reduce pipe size only at flow center and heat pump as necessary to make connections.
PROCEDURE 1—FILL AND FLUSH A NEW SYSTEM
On systems where the ground loop has been filled and flushed by the loop installer, skip to Procedure 3.
Ensure that all piping is installed according to one of the piping schematics.
NOTE: Incorrect piping may not eliminate the air pockets.
1. Open the top of the canister and fill with clean potable water.
2
Loading...
+ 2 hidden pages