B+B THERMO-TECHNIK HYG LECKAGE 24V Datasheet

OPERATION MANUAL
Leakage alarm unit water detector, model 12 V or 24 V AC/DC
Description
DescriptionDescription
Characteristic features
Safe operation, impedance measuring principle
Operating voltage 12 V DC/AC
2 integrated, gold plated measuring tips
Potential free switch output (Relay) 30 V / 4 A
Adjustable sensitivity and switching mode
Adjustable measuring level 0...15 mm
Simple mounting
Areas of application
Sanitary plants, water installation
Monitoring of cooling systems
Condensate switch for collection tanks
Building instrumentation, air-conditioning
Technical data
Leckage alarm unit
Measuring principle electrolytic conductivity Measuring medium Application temperature Operating voltage 12 V (optionally) 24 V
Current consumption 13,5 mA (without leckage)
Switching power Switching point Switching output
Cable gland Electrical connection Housing ABS, Ingress protection IP54 EMC noise emission EN 61000-6-3:2011 EMC noise immunity EN 61000-6-1:2007 CE-Conformance 2004/108/EG Dimensions (W x H x D) 82 x 130 x 60 mm
Article Description Art.-No.
Leakage alarm unit 12 V Leakage alarm unit 24 V LEME-24V
conducting liquids, construction material +5...+60 °C 12 VDC ±10 %, max. 80 mA 24 VDC ±10 %, max. 80 mA
58 mA (with leckage) max. 80 mA (with leckage and extra probe) 30 V / 4 A (100 k)
approx. 2...60 kΩ (type. 15 kΩ)
16 A / 250 V AC 16 A / 30 V AC M16 x 1,5
compression tting 1,5 mm²
LEME-12V
Functional description
The leakage monitor works as per the operating principle of electrolytic conductance measurement. There are two electrodes beneath the device which are evaluated by means of AC impedance measurement. As soon as the conductance value between the electrodes rises over an adjust able limit, the relay contact closes. Because of the universally concepted model with gold plated spring loaded electrodes with height adjustable device feet, it is suitable for a wide variety of applications.
-
Monitoring of collection tanks:
The device can be directly placed in the tank to be monitored. Over the height adjustable feet, the permissible liquid level can be adjusted at which the device has to switch (approx. 0.5...15 mm).
Leakage monitor:
In order to detect small liquid quantities, the spring loaded electrodes are placed directly on an insulating base of absorbent material (for example hardboard, cardboard, cloth). As soon as the leaking out liquid is ab sorbed by the base, the device gives out an alarm.
-
Construction or wood humidity monitor:
For this application, the springy electrodes are put directly on the material to be monitored. If there is high humidity in the underground, the device gives out an alarm.
Technical changes reserved 0141 0316-83 11.08.2015
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
1 / 3
OPERATION MANUAL
Leakage alarm unit water detector, model 12 V or 24 V AC/DC
Connection
After unscrewing the sensor cover, the control cable is inserted into the cable gland M16. The operating voltage supply (12 or 24 V AC/DC) is connected at the terminals AC/DC+ and AC/GND. The potential free changeover contacts are connected to terminals NC, COM and NO. Care to be taken that the cable gland is assembled water tight and the cover gasket is correctly inserted.
Up-Keeping
The leakage alarm unit is, as far as possible, maintenance free. How­ever, the housing lower side and the measuring tips should be occasi­onally (e.g. once in a year, depending on mounting location) cleaned with a wet cloth. If there is a continuous alarm, even without touching the water, that means there is a heavy contamination.
Application Notes
Because of the electrolytic evaluation, the device is suitable for all liquids or construction material, which are electrically conductive (> 150 μS). However, the device is not suitable for detection of nonconducting liquids like oil or distilled water. In acidic or alkaline media or in unk­nown materials with impurities, the material compatibility of the probe is to be checked before use. In case of application in dirty medium, the
probe tips should be periodically cleaned. The use in inammable or
explosive environment is not permissible. The device is not intended for connecting to the mains voltage. While monitoring of tanks, cros­sing over the tank should be avoided. The safety regulations are to be duly followed!
Jumper Plugs
Conguration
1 S3 Signal generator switching mode (dry) 2 S2 Middle contact for S3, S1 3 S1 Signal generator switching mode (wet) 4 GND Signal generator grounder 5 BUZ Signal generator output 6 T3 Relay switching mode (dry) 7 T2 Middle contact for T3, T1 8 T1 Relay switching mode (wet) 9 HZ1 Heating (only for external sensor)
10 HZ2 Heating (only for external sensor)
Factory setting: S3-S2, T1-T2, HZ1-HZ2
Connection Layout
Clamp Function Description
1 AC/GND Versorgung 12 or 24 V AC/DC* 2 AC/DC+ Versorgung 12 or 24 V AC/DC* 3 REL-COM Hauptrelais, Bockpol 4 REL-NO Hauptrelais, Schliesserl
5
*according to model
A further probe (special accessories) can be connected to the sensor connection, which can be additionally monitored by the built in elect­ronics.
REL-NC Hauptrelais, Öffner
Settings
Output signal generator (optional): A passive Piezo-signal generator can be connected at the plug con­nector (Pin BUZ and GND). The status of signal (acoustic signal at dry or wet) can be adjusted with the jumper plugs S1-S2 or S2-S3. In the position S2-S3, the signal generator is active on detecting leakage.
Switching mode: The switching mode of the relay (closed or open during wet) can be adjusted with the jumper plugs of T1-T2 or T2-T3. In the factory routine adjustment, the jumper T1-T2 is plugged and the relay closes if the electrodes detect leakage.
Sensitivity setting: The sensitivity of humidity alarm can be changed with a potentiometer. A higher sensitivity is achieved if the potentiometer axis is rotated in the clockwise direction. Normally, the middle position is most suitable. Please note that no functioning takes place at the end positions.
Technical changes reserved 0141 0316-83 11.08.2015