B + B Thermo-Technik FREG-BAD Operation Manual

OPERATION MANUAL
Humidity regulator for sanitary rooms FREG-BAD
DescriptionDescription
Characteristic features
• Automatic humidity regulation for bathrooms, sanitary rooms and kitchens
• Direct control of blowers
• Regulation of room climate
• High quality, long term stable humidity probe
• On delay and time delay switch
• Switch input for light circuit
• Switch output for Humidity OFF
Typical areas of application
• Humidity regulation for inside bathrooms
• WC and showers, other sanitary rooms Kitchens and cooking chambers
Technical data
Humidity regulation
Switching point 70% RH or strong Humidity increase
Cable length 3m to Humidity Probe
General
ON delay 40 sec.
OFF delay 300 sec
Humidity application range Temperature application range Operating voltage 230 V AC/ 3VA
Switch output Triac with No voltage switch, 230V/1A
Switch output “Light“ 230V AC/ approx. 1 mA
Switch output “Humidity Off“ Over voltage protection Varistor at mains input and switch output
CE-conformance 2004/108/EG
EMV-noise emission EN 61000-6-3:2011
EMV-noise withstanding EN 61000-6-1:2007
Ordering No. FREG-BAD
Rights reserved for change in technical data due to technological advancements!
0..100% relative Humidity
0...40 °C
230V AC/ approx. 1 mA
Description
This innovative product is a problem solution for humid rooms like showers, bathrooms and sanitary rooms, in order to avoid fungus growth on the walls and prevent damage to buildings. In modern new type of buildings, the bathroom ( or even the “Kitchen”) is also placed in the centre of the house and therefore is often without
a window. Therefore, to ensure a minimum air ow level, normally a
forced ventilation system is envisaged. In previous ventilation concepts, the fan was either switched on
through a switch or by an automatic timer. The rst solution is not
comfortable and it performs wrongly by all means. The second solution which is achieved by means of time control is functionally not
sufcient. Without regulation, such a ventilation cannot operate in a
power and demand optimised manner and results in problems like fungus growth after some time. All these disadvantages are ruled out by using our fan control for humidity regulation. Then the fan runs only if it is necessary and switched off again after some time with unwanted climatic conditions, if after the change of air no more drying is observed The device operates automatically, requires no maintenance or addi­tional service and offers optimum protection from humidity and fungal damage together with energy cost savings. The acquisition costs gets amortised within a short time.
Technical changes reserved
0141 0316-167 20.08.2015
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
1 / 2
OPERATION MANUAL
Humidity regulator for sanitary rooms FREG-BAD
Functional description
The switching device is meant for triggering of a bathroom fan, in order to ensure both the basic ventilation and also to maintain the hu­midity within a limiting value. As in the case for conventional devices, there is an integrated timer and the fan is switched ON after the ba­throom is occupied for at least 40 seconds (ON delay). Thereafter, the fan runs with a time control for at least 5 minutes, in order to ensure the basic ventilation after use of WC or the shower. In addition, the control device also has an integrated humidity regu­lator which switches ON the ventilator, if a fast humidity increase is registered (for example during use of shower) or if the humidity value rises to over 70% rH. With this, the fungus growth in walls and room corners is prevented, even if there is an unreasonable utilisation (e.g. drying or washing) of water quantity involved. However, the fan is
operated only for a long time till the area is again sufciently dry, for
example, to save the heating costs in winter. Moreover, the device also has a protective mechanism to prevent unnecessary running of the fan, if for example, with unwanted external climatic conditions, no further drying level can be achieved. With a switch input, a timer controlled operation with ON delay and OFF delay is also possible. With a second switch input, the humidity regulation can be switched OFF on demand. In this case, the ventilators are again put to operati­on by triggering through „Light“ based switch input.
Accessories (optional, not in scope of supply)
PIR-Sensor (Movement alarm unit) the optional sensor is for the purpose of presence recognition. If a movement is detected for more than 40 seconds in the area, then the timer controlled fan is switched ON.
Safety instructions
The product should be installed and used only according to the intended application. The regulation device works on mains voltage. Contact with live voltage parts leads to fatal
dangers. Therefore, tment and maintenance of the device shall be
carried out by only trained personnel. The device must be assem­bled inside a switchgear cabinet or in a fully closed plastic housing. Mounting and servicing operations should be carried out only after switching off the voltage. Touching the electronic components in switched off condition should also be avoided. Electronic components can get damaged due to electrostatic discharge process. The product is not meant for controlling electrical systems which perform safety related functions. In normal operation also, there is al­ways a danger of malfunctioning due to any fault or disturbance in the output stage. The user has to ensure that there are no consequential
damages due to malfunctioning or undened switching status.
Due to wrong tightening of screws of the connection terminals or by use of inappropriate tool, the terminals can get damaged because of which the insulation or the contact can get disturbed. Badly connec­ted leads can come out during operation and cause a serious risk to safety. Due to contact resistance at terminal connections, there
can be increased heat generation which can cause re. Wrongly
wired connections can destroy electric components and cause other damages. While mounting the fans, legal guidelines and standards are to be followed. Fire protection measures shall be duly taken care of !
Attention
Please avoid extreme mechanical and inappropriate exposure.
Light sensor: Alternatively, the presence detection can also be done with an optional light sensor. This is possible, since bathrooms on the inner areas do not have windows, and hence, while entering normally the light is switched on. By the application of PIR-Sensor or light-sensor, the wiring expenses are reduced, since no switched phase of the light switch is to be wired.
Dew formation sensor: In addition to humidity sensor, an optional dew formation sensor can be used at cooling junctions to detect the onsetting condensation. This results in an enhanced system safety against fungus formation in critical zones (e.g. outside walls or room corners).
Technical changes reserved
0141 0316-167 20.08.2015
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen Fon +49 771 83160 | Fax +49 771 831650 | info@bb-sensors.com | bb-sensors.com
The device/product is not suitable for potential explosive areas and medical-technical applications.
Connection diagram
2 / 2