B + B Thermo-Technik DRMOD-I²C Operation Manual

OPERATION MANUAL
Pressure sensor module with voltage output and I²C-bus
DescriptionDescription
Characteristic features
Digital I²C and analogue interface 0…5 V
Calibrated and ready-to-use
Wide application spectrum
Ceramic or piezo resistive measuring cells
Environment resistant and long term stable
Miniaturised dimensions
Optimal price-performance ratio
Customised product variants and OEMdesigns possible
Typical areas of application
Building instrumentation
Ventilation control
Fill condition measurement
Filter monitoring
Automation technology
Customised solutions
Technical Data
Pressure sensor module DRMOD-I²C
Signal processing
Measuring range
Temperature compensation 0...50 °C Accuracy Linearity/ Hysteresis Operating voltage
Current consumption Temperature application range Voltage output 0…5 V for pressure
I²C-Interface 100 / 400 kHz, address 0x78
Electrical connection 5-pin RM 2.54mm
Media connection Hose connection 6/4 mm
CE-Conformance 20047108/EG
EMV-noise emission EN 61000-6-3:2011
EMV-noise withstanding EN 61000-6-1:2007
Pressure measuring cells, ceramic or piezo resistive Digital in ASIC: linearisation, temperature compensation See table
Piezo resistive < ± 0,3 % FSR* Ceramics < ± 0,3 % FSR* 6…15 V
< 5 mA
-40...+100 °C
Features
The B+B pressure modules combine modern sensor technology with
exible signal processing of an ASIC.
The module has a calibrated, analoge voltage output of 0…5 V and also a digital I²C-interface, which can directly communicate with a microcon troller. By a precise calibration at 7 measuring points, one can achieve an outstanding precision and a very low temperature residual error. The completely processed, calibrated, pressure measured values are made ready with high resolution which makes simple integration possible with
customer specic products. The calibrated and standard output signal
guarantees simple integration of sub-system in development phase and enables shortest time-to-market product developments. The probes are ideally suitable for measurement of static and dynamic relative pres
sure in liquids and gases. Typical application areas emerge in the eld
of pneumatics, hydraulics as well as in industrial applications. Besides
the standard variants, customer specic models are also available
e.g. with other operating voltage, special calibration, ratiometric vol tage output and also with digital output signal. Further information on www.bb-sensors.com are available on enquiry!
-
-
-
* Full-Scale-Range
Technical changes reserved 0141 0316-120 19.08.2015
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen Fon +49 771 83160 | Fax +49 771 8316-50 | info@bb-sensors.com | bb-sensors.com
1 / 3
OPERATION MANUAL
Pressure sensor module with voltage output and I²C-bus
Standard model
The module is congured as follows:
Operating voltage range 6 to 15 V / 3 mA
Calibrated at 8.0 V
I²C Interface for pressure
Voltage output 0...5 V
Temperature measurement with Pt1000
Application notes
Supply with 5 V is possible, if analogue output is not used. The calib-
ration at factory is done at 8 V. The specied technical data is valid at this operating voltage. Other congurations and special calibration as
per customer requirements are possible. While connecting the measu­ring probes over longer routes, the used I²C-Bus external to the device should not be used internally, in order to avoid coupling of interferen­ces to the device internal communication. The EMV-guidelines are to be followed and shielded lines are recommended. A RESET of the pressure sensor can be initiated by a short time inter­ruption of the operating voltage. If the operating voltage can be swit­ched off, then the pullup resistance of the I²C bus must be connected to the switched voltage. To simplify your product development, a com­munication board and an USB-I²C-adapter is available. Please send us your enquiry!
Operating voltage
Standard supply is 6 to 12 V operating voltages which are stabilised in the module to 5 V. The 5 V operating voltage also serves as the reference level for the digital I²C communication.
Voltage output
On PIN1, the measured pressure is given out as analoge voltage sig­nal. The voltage range of 0...5 V represents the measuring range: 0 V corresponds to the smallest measured value or lower limit, 5 V repre­sents the measured range limit or upper limit. The connection impedance should not be less than the minimum value of 10 kΩ. The output impedance is around 50 Ω. The output is protec­ted against short circuit transients. External voltage at the output can lead to a damage of the ASIC and should be certainly avoided.
ble on request or can be downloaded from www.bb-sensors.com. The standard address of the component is 0x78, the component can always be communicated with this address. The address is to be un-
derstood as a 7 bit address, left justied and with masked R/WBit is the
Read-address 0xF1. Additionally, a second address can also be programmed during
conguration ex factory, through which the pressure sensor can be
addressed. From this address 0x78 (7 bit address), 2 Bytes can be read. The fol­lowing assignment is applicable:
Data
0x78 Byte_0 MSB pressure
Byte_1
LSB pressure
Scaling of measured value
The pressure is transferred as 15 bit value (bit 0 –14). From the 15 bit measured values, approx. 12 bit are used as resolution, the three least
signicant bits can be ignored. The most signicant bit (15) is always 0 during normal operation and in
case of error, it is set to 1. Further notes on the error codes are availa­ble in the write-up “Serial Interface of B+B ASIC“. Following scaling is applicable for the measured values:
Pressure
Numeric value over I²C Interface
Physical value
Scaling P =V / 32768 * measuring range
0x 0000...7FFF dec. 0...32767
as per model
Pin strip connection layout
Pin Title Function
1 OUT Voltage output
2 SDA
3 SCL Serial pulse I²C
4 GND Ground
5 VDD Operating voltage 6...12 V
Serial data I²C
I²C-Interface
The communication corresponds to the standard I²C protocol. All technical specication of the protocol can be obtained from the docu­mentation “Serial Interface of B+B ASIC“. The documentation is availa-
Technical changes reserved 0141 0316-120 19.08.2015
B+B Thermo-Technik GmbH | Heinrich-Hertz-Straße 4 | D-78166 Donaueschingen Fon +49 771 83160 | Fax +49 771 8316-50 | info@bb-sensors.com | bb-sensors.com