1. ................. Preface ........................................................................................................... Fehler! Textmarke nicht definiert.
2. ................. General hazard and warning notices .......................................................... Fehler! Textmarke nicht definiert.
.............. Notes on documentation ............................................................................. Fehler! Textmarke nicht definiert. 2.1.
.............. Safety instructions ....................................................................................... Fehler! Textmarke nicht definiert. 2.2.
3. ................. General information ......................................................................................................................................... 4
.............. Description of the LED display ........................................................................................................................... 8 8.2.
11. ............... Repair and calibration service ........................................................................................................................ 9
12. ............... Care and maintenance ..................................................................................................................................... 9
14. ............... Technical data .................................................................................................................................................. 9
15. ............... Order date ....................................................................................................................................................... 10
Dear customer,
Thank you for purchasing this VOC sensor. We are pleased that you have decided on a product from B+B Thermo-Technik GmbH.
We hope that this product will give you many years of good service and that it will help you in your work.
You have purchased a device that was developed and produced to the latest technical standard. This product meets all requirements
of the applicable European and national guidelines. Please observe these operating instructions to keep the product in this state and
ensure safe operation. In the event of any unexpected malfunctions that you cannot resolve yourself, please contact one of our
service points or your retailer. We always strive to provide fast, expert assistance to spare you long down times.
These operating instructions are an important part of the product. They contain important information on how to start up and handle
the product.
2. General hazard and warning notices
Notes on Documentation 2.1.
Please read the following notes before commissioning! The symbols used in the operating instructions aim to raise awareness of
risks to safety. The symbol used cannot replace the text of the safety notice. For this reason, always read the text in full!
This symbol indicates a hazard to persons, material or the environment. Always comply with the information in the text to prevent
risks.
This symbol indicates important operating information and tips that are necessary for successfully performing the work step, and that
must be observed in order to achieve good working results.
Safety instructions 2.2.
Please read these instructions carefully in full before starting up the device. Observe and follow the indicated safety instructions, in
particular the safety instructions for devices powered by line voltage.
The product may only be used in line with its intended use as described in this manual. Any other usage is against the intended use
and will result in the loss of guarantee and exemption from liability. This also applies to modifications and any other alterations made
to the device.
Defective fuses may only be replaced by fuses that are identical in terms of tripping current, tripping characteristic and mechanical
dimensions. Bridged fuses represent a significant safety risk and are not permitted under any circumstances.
The connection terminals can be switched with line voltage. Contact with live components poses a life-threatening risk. Assembly or
maintenance work may only be carried out by trained personnel who are qualified to perform the work. Observe the applicable safety
rules. Assembly and servicing may only be performed when the device is disconnected from the voltage.
The product is intended exclusively for the purpose of controlling electrical equipment that have functions relevant to safety. Even in
normal operation, there is the risk of unexpected malfunctions due to a component failure or other deficiency. The user must ensure
that no consequential damage can occur as the result of a malfunction or undefined switching state on the relay. This applies above
all if heavy consumers like heaters or motors are being controlled.
The user must comply with the safety rules that apply to the special application. The device must be assembled in dry areas only.
Attention
Please avoid extreme mechanical and inappropriate exposure.
The device/product is not suitable for potential explosive areas and medical-technical applications.
Please read the following notes before using the device. The symbols used in
the operating instructions aim above all to raise awareness of safety risks. The
symbol used in each case cannot replace the text of the safety instruction.
Therefore, always read the text in full.
Observe the following
This symbol indicates important information and tips that are necessary for
successfully performing the work step and that must be observed in order to
achieve good working results
Warnings
Meaning
Warnings
Meaning
This symbol indicates a hazard to
persons, material or the environment
The information contained in the text
must be observed in order to prevent
risks
Warning against electromagnetic field (BGV A8,
GUV-V A8/W12)
Warning against hot surfaces (BGV
A8, GUV-V A8/W26), as well as hot
liquids or media
Warning against cold
(BGV A8, GUV-V A8/W17)
Warning against hot liquids and hot
media
Warning against dangerous electrical voltage
(BGV A8, GUV-V A8/W08)
Warning against substances at risk of
explosion
(BGV A8, GUV-V A8/W02)
Warning against explosive atmosphere
(BGV A8, GUV-V A8/W21)
Warning against moving machinery
(W29)
Warning against moving components
Electronic waste
Take protective measures against
electrostatic discharges on electronic
components
(DIN EN 61340-5-1, 61340-5-3)
VOC-probe for a comfortable indoor climate
3. General information
This documentation contains information that must be observed to ensure safe and efficient use of the product.
Please read this documentation carefully in full and familiarize yourself with the product's operation before using it. Please keep this
document to hand so that you can refer to it as needed.
4. Symbols
5. Safety instructions
B+B Thermo-Technik GmbH shall assume no liability for damages that occur as a result of non-compliance with these safety
instructions and the operating manual.
Any deviation from the use described in the operating manual can lead to damage or failure of the device. Non-intended use can
also lead to risks such as short circuit, fire, electric shock, etc.
Preventing personal injury and damage to objects
The measurement system may only be used by authorized personnel.
Do not apply a voltage to the inputs and do not allow the inputs to come into contact with voltage supplies.
If using in commercial facilities, please observe the accident prevention regulations of the respective commercial trade
association for electrical systems and equipment (e.g. BGB A1).
The system is not approved for use in explosive atmospheres or in/on substances at risk of explosion.
Do not use the measurement system on or in living organisms.
Keep the measurement system away from children.
Never store the measurement system with solvents and never use desiccants.
Do not use the measurement system on moving components.
Do not expose the measurment system to heavy vibrations, impacts or pressure.
Do not use the measurement system in strong electrical or magnetic fields.
Do not use the measurement system for medical and diagnostic purposes.
Ensuring product safety
Only operate the measurement system within the parameters indicated in the technical data.
Only use the measurement system appropriately and for the intended purpose. Do not use force.
All data concerning the temperature range relate only to the measuring range of the sensor assembly.
The device can be damaged if used for longer periods of time at high or low temperatures.
Do not open the measurement system or attempt to open it.
Disposal instructions 5.1.
Please return the device to B+B Thermo-Technik GmbH after its service life.
6. Intended use
Only use the device for the purposes for which it was designed. If in doubt, please consult B+B Thermo-Technik GmbH. The fields of
application detailed in the section "safety instructions" are excluded.
The VOC sensor is suitable for the precise measurement of VOC gases. Depending on the version, it can also measure
relative humidity and temperature.
The product can be used in all fields of application that do not conflict with the applications that are excluded in the section "Safety
instructions".
The device may never be used however in the following areas:
areas at risk of explosion
for diagnostic measurements in the medical sector
in very dusty environments
7. Product description
This powerful sensor will help you find our precisely when it is time to get some fresh air into residential or commercial spaces.
Installed simply in a wall-mounted housing, it measures the air quality (VOC gases), humidity and temperature. The measured
value is displayed using LEDs. VOC refers to gaseous and vapourous evaporations from people, installations, walls, etc. These
include hydrocarbons, alcohols, aldehydes, sulfur compounds and organic acids. The VOC sensor can be used for a range of
purposes, for example in school buildings, offices, hotel rooms, lecture theaters, meeting rooms, living rooms, commercial ar eas,
gyms, in building services and in climate recording.
Voltage output 7.1.
The VOC sensor provides an output scaling of 0 - 10 V, which represents the measuring range of 450 - 2000 ppm. In the version for
measuring relative humidity and temperature, a linear output scaling of 0 - 10 V is also supplied.
The device is supplied with voltage exclusively via the compression fitting 14 - 27 V DC.
Switching output 7.3.
A fan or window lifter can be controlled via the relay for ventilation.
8. Commissioning
Assembly 8.1.
1. Take the VOC sensor from the box and remove the packaging.
2. Drill holes to mount the sensor, observing the position of the cable outlet (Fig. 1).
3. Insert the 5 mm wall plugs included in delivery into the bore holes.
4. Screw in the screws until the screw heads are 5 mm from the wall.
5. Open the sensor.
6. Feed the connection wires through the wire outlet prior to mounting.
7. Place the housing on the screws so that the LEDs are arranged on the right, then turn the housing so that it is straight.
8. Using a small Phillips screwdriver, connect the power supply, along with any relay output and the voltage signal output(s). See pin
assignment, figure 2. The connection wires can be fed out from the housing directly beneath the compression fittings.
Avoid static charges and contact with electrical contacts. Electrostatic discharges can damage the device or sensor! Ensure that
no electrical voltage is applied on the wires. Connect the power supply (14 - 27 V DC) to the screw terminal AN1. See pin
assignment, figure 2.
9. Carefully insert the cover onto the enclosure base, so that the ventilation slots face upward and downward and the LEDs are
This drawing illustrates the boreholes and the wire outlet on the drilling template.
Figure 1 - Assembly drawing
9.
Pin assignment 9.1.1.
Connection options for the VOC sensor:
Figure 2 - Pin assignment
AN1: Power supply 24 V DC
AN2: Voltage output VOC 0 - 10 V
AN3: Voltage signal output temperature 0 - 10 V
AN4: Voltage signal output relative humidity 0 - 10 V
AN5: Switching output connection
Note: AN2, AN3 and AN4 not assigned on item no. 0565 0004
Description of the LED display 9.2.
This section briefly describes the range in which the VOC value lies when the LED display illuminates green, yellow or red:
The first LED illuminates green when the VOC value is below 800 ppm, meaning the air quality is good.
The second LED illuminates yellow when the VOC value is between 800 and 1200 ppm, meaning the air quality is moderate.
The third LED illuminates red when the VOC value is above 1200 ppm, meaning the air quality is poor.
The bottom LED illuminates red when the device is connected to the power supply.
Each time the device is rebooted, the three LEDs will flash for approximately 5 minutes. The VOC sensor is warmed up during this
time. The display will then switch to normal.
10. Error messages
Possible error message:
Green and red LEDs flash. A sensor was not recognized. Reboot the device.
Should the error not be resolved, please contact our customer service:
Tel. +49 771 8316-0 or info@bb-sensors.com.
Never repair the device yourself.
11. Guarantee
Congratulations on purchasing this premium product! The quality of our products is constantly monitored as part of our quality
management system, which meets the ISO 9001 standard. Should you still have reason to complain however, we will resolve the
defect for free within the guarantee period of 24 months, providing that the defect in question can be verifiably linked to us.
The guarantee service can only be provided if you inform us of the defect immediately and within the guarantee period.
Any damages that are the result of incorrect use or non-compliance with the operating instructions are excluded from the guarantee.
Also excluded are defective sensors and measuring sensors, as well as calibration services.
The guarantee is also voided if the reference cell is opened. The serial number on the item label may not be altered, damaged or
removed.
Repairs carried out as part of the guarantee service are at no extra cost. Any additional repairs required are billed separately, along
with postage and packing.
Claims for liability or damages beyond the guarantee are excluded, provided that these are not legally mandated.
3 LEDs
Green: < 800 ppm (air quality good)
Yellow: 800...1200 ppm (air quality moderate)
Red: > 1200 ppm (air quality poor)
A fourth LED indicates whether the device is activated
and whether the sensors are functioning.
Relay
250 V AC/8 A
Relay switching threshold
1200 ppm
Humidity
Measuring range
0 - 100% RH
Accuracy
±3% RH (at 20…80% RH)
Output scaling
0 - 10 V
Ambient temperature
Measuring range
0 - +50 °C
Accuracy
±0.5 °K (bei +20…+40 °C)
Output scaling
0 - 10 V
General
Operating temperature
0 - +50 °C
Power supply
14 - 27 V DC
Power consumption
max. 70 mA
Dimensions
(LxWxH) 71 x 71 x 27mm
Housing
Plastic ABS, white, RAL 9010
Mounting type
Wall mounting
Protection class
IP20
CE conformity
2014/30/EU
VOC-probe for a comfortable indoor climate
12. Repair and calibration service
We are pleased to offer you a range of services for your product. If you experience functional defects, simply send us the product
with a quick description of the problem. Don't forget to add your telephone number for any questions we may have.
We will inform you of the costs for any repair before conducting it. This cost estimate is free of charge. Postage and packing for
returning your product are billed separately on a T&M basis.
12. Care and maintenance
If the housing is dirty, carefully clean it with a damp cloth. Do not use any strong detergents or solvents. The product requires no
maintenance.
13. Technical data
VOC sensor
High-performance measurement device for determining the VOC value in the room air, optionally available with sensors for relative
humidity and temperature. The integrated switching output (relay) can be used to directly control a fan or window lifter.
The measurement device has an LED display with three colors (green/yellow/red).
Measuring range for air quality: 450 - 2000 ppm (CO² equivalent)
Measuring range for humidity: 0 - 100% RH
Measuring range for temperature: 0 - 50 °C
Relay switching output
VOC sensor
0565 0004
Measuring range for air quality: 450 - 2000 ppm (CO² equivalent)
Relay switching output
VOC-probe for a comfortable indoor climate
14. Order date
15. Questions
Should you have any questions that cannot be answered in these operating instructions, please contact:
Your temperature partners,
B+B Thermo-Technik GmbH
We have carefully checked the technical information in this documentation, which aims to inform you about the product and its possible applications. This information
should not be seen as a guarantee of certain properties and should be checked by the user for the intended purpose. Any third-party property rights should be
respected.
Issued 01.07.2015.
This data sheet replaces all previous editions