Power Supplies
PS5R Standard Series
PS5R Standard Series
Switching Power Supplies
Key features of the PS5R standard series include:
Wide power range: 7.5W-240W
•
Universal input :
•
7.5W-50W: 85-264V AC/105-370V DC
100W: 85-132V AC/170-264V AC
240-370V DC (selectable)
75W, 120W, 240W: 85-264V AC/110-350V DC
Overcurrent/overvoltage protection
•
Power Factor Correction (75W, 120W, 240W models)
•
EN61000-3-3
EN61000-3-2
Voltage adjustment +10%
•
Spring-up crew terminal, IP20 (fi nger-safe)
•
DIN rail or panel surface mount
•
Approvals:
•
CE marked
UL 508 Listed
UL, c-UL
TÜV approved
EMC Directives:
EN50081-2
EN50082-2
EN61000-6-2
LVD EN60950:2000
Item Watts
Rated
Voltage
Rated
Current
Part Numbers
Part
Number
UL 508 Listed
File #E177168
Item Watts
Cert No.
BL980213332392
Rated
Voltage
Rated
Current
PLCs Operator Interfaces Automation Software Power Supplies Sensors
Part
Number
5V DC 1.5A PS5R-A05
12V DC 0.6A PS5R-A12
7.5
24V DC 0.3A PS5R-A24
5V DC 2.5A PS5R-B05
12V DC 1.2A PS5R-B12
15
24V DC 0.6A PS5R-B24
12V DC 2.5A PS5R-C12
30
24V DC 1.3A PS5R-C24
50 24V DC 2.1A PS5R-D24
75 24V DC 3.1A PS5R-Q24
100 24V DC 4.2A PS5R-E24
120 24V DC 5A PS5R-F24
Communication & Networking
USA: 800-262-IDEC Canada: 888-317-IDEC
240 24V DC 10A PS5R-G24
113
PS5R Standard Series
Power Supplies
Specifi cations
Part
Numbers
PLCsOperator InterfacesAutomation SoftwarePower SuppliesSensors
Output Capacity 7.5W 15W 30W 50W 75W 100W 120W 240W
Input Voltage (singlephase, 2-wire)
Input Current (typical)
Internal Fuse Rating 2A 2A 3.15A 3.15A 3.15A 4A 4A 6.3A
Input
Inrush Current 50A maximum (at cold start at 200V AC)
Leakage Current (at
no load)
Typical Effi ciency
Overvoltage Protection Outputs turns off at 105% (typical)
Voltage and Current
Ratings
Voltage Adjustments ±10% (V.ADJ screw on top)
Output Holding Time 20ms minimum (at full rated input and output)
Rise Time 200ms maximum (at full rated input and output) 150ms max.
Line Regulation 0.4% maximum
Output
Load Regulation 1.5% maximum
Fluctuation due to
Ambient Temperature
Change
Ripple Voltage 2% peak to peak maximum (including noise)
Overload Protection 120% typical (Zener-limiting) 120% typical, auto reset
Operation Indicator LED (green)
Parallel Operation
Allowed
Dielectric Strength
Insulation Resistance Between input and output terminals/input terminals and housing: 100MΩ minimum (500V DC megger)
Operating Temperature –10˚ to +60˚C (14˚ to 140˚F) (see derating curves)
Storage Temperature –30˚ to +85˚C (-22˚ to 185˚F)
Operating Humidity 20 to 90% relative humidity (no condensation)
Vibration Resistance 45m/s2, 10 to 55Hz, 2 hours on each of 3 axes 10 to 50Hz, 0.75mm p-p, 2 hrs on each of 3 axes
Shock Resistance 300m/s
Approvals
Weight 150g 170g 360g 390g 800g 600g 1200g 2000g
Termination Spring-up, fi ngersafe terminals with captive M3.5 screws
IP protection IP20 (fi nger safe)
Dimensions H x W x D (mm) 75 x 45 x 70 75 x 45 x95 75 x 90 x 95 75 x 90 x 95 120 x 85 x 140 75 x 145 x 95 120 x 115 x140 120 x 200x 140
Dimensions H x W x D
(inches)
1. For dimensions, see page 117.
Communication & Networking
2. For usage instructions, see page 116.
3. *12.5W for 5VDC model.
PS5R-A05 PS5R-B05* — — — —
PS5R-A12 PS5R-B12 PS5R-C12 — — —
PS5R-A24 PS5R-B24 PS5R-C24 PS5R-D24 PS5R-Q24 PS5R-E24 PS5R-F24 PS5R-G24
100 to 120V AC,
100 to 240V AC nominal (85 to 264V AC), 50/60Hz (47 to 63Hz)
110 to 340V DC nominal (105 to 370V DC)
0.17A at
100V AC
5V, 1.5A
12V, 0.6A
24V, 0.3A
PS5R-A PS5R-B PS5R-C PS5R-D PS5R-Q PS5R-E PS5R-F PS5R-G
2.95 x 1.77 x
2.76
0.3A at
100V AC
69% at 5V
75% at 12V
79% at 24V
5V, 2.5A
12V, 1.2A
24V, 0.6A
Conforms to EMC Directives EN50081-2 & EN50082-2. LVD Directive EN60529 — Certifi ed to EN60950.
2.95 x 1.77 x
3.74
0.68A at
100V AC
0.75mA maximum (60Hz, measured in conformance with UL, CSA, VDE)
75% at 12V
75% at 24V
12V, 2.5A
24V, 1.3A
No Yes No Yes
Between input terminals and housing: 2,000V AC, 1 minute
UL508 listed. UL, c-UL, TUV approved. CE marked. EN61000-3-2
2.95 x 3.54 x
3.74
1.15A at
100V AC
79% at 24V 83% at 24V 85% at 24V 83% at 24V
24V, 2.1A 24V, 3.1A 24V, 4.2A 24V, 5A 24V, 10A
Between input and output terminals: 3,000V AC, 1 minute
Between output terminal and housing: 500V AC, 1 minute
2
(30G), 3 shocks in each of 6 directions
2.95 x 3.54 x
3.74
1.1A at
100V AC
70A maximum
(at cold start at
230V AC)
0.05% maximum
4.72 x 3.35 x
5.52
50/60Hz
200 to 240V AC,
50/60Hz
(jumper selectable)
240 to 370V DC
2.5A at 100V AC
1.5A at 200V AC
50A maximum (at
cold start at 200V
AC)
2.95 x 5.71 x 3.74
100 to 240V AC, 50/60Hz,
110 to 340V DC
1.8A at
100V AC
70A maximum (at cold start at
230V AC)
4.72 x 4.53 x
5.52
4A at 100V AC
4.72 x 7.87 x
5.51
114
www.idec.com