B&B Electronics NTPS-24-3 Datasheet

PULS does it again: practical, versatile and reliable like the SilverLine – yet small like no other.
Data Sheet
with DC 24-28V / 72W
• Mounted and connected in record time, no tools required
• World-wide approvals (UL, EN, CSA, CB Scheme) for industry and office/ home
• Tiny: WxHxD = 45 x 75 x 91 mm
• Adjustable output voltage up to DC 28V
• Input: AC 115/230V switchable (Manual Select Input)
• PULS Overload Design™ (High output overload capability)
• NEC Class 2 Power Supply
PULS GmbH, Arabellastrasse 15, 81925 München Tel. +49.(0)89.9278-244, Fax: +49.(0)89.9278-199 sales@puls-power.com, http://www.puls-power.com
Mini is more.
ML70e100/041201
]
]
Technical Data ML70.100
s
p
m
la
C
g
n
i
r
p
S
X Input
Input voltage AC 100-120/220-240V (switchable), 47...63Hz
(AC 85...132V / AC 184...264V, DC 220...375V)
Input current <1.6A (@ AC 100V, 72W P
<0.8A (@ AC 220V, 72W P
out
out
) )
External fusing Not required, unit provides internal fuse
(T3A15H, not accessible)
Transient immunity Transient resistance acc. to VDE 0160 / W2
(750V / 1.3ms), over entire load range
Hold-up time (see diagram below)
>25ms @ AC 100V, 24V / 3A >27ms @ AC 196V, 24V / 3A >40ms @ AC 230V, 24V / 3A
X Efficiency, Reliability
Efficiency
Losses
MTBF (Reliability) appr. 600.000h acc. Siemensnorm SN29500
Prior to shipment, every unit undergoes the following tests in order to isolate any defective units which might suffer an early failure:
• Run-in / burn-in (Full load, T
• Functional test (100%)
typ. 89% (AC 230V, 24V / 3A) (see also diagram below) typ. 8.7W (AC 230V, 24V / 3A)
(24V / 3A, AC 230V, T
= +60°C, on/off cycle)
amb
amb
= +40°C)
X Construction, Mechanics, Installation
Robust plastic housing (US Patent No. D442, 923S), fine ventilation grid on three housing sides to keep out small parts (e.g. screws), IP20
Dimensions and weight
• W x H x D
•Weight
Mounting orientation ,
Ventilation/Cooling
• Free space f. cooling
Easy snap-on mounting onto the DIN Rail (TS35/7,5 or TS35/15). Unit sits safely and firmly on the rail; no tools required even to remove
Connection by Spring Clamp terminals; uniformly firm hold,
Connector size range
• flexible cable
• solid cable
• Wire strip length
45mm x 75mm x 91mm (+ DIN rail) Depth incl. terminals: 91mm (+ DIN rail) 260g
or (cf. ’Output’)
Normal convection, no fan required recom’d.: 25mm on sides with ventilation grid
vibration-resistant and maintenance-free: 2 terminals per output
2
0.3-2.5mm
0.3-4mm
(28-12 AWG)
2
(28-12 AWG) Ferrules admissible 6mm (0.24in) recommended
X Output
Output voltage
• preset
Voltage regulation stat. <1% V
Ripple/Noise <50mV
Overvoltage prot. (OVP) <40V
Rated continuous
loading
Overload behaviour PULS Overload Design™: No switch-off at
Protection Unit is protected against (also permanent) short-
Derating see diagram below
Power back immunity max. 35V
Operating indicator Green LED
DC 24-28V adj. by front panel potentiometer;
24.5V ±0.5% at rated load
dyn. < ±2% V
out
over all
out
(20MHz bandw., 50 Ω measurem.)
PP
up to 3A @ 24V /2.6A @ 28V (convection cooling) depending on built-in orientation, V
and T
in
amb
for details see derating diagram below
overload/short-circuit, instead: up to 1.5 ⋅ I
rated.
So you need no oversizing to start awkward loads.
circuit, overload and open-circuit.
X Environmental Data, EMC, Safety
Ambient temperature range (measured 25mm below unit)
• storage/transport
• operation
Humidity max. 95% (without condensation)
Electromagnetic emissions (EME)
Electromagnetic immunity (EMI)
Safe low voltage: Prot. class/degree:
The PSU complies with all major safety approvals for EU (EN 60 950, EN 60204-1, EN 50178), USA (UL 60950, UL508 LISTED), Canada (CAN/CSA-C22.2 No 60950 [CUR], CAN/CSA-C22.2 No. 14 [CUL]), CB Scheme (IEC 60950). NEC Class 2 Power Supply
Design details – for your advantage:
• All terminals are easy to reach as mounted on the front panel.
• Input and output are strictly apart from each other (input below, out­put above) and so cannot be mixed up
Mounting and connection do not require any screwdriver
Easy, quick, durable and reliable installation
-25°C ... +85°C
-10°C ... +70°C (for derating see diagram below)
EN 61000-6-3 (includes EN 61000-6-4) Class B (EN 55011, EN 55022)
EN 61000-6-2 (includes EN 61000-6-1)
SELV (EN 60950, VDE0100/T.410), PELV (EN 50178) Class I (EN 60950) / IP20 (EN 60529)
;
X Diagrams
Output characteristic V (min.)
32
28
Vout range
24
20
16
12
Vin = AC 115/230V
8
Output voltage Vout [V
4
0
0 0,5 1 1 ,5 2 2,5 3 3,5 4 4 ,5 5
Product information (ML70e100), Rev: 1. December 2004. Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.. PULS GmbH, Arabellastraße 15, D-81925 München X Tel: +49.(0)89.9278-244, Fax: +49.(0)89.9278-199, E-Mail: sales@puls-power.com X www.puls-power.com
Output current Iout [A]
out/Iout
Efficiency (@ V
= 24.5V, typ.)
out
95
90
85
80
75
70
Efficiency [%]
65
60
55
50
0,51 1,52 2,53
Output current Iout [A]
230V ACin 115V ACin
Derating of output power
80
A
70
60
50
40
Mounting
30
Output power [W]
85-132 V ACin A-a A-a A-b
185-264 V ACin A-a A-a A-b
20
220-375 V DCin A-a A-a A-b
10
0
-10 0 10 20 30 40 50 60 70 Ambient temperature [°C]
Hold-up time with ACin (@ V
= 24.5V, typ. + min.)
out
160
140
120
a
100
b
80
60
Hold-up time [ms
40
20
switch pos.
115V
0
80 120 160 200 240 280
Input voltage VACin [V]
Pout=72W, typ. Pout=72W, min. Pout=36W, typ. Pout=36W, min.
switch pos.
230V
Loading...