B&B Electronics MESP211D-T Datasheet

www.bb-elec.com orders@bb-elec.com support@bb-elec.com
European Office: Westlink Commercial Park Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
PRODUCT INFORMATION B&B ELECTRONICS
Specifications
Power
Source
External power supply included
Input Voltage
10 to 30 VDC
Connector
Barrel connector 5.5 x 2.1mm
Power Consumption
2.5 W
Mechanical
LED Indicators
Serial Port, Ethernet Link, Ready LEDs
Switches
Reset Button
Dimensions
3.1 x 0.9 x 2.0 (with ears 2.89) inches
Enclosure
Metal, IP 30
Environmental
Operating Temperature
-40 to 80°C (-40 to 176° F)
Operating Humidity
10 to 95% Non-condensing
MTBF
186,310 hours
MTBF Calc Method
Parts Count Reliability Prediction
Network
Serial Memory
8 KB per port
Network Memory
4 KB
IP Port Addresses
Setting in TCP Mode 8899
LAN
10/100 Mbps Auto-detecting , 10BaseT or 100BaseTX
Ethernet
IEEE 802.3 auto detecting & auto MDI/MDX, 10BaseT and 100Base TX
Ordering Information
Model
MESP211D
MESP211T
Serial port
RS-232/422/485
RS-232/422/485
Serial connector
DB9 Male
Removable terminal block
Ethernet port 1 1
Ethernet
connector
RJ45
RJ45
Accessories
MDR-40-24
Din Rail Mount, 24VDC, 40 W
DRAD35
Din Rail Adapter Clip (pair)
232NM9
Null Modem Crossover Cable
TB5P508SR-2PK
Replacement terminal block for the MESP211T
MESP211
Vlinx ™ Ultra Compact Modbus Gateways
Modbus TCP Ethernet, Modbus ASCII & RTU RS-232/422/485 Modbus Flexibility – Serial & Ethernet, Masters & Slaves View Messaging Status in Real Time Wide Operating Temperature (-40 to 80C) Wide Voltage input 10 to 30 VDC Ultra Compact IP30 Metal Enclosure Heavy industrial 61000-6-2 EMC Level 3 tested for harsh environments
Vlinx™ MESP211 series Modbus Gateways connect
Modbus devices to Ethernet networks and let you monitor and control your Modbus devices from anywhere on the Ethernet LAN or WAN. Supporting up to 16 masters and 32 slaves, the gateways feature an auto-detecting 10/100 Ethernet copper RJ-45 port and a serial port that supports RS-232/422/485 communications via a DB9 male or a terminal block connection. The product is built for use in industrial environments, featuring a heavy duty metal enclosure that is panel (standard) or DIN rail mountable (with optional adapters). The product is supplied with a DC power source ranging from 10 to 30VDC and features a barrel connector.
Ease of Use Configuration, upgrades and monitoring of the serial server are simple, easy tasks with Vlinx Manager Software. It installs right on your PC giving you access the serial server via your desktop. Remotely manage the Modbus Gateway over a LAN or WAN via the build-in web server. This is helpful for off-site troubleshooting and can be done with a simple web browser.
International Office:
pn710-08860-05_R1_MESP211_2713ds
© 2013 by B&B Electronics. All rights reserved.
www.bb-elec.com orders@bb-elec.com support@bb-elec.com
European Office: Westlink Commercial Park Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
Approvals / Certifications
Emissions
FCC Class B, CISPR Class A (EN55022)
CE
EN61000-6-2:2005
(Heavy Industrial)
EN61000-4-2:2008
(ESD)
+/-8kV Contact, +/-15kV Air
EN61000-4-3:2006
(RI)
10V/m, 80-1000MHz; 3V/m, 1.3 to 2.7 GHz
EN61000-4-4:2004
(EFT Burst)
+/-2kV DC ports; +/-1kV signal ports
EN61000-4-5:2005
(Surge)
+/- 0.5 kV DC Ports, +/- 1 kV Signal Ports
EN61000-4-6:2005
(CI)
10 VRMS, 0.15 to 80 MHz
EN61000-4-8:2001
(Magnetic)
10A/m, 50Hz & 60Hz
Shock
IEC60068-2-27
50G peak, 11ms, 3 axes
Vibration
10-500Hz, 4G, 3 axes
Freefall (Drop)
IEC60068-2-32
10 total drops from sides, corner and edges, 1M
Specifications
Serial Technology
RS-232 (DB9)
TD, RD, DTR, DSR, RTS, CTS, DCD, Signal Ground
RS-232 (Terminal Block)
TD, RD, RTS, CTS, Signal Ground
RS-485 2-Wire
Data A(-), Data B(+), GND
RS-422/485 4-Wire
TDA(-), TDB(+), RDA(-), RDB(+), GND
Serial Connector
DB9M or Removable Terminal Blocks
Data Rate
Up to 230.4 Kbps
Protocols
Protocols
TCP, IPv4, UDP, ARP, HTTP 1.0, ICMP/PING, DHCP/BOOTP
IP Mode
Static, DHCP
TCP/UDP UDP
User definable Unicast or Multicast
Other
Connection Mode
MODBUS RTU Master / Slave, MODBUS ASCII Master/Slave
Search
Serial direct COM and Ethernet Auto Search or specific IP
Diagnostics
Display PC IP, ping, save test config (text readable)
Firmware Upgrade
Firmware can be updated through the manager software
Modbus Monitor
The Manager Software has a Modbus Monitor feature
Configuration Software
OS Compatibility
XP (32/64), Vista (32/64), Windows 7 (32/64), Windows 8 (32/64), Server 2003 (32/64), Server 2008 (32/64), Server 2012 (64)