11.. CChheecckk ffoorr RReeqquuiirreedd HHaarrddwwaarree
ILinx FOSTCDRI-PH-xx Fiber Optic Converter This Quick Start Guide Additional Items Required but not included
o A 10 to 48 VDC Power Supply. The Converter
draws 2.6W Max.
22.. IInnffoorrmmaattiioonn
UULL CCllaassss 11 DDiivv 22
1. Refer to the Nonincendive Field Wiring Apparatus Control Drawing for important information .
2. Power, Input / output (I/O) wiring for the end use enclosure must be in accordance with Class 1 Division 2 wiring methods (Article 501.10(B) of the National Electric Code, NFPA 70) and in accordance with the local authority having jurisdiction.
3. Maximum ambient air temperature 85°C.
4. Temperature rating of field installed conductors 105°C. Use Copper Wire Only.
5. These devices must be installed in end use enclosure suitable for the location.
6. WARNING – EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.
7. WARNING – EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
8. WARNING – THIS APPARATUS IS SUITABLE FOR USE IN CLASS 1 DIVISION 2, GROUPS A, B, C, AND D OR NONHAZARDOUS LOCATIONS ONLY.
Quick Start Guide
ILinx FOSTCDRI-PH-xx
Triple Isolated Serial to Fiber
Optic Converter
33.. FFrroonntt // BBaacckk PPaanneell,, TTBB11
A
Power LED
Red, ON When Power Applied
B
Data LEDs
Green. LEDs Flash When Data is on
Port. Left LED’s for Fiber, Right LED’s for Copper
C
Fiber Optic Connectors
ST or SC, MM or SM, depending on model.
D
Serial TB
5 Position, Removable
E
Ground Lug
Chassis Ground to Earth Ground
F
DIP Switch
Used to Configure
G
Serial Mode Switch
Used to configure serial mode. RS­232 or RS-422/485.
H
Power TB
2 Position, Removable
TB1 – RS-422/485
Terminal
RS-485 2-Wire
RS-422/485 4-Wire
A
---
TDA(-)
B
---
TDB(+)
C
DATA A(-)
RDA(-)
D
DATA B(+)
RDB(+)
E
Ground
Ground
TB1 RS-232
Terminal
Signal
Direction
A
RD
Output
B
---
--- C TD
Input D ---
---
E
Ground
----
44.. CCoonnffiigguurraattiioonn DDIIPP SSwwiittcchh
Highlighted settings indicate factory default.
Communications Mode
Switch
1 2 3 4
RS-485
2-Wire
Half Duplex
ON
ON
ON
ON
RS-485
4-Wire
Full Duplex
ON
OFF
OFF
OFF
RS-422
Full Duplex
OFF
OFF
OFF
OFF
Built-in Termination Resistor
Switch
5
Use the 120Ω Built-in Termination
ON
Use External or No Termination
OFF
Built-in Transmit Bias Resistor
Switch
6 Use External or No Bias Resistor
ON
Use the 1.2K Ω Transmit Bias Resistor
OFF
Built-in Receive Bias Resistor
Switch 7
Use External or No Bias Resistor
ON
Use the 1.2K Ω Receive Bias Resistor
OFF
Fiber Optic Mode
Switch 8
Multi-drop Ring
ON
Point-to-Point
OFF
For an explanation of RS-485 termination and biasing requirements, refer to B&B Electronics’ RS-485 application note. This publication can be downloaded at: www.bb-elec.com
Documentation Number – p/n 8933R1x FOSTCDRI-PH-xx-0812qsg
©2010 B&B Electronics Manufacturing Company
66.. WWiirriinngg EExxaammpplleess
For RS-422/485 Place the Serial Mode Switch to RS­422/485. For RS-232, place the switch to RS-232.
2-Wire RS-485
RS-422 / 4-Wire RS-485
RS-232
77.. FFiibbeerr OOppttiicc
Point-to-Point
Multi-drop Ring
88.. RRSS--223322 LLooooppbbaacckk TTeesstt
1. Configure the converter for RS-232.
2. Set DIP Switch Position 8 to OFF.
3. Cross connect the fiber optic TD and RD.
4. Connect a PC to the serial port.
5. Using hyper terminal or similar program, connect the appropriate COM Port. Ensure hyper terminal local echo is off.
6. Transmit data. If the same characters are returned, the test is good.
55.. PPoowweerr && GGrroouunndd CCoonnnneeccttiioonn
1. It is recommended that the chassis be grounded.
2. Connect a grounding wire from the ground lug to a good source of Earth Ground.
3. Connect Power. Power Requirements: 10 to 48 VDC, 2.6W
Maximum.
4. The terminal block will accept 28 to 12 AWG wire.
Documentation Number – p/n 8933R1x FOSTCDRI-PH-xx-0812qsg